Pegase Environnement sprl Rue du Vallon, 92 – B-1332 Genval
TVA: 0462 615 863 – IBAN (BNP Paribas Fortis): BE28 2100 0810 6020 – BIC: GEBABEBB Mobile: +32 477 30 22 57 - Email: info@pegase-environnement.be www.pegase-environnement.be
Asbestos Survey
Y/Project Reference W912PA15T0080_AsbestosSurvey
O/Project Reference 114-15-V
Address CHIEVRES AIR BASE, 7950 CHIEVRES, BELGIUM
Survey’s Reference 20002
Survey office responsible:
I, hereby undersigned Paul-Adelin REMY, declare that the information included in the present survey report, is complete and exact.
Date on December 22, 2015 in Genval
Signature of the responsible of the study:
Paul-Adelin REMY
Director
Asbestos management responsible:
I, hereby undersigned Sabine Schneider, responsible of the environment, declare that I have read and agreed with the information included in this report.
Date on , in Chièvres
Signature of the responsible of the environment:
Sabine Schneider
Responsible of the Environment, US Army
Building: 20002 Reference: 114-15-V / W912PA15T0080 CHIEVRES AIR BASE, 7950 CHIEVRES page 2 of 17
Table of Content
1 Introduction
1.1 General description
1.2 Legal Charter
1.3 Scope of Works
1.4 Possible restraints
1.4.1 General restraints
1.4.2 Accessibility restraints
1.5 Description of the method used to set up the survey, sampling and analysis
1.5.1 Tools
1.5.2 Laboratory analysts
1.6 Risk assessment
1.7 Management Plan
2 Study and inventory
2.1 Records
2.1.1 Material for which the analysis showed the absence of asbestos
2.1.2 Material containing asbestos
2.2 Summary and management plan of the applications containing asbestos 3 Annexes
3.1 Drawings and diagrams
3.2 Material analysis report
3.3 Advise for asbestos management
3.3.1 General information
This survey report can only be reproduced in its entirety; no sections of the documentation can be formed and distributed, without written consent.
Abbreviations used in this report:
ACM Asbestos containing material MKCA Material known to contain asbestos
General conclusion of the report:
( ) No Asbestos Containing Material has been found.
(X) Asbestos Containing Material has been found.
CHIEVRES AIR BASE, 7950 CHIEVRES page 3 of 17
1 Introduction
1.1 General description
Topic: ASBESTOS SURVEY
Project: 114-15-V
Building name: 20002
Address: Chièvres Air Base – 7950 Chièvres
Client: US ARMY Grand Rue, 56 7950 Chièvres
Contact: Mrs. Sabine Schneider USAG Benelux, DPW - C/Env. Div.
DSN: 361-5704
COMM: +32.68/27.57.04
Email: sabine.schneider.ln@mail.mil
General Service Provider: SBMI Zeelstraat, 16 9681 Maarkedal M. Axel Tasté Tel: +32 499/51.09.51 a.taste@sbmi.be
Asbestos Survey Office: PEGASE ENVIRONNEMENT S.P.R.L.
Rue du Vallon 92
1332 – GENVAL (BELGIUM)
Tel/Fax: +32 477 30 22 57 E-mail: info@pegase-environnement.be URL: www.pegase-environnement.be
Laboratory: a-ULaB S.A.
Rue Auguste Piccard, 48 6041 Gosselies (BELGIUM)
Survey visit date: November 30, 2015
Sample analysis date: December 14, 2015
Reporting date: December 22, 2015
Inspector: Paul BOGAERTS
Survey method: Visual inspection
Sample analysis method: Polarized Light Microscopy (PLM)
CHIEVRES AIR BASE, 7950 CHIEVRES page 4 of 17
1.2 Legal Charter
In respect of the Performance Work Statement “W912PA15T0080_AsbestosSurvey” - ASBESTOS SURVEY FOR CHIEVRES AIR BASE, 7950 CHIEVRES, BELGIUM, of 88 buildings , the current survey is non-destructive (suspected ACM, visually accessible) and is produced according to the Belgian Royal Decree of 16 March 2006 (survey so-called "Management Plan").
However, if renovation/destruction works are to be undertaken, a destructive asbestos survey should be made.
1.3 Scope of Works
- Geographical scope of the works: building 20002
- Asbestos history of the building: some of the buildings were surveyed during year 2000 but only partial and incomplete information was available for consultation.
