20230912 Addendum 02 Chgs and Attachments.pdf
PDF 360 KB Posted
- Attached to
- 23-R-1002 - DOMOPS Storage Federal contract opportunity
- Solicitation number
- W912LM23R1002
About this file
This document package includes electrical drawings and specifications for a federal construction project along with the related solicitation number.
The drawings and specifications are for electrical systems at a new DOMOPS Storage facility and include details for a lighting plan, schedules for fixtures and controls, diagrams for power distribution and grounding, and notes for access control, fire alarm and intrusion detection systems. The solicitation seeks bids for construction of the storage building per the specifications, which require a base bid for rough-in of an access control system along with options to provide devices, cabling and a complete installed system. The opportunity was released by the Department of the Army Minnesota Army National Guard for Project Number 170859 at the 148th Fighter Wing base. The response due date is May 10, 2023.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 23-R-1002 Amendment 02.pdf | ||
| 20230912 Amendment 02 - DOMOPS.docx | DOCX document | |
| 20230901 Addendum 01 LHB.pdf | ||
| 20230901 Amendment 01 - DOMOPS.docx | DOCX document | |
| 23-R-1002 Amendment 01.pdf | ||
| DOMOPS Pre Proposal.pptx | PPTX presentation | |
| DOMOPS site visit roster - 16 Aug 23.pdf | ||
| 20230807 23-R-1002 DOMOPS.pdf | ||
| 20230804 23-R-1002 DOMOPS.pdf | ||
| DOMOPS BID DWGS 051023.pdf | ||
| 20230510 EXHIBIT B.docx | DOCX document | |
| DOMOPS Bid SPEC 051023.pdf | ||
| 20230804 23-R-1002 DOMOPS.pdf | ||
| 20230510 EXHIBIT A.docx | DOCX document | |
| 20230510 EXHIBIT C Reference_Questionnaire_Package.docx | DOCX document | |
| 20230510 EXHIBIT D Letter of Commitment.docx | DOCX document |
Show all 16
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
MnANG Construct DOMOPS Storage LHB Project No. 170859 FMKM169006
Issued for BID 05/10/2023
ACCESS CONTROL
28 1800 - 1
Addendum 02
SECTION 28 1800
ACCESS CONTROL
PART 1 GENERAL
1.01 SECTION INCLUDES
A. Security access control system
1.02 RELATED REQUIREMENTS
A. Section 01 2300 - Bid Options.
B. Section 08 7100 - Door Hardware.
C. Section 26 0519 - Low-Voltage Electrical Power Conductors and Cables (600 V and Less).
D. Section 26 0534 - Conduit.
E. Section 26 0553 - Identification for Electrical Systems.
1.03 REFERENCES
A. NFPA 70 - National Electrical Code; National Fire Protection Association; 2008.
B. Air Force Instruction AFI 31-101.
C. ICD/ICS 705 - Technical Specifications for Construction and Management of Sensitive
Compartmented Information Facilities.
1.04 SYSTEM DESCRIPTION
A. Security Access Card Reader
1. Base Bid: Rough-in only
2. Bid Option: Includes cabling, terminations and devices for a complete system
3. Refer to Drawings for locations.
B. Equipment shall be compatible with AFI 31-101 and the existing Base Security Force's Advantor security system.
1.05 ADMINISTRATIVE REQUIREMENTS
A. Coordination:
1. Coordinate the installed locations with work provided under other sections or by others.
2. Notify Architect of any conflicts with or deviations from the contract documents. Obtain direction before proceeding with work.
B. Sequencing:
1. Do not install sensors and keypads until final surface finishes and painting are complete.
1.06 SUBMITTALS
A. See Section 01 3000 - Administrative Requirements, for submittal procedures.
B. Submittals for Review:
1. Product Data: Provide electrical characteristics and connection requirements.
2. Shop Drawings:
a. Provide system wiring diagram showing each device and wiring connection required.
b. Provide dimensions of control panel and controller enclosures.
C. Submittals for Information:
1. Installer Documentation: Submit documentation that all persons installing items in this section are United States Citizens.
2. Manufacturer's Installation Instructions: Indicate application conditions and limitations of use stipulated by product testing agency. Include instructions for storage, handling, protection, examination, preparation, installation, and starting of product.
D. Submittals for Closeout:
1. Project Record Documents: Record actual locations of access authorization equipment.
2. Operation and Maintenance Manual:
a. Test Reports: Include completed test reports and inspections.
Issued for BID 05/10/2023
ACCESS CONTROL
28 1800 - 2
Addendum 02
b. Product Information: Include approved shop drawings and product data.
c. Operation Data: Operating instructions.
d. Maintenance Data: Maintenance and repair procedures.
e. Documentation of Training: Indicate date of training. Include attendance roster and training outline.
3. Maintenance Materials: Furnish the following for Government's use in maintenance of project.
a. See Section 01 6000 - Product Requirements, for additional provisions.
b. Deliver keys/cards not used in initial installation to Government as directed.
1.07 QUALITY ASSURANCE
A. Conform to requirements of NFPA 70.
B. Installer Qualifications:
1. Company specializing in installing the products specified in this section with minimum three years documented experience.
2. Installers: Workers specializing in installation of Products specified in this section with minimum three years documented experience.
3. Individuals installing products in this section are documented United States Citizens.
C. Products: Furnish products listed and classified by Underwriters Laboratories Inc. as suitable for purpose specified and indicated.
1.08 MAINTENANCE SERVICE
A. Furnish service and maintenance of security access system for one year from Date of Substantial Completion.
PART 2 PRODUCTS
2.01 MANUFACTURERS
A. Security Access Control and Intrusion Detection System:
1. Advantor .
2. Substitutions: Not Permitted.
2.02 CONTROL PANEL
A. The Security Access Control System shall be manufactured by Advantor and consist of a V5
ACS Server(s), keypads, readers, door hardware, and other I/O.
B. The system shall have backup batteries capable of operating the system for 24 hours without normal AC power.
C. Data Transponders shall be an 8-input unit D. System shall include all components as required to support the following Sequence of
Operations:
1. Controlled Entry of Building
a. Use Card Reader to release strike and enter building.
b. Building shall require access control at all times.
2.03 CONTROLLERS
A. Access Control Enclosure: Advantor MR-50, 2.5 amp 12 volt power supply, 7 amp battery, PD-8.
B. Access Control Enclosure (ACE).
1. Nema 1 enclosure, 120 volt power source.
2. Relay, door strike: 2.5 amps, AC/DC.
3. Product:
a. As indicated in Intrusion Detection Device Schedule on Drawings.
b. Substitutions: Not Permitted.
Issued for BID 05/10/2023
ACCESS CONTROL
28 1800 - 3
Addendum 02
2.04 DEVICES
A. Card Reader Rough-in: 4" square, deep junction box with single gang trim ring. Provide (1) 1" empty conduit concealed within wall to above indoor accessible ceiling. Provide bushings at each end.
B. Encoded Cards: Compatible with Advantor system. Provide 20 encoded cards (Bid Option) C. Electric Strikes:
1. Refer to Section 08 7100 - Door Hardware.
2.05 SYSTEM CABLE
A. Minimum size: 18 AWG twisted shielded.
2.06 SEQUENCE OF OPERATOINS
A. Controlled Entry of Secure Space.
1. Use Card Reader with keypad to release strike and enter secure door.
a. Secure space shall require access control at all times.
B. Utilizing assigned passwords, it shall be possible to define the levels of system operation for each individual operator. System operation for individual operators shall include, but not be limited to, restricted time periods for login and default language selection at login. Operator actions range from basic monitoring to full control of the system including programming.
C. The system programming shall be user friendly. The programming shall be menu driven and include on-line "Help" as well as on-line data entry examples. The software shall utilize drop boxes for a all previously entered system-required data.
D. After installation, the customer shall be able to perform hardware configuration changes. These shall include, but not be limited to, door open time, door contact shunt time, point and reader names, when and where a cardholder is valid, and the ability to add or modify card databases as desired.
E. The file server station shall operate in both a programmed and a manual mode.
F. Basic System Capabilities
1. All databases will have the ability to ADD, DELETE, REPORT, VIEW or EDIT information.
2. Log all events by time and date.
3. Provide capability to store all or selected system transactions to a disk file.
4. Provide storage of all system transactions ina retreivable file.
PART 3 EXECUTION
3.01 INSTALLATION
A. Install in accordance with applicable codes.
B. Use 18 AWG minimum size conductors for detection and signal circuit conductors. Install wiring in conduit.
C. Make conduit and wiring connections to door hardware devices furnished and installed under
Section 08 7100.
1. Verify operating voltage of security system door release circuits, provide data to door hardware provider.
D. Provide fiber optic cable from Security System control panel to receiving station at Central
Security Building.
3.02 FIELD QUALITY CONTROL
A. Perform field inspection and testing in accordance with Section 01 4000.
B. In the presence of representative from Base Security, test entire system for proper operation.
Correct all defects.
C. Provide written certification system was installed according to manufacturer's instructions and operated properly during final acceptance test. Include certification as part of O&M manual.
Issued for BID 05/10/2023
ACCESS CONTROL
28 1800 - 4
Addendum 02
3.03 DEMONSTRATION AND TRAINING
A. Demonstrate normal and abnormal modes of operation, and required response to each.
B. Provide 2 hours of instruction each for Base personnel.
1. Conduct instruction at project site with manufacturer's representative.
END OF SECTION
KEYED SHEET NOTES
PROJECT ANCHOR BOLTS ABOVE TOP
OF BASE, PROVIDE DOUBLE NUTS FOR
LEVELING. GROUT VOID BETWEEN BASE
FLANGE & TOP OF CONRETE.
ANCHOR BOLTS FURNISHED
BY POLE MANUFACTURER.
FINISHED GRADE
GRS SWEEP, CONDUIT AND WIRE
SIZE AS INDICATED ON PLANS.
9 #4 REBAR, 12" O.C.
HORIZONTAL (19" DIA CIRCULAR)
4 #4 REBAR VERTICAL
ON 18" DIA CIRCLE
REINFORCED CONCRETE
BASE BY E.C. REFER TO
SITE PLAN FOR LOCATIONS
WHERE A 36" POLE BASE
IS REQUIRED.
3/4" PVC W/
BUSHING, #6 GND
GROUND ROD PER
SPECIFICATIONS
1" CHAMFER
BASE COVER
HANDHOLE - PROVIDE BOND
GROUND TO POLE
1" COMMUNICATION CABLE CONDUIT
6'
2'
" 1'
0'
2' - 0"
LEVEL 1
ROOF
GRADE
ELEC 106
MV
DISTRIBUTION
TRANSFORMER
T-SA/DOMOPS
PANEL A
208Y/120VAC
3-PHASE, 4 WIRE
200A MCB
PANEL B
208Y/120VAC
3-PHASE, 4 WIRE
200A MCB
T1
MDP
480Y/277VAC
3-PHASE, 4 WIRE
400A MCB
SERVICE ENTRANCE
RATED
2 3
SPD
TRANSFORMER T1: 480VAC
DELTA PRIMARY, 208Y/120VAC
SECONDARY, 75 KVA
SPD SPD
SECONDARY
CONNECTION
CABINET
SCC-SA
M
M
M
FEEDER
NUMBER
FROM TO VOLTAGE PHASE
FEEDER SCHEDULE
UTILITY XFMR MDP 277/480 3 2 @ 3" 3#3/0 AWG Cu1
MDP XFMR T1 480 3 1 @ 1.25"2
XFMR T1 PANELS A & B 120/208 3 1 @ 2"3
CONDUIT
QNTY & SIZE
PHASE COND
QNTY & SIZE
NEUT COND
QNTY & SIZE
GROUND COND
QNTY & SIZE
3#2 AWG Cu
3#3/0 AWG Cu
1#3/0 AWG Cu
(NONE)
1#3/0 AWG Cu
1#3 AWG Cu
1#8 AWG Cu
1#6 AWG Cu
PVC SLEEVE
LINK SEAL
SEE PLANS FOR SIZE
& LOCATION
COPPERCLAD
GROUND ROD
PER SPECIFICATION
SECTION 13100
EXOTHERMIC CONNECTION
PARALLEL SPLICER
BIMETAL SPLICER
EXOTHERMIC
CONNECTION
COPPERCLAD
GROUND ROD
PER SPECIFICATION
SECTION 13100 EXOTHERMIC
CONNECTION
COPPERCLAD STEEL
GROUND ROD
CROSS RUN
CABLE CLAMP
ENCIRCLING
COUNTERPOISE
NO. GWP-1024: 10" DIA x 24"
PVC GROUND WELL WITH COVER
BARE CU
CONDUCTOR
COUNTERPOISE
CONDUCTOR
FIBER OPTIC
CABLES
CONCRETE
UNDERGROUND
WARNING TAPE
GRADE
2' - 3"
0'
1/ 2"
M A
X I M
U M
M
IN
IM
U
M
0'
0' - 6" 0' - 7 1/2" 0' - 7 1/2" 0' - 6"
4" CONDUIT4" CONDUIT WITH 3-CELL
TEXTILE INNERDUCT2 2
1. PROVIDE SCHEDULED FEEDER FROM EXISTING SPARE METER
LOCATED IN EXISTING SECONDARY CONNECTION CABINET.
FILE:
DRAWN BY:
CHECKED BY:
PROJ. NO:
DRAWING NO:
DRAWING TITLE:
PROJECT NAME:
I HEREBY CERTIFY that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under the laws of the State of Minnesota.
Signature:
Typed or Printed Name:
Date: Reg. No.:
THIS SQUARE APPEARS 1/2"x1/2"
ON FULL SIZE SHEETS
CLIENT:
DULUTH, MINNESOTA
148th FIGHTER WING
MINNESOTA AIR
NATIONAL GUARD
CONSTRUCT
DOMOPS STORAGE
170859 MnANG DOMOPS Storage MEP19 Central.rvt
FMKM169006
COPYRIGHT 2023 BY LHB, INC. ALL RIGHTS RESERVED.
NO DATE ISSUED FOR
21 W. Superior St., Ste 500 | Duluth, MN 55802 | 218.727.8446
08/11/2020 B.3 FINAL SUBMITTAL
MARK J. VINCENT
52349
05/10/2023 BID
B
IM
/M n A
N G
P ro je c ts
/1
M n A
N G
D O
M O
P S
S to ra g e M
E P
C e n tr a l.
rv t
/1
/2
:2
:3
P
M
E501
05/10/2023
AML
MJV
170859
ELECTRICAL DETAILS
AND DIAGRAMS
NOT TO SCALE1
LIGHT POLE BASE DETAIL
NOT TO SCALE6
ELECTRICAL POWER DISTRIBUTION DIAGRAM
NOT TO SCALE2
FOUNDATION PENETRATION DETAIL
NOT TO SCALE3
CONNECTION AND SPLICE DETAILS
NOT TO SCALE4
GROUND ACCESS WELL DETAIL
NOT TO SCALE5
DUCT BANK DETAIL
NO DATE REVISION
1 06/28/2021 ADDENDUM 01
2 09/11/2023 ADDENDUM 02
Typed or Printed Name:
Date: Reg. No.:
I HEREBY CERTIFY that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under the laws of the State of Minnesota.
I HEREBY CERTIFY that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under the laws of the State of Minnesota.
I HEREBY CERTIFY that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under the laws of the State of Minnesota.
Signature:
AUSTEN JAMES BRYAN
09/11/2023 57136
A. UNIVERSAL AND MULTI-VOLT DRIVERS ACCEPTABLE.
B. WHERE "APPROVED EQUAL" IS LISTED IN THE MANUFACTURER COLUMN, FIXTURES MUST BE SUBMITTED AS A SUBSTITUTION FOR APPROVAL PRIOR TO BID SUBMISSION.
GENERAL NOTES:
A. OCCUPANCY SENSOR TIME OUT IS 15 MINUTES UNLESS OTHERWISE NOTED.
GENERAL NOTES:
1. NOTE 1.
SCHEDULE NOTES:
A. DEVICES PROVIDED BY DIVISION CALLED OUT IN COLUMN. DIVISION 28 CONTRACTOR SHALL WIRE ALL LOW VOLTAGE CABLING/COMPONENTS AND DIVISION 26 CONTRACTOR SHALL PROVIDE ALL 120V POWER.
B. VOLTAGE REQUIREMENTS TO BE COORDINATED WITH DOOR HARDWARE.
C. COORDINATE WITH OWNER FOR SCHEDULING OF INSTALLATION.
D. DIVISION 26 CONTRACTOR SHALL SUPPLY 120V POWER TO ACCESS CONTROL POWER SUPPLY LOCATIONS AS SHOWN.
GENERAL NOTES:
1. BASE BID: PROVIDE ROUGH-IN FOR FUTURE CARD READER / ACCESS CONTROL SYSTEM. AS PART OF A BID OPTION: PROVIDE AND INSTALL CABLING, DEVICES AND TERMINATIONS FOR A COMPLETE ACCESS CONTROL SYSTEM. REFER TO SPECIFICATIONS.
SCHEDULE NOTES:
FILE:
DRAWN BY:
CHECKED BY:
PROJ. NO:
DRAWING NO:
DRAWING TITLE:
PROJECT NAME:
I HEREBY CERTIFY that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under the laws of the State of Minnesota.
Signature:
Typed or Printed Name:
Date: Reg. No.:
THIS SQUARE APPEARS 1/2"x1/2"
ON FULL SIZE SHEETS
CLIENT:
DULUTH, MINNESOTA
148th FIGHTER WING
MINNESOTA AIR
NATIONAL GUARD
CONSTRUCT
DOMOPS STORAGE
170859 MnANG DOMOPS Storage MEP19 Central.rvt
FMKM169006
COPYRIGHT 2023 BY LHB, INC. ALL RIGHTS RESERVED.
NO DATE ISSUED FOR
21 W. Superior St., Ste 500 | Duluth, MN 55802 | 218.727.8446
08/11/2020 B.3 FINAL SUBMITTAL
MARK J. VINCENT
52349
05/10/2023 BID
B
IM
/M n A
N G
P ro je c ts
/1
M n A
N G
D O
M O
P S
S to ra g e M
E P
C e n tr a l.
rv t
/1
/2
:2
:3
P
M
E601
05/10/2023
AML
MJV
170859
ELECTRICAL
SCHEDULES
LIGHTING CONTROL DEVICE SCHEDULE
TYPE DESCRIPTION MANUFACTURER
DT OCCUPANCY SENSOR / HIGH BAY WITH AUXILIARY
CONTACTS FOR CONNECTION TO HVAC CONTROLS.
SEE
SPECIFICATIONS
LVD SINGLE GANG, SINGLE PUSHBUTTON FOR LIGHTING
CONTROL.
SEE
SPECIFICATIONS
OSIR OCCUPANCY SENSOR / SWITCH PASSIVE INFRARED,
WHITE WITH STAINLESS STEEL WALL PLATE.
SEE
SPECIFICATIONS
LIGHTING FIXTURE SCHEDULE
TYPE
FIXTURE HOUSING LIGHT SOURCE
DRIVER VOLT WATT NOTEDESCRIPTION LENS / DIFFUSER MOUNTING SOURCE
MINIMUM
LUMEN
OUTPUT
(lm)
MINIMUM
COLOR
TEMP
(KELVIN) CRI
MINIMUM
PROJECTED LIFE
(HOURS)
E1 CONTEMPORARY LED SINGLE FACED EXIT SIGN
WITH BLACK POWDER PAINT ALUMINUM
HOUSING, BRUSHED ALUMINUM FACE, RED
LETTERS, AND CHEVRON ARROWS AS SHOWN ON
PLANS.
--- UNIVERSAL LED --- --- --- 50,000 --- 120 V 5 W
H1 14" X 11" LED HIGH BAY WITH WIDE DISTRIBUTION,
HIGH EFFICIENCY, DIFFUSE LENS, INTEGRAL
DAYLIGHT / OCCUPANCY SENSOR, 5' Y-CABLE &
HOOK, 6' 18GA CORD, 20A TWIST-LOCK PLUG,
WHITE FINISH.
