Text version
M201
FIRST FLOOR
MECHANICAL
PLANS
PROJECT # NGB
DRAWN BY
DATE 01-06-2017
Date Revision Description
DRAWINGS
CONSTRUCTION
TMS @@@CHECKED BY
DRAWING NUMBER
DRAWING TITLE
N
N
N
AutoCAD SHX Text
NDI LAB
AutoCAD SHX Text
AutoCAD SHX Text
NDI X-RAY
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
SPECIFIC PLAN NOTES
AutoCAD SHX Text DISCONNECT AND REMOVE EXISTING OUTSIDE AIR INTAKE LOUVER. POWER TO BE DISCONNECTED BY ELECTRICAL CONTRACTOR. PROVIDE TRANSFER DUCT THROUGH BLOCK WALL OPENING. (NOMINAL 15"x7" DUCT.) PROVIDE WITH TRANSFER GRILLES ON EACH SIDE OF BLOCK WALL EQUAL TO CARNES STURDICORE STYLE HEAVY DUTY GRILLES WITH 40° DEFLECTION. SIZE GRILLES TO EXTEND TO EDGE OFANGLE IRON FRAME. PRIME AND PAINT GRILLES AND ANGLE IRON TO MATCH WALL COLOR. DISCONNECT AND REMOVE EXISTING EXHAUST FAN. RETAIN CURB FOR RE-USE. SEE PLAN FOR NEW WORK. POWER TO BE DISCONNECTED BY ELECTRICAL CONTRACTOR.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
NDI LAB
AutoCAD SHX Text
AutoCAD SHX Text
NDI X-RAY
AutoCAD SHX Text
AutoCAD SHX Text 10"x10" ALUMINUM EXHAUST DUCT UP TO EXHAUST FAN EF-1.EF-1..
AutoCAD SHX Text 16"x6" ALUMINUM OPEN ENDED EXHAUST DUCT.
AutoCAD SHX Text THREE 4" PVC EXHAUST DROPS DOWN TO RESPECTIVE TEST STANDEQUIPMENT (OFFSET ALONG WALL AS REQUIRED TO CENTER OVER TEST STAND.) STOP 4" PVC 12" MIN. ABOVE TEST STAND EQUIPMENT.(FIELD VERIFY). PROVIDE WITH 45° ELBOW AND CONNECTION COUPLINGADAPTER FOR CONNECTION TO TEST STAND HOSE ADAPTER.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text M
AutoCAD SHX Text INSTALL ALL NEW ALUMINUM EXHAUST DUCTWORK AS TIGHT TO THE UNDERSIDE OF STRUCTURE AS POSSIBLE.
AutoCAD SHX Text M
AutoCAD SHX Text REUSE EXISTING EQUIPMENT CURB. PROVIDE CURB ADAPTER AS NEEDED TO ALLOW FOR NEW FAN ASSEMBLY TO BE MATED TO EXISTING EQUIPMENT CURB.
AutoCAD SHX Text 6"x16" ALUMINUM OPEN ENDED EXHAUST DUCT
AutoCAD SHX Text 10"x10" ALUMINUM EXHAUST DUCT
AutoCAD SHX Text THREE 4" PVC EXHAUST DROPS DOWN TO RESPECTIVE TEST STANDEQUIPMENT (OFFSET ALONG WALL AS REQUIRED TO CENTER OVER TEST STAND.) STOP 4" PVC 12" MIN. ABOVE TEST STAND EQUIPMENT.(FIELD VERIFY). PROVIDE WITH 45° ELBOW AND CONNECTION COUPLINGADAPTER FOR CONNECTION TO TEST STAND HOSE ADAPTER.
AutoCAD SHX Text SLIGHTLY EXTEND 4" EXHAUST DUCTS INTO 6"x16"OPEN END DUCT TO ESSENTIALLY CREATE A THIMBLE CONNECTION. DO NOT DIRECT CONNECT THE 4" DO NOT DIRECT CONNECT THE 4" DIRECT CONNECT THE 4" EXHAUST DUCTS TO THE 6"x16" EXHAUST MAIN.
AutoCAD SHX Text
TEST STAND EQUIPMENT SHOWN FOR INTENT.
AutoCAD SHX Text
FINAL CONNECTION TO TEST STAND EQUIPMENT BY OWNER.
AutoCAD SHX Text EF-1: ALUMINUM/CORROSION RESISTANT ROOF STYLE EXHAUST FAN RATED : ALUMINUM/CORROSION RESISTANT ROOF STYLE EXHAUST FAN RATED FOR 120 CFM AT 0.25" ESP, 120V. EQUAL TO COOK 70C15DH. PROVIDE WITH ELECTRONIC SPEED CONTROLLER FOR BALANCING PURPOSES. POWER TO BE EXTENDED BY ELECTRICAL CONTRACTOR. FAN TO RUN CONTINUOUS.
AutoCAD SHX Text MOTOR OPERATED DAMPER INTERLOCKED WITH FAN CONTROL SWITCH. LOCATE SWITCH ON WALL OF TEST STAND EQUIPMENT. FIELD VERIFY.
AutoCAD SHX Text
RELOCATED LIGHT FIXTURE SHOWN FOR COORDINATION.
AutoCAD SHX Text
RELOCATED LIGHT FIXTURE SHOWN FOR COORDINATION.
AutoCAD SHX Text INSTALL ALL NEW ALUMINUM EXHAUST DUCTWORK AS TIGHT TO THE UNDERSIDE OF STRUCTURE AS POSSIBLE.
AutoCAD SHX Text
EXISTING STRUCTURAL JOISTS SHOWN FOR COORDINATION INTENT.
AutoCAD SHX Text
BUILDING 2050, 175TH WG
AutoCAD SHX Text
BALTIMORE MARYLAND
AutoCAD SHX Text
235 CEF
AutoCAD SHX Text
NDI LAB X-RAY ROOM EXHAUST
AutoCAD SHX Text
2701 EASTERN BLVD, 2050 BUILDING
AutoCAD SHX Text
BALTIMORE, MARYLAND 21220
AutoCAD SHX Text
KEY PLAN
AutoCAD SHX Text
FIRST FLOOR MECHANICAL DEMOLITION PLAN
AutoCAD SHX Text
SCALE: 1/4" = 1'-0"
AutoCAD SHX Text
AutoCAD SHX Text M201
AutoCAD SHX Text
FIRST FLOOR MECHANICAL PLAN
AutoCAD SHX Text
SCALE: 1/4" = 1'-0"
AutoCAD SHX Text
AutoCAD SHX Text M201
AutoCAD SHX Text
SECTION OF NDI X-RAY ROOM
AutoCAD SHX Text
SCALE: N.T.S.
AutoCAD SHX Text
AutoCAD SHX Text M201
File details come from the government source that posted it. Updated .