1.4 Possible restraints
1.4.1 General restraints
Some remarks should be made concerning the survey:
1) Roofs: there are bituminous roof coatings containing asbestos (roofing type). Sometimes fibrous asbestos plates are present between the underlay and the roofing felt.
This also can only be ascertained by a destructive survey. As it is impossible to take a representative sample without damaging the surface (risk of damage to the seal), we advise to make additional analysis just before any renovation or demolition of the building.
2) Equipment in general: unless any contrary advice in the following text, the potential ACM have been checked as close as possible, however without any dismantling. So it is possible that our description could be incomplete, and that inaccessible ACM could be discovered afterwards.
3) Gaskets between flanges: they are being studied based on samples taken randomly when practical.
When gaskets of which composition is unknown must be replaced, we advise to consider them as ACM before replacement.
4) Underground areas: The networks of underground areas are not a part of the study as they are inaccessible. However, a potential presence of asbestos cannot be excluded for example, pipework insulation and asbestos based cement products. So the survey is not exhaustive. But we can extend the survey to apparent and visually accessible sections of underground areas.
5) Floor and wall covering: floor and wall covering generally in good condition was not damaged to ascertain the nature of the underlay.
6) Fire doors: the fire doors were not investigated because it can only be done by a destructive survey.
1.4.2 Accessibility restraints
Locations not visited during the survey: the roofs, sub-roofs and attics were not accessible.
Potential and exploitation of the conclusion of the survey to the inaccessible areas: nil.
Description of the destructive soundings still to be performed: the inventory was conducted in a non-destructive way. A destructive survey should be performed before any refurbishment or demolition works.
1.5 Description of the method used to set up the survey, sampling and analysis
A consultation with the site manager occurs first, when possible. A survey method is established based on the on-site configuration. When it’s possible, samples will be taken on suspected material in order to reveal a possible presence of asbestos. These samples are analyzed in our dedicated laboratory. In the laboratory reports, in attachment to the current survey, the fiber type of the asbestos present in the ACM is determined.
The characteristics of the ACM (fibrous asbestos, asbestos cement, …) can be important, and will define the choice of the removal method. When the sampling is not possible, we specify the methodology used to determine the presence of asbestos in the material (e.g. documents consultation, visual recognition …).
CHIEVRES AIR BASE, 7950 CHIEVRES page 5 of 17
Pegase Environnement has undertaken to the best of its ability to recognize the asbestos based materials within this report data. However, considering the incompleteness of localization, Pegase Environnement does not accept any responsibility for potential in corrections concerning the naming of the locations and for the modifications which would be produced after this survey.
The areas not mentioned in the current report were either inaccessible, or were not a part of the survey request, these areas were not examined. Nevertheless, in the case of repetition of identical structures, only a representative number of these structures have been examined, under authorization. In this case, this has been noted in the report.
Based on the visual inspection, the locations where samples have been taken are as indicated.
1.5.1 Tools
The inspector in charge has all the necessary tools in order to perform the samplings. He uses among others:
flat nose and curved pliers, a cutter, a folder bag, different screw drivers, a hammer, corer, gloves, asbestos encapsulation spray, wipes to clean tools, etc.
1.5.2 Laboratory analysts
Sampling and analysis were performed according to HSG248 guidance publication “the analysts’ guide for sampling, analysis and clearance procedures”.
Samples were examined in our laboratory. To determine the presence of following types of asbestos fibers:
-Chrysotile (white asbestos) -Amosite (brown asbestos) -Crocidolite (blue asbestos) -Anthophylite, tremolite et actinolite
= serpentine group = amphibole group = amphibole group = amphibole group
Briefly, after screening under a stereomicroscope suspicious fibers have been analyzed under a polarized microscope. The optical features of the fibers, such as refraction index, pleochroism, polarization colors, elongation and extinction angle have been checked. Dispersion staining colors according to McCrone are determined for confirmation.
Material samples can be found in the following laboratory report:
a-ULaB report n°: 151235-017-PLM
Following information is reported:
Location of the samples Composition of the analyzed material Potential presence of one or more types of asbestos
1.6 Risk assessment
General observations concerning the security of the site:
Mask wearing (P3 type): no Security shoes and helmet: no Others: no
1.7 Management Plan
A regular evaluation, at least annually, of the state of asbestos and asbestos-containing materials must be made. Everyone involved should also be informed of the actions that can lead to exposure to asbestos for instance do not drill, saw, rub, work mechanically asbestos-containing materials. The survey record will also inform what type of action is required to ensure the ACM are safe. This can be removal, encapsulation and management.
