Binder1.pdf

PDF 2 MB Posted

Attached to
Rilea Electrical Repair Federal contract opportunity
Solicitation number
W912JV-17-B-4003
Issued by
Department of the Army Oregon Army National Guard

About this file

Specs and Drawings

View the file

Other files for this federal contract opportunity

Other files attached to Rilea Electrical Repair, newest first.
File Type Posted
A_07_Soliciation_0002.pdf PDF
BRFI_004a.pdf PDF
BRFI_003R_Response_Worksheet_20170207.pdf PDF
BRFI_004.pdf PDF
BRFI_003_Response_Worksheet_20170201.pdf PDF
BRFI_001_Response_Worksheet_20170131.pdf PDF
BRFI_002_Response_Worksheet_20170131.pdf PDF
A_01_SOW_Camp_Rilea_Type_B3__SPEC_BOOK_20140414.pdf PDF
A_01_AF_Form_66_ERWM132060_Electrical_Service_Upgrades.pdf PDF
A_07_Solicitation.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

I:\ P

R O

JE

C

T\

\1

.0 0\

D R

A W

IN

G

S\

EL

EC

\E

-0

.D W

G

4/

/2

:0 2:

A

M

1. WORK PERFORMED INCLUDES ALL LABOR, MATERIALS, AND EQUIPMENT

REQUIRED TO INSTALL A COMPLETE ELECTRICAL SYSTEM AS

INDICATED ON THESE DRAWINGS AND AS SPECIFIED.

2. CONTRACTOR SHALL VERIFY ALL EQUIPMENT SIZES AND POWER

REQUIREMENTS FOR EQUIPMENT SUPPLIED BY OTHERS.

3. ALL ELECTRICAL WORK SHALL COMPLY WITH APPLICABLE PORTIONS OF

THE NATIONAL ELECTRIC CODE (NEC) AS WELL AS LOCAL CODES IN

FORCE AT THE TIME OF CONSTRUCTION.

4. ALL ELECTRICAL EQUIPMENT AND MATERIALS SHALL BE APPROVED BY

UNDERWRITERS LABORATORIES INC. (UL) FOR THE PURPOSE FOR

WHICH THEY ARE USED AND SHALL BEAR THEIR LABEL.

5. ALL ELECTRICAL INDUSTRIAL CONTROL PANELS SHALL BEAR THE LABEL

OF A UL 508A APPROVED PANEL SHOP.

6. ALL ELECTRICAL EQUIPMENT AND RACEWAY SHALL BE SUPPORTED/

ANCHORED/ BRACED TO MEET ALL IMPOSED GRAVITY, WIND AND/OR

SEISMIC FORCES IN ACCORDANCE WITH THE REQUIREMENTS OF THE

2010 OREGON STRUCTURAL SPECIALTY CODE. WHERE THE DESIGN OF

THESE SUPPORT SYSTEMS ARE NOT PROVIDED AS PART OF THESE

ENGINEERING DRAWINGS, THE CONTRACTOR SHALL BE RESPONSIBLE

FOR THIS DESIGN AND SHALL PROVIDE MANUFACTURERS DATA OR

CALCULATIONS PREPARED BY A STRUCTURAL ENGINEER REGISTERED

IN THE STATE OF OREGON VERIFYING COMPLIANCE WITH THESE

REQUIREMENTS.

7. PROVIDE ENGRAVED NAMEPLATES ON ALL ELECTRICAL EQUIPMENT

INDICATING SERVICE/USE.

8. ALL CONDUIT ENTRANCES INTO OUTDOOR PANELS, DEVICES,

INSTRUMENTS, ETC. SHALL BE MADE WITH UL LISTED WEATHERPROOF

CONDUIT HUBS..

9. WEATHERPROOF RECEPTACLE COVERS SHALL BE LEVITON 5997-DGY

OR APPROVED EQUAL.

10. ALL TRENCHING AND BACKFILL FOR BORING OR BURIED ELECTRICAL

CONDUITS SHALL BE BY THE CONTRACTOR UNLESS NOTED

OTHERWISE.

11. PROVIDE METALLIC TAPE ABOVE BURIED PVC CONDUIT FOR FUTURE

LOCATING.

12. CONTRACTOR, AT HIS/HER OPTION, MAY COMBINE CONDUIT RUNS FOR

BRANCH CIRCUITS PROVIDED THAT THE AMPERE RATING OF THE

CONDUCTORS IS DERATED PER ARTICLE 310, NOTE 8 TO THE AMPACITY

TABLES OF THE N.E.C.

13. DRAWINGS ARE INTENDED TO SHOW GENERAL ARRANGEMENT, DESIGN

AND EXTENT OF WORK AND ARE MORE OR LESS DIAGRAMMATIC.

DRAWINGS ARE NOT INTENDED TO SHOW EXACT LOCATIONS EXCEPT

WHERE DIMENSIONS ARE SHOWN. ELECTRICAL WORK IS SHOWN ON

PLANS USING STANDARD INDUSTRY SYMBOLS. BEFORE ORDERING

MATERIALS OR DOING WORK, THE CONTRACTOR SHALL VERIFY ALL

MEASUREMENTS PERTAINING THERETO AND ASSUME RESPONSIBILITY

THEREFOR. ANY SUBSTANTIAL DIFFERENCES EXISTING BETWEEN

DRAWINGS AND CONDITIONS IN THE FIELD SHALL BE SUBMITTED TO

THE CONTRACTING OFFICER FOR CONSIDERATION BEFORE

PROCEEDING WITH WORK.

14. ANY AND ALL INFORMATION SHOWN ON THESE DRAWINGS WITH

RESPECT TO EXISTING STRUCTURES, UTILITIES, AND ELECTRICAL

SYSTEMS, IS AS EXACT AS COULD BE SECURED. THE INFORMATION IS

NOT WARRANTED NOR GUARANTEED ACCURATE, FIELD VERIFY ALL

EXISTING CONDITIONS PRIOR TO PROCEEDING WITH WORK.

15. PROVIDE CLEARLY VISIBLE ARC FLASH LABELING ON NEW ELECTRICAL

EQUIPMENT TO COMPLY WITH NEC ARTICLE 110.16: "ELECTRICAL

EQUIPMENT, SUCH AS SWITCHBOARDS, PANELBOARDS, INDUSTRIAL

CONTROL PANELS, METER SOCKET ENCLOSURES AND MOTOR

CONTROL CENTERS, THAT ARE IN OTHER THAN DWELLING UNITS, AND

ARE LIKELY TO REQUIRE EXAMINATION, ADJUSTMENT, SERVICING, OR

MAINTENANCE WHILE ENERGIZED SHALL BE FIELD MARKED TO WARN

QUALIFIED PERSONS OF POTENTIAL ARC FLASH HAZARDS."

16. COORDINATE ALL POWER INTERRUPTIONS WITH OWNER. SUBMIT

POWER SHUTDOWN REQUEST NO LATER THAN 7 DAYS PRIOR TO

SCHEDULED SHUTDOWN. FOLLOW OWNERS LOCKOUT/TAGOUT

PROCEDURES.

17. ACCURATE AND LEGIBLE RECORD (AS-BUILT) DRAWINGS SHALL BE

MAINTAINED AT THE JOB SITE, AND SUBMITTED TO THE CONTRACTING

OFFICER AT PROJECT COMPLETION.

GENERAL NOTES:

FACP

H

MAGNETIC MOTOR CONTROLLER

COMBINATION STARTER

MANUAL MOTOR STARTER-3 PHASE

FIRE ALARM CONTROL PANEL

FIRE ALARM PULL STATION

HEAT DETECTOR

DUCT SMOKE DETECTOR

SMOKE DETECTOR

C

OS

OS

U

PHOTO-EYE

OS

LC

LCPx

PE

HANDHOLE

MANHOLE

H

J

M

CEILING MOUNTED EXIT FIXTURE

WALL MOUNTED EXIT FIXTURE

SURFACE OR STEM MOUNTED FIXTURE

POLE MOUNTED FIXTURE

EMERGENCY LIGHTING UNIT

WALL BRACKET MOUNTED FIXTURE

RECESSED FIXTURE

WALL BRACKET MOUNTED FLUORESCENT FIXTURE

SURFACE OR STEM MOUNTED FLUORESCENT FIXTURE

RECESSED 2 x 4 FLUORESCENT FIXTURE

RECESSED 2 x 2 FLUORESCENT FIXTURE

RECESSED 1 x 4 FLUORESCENT FIXTURE

OCCUPANCY SENSOR CEILING MOUNTED

OCCUPANCY SENSOR ULTRASONIC CEILING MOUNTED

OCCUPANCY SENSOR WALL SWITCH

LIGHTING CONTROL PANEL (x REPRESENTS PANEL DESIGNATION)

LIGHTING CONTACTOR

UNDERGROUND CONDUIT

ABOVEGROUND CONDUIT

JUNCTION BOX

CONCEALED CONDUIT IN CEILING OR WALL

WIREWAY, SIZE AND TYPE AS INDICATED ON DRAWINGS

CABLE TRAY, SIZE AND TYPE AS INDICATED ON DRAWINGS

SPECIFICATION GRADE DUPLEX RECEPTACLE

F

V

D

T

DATA OUTLET

W

VISUAL NOTIFICATION APPLIANCE

WATERFLOW SWITCH

TAMPER SWITCH

AUDIBLE/VISUAL NOTIFICATION APPLIANCE

ELECTROMAGNETIC DOOR HOLDER/CLOSER

TELEPHONE OUTLET

FLOOR MOUNTED TELEPHONE OUTLET

DATA/TELEPHONE OUTLET

TV

EQUIPMENT RACK

BROADCAST TELEVISION CABLE OUTLET

FLOOR MOUNTED DATA/TELEPHONE OUTLET

FLOOR MOUNTED DATA OUTLET

GFI

WP

S

C

SFD

SL

SPECIFICATION GRADE CEILING MOUNTED QUADRUPLEX RECEPTACLE

LOW VOLTAGE SWITCH

SPECIFICATION GRADE SINGLE POLE SWITCH

SPECIFICATION GRADE FLUORESCENT DIMMER SWITCH

SPECIFICATION GRADE SINGLE RECEPTACLE

SPECIFICATION GRADE WEATHERPROOF DUPLEX RECEPTACLE

SPECIFICATION GRADE QUADRUPLEX RECEPTACLE

SPECIFICATION GRADE GROUND FAULT INTERRUPTER DUPLEX RECEPTACLE

SPECIFICATION GRADE FLOOR MOUNTED SINGLE RECEPTACLE

SPECIFICATION GRADE FLOOR MOUNTED DUPLEX RECEPTACLE

D

SWITCHBOARD (x REPRESENTS SWITCHBOARD DESIGNATION)

WALL MOUNTED LIGHTING AND POWER TRANSFORMER-DRY TYPE

GENERAL LIGHTING AND POWER TRANSFORMER-DRY TYPE

GENERAL LIGHTING AND POWER PANELBOARD

TELEPHONE OUTLET FOR WALL MOUNTED TELEPHONE

S

S

S

ACU

LOC

MNS

V

LOUDSPEAKER

A/E

AFF

AFG

AHU

ACCU

C

ALT

CF

CHWP

DH

CUH

DO

EF

CP

DUCT HEATER

EXHAUST FAN

DOOR OPERATOR

ALTERNATE

CONDUIT

CHILLED WATER PUMP

CIRCULATION PUMP

CABINET UNIT HEATER

AUTONOMOUS CONTROL UNIT

LOCAL OPERATING CONSOLE

MASS NOTIFICATION SYSTEM

ARCHITECT/ENGINEER

AIR HANDLING UNIT

ABOVE FINISHED GRADE

ABOVE FINISHED FLOOR

AIR COOLED CONDENSING UNIT

CIRCULATION FAN

CEILING SPEAKER

VOLUME CONTROL

WALL MOUNTED SPEAKER

EMT

EWH

EWC

ETR

FA

FAF

GFI

GRS

FIRE ALARM

HD

HP

HWB

HVAC

IMC

IH

HWP

IEWH

HAND DRYER

HORSEPOWER

GWH

NL

NIC

NTS

NL/EL

SP

SF

RF

RCP

PVC

NIGHT LIGHT

NOT TO SCALE

RETURN FAN

SUPPLY FAN

RADIATE CEILING PANEL

SUMP PUMP

SS

TBR

TYP

UC

UH

VER

WFE

UNO

UG

TYPICAL

UNDERGROUND

UNIT HEATER

UNIT COOLER

TO BE REMOVED

MAU

HOT WATER PUMP

HOT WATER BOILER

HEATING, VENTILATION, AIR CONDITIONING

MAKE-UP AIR UNIT

INFRARED HEATER

POLYVINYL CHLORIDE

INTERMEDIATE METALLIC CONDUIT

INSTANTANEOUS ELECTRIC WATER HEATER

NOT IN CONTRACT

NIGHT LIGHT AND EMERGENCY LIGHT

STAINLESS STEEL

UNLESS NOTED OTHERWISE

WELDING FUME EXTRACTOR

VEHICLE EXHAUST REEL

EXISTING TO REMAIN

ELECTRICAL WATER HEATER

ELECTRICAL WATER COOLER

GROUND FAULT INTERRUPTER

GALVANIZED RIGID STEEL

GAS WATER HEATER

FORCED AIR FURNACE

ELECTRICAL METALLIC TUBING

WL

WP

4X 3R

WEATHERPROOF

WET LOCATION LISTED

NEMA 3R RATING

NEMA 4X RATING

EL EMERGENCY LIGHT

M

SWBD-x

GROUND ROD

G

WT

T

DISCONNECT SWITCH

FUSED DISCONNECT SWITCH

UTILITY METER SOCKET

GROUNDING CONDUCTOR

SM

3 PHASE MOTOR CONNECTION

EQUIPMENT CONNECTION

1 PHASE MOTOR CONNECTION

120/208V-3PH

MANUAL MOTOR STARTER-1 PHASE

M

1. ALL ELECTRICAL EQUIPMENT AND FIXTURES WHICH ARE NOTED TO BE

REMOVED AS PART OF ANY DEMOLITION WORK SHALL BE TURNED

OVER TO THE GOVERNMENT UNLESS DIRECTED OTHERWISE BY THE

GOVERNMENT. ALL RACEWAY AND WIRE NOT WANTED BY THE

GOVERNMENT SHALL BE DISPOSED OF BY THE CONTRACTOR.

2. REMOVAL SHALL CONSIST OF REMOVING CONNECTING EQUIPMENT OR

DEVICE(S), CONDUIT AND WIRE BACK TO THE POINT OF SERVICE.

IWH INSTANTANEOUS WATER HEATER

WALL MOUNTED ANTENNA

SM SINGLE-MODE FIBER OPTIC CABLE

MM MULTI-MODE FIBER OPTIC CABLE

MNS MASS NOTIFICATION SYSTEM

GROUND ACCESS WELL

TGB

MASS NOTIFICATION STROBE

TELEPHONE GROUNDING BUS

OS OCCUPANCY SENSOR DUAL LEVEL SWITCHING WALL SWITCH

REQ'D REQUIRED

SPECIFICATION GRADE FLOOR MOUNTED QUADRUPLEX RECEPTACLE

C SPECIFICATION GRADE CEILING MOUNTED DUPLEX RECEPTACLE

C SPECIFICATION GRADE CEILING MOUNTED SINGLE RECEPTACLE

PAD MOUNTED SWITCHPMS

ELECTRICAL SYMBOL SCHEDULE

LIGHTING FIXTURES

LIGHTING CONTROLS

RACEWAYS

RECEPTACLES

SWITCHES

COMMUNICATIONS

FIRE ALARM SYSTEM

MOTORS AND MOTOR CONTROLS

SERVICE AND DISTRIBUTION SOUND AND PAGING SYSTEM

ABBREVIATIONS

DEMOLITION NOTES:

COMBINATION SMOKE/HEAT DETECTOR

SH

INBOARD MIDDLE LAMP ON 3 LAMP FIXTURE

OUTBOARD TWO OUTSIDE LAMPS ON 3 LAMP FIXTURE

S ID SPECIFICATION GRADE INCANDESCENT DIMMER SWITCH

SIPR SIPRNET - SECRET IP ROUTER NETWORK

NIPR NIPRNET - NON-CLASSIFIED (SECURE) IP ROUTER NETWORK

TACLANE TACTICAL LOCAL AREA NETWORK ENCRYPTOR

JAFAN JOINT AIR FORCE - ARMY - NAVY

RELCAN RELEASABLE TO CANADA

MASTER CONTROL PUSH BUTTON STATION

BLUE LIGHT SYSTEM

SB SPECIFICATION GRADE BLUE LIGHT OVER RIDE SWITCH

B

B CEILING MOUNTED BLUE LIGHT

WALL MOUNTED BLUE LIGHT

ACCESS CONTROL SYSTEM

C

K

L

S

IDS

E

CARDREADER

ELECTRIC STRIKE

PIN-PAD

MAGNETIC LOCK

STATUS SENSOR

INTRUSION DETECTION SYSTEM

ACS ACCESS CONTROL SYSTEM

BMS BALANCED MAGNETIC SWITCH

M MOTION SENSORPIR

© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.

Mead & Hunt, Inc.

201 NE Park Plaza Drive, Suite 167 Vancouver, WA 98684 phone: 360-883-0047 meadhunt.com

SHEET CONTENTS

DO NOT SCALE DRAWINGS

M&H NO.:

DATE:

DESIGNED BY:

DRAWN BY:

CHECKED BY:

ISSUED

03-28-14 TYPE B2 FINAL

SHEET NO.

U S

W

AR

R E

N

TO

N , O

R

C A

M P

R

IL

E A

E

LE

C

TR

IC

A

L S

E R

V

IC

E S

U P

G R

A D

E

E-001

3142300-122094.01

NOTES, SYMBOLS &

ABBREVIATIONS

03-28-14

RDS

GGI

TDS

© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.

Mead & Hunt, Inc.

201 NE Park Plaza Drive, Suite 167 Vancouver, WA 98684 phone: 360-883-0047 meadhunt.com

SHEET CONTENTS

DO NOT SCALE DRAWINGS

M&H NO.:

DATE:

DESIGNED BY:

DRAWN BY:

CHECKED BY:

SHEET NO.

U S

W

AR

R E

N

TO

N , O

R

C A

M P

R

IL

E A

E

LE

C

TR

IC

A

L S

E R

V

IC

E S

U P

G R

A D

E

E-013

SITE

POWER PLAN

GGI

TDS

1. CABLE AND CONDUIT SIZING BASED ON INFORMATION FROM AS-BUILT COMMUNICATIONS ELECTRONICS

TRAINING CENTER DRAWINGS, JAN-97.

2. ALL UNDERGROUND CONDUIT SHALL BE SCHEDULE 40 PVC. ALL ABOVE GROUND CONDUIT SHALL BE

RIGID GALVANIZED STEEL.

UNDERGROUND CONDUIT

(N) NEW

(E) EXISTING

SITE POWER PLAN1 1/16" = 1'-0"

NORTH

PLAN

32'16'8'0

E-104

E-104

E-103

E-103

POWER PLAN GENERAL NOTES:

POWER PLAN KEYED NOTES:

LEGEND

I:\ P

R O

JE

C

T\

\1

.0 0\

D R

A W

IN

G

S\

EL

EC

\E

-0

.D W

G

4/

/2

:0 2:

A

M

PROVIDE ELECTRICAL UPGRADES FOR NORTH WAREHOUSE, SEE DRAWING E-103

PROVIDE ELECTRICAL UPGRADES FOR SOUTH WAREHOUSE SEE DRAWING E-104

REMOVE ONE EXISTING 100A DISCONNECT SWITCH AND RECEPTACLE AND REPLACE WITH 60A FUSED DISCONNECT SWITCH AND MILITARY CLASS L RECEPTACLE. REPLACE OTHER 100A RECEPTACLE WITH MILITARY CLASS L RECEPTACLE. VERIFY RECEPTACLE PIN OUT WITH OWNER. SERVICE EXISTING

DISCONNECT AS REQUIRED.

REMOVE EXISTING RECEPTACLES AND REPLACE WITH MILITARY CLASS L RECEPTACLES. VERIFY RECEPTACLE PIN OUT WITH OWNER. PROVIDE AND INSTALL NEW FUSED DISCONNECT AND GFCI QUAD

RECEPTACLE. SERVICE EXISTING DISCONNECTS AS REQUIRED.

PROVIDE AND INSTALL NEW UNDERGROUND 225A FEEDER TO SOUTH WAREHOUSE.

PROVIDE AND INSTALL NEW POWER STANDS WITH FUSED DISCONNECT SWITCHES AND MILITARY

CLASS L RECEPTACLES. PROVIDE J-BOX FOR DATA/TELECOM. VERIFY RECEPTACLE PIN OUT WITH

OWNER. SEE SINGLE LINE DIAGRAM FOR DETAILS.

REMOVE CONDUCTORS AND REUSE EXISTING UNDERGROUND CONDUIT, RE-FEED EXISTING POWER

STANDS. SEE SINGLE LINE DIAGRAM E-704 FOR DETAILS.

INSTALL NEW UNDERGROUND CONDUIT FOR DATA/TELECOM FROM EXISTING J-BOX AT EAST POWER

STAND TO NEW POWER STANDS. PULL MAXELL INTERDUCT FOR DATA/TELECOM CABLE.

INSTALL 18" x 18" PRECAST UTILITY TRENCH WITH TRAFFIC RATED COVER. SEE CIVIL DRAWINGS FOR

DETAILS.

REPLACE EXISTING SERVICE TO NORTH WAREHOUSE WITH NEW UNDERGROUND 225 AMP FEEDER TO EXISTING DISTRIBUTION PANEL. INSTALL NEW MAIN BREAKER IN PANEL REMOVE EXISTING FEEDER

AND ABANDON CONDUIT IN PLACE.

PROVIDE AND INSTALL NEW 3/4" X 10' GROUND ROD AND WELL, SEE DRAWING E-504.

PROVIDE AND INSTALL NEW 18" X 6" NON METALLIC CABLE TRAY AND SUPPORTS. SEE DETAIL 3, DRAWING E-504.

PROVIDE SERVICE ENTRANCE GROUND ROD AND BONDING PER NEC REQUIREMENTS.13

3142300-122094.01 03-28-14

RDS

MEZZANINEWAREHOUSE

NORTH

MEZZANINE

C

C

C

C

I:\ P

R O

JE

C

T\

\1

.0 0\

D R

A W

IN

G

S\

EL

EC

\E

-1

.D W

G

4/

/2

:0 2:

A

M

© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.

Mead & Hunt, Inc.

201 NE Park Plaza Drive, Suite 167 Vancouver, WA 98684 phone: 360-883-0047 meadhunt.com

SHEET NO.

ENLARGED NORTH WAREHOUSE LOWER LEVEL POWER PLAN2 1/8"=1'-0"

8'4'0 16'

ENLARGED NORTH WAREHOUSE UPPER LEVEL POWER PLAN3 1/8"=1'-0"

8'4'0 16'

1. ALL WORK SHOWN IN BOLD IS NEW WORK OR EXISTING TO BE MODIFIED. ALL

OTHER IS EXISTING TO REMAIN.

2. INTERIOR RACEWAYS SHALL BE ELECTRICAL METALLIC TUBING WITH STEEL

COMPRESSