Heat exchanger constructed and tested in accordance with
ASME Section IV standard.
CROWN Series 32 boilers are designed for the special heating needs of businesses, institutions, apartments and other commercial buildings Series 32 boilers are equipped with proven con-trols and safety features to optimize opera-tion. With built-in draft hoods, they will fit under low ceilings. Control options make them the best choice for a wide variety of installations.
Wide range of sizes The Series 32 boilers can supply heating loads from 475 to 2,850 MBH input.
Domestic hot water can be provided by an optional tankless coil water heater on water boilers only. The steam boilers are tapped for Mega-Stor or Maxi-Therm indirect water heaters.
The hot water boiler has a maximum allowable working pressure of 50 PSI. The steam boiler has a maximum allowable working pressure of 15 PSI. Both have combustion efficiencies of
80.5 percent, meeting the requirements of
ASHRAE 90.1.
Durable materials Heat exchanger sections for the Series 32 boiler are constructed of cast iron that transfers heat quickly and efficiently. The burners are long lasting stainless steel, and designed for quiet, trouble free operation.
For optimum efficiency, the heating surfaces and vertical flues in the heat exchangers are cast with pins to increase the surface area.
This design gets the maximum heat from every BTU of fuel while keeping draft losses low.
Cast iron push nipples – which are used to assemble the heat exchanger sections – resist corrosion from petroleum-based chemicals including corrosion inhibitors, pump lubricants and antifreeze, and won’t break down from contact with flue gases.
Cast iron push nipples expand and contract at the same rate as the sections they join, so the entire assembly will remain water tight.
Modular design The Series 32 has a compact design which uses preassembled and tested base modules.
These modules have individual gas trains with a residential style combination gas valve and ignition control for simplicity and redundancy.
These base modules are combined to provide the appropriate input.
Heat exchanger sections are shipped unassembled, which makes them easier to han-dle, get through narrow doorways and assem-ble. The sections can be ordered factory assembled.
Products that serve customers well Like all
CROWN
boilers, the Series 32 design draws upon years of experience providing products that serve our customers well. The Series 32 joins an extensive lineup of boilers that heat homes and businesses with chimneys and those that require through the wall venting or sealed combustion. CROWN’s line provides hot water or steam, fueled by gas or oil. And all CROWN products are backed by competitive warranties and by outstanding technical support.
Standard Equipment For Natural Gas only Sections unassembled; end section tapped for use with optional tankless coil (water only) Base and gas train fully assembled and tested before shipment Water Trim: 30 PSI relief valve (50 PSI optional); pres-sure temperature gauge, L4006A high limit control Steam Trim: 15 PSI safety valve, steam gauge, gauge glass set, pressure limit control, #67 LWCO
Tankless Coil Model Number
For Use In Boilers
Continuous Draw Coil Ratings
40° - 140° Rise with 200°F Boiler
Temperature
Pressure Drop Through Coil
(psi)
Minimum Number of Sections
Required Per Coil
Clearance Requirement For
Coil Removal
T-1 All Sizes 4.5 GPM 8.8 5 27"
T-2 All Sizes 5.0 GPM 18.0 6 32"
T-3 32-665 & Larger 6.0 GPM 1.2 8 42"
All Series 32 boilers are furnished with left and right heater end sections. It is possible to install a heater in both ends provided the number of sections in the boiler in not less than the sum of the number of sections required for each heater as indicated in the table. Example: T2 + T3 = 6 + 8 = 14 section or larger boiler.
Data for Optional Tankless Coil Water Heater
Optional Equipment CSD-1 compliant control system Factory assembled sections Selection of LWCO, feeders and limit controls available Mega-Stor or Maxi-Therm indirect water heater
Features A. Built-in draft hood enables installation under low ceilings.
B. High performance tankless coil available on water boilers for domestic hot water.
C. Stainless steel burners assure long life and resist corrosion.
D. Gas controls meet full requirements of ANSI Z21.13. Gas train constructed of simple, residential style combination gas valves.
E. Supply tappings at top for ease of system piping.
A
B
C
D
E
Jacket Overall Length
'A' 'B'
Dia.
'C' Dia.
'D' Dia.
'E' Dia.
'F' Dia.
'G' Dia.
'H' 'J' 'K' 'L' 'M' 'N' 'P' 'R' 'S' 'T' 'U' 10" 12"
32-475 36 3/4 12 - - - - - - - - - - 18 3/8 27 3/16 - - - - - 1
32-570 42 1/4 10 10 - - - - 16 5/16 - - - - 12 15/16 32 5/8 - - - - 2 -
32-665 47 5/8 10 12 - - - - 19 1/16 - - - - 15 11/16 38 1/16 - - - - 1 1
32-760 53 1/8 12 12 - - - - 21 3/4 - - - - 15 11/16 43 1/2 - - - - - 2
32-855 58 1/2 12 12 - - - - 24 7/16 - - - - 18 3/8 48 15/16 - - - - - 2
32-950 64 12 12 - - - - 27 3/16 - - - - 18 3/8 54 3/8 - - - - - 2
32-1045 69 3/8 10 12 12 - - - 19 1/16 21 3/4 - - - 15 11/16 27 3/16 32 5/8 - - - 1 2
32-1140 74 7/8 12 12 12 - - - 21 3/4 21 3/4 - - - 15 11/16 32 5/8 32 5/8 - - - - 3
32-1235 80 1/4 10 12 12 - - - 21 3/4 27 3/16 - - - 18 3/8 32 5/8 38 1/16 - - - 1 2
32-1330 85 3/4 12 12 12 - - - 24 7/16 27 3/16 - - - 18 3/8 38 1/16 38 1/16 - - - - 3
32-1425 91 1/8 12 12 12 - - - 27 1/4 27 3/16 - - - 18 3/8 38 1/16 43 1/2 - - - - 3
32-1520 96 5/8 12 12 12 12 - - 21 3/4 21 3/4 21 3/4 - - 15 11/16 43 1/2 43 1/2 - - - - 4
32-1615 102 10 12 12 12 - - 19 1/16 24 7/16 27 3/16 - - 18 3/8 32 5/8 32 5/8 27 3/16 - - 1 3
32-1710 107 1/2 12 12 12 12 - - 21 3/4 24 7/16 27 3/16 - - 18 3/8 32 5/8 38 1/16 27 3/16 - - - 4
32-1805 112 7/8 12 12 12 12 - - 24 7/16 27 1/4 27 3/16 - - 18 3/8 32 5/8 32 5/8 38 1/16 - - - 4
32-1900 118 3/8 12 12 12 12 - - 27 1/4 27 1/4 27 3/16 - - 18 3/8 32 5/8 38 1/16 38 1/16 - - - 4
32-1995 123 3/4 10 10 12 12 12 - 16 5/16 21 3/4 27 3/16 27 3/16 - 18 3/8 38 1/16 38 1/16 38 1/16 - - 2 3
32-2090 129 1/4 12 12 12 12 12 - 21 3/4 21 3/4 24 7/16 27 3/16 - 18 3/8 32 5/8 32 5/8 27 3/16 27 3/16 - - 5
32-2185 134 5/8 12 12 12 12 12 - 21 3/4 24 7/16 27 3/16 27 3/16 - 18 3/8 38 1/16 32 5/8 27 3/16 27 3/16 - - 5
32-2280 140 1/8 12 12 12 12 12 - 24 7/16 27 3/16 27 3/16 27 3/16 - 18 3/8 32 5/8 32 5/8 32 5/8 32 5/8 - - 5
32-2375 145 1/2 12 12 12 12 12 - 27 3/16 27 3/16 27 3/16 27 3/16 - 18 3/8 32 5/8 32 5/8 32 5/8 38 1/16 - - 5
32-2470 151 10 10 12 12 12 12 16 5/16 21 3/4 27 3/16 27 3/16 27 3/16 18 3/8 32 5/8 32 5/8 38 1/16 38 1/16 - 2 4
32-2565 156 3/8 10 12 12 12 12 12 19 1/16 24 7/16 27 3/16 27 3/16 27 3/16 18 3/8 38 1/16 32 5/8 38 1/16 38 1/16 - 1 5
32-2660 161 7/8 12 12 12 12 12 12 21 3/4 24 7/16 27 3/16 27 3/16 27 3/16 18 3/8 32 5/8 32 5/8 32 5/8 27 3/16 27 3/16 - 6
32-2755 167 1/4 12 12 12 12 12 12 24 7/16 27 3/16 27 3/16 27 3/16 27 3/16 18 3/8 32 5/8 32 5/8 32 5/8 32 5/8 27 3/16 - 6
32-2850 172 3/4 12 12 12 12 12 12 27 3/16 27 3/16 27 3/16 27 3/16 27 3/16 18 3/8 32 5/8 32 5/8 32 5/8 32 5/8 32 5/8 - 6
1. All Dimensions Are Approximate.
Flue Outlet No. & Size
Boiler Model Number
Top Supply Location
Drafthood Size & Location
Dimensions (inches): When ordering specify water or steam
(BOTH SIDES)
3" RETURN TAPPING
5 1/2
24 1/4
4 3/4 4 3/4
'A'
' H ' ' J ' ' K ' ' L ' ' M ' ' N '
' B ' ' D ' ' E '' C ' ' F ' ' G '
' P ' ' R ' ' S ' ' T ' ' U ' 8 3/4
42 5/8
49 1/8
46 5/8
54 1/4
12 1/4
14 7/8
3" SUPPLY TAPPINGS
TANKLESS HEATER
OPENING (BOTH SIDES)
32 1/4 7 3/4
TOP VIEW
FRONT VIEWLEFT SIDE VIEW RIGHT SIDE VIEW
General Configuration of the Base Model
(See Manual If Required) Bypass Line
Gauge
Limit
Limit Manual Reset
Cut-Off Low Water
Valve Drain System
From
Valve Throttling
Valve Throttling
Line Cold Water
Expansion Tank
Circulator
Air Vent
Fill Valve
To System
Isolation Valve
Valve Isolation
Relief Valve
Recommended Hot Water Boiler Piping
Hot Water Boiler Supply and Return Pipe Sizes
Supply Supply Water Return Return Water Boiler Header Riser Connections Header Connections Model Size (in) Quantity Size (in) Size (in) Quantity Size (in)
32-475 2 1 2 2 1 2 32-570 2 1 2 2 1 2 32-665 2 1/2 1 2 1/2 2 1/2 1 2 1/2 32-760 2 1/2 1 2 1/2 2 1/2 1 2 1/2 32-855 2 1/2 1 2 1/2 2 1/2 1 2 1/2 32-950 3 1 3 3 1 3 32-1045 3 1 3 3 1 3 32-1140 3 1 3 3 1 3 32-1235 3 1 3 3 1 3 32-1330 3 1 3 3 1 3 32-1425 3 1 3 3 1 3 32-1520 3 2 2 1/2 3 2 2 1/2 32-1615 3 2 2 1/2 3 2 2 1/2 32-1710 3 2 2 1/2 3 2 2 1/2 32-1805 3 2 2 1/2 3 2 2 1/2 32-1900 3 2 3 3 2 3 32-1995 4 2 3 4 2 3 32-2090 4 2 3 4 2 3 32-2185 4 2 3 4 2 3 32-2280 4 2 3 4 2 3 32-2375 4 2 3 4 2 3 32-2470 4 2 3 4 2 3 32-2565 4 2 3 4 2 3 32-2660 4 2 3 4 2 3 32-2755 4 2 3 4 2 3 32-2850 4 2 3 4 2 3
Note: 1.The pipe sizes listed above are nominal trade sizes for Schedule 40 pipe.
CLOSE OR
SHOULDER
D
E
TEE
E
GATE VALVE
NIPPLE ONLY
HEADER - MINIMUM 24"
ABOVE NORMAL WATER LINE
GLOBE
VALVE
GATE
VALVE
D
D
C
C
C
A
RISER
A
SUPPLY MAIN(S) TO BE TAKEN OFF TOP OF
HEADER VERTICALLY OR AT A 45° ANGLE
PIPE DISCHARGE TO
A SAFE LOCATION
MAKE-UP
FROM SYSTEM
DOWN TO BOILER
PREFERRED PIPING
ALTERNATE PIPING
CONNECTION
E
E
E
E
E
EQUALIZER
RETURN
CLEAN-OUT PLUG
TEE WITH
WET RETURN - PITCH
PROVIDE DRAIN VALVE FOR
FLUSHING BOILER AND SYSTEM
WATER"Y" HARTFORD RETURN
C A
A
TO SYSTEM
TO SYSTEM
B
A
SUPPLY
24" MIN
SUPPLY
ARISER
ARISER
N.W.L.
LINE
FLOOR
36 1/2"
KEEP BOILER
FILLED TO NORMAL
WATER LINE
2"
BOILER
FRONT OF
STEAM SUPPLY MAIN(S) - SLOPE DOWN FROM HIGH POINT
ABOVE BOILER AND DRIP END(S) INTO WET RETURN -
LOW POINT OF SUPPLY MAIN(S) TO BE NOT LESS THAN
28" ABOVE NORMAL WATER LINE.
INSTALL SAFETY VALVE
ON SIDE OPPOSITE TRIM
Three Supply Connections;
Gravity Return
Minimum Pipe Sizes
Minimum Pipe Sizes
FOR A GIVEN SIZE BOILER IN THIS RANGE.
USING THE LARGEST PIPE DIAMETER AS INDICATED IN B
TO FABRICATE THE ENTIRE LENGTH OF THE STEAM HEADER
NOTE: FOR BOILER MODELS 1045 THRU 1520 IT IS PERMISSIBLE
2" 2-1/2"
6" 4" 3"
32-152032-142532-133032-123532-114032-1045 A B
D C
E
5"
3" 3" 3" 3" 3"
2-1/2" 2"
5" 5" 5" 5" 2-1/2"2-1/2"2-1/2"2-1/2"
2"2"2"2"
4" 4" 4" 4" 4"
STEAM SUPPLY MAIN(S) - SLOPE DOWN
FROM HIGH POINT ABOVE BOILER AND
DRIP END(S) INTO WET RETURN - LOW
POINT OF SUPPLY MAIN(S) TO BE NOT LESS
THAN 28" ABOVE NORMAL WATER LINE
A
A
A
A
A
B
B B
C
D
D D
C
D
2"
24" MIN
36-1/2"
N.W.L.