CHIEVRES AIR BASE, 7950 CHIEVRES page 6 of 17
2 Study and inventory
2.1 Records
2.1.1 Material for which the analysis showed the absence of asbestos
Application 1.
Sample(s) : 2 a-ULaB: 151235-017-002
Material type Floortile & brown glue
Location Hall at entrance between offices 101 & 104, old floor covering
Location of the samples Hall at entrance between offices 101 & 104
Material accessibility Difficult (under a newer tiling)
Surface protection Under a newer tiling
Condition of material Damaged
Observations:
Conclusion
No asbestos
According to laboratory analysis
CHIEVRES AIR BASE, 7950 CHIEVRES page 7 of 17
2.1.2 Material containing asbestos
*MKCA = Material known to contain asbestos
Application 2.
Sample(s) : 1 a-ULaB: 151235-017-001
Material type Floortile & black glue
Location Breakroom # 106, old floor covering
Location of the samples Breakroom # 106
Surface protection Under a newer tiling
Material accessibility Difficult (under a newer tiling)
Condition of material Damaged
Conclusion
Asbestos category Non friable
Asbestos type Chrysotile
According to Laboratory analysis
Management plan Long term
Treatment Sealed area
Observations: the same kind of floortile and glue is possibly present in other offices under the actual floor tiles
CHIEVRES AIR BASE, 7950 CHIEVRES page 8 of 17
Application 3.
Sample(s) : -a-ULaB: -
Material type Rectangular fibrocement pipe
Basement in boiler rooms under offices 104C/104D and 111, ventilation pipes location of the samples -
Surface protection NIl
Material accessibility Medium
Condition of material Slightly damaged
Conclusion
Asbestos category Non friable
Asbestos type *MKCA
According to Visual recognition
Management plan Long term
Treatment Simple treatment
Observations:
CHIEVRES AIR BASE, 7950 CHIEVRES page 9 of 17
Other pictures of application 3:
CHIEVRES AIR BASE, 7950 CHIEVRES page 10 of 17
Application 4.
a-ULaB: -
Material type Fibrocement pipe
Basement in boiler rooms under offices 104C/104D and 111, sleeves for old heating pipes location of the samples -
Surface protection NIl
Material accessibility Difficult
Condition of material Slightly damaged
Conclusion
Asbestos category Non friable
Asbestos type *MKCA
According to Visual recognition
Management plan Long term
CHIEVRES AIR BASE, 7950 CHIEVRES page 11 of 17
Application 5.
a-ULaB: -
Material type Fibrocement pipe
Roof, above boiler rooms and offices
104C/104D and 111, flue pipes
Location of the samples -
Surface protection Nil
Material accessibility Medium
Condition of material Slightly damaged
Conclusion
Asbestos category Non friable
Asbestos type *MKCA
According to Visual recognition
Management plan Long term
CHIEVRES AIR BASE, 7950 CHIEVRES page 12 of 17
2.2 Summary and management plan of the applications containing asbestos
CHIEVRES AIR BASE, 7950 CHIEVRES page 13 of 17
3 Annexes
3.1 Drawings and diagrams
This section only concerns the surveyed soil locations and it contains sketches including the area of the applications containing suspicious materials. These sketches are not to scale; the suspicious materials are located and referenced from the main building and to the confines of the plot of land.
1. Roof
Application 5:
CHIEVRES AIR BASE, 7950 CHIEVRES page 14 of 17
2. Main Floor
Application 1:
Sample 2:
Application 2:
Sample 1:
CHIEVRES AIR BASE, 7950 CHIEVRES page 15 of 17
3. Basement
Application 3:
Application 4:
CHIEVRES AIR BASE, 7950 CHIEVRES page 16 of 17
3.2 Material analysis report
CHIEVRES AIR BASE, 7950 CHIEVRES page 17 of 17
3.3 Advise for asbestos management
3.3.1 General information
ACM removal or demolition must satisfy to the rules fixed by Belgian Royal Decree dated March 16, 2006 and to the Code concerning the protection of the workers against the risks linked to the exposition to asbestos.
All asbestos containing material must be removed by a licensed asbestos removal company, except for the simple treatment method where the risk of release of asbestos is so limited in all cases that the fiber concentration of 0.01 cm³ is not exceeded. Simple treatments can be carried out by all employers, provided that the workers have received specific training that meets the requirements of the law.