120 DEGREE
DIFFUSE LENS
CABLE
SUSPENDED
ANTI-SWAY
LED 18,000 4000 --- L70 100,000 DIMMABLE
0-10V
277 V 88 W
H1-E 14" X 11" LED HIGH BAY WITH WIDE DISTRIBUTION,
HIGH EFFICIENCY, DIFFUSE LENS, INTEGRAL
DAYLIGHT / OCCUPANCY SENSOR, 5' Y-CABLE &
HOOK, 6' 18GA CORD, 20A TWIST-LOCK PLUG,
WHITE FINISH.
120 DEGREE
DIFFUSE LENS
CABLE
SUSPENDED
ANTI-SWAY
LED 18,000 4000 --- L70 100,000 DIMMABLE
0-10V
277 V 88 W
S1 4' LONG LED STRIP, WIDE DISTRIBUTION. FULL FROSTED
ACRYLIC
DIFFUSE DROP
LENS
SURFACE LED 4,900 3500 --- L87 60,000 DIMMABLE
0-10V
10-100%
277 V 41 W
S1-E 4' LONG LED STRIP, WIDE DISTRIBUTION. FULL FROSTED
ACRYLIC
DIFFUSE DROP
LENS
SURFACE LED 4,900 3500 --- L87 60,000 DIMMABLE
0-10V
10-100%
277 V 41 W
AA1 SINGLE-HEAD FULL CUT-OFF AREA LUMINAIRE
WITH DIE-CAST ALUMINUM HOUSING, TYPE IV
MEDIUM DISTRIBUTION, IP-65 RATED, EMBEDDED
MULTI-LEVEL 30%-100% MOTION SENSOR AND
NEMA 7-PIN RECEPTACLE FOR PHOTOCELL.
ACRYLIC 25' POLE LED 10,613 3000 80 L70 100,000 LED DRIVER 120 V 89 W
WW1 LED WALL PACK WITH CAST ALUMINUM HOUSING,
INTEGRAL SURGE PROTECTION, LEAF / DEBRIS
GUARD, TYPE 3 OPTICS, IDA DARK SKY
COMPLIANT, UL LISTED FOR WET LOCATION,
EMBEDDED MULTI-LEVEL 30%-100% MOTION
SENSOR, AND NEMA 7-PIN RECEPTACLE FOR
PHOTOCELL.
LEAF / DEBRIS
GUARD
WALL
SURFACE
LED 3,343 4000 70+ L70 150,000 LED DRIVER 277 V 47 W
WW1-E LED WALL PACK WITH CAST ALUMINUM HOUSING,
INTEGRAL SURGE PROTECTION, LEAF / DEBRIS
GUARD, TYPE 3 OPTICS, IDA DARK SKY
COMPLIANT, UL LISTED FOR WET LOCATION,
EMBEDDED MULTI-LEVEL 30%-100% MOTION
SENSOR, AND NEMA 7-PIN RECEPTACLE FOR
PHOTOCELL.
LEAF / DEBRIS
GUARD
WALL
SURFACE
LED 3,343 4000 70+ L70 150,000 LED DRIVER 277 V 47 W
LIGHTING CONTROL SEQUENCE OF OPERATIONS SCHEDULE
ROOM ROOM NAME
FC
TARGET
LINE
VOLTAGE
SWITCH
TIME SCHEDULED OCCUPANCY SENSORS OVERRIDE
DAYLIGHT
SENSOR
POWER
PACK (PLUG
LOAD) NOTES
PHOTO
CELL
TIME
CLOCK
AUTO
ON
MANUAL
ON
TIME
DELAY
WALL
SWITCHES
WALL
DIMMERS
MULTI-
ZONE
100 BSERV 50 --- --- --- X --- 15 MIN --- X --- --- X
101 VEHICLE STORAGE 50 --- --- --- X --- 15 MIN --- X --- --- X
102 STORAGE 50 --- --- --- X --- 15 MIN --- X --- --- X
103 TLT 10 --- --- --- X --- 15 MIN X --- --- --- ---
104 COMM 10 --- --- --- --- X --- X --- --- --- ---
105 MECH 10 --- --- --- --- X --- X --- --- --- ---
106 ELEC 10 --- --- --- --- X --- X --- --- --- ---
DOOR HARDWARE, FIRE ALARM, ACCESS CONTROL & INTRUSION DETECTION REQUIREMENTS
LOCATION DOOR NO.
HARDWARE SET
(DIV 08)
POWER TRANSFER
(DIV 08)
ELECTRIC
TRANSFER HINGE
(DIV 08)
AUTO DOOR
OPERATOR/ACTUA
TORS (DIV 08)
DOOR POSITION
SWITCH (DIV 28)
DOOR OPEN
AUDIBLE DEVICE
(DIV 28)
VIDEO
INTERCOM/DOOR
RELEASE (DIV 08)
LATCH
RETRACTION
(DIV 08)
ELECTRIC STRIKE
(DIV 08)
DURESS PUSH
BUTTON (DIV 28)
REQUEST TO EXIT
(DIV 28)
DOOR POSITION
SWITCH - OH DOOR
(DIV 08)
RADIO CONTROL
(DIV 08)
CARD READER
(DIV 28) KEYPAD (DIV 28)
POWER SUPPLY
(DIV 28)
MAGNETIC HOLD
OPEN (DIV 28)
FIRE ALARM
INTERFACE (DIV 28) NOTES
BSERV 100 100.1 5 --- --- --- SEE NOTE 1 --- --- --- SEE NOTE 1 --- SEE NOTE 1 --- --- XX --- SEE NOTE 1 --- ---
VEHICLE STORAGE 101 101.8 5 --- --- --- SEE NOTE 1 --- --- --- SEE NOTE 1 --- SEE NOTE 1 --- --- XX --- SEE NOTE 1 --- ---
STORAGE 102 102.1 5 --- --- --- SEE NOTE 1 --- --- --- SEE NOTE 1 --- SEE NOTE 1 --- --- XX --- SEE NOTE 1 --- ---
STORAGE 102 102.7 5 --- --- --- SEE NOTE 1 --- --- --- SEE NOTE 1 --- SEE NOTE 1 --- --- XX --- SEE NOTE 1 --- ---
NO DATE REVISION
1 09/11/2023 ADDENDUM 02
Typed or Printed Name:
Date: Reg. No.:
I HEREBY CERTIFY that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under the laws of the State of Minnesota.
I HEREBY CERTIFY that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under the laws of the State of Minnesota.
I HEREBY CERTIFY that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under the laws of the State of Minnesota.
Signature:
AUSTEN JAMES BRYAN
09/11/2023 57136
1. PROVIDE NEAM-3R DISCONNECT.
2. PROVIDE DISCONNECT MOUNTED 48" ABOVE GRADE BELOW EXTERIOR FAN. CONCEAL CONDUIT AND CONDUCTORS ROUTED VERTICALLY TO SERVE FAN.
3. RECEIVE PUSHBUTTON CONTROL PAD FROM MANUFACTURER AND INSTALL PER DRAWINGS. PROVIDE CONDUIT AND CONDUCTORS AND MAKE FINAL
CONNECTIONS FOR A COMPLETE AND OPERABLE INSTALLATION.
SCHEDULE NOTES:
1. NOTE 1.
SCHEDULE NOTES:
FILE:
DRAWN BY:
CHECKED BY:
PROJ. NO:
DRAWING NO:
DRAWING TITLE:
PROJECT NAME:
I HEREBY CERTIFY that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under the laws of the State of Minnesota.
Signature:
Typed or Printed Name:
Date: Reg. No.:
THIS SQUARE APPEARS 1/2"x1/2"
ON FULL SIZE SHEETS
CLIENT:
DULUTH, MINNESOTA
148th FIGHTER WING
MINNESOTA AIR
NATIONAL GUARD
CONSTRUCT
DOMOPS STORAGE
170859 MnANG DOMOPS Storage MEP19 Central.rvt
FMKM169006
COPYRIGHT 2023 BY LHB, INC. ALL RIGHTS RESERVED.
NO DATE ISSUED FOR
21 W. Superior St., Ste 500 | Duluth, MN 55802 | 218.727.8446
08/11/2020 B.3 FINAL SUBMITTAL
MARK J. VINCENT
52349
05/10/2023 BID
B
IM
/M n A
N G
P ro je c ts
/1
M n A
N G
D O
M O
P S
S to ra g e M
E P
C e n tr a l.
rv t
/1
/2
:2
:3
P
M
E602
05/10/2023
AML
MJV
170859
ELECTRICAL
SCHEDULES
ELECTRICAL EQUIPMENT SCHEDULE
NO. DESCRIPTION ROOM
LOAD
VOLT PHASE
CONDUIT &
WIRE SIZE
STARTER
COMPONENT
CONTROL DEVICE
COMPONENT
DISCONNECT
COMPONENT NOTESHP A W
ACCU-1 AIR COOLED CONDENSING UNIT 200 7 0 208 1 2#12, 1#12G,
1/2"C
BY MANUF BY DIV 23 NFS
EB-1 ELECTRIC HEATER 105,106 0 761 208 1 2#12, 1#12G,
1/2"C
BY MANUF BY DIV 23 NFS
EF-1 EXHAUST FAN ROOF 2 0 0 208 1 2#12, 1#12G,
1/2"C
BY MANUF BY DIV 23 NFS 1,2
EF-2 EXHAUST FAN 106 4/25 0 0 120 1 2#12, 1#12G,
1/2"C
BY MANUF BY DIV 23 NFS 1,2
ERV-1 AIR TO AIR HEAT EXCHANGER 200 1.5 0 0 208 1 2#12, 1#12G,
1/2"C
BY MANUF BY DIV 23 NFS
FC-1 FAN COIL UNIT 104 1 0 208 1 2#12, 1#12G,
1/2"C
BY MANUF BY DIV 23 NFS
OHD OVERHEAD DOOR VARIES 5 0 120 1 2#12, 1#12G,
1/2"C
SEE NOTE SEE NOTE SEE NOTE 3
P-1 PUMP 105 2 0 120 1 2#12, 1#12G,
1/2"C
BY MANUF BY DIV 23 MRS
UH-1 UNIT HEATER 102 1/4 0 0 120 1 2#12, 1#12G,
1/2"C
BY MANUF BY DIV 23 INTEGRAL
UH-2 UNIT HEATER 101 1/2 0 0 120 1 2#12, 1#12G,
1/2"C
BY MANUF BY DIV 23 INTEGRAL
WH-1 WATER HEATER 105 0 0 120 1 2#12, 1#12G,
1/2"C
BY MAUF BY DIV 23 MRS
SPECIFIC USE EQUIPMENT SCHEDULE
NO. DESCRIPTION ROOM
LOAD
VOLT PHASE
CONDUIT &
WIRE SIZE CONNECTION
CONTROL
DEVICE
COMPONENT
DISCONNECT
COMPONENT NOTEA
EQ-01 30A SHORELINE BATTERY CHARGER PIN & SLEEVE 100 30 120 1 3-WIRE RCPT INTEGRAL
EQ-02 SHORELINE INLET TWIST LOCK 100 50 208 1 4-WIRE RCPT INTEGRAL NEMA H-37
EQ-03 120V DUPLEX 101 0 120 1 3-WIRE RCPT INTEGRAL NEMA 1-15
EQ-04 PIN & SLEEVE SHORE POWER 101 30 208 3 5-WIRE RCPT INTEGRAL
EQ-05 TWIST LOCK SHORE POWER 101 50 208 1 4-WIRE RCPT INTEGRAL NEMA H-37
EQ-06 L14 30P TWIST LOCK 101 30 208 3 4-WIRE RCPT INTEGRAL NEMA H-20
EQ-07 120V DUPLEX 102 0 120 1 3-WIRE RCPT INTEGRAL NEMA 1-15
EQ-08 HUBBELL TWIST LOCK 102 50 208 3 4-WIRE RCPT INTEGRAL NEMA H-38
1. PANEL B IS FEED THROUGH LUGS AND SHOULD NOT OCCUPY THIS POLE SPACE (50,52, & 54).
NOTES:
SPEC 10400 VA 100.00% 10400 VA EST. DEMAND CURRENT: 194 A
MTR 22734 VA 104.29% 23708 VA CONNECTED CURRENT: 262 A
LITES 356 VA 125.00% 445 VA ESTIMATED DEMAND: 69907 VA
RCPT 60828 VA 58.22% 35414 VA CONNECTED LOAD: 94266 VA
Other 0 VA 0.00% 0 VA
LOAD CLASSIFICATION CONNECTED DEMAND ESTIMATED PANEL TOTALS
TOTAL AMPS: 279 A 290 A 230 A
TOTAL LOAD: 33 kVA 34 kVA 28 kVA
SPARE 20 A 1 53 0.0 23.2 54
SPARE 20 A 1 51 0.0 29.1 52
SPARE 20 A 1 49 0.0 26.6 50
3 20 A PANEL B
SPARE 20 A 1 47 0.0 0.0 48 1 20 A SPARE
SPARE 20 A 1 45 0.0 0.0 46 1 20 A SPARE
SPARE 20 A 1 43 0.0 0.0 44 1 20 A SPARE
SPARE 20 A 1 41 0.0 0.0 42 1 20 A SPARE
SECP 104 20 A 1 39 0.0 0.0 40 1 20 A HD 103
FACP 104 20 A 1 37 0.0 0.4 38 1 20 A RCPT 200
35 0.0 0.0 36 1 20 A RCPT 103
SPEC 104 20 A 2
33 0.0 0.4 34 1 20 A RCPT 105
RCPT 101 20 A 1 31 0.9 0.2 32 1 20 A RCPT 106
OHD 101 20 A 1 29 0.6 0.5 30 1 20 A RCPT 104
OHD 101 20 A 1 27 0.6 0.0 28
OHD 101 20 A 1 25 0.6 0.0 26
2 20 A SPEC 104
OHD 100 20 A 1 23 0.6 0.6 24 1 20 A OHD 102
RCPT & EQ-03 101 20 A 1 21 0.4 0.6 22 1 20 A OHD 102
RCPT 100 20 A 1 19 0.7 0.5 20 1 20 A RCPT 102,104
RCPT 101 20 A 1 17 0.4 0.2 18 1 20 A RCPT & EQ-O7 102
RCPT 101 20 A 1 15 0.4 0.9 16 1 20 A RCPT 102
RCPT 100 20 A 1 13 0.4 0.4 14 1 20 A RCPT 102
RCPT 100 20 A 1 11 0.4 0.6 12 1 20 A OHD 102
OHD 101 20 A 1 9 0.6 0.6 10 1 20 A OHD 102
OHD 101 20 A 1 7 0.6 0.6 8 1 20 A OHD 102
OHD 101 20 A 1 5 0.6 0.0 6 1 20 A SPARE
OHD 101 20 A 1 3 0.6 0.0 4 1 20 A SPARE
OHD 100 20 A 1 1 0.6 0.4 2 1 20 A LITES SITE
LOAD DESCRIPTION BKR P CKT A B C CKT P BKR LOAD DESCRIPTION
BUS AMPS: 225 AMPS
MAIN DEVICE: 225 A MAIN CB SPECIAL:
MOUNTING: SURFACE NEMA 1 A.I.C. RATING: 10,000 AMPS SYMMETRICAL
LOCATION: ELEC 106 VOLTAGE: 208Y/120 V. 3 ø 4 W.
PANELBOARD: PANEL A
NOTES:
EST. DEMAND CURRENT: 160 A
CONNECTED CURRENT: 219 A
SPEC 10400 VA 100.00% 10400 VA ESTIMATED DEMAND: 57690 VA
MTR 14485 VA 105.68% 15308 VA CONNECTED LOAD: 78860 VA
RCPT 53988 VA 59.26% 31994 VA
LOAD CLASSIFICATION CONNECTED DEMAND ESTIMATED PANEL TOTALS
TOTAL AMPS: 226 A 247 A 193 A
TOTAL LOAD: 27 kVA 29 kVA 23 kVA
SPARE 20 A 1 53 0.0 0.0 54 1 20 A SPARE
SPARE 20 A 1 51 0.0 0.0 52 1 20 A SPARE
SPARE 20 A 1 49 0.0 0.0 50 1 20 A SPARE
SPARE 20 A 1 47 0.0 0.0 48 1 20 A SPARE
SPARE 20 A 1 45 0.0 0.0 46 1 20 A SPARE
SPARE 20 A 1 43 0.0 0.0 44 1 20 A SPARE
SPARE 20 A 1 41 0.0 0.0 42 1 20 A SPARE
SPARE 20 A 1 39 0.0 0.0 40 1 20 A SPARE
SPARE 20 A 1 37 0.0 0.0 38 1 20 A SPARE
SPARE 20 A 1 35 0.0 0.0 36 1 20 A SPARE
SPARE 20 A 1 33 0.0 0.2 34 1 20 A P-1
SPARE 20 A 1 31 0.0 0.0 32 1 20 A INVERTER
SPARE 20 A 1 29 0.0 0.2 30 1 20 A WH-1
27 6.0 1.2 28 1 20 A UH-2
25 6.0 1.2 26 1 20 A UH-2RCPT 102 50 A 3
23 6.0 1.4 24 1 20 A UH-1
21 3.6 1.4 22
19 3.6 1.4 20
2 20 A EF-1
EQ-06 101 50 A 3
17 3.6 1.4 18
15 3.6 1.4 16
2 20 A EF-1
13 3.6 0.1 14 1 20 A EF-2EQ-04 101 50 A 3
11 3.6 0.8 12
9 5.2 0.8 10
2 20 A EB-1
EQ-05 101 50 A 2
7 5.2 1.1 8
5 5.2 1.1 6
2 20 A ERV-1
EQ-02 100 50 A 2
3 5.2 0.7 4
EQ-01 100 50 A 1 1 3.6 0.7 2
2 20 A ACCU-1
LOAD DESCRIPTION BKR P CKT A B C CKT P BKR LOAD DESCRIPTION
BUS AMPS: 225 AMPS
MAIN DEVICE: 225 A MAIN CB SPECIAL:
MOUNTING: SURFACE NEMA 1 A.I.C. RATING: 10,000 AMPS SYMMETRICAL
LOCATION: ELEC 106 VOLTAGE: 208Y/120 V. 3 ø 4 W.
PANELBOARD: PANEL B
125/250
125/250
1. FOR 20A CIRCUIT BREAKERS PROVIDE 60A FRAME MAXIMUM OR SMALLER SIZEPER MANUFACTURER'S STANDARD PRODUCT
OFFERING.
NOTES:
EST. DEMAND CURRENT: 89 A
CONN. CURRENT: 117 A
EST. DEMAND LOAD: 74151 VA
SPEC 10400 VA 100.00% 10400 VA CONN. LOAD: 97657 VA
MTR 22734 VA 104.29% 23708 VA
LITES 4123 VA 125.00% 5154 VA
RCPT 60828 VA 58.22% 35414 VA
Other 0 VA 0.00% 0 VA
LOAD CLASSIFICATION CONNECTED DEMAND ESTIMATED PANEL TOTALS
7 60 A 1 20 A 0.4 kVA LITES 3 60 A 1 20 A 1.2 kVA LITES 2 200 A 3 110 A 94.3 kVA T1 1 60 A 1 20 A 2.1 kVA LITES
CKT FRAME POLES RATING
CONNECTED
KVA DESCRIPTION/NAMEPLATE NOTES
SECTION No. 1
BUS AMPS: 400 AMPS SPECIAL:
MAIN DEVICE: 400 A MCB A.I.C. RATING: 24,000 AMPS SYMMETRICAL
LOCATION: ELEC 106 VOLTAGE: 480Y/277 V. 3 ø 4 W.
DISTRIBUTION PANEL: MDP
NO DATE REVISION
1 07/12/2021 ADDENDUM 02
2 09/11/2023 ADDENDUM 02
2 2
Typed or Printed Name:
Date: Reg. No.:
I HEREBY CERTIFY that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under the laws of the State of Minnesota.
I HEREBY CERTIFY that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under the laws of the State of Minnesota.
I HEREBY CERTIFY that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under the laws of the State of Minnesota.
Signature:
AUSTEN JAMES BRYAN
09/11/2023 57136
File details come from the government source that posted it. Updated .