FLOOR
LINE
RISER*
RISER
SUPPLY
FRONT OF
BOILER
KEEP BOILER
FILLED TO NORMAL
WATER LINE
HEADER - MINIMUM 24"
ABOVE NORMAL WATER LINE
SUPPLY MAIN(S) TO BE TAKEN OFF TOP OF
HEADER VERTICALLY OR AT A 45∞ ANGLE
PIPE DISCHARGE TO
A SAFE LOCATION
RETURN
"Y"
TEE
GATE VALVE
MAKE-UP
HARTFORD RETURN
PREFERRED PIPING
WET RETURN - PITCH
DOWN TO BOILER
CLOSE OR
SHOULDER
NIPPLE ONLY
PROVIDE DRAIN VALVE FOR
FLUSHING BOILER AND SYSTEMCLEAN-OUT PLUG
TEE WITH
TO SYSTEM
EQUALIZER
FROM SYSTEM
WATER
C
B
D
GLOBE
VALVE
GATE
VALVE
D
D
ALTERNATE PIPING
CONNECTION
INSTALL SAFETY VALVE
ON SIDE OPPOSITE TRIM
* SECOND SUPPLY RISER OPTIONAL
2"2"
2-1/2"
5"
3"
2-1/2"
4"
3"
2"
2-1/2" 4"
3"
2"
2-1/2" 4"
3"
1-1/2"
2"
4"
3"3"
1-1/2"
2"
3"
C
D
B
A
32-475* 32-570 32-665 32-760 32-855 32-950
Recommended Steam Boiler Piping
One or Two Supply Connections;
Gravity Return
Minimum Pipe Sizes
NOTE: FOR BOILER MODELS 1615 THRU 2850 IT IS PERMISSIBLE TO FABRICATE THE ENTIRE LENGTH OF THE STEAM HEADER USING THE LARGEST PIPE DIAMETER AS INDICATED IN C, D OR E FOR A GIVEN SIZE BOILER IN THIS RANGE.
2"
6"
2"
1615*
2-1/2"
6"
4"
3"
6"
2-1/2"
1710*
6"
4"
3"
6"
2-1/2"
1805*
3"
6"
4"
3"
6"
2-1/2"
1900*
3"
6"
4"
3"
6"
2-1/2"
1995*
3"
6"
4"
3"
6"
2-1/2"
2090*
3"
6"
4"
3"
8"
2-1/2"
2185**
3"
8"
6"
4"
3"
8"
2-1/2"
2280**
3"
8"
6"
4"
3"
8"
2-1/2"
2375**
3"
8"
6"
4"
3"
8"8"8"8"8"F
4"4"4"4"3"G
3"3"
6"6"6"6"
2850***2755***2565** 2660***2470**
3"
4"4"
3"3"
4"4"
3"3"
4"
6"C
B
A
8"
8"
H 2-1/2" 3" 3"
8"8"-
8"8"8"8"
-E
D
* FOUR SUPPLY RISERS REQUIRED ** FIVE SUPPLY RISERS REQUIRED *** SIX SUPPLY RISERS REQUIRED
A
RISER
RISER
RISER
RISER
SUPPLY
SUPPLY
SUPPLY
A
A
A
A
A
A
A
A
SUPPLY
SUPPLY
A
D
C
B
A
F F
E F
SUPPLY MAIN(S) TO BE TAKEN OFF TOP
OF HEADER VERTICALLY OR AT A 45° ANGLE
ABOVE NORMAL WATER LINE
HEADER - MINIMUM 24"
F
TO SYSTEM
RISERA
CONNECTION
ALTERNATE PIPING
H
H
VALVE
GATE
VALVE
GLOBE
H
G
WATER
FROM SYSTEM
EQUALIZER
TEE WITH
CLEAN-OUT PLUG
FLUSHING BOILER AND SYSTEM
PROVIDE DRAIN VALVE FOR
NIPPLE ONLY
SHOULDER
CLOSE OR
DOWN TO BOILER
WET RETURN - PITCH
PREFERRED PIPING
HARTFORD RETURNMAKE-UP
GATE VALVE
TEE
"Y"
RETURN
PIPE DISCHARGE TO
A SAFE LOCATION
WATER LINE
FILLED TO NORMAL
KEEP BOILER
BOILER
FRONT OF
RISER
LINE
FLOOR
N.W.L.
36-1/2"
24" MIN
2"
H
G
HH
H
G
A
PIPE
DISCHARGE
TO A SAFE
LOCATION
INSTALL SAFETY VALVE ON SIDE
OPPOSITE TRIM (2280 & SMALLER)
STEAM SUPPLY MAIN(S) - SLOPE DOWN FROM
HIGH POINT ABOVE BOILER AND DRIP END(S)
INTO WET RETURN - LOW POINT OF SUPPLY
MAIN(S) TO BE NOT LESS THAN 28" ABOVE
NORMAL WATER LINE.
INSTALL SAFETY VALVE AT THIS LOCATION
FOR BOILER MODELS 2375 & HIGHER.
Recommended Steam Boiler Piping
Four, Five or Six Supply Connections;
Gravity Return
Since 1949, homeowners have depended on us for quality, value and service 3633 I Street, P. O. Box 14818 Philadelphia, PA 19134 Phone: (215) 535-8900 Fax: (215) 535-9736 Visit us on the web: www.crownboiler.com
S32-11/07 (10M) R-1
PN980535
Water
(MBH) (MBH) (Sq. ft) (MBH) (MBH) (Gal) (Gal)
32-475 6 475 380 1188 285 330 80.5 28.58 39.80 11.4
32-570 7 570 456 1425 342 397 80.5 32.65 45.47 13.6
32-665 8 665 532 1663 399 463 80.5 36.72 51.14 15.9
32-760 9 760 608 1900 456 529 80.5 40.79 56.81 18.2
32-855 10 855 684 2138 513 595 80.5 44.86 62.48 20.4
32-950 11 950 760 2376 570 661 80.5 48.93 68.15 22.7
32-1045 12 1045 836 2613 627 727 80.5 53.00 73.82 25.0
32-1140 13 1140 912 2851 684 793 80.5 57.07 79.49 27.2
32-1235 14 1235 988 3088 741 859 80.5 61.14 85.16 29.5
32-1330 15 1330 1064 3326 798 925 80.5 65.21 90.83 31.8
32-1425 16 1425 1140 3563 855 991 80.5 69.28 96.50 34.1
32-1520 17 1520 1216 3801 912 1057 80.5 73.35 102.17 36.3
32-1615 18 1615 1292 4050 972 1123 80.5 77.42 107.84 38.6
32-1710 19 1710 1368 4312 1035 1190 80.5 81.49 113.51 40.9
32-1805 20 1805 1444 4575 1098 1256 80.5 85.56 119.18 43.1
32-1900 21 1900 1520 4839 1161 1322 80.5 89.63 124.85 45.4
32-1995 22 1995 1596 5102 1225 1388 80.5 93.70 130.52 47.7
32-2090 23 2090 1672 5366 1288 1454 80.5 97.77 136.19 49.9
32-2185 24 2185 1748 5628 1351 1520 80.5 101.84 141.86 52.2
32-2280 25 2280 1824 5890 1414 1586 80.5 105.91 147.53 54.5
32-2375 26 2375 1900 6143 1474 1652 80.5 109.98 153.20 56.8
32-2470 27 2470 1976 6392 1534 1718 80.5 114.05 158.87 59.0
32-2565 28 2565 2052 6638 1593 1784 80.5 118.12 164.54 61.3
32-2660 29 2660 2128 6884 1652 1850 80.5 122.19 170.21 63.6
32-2755 30 2755 2204 7130 1711 1917 80.5 126.26 175.88 65.8
32-2850 31 2850 2280 7376 1770 1983 80.5 130.33 181.55 68.1
WATER
VOL. 2 BHP
OUTPUT3
1. Water Volume Total To Normal Water Line (Steam Boiler).
2. Water Volume Total (Water Boiler).
3. Ratings Based on 33,475 Btuh Per Boiler Horsepower
BASIC
BOILER
MODEL
NUMBER
OF
SECTIONS
WATER
VOL. 1
NATURAL GAS ONLY
HEATING
CAPACITY
Combustion Efficiency
INPUT
I=B=R NET RATING
Steam STEAM WATER
SHIPPING
WEIGHT
(APPROX)
Specifications: When ordering specify water or steam
Not for installation on combustible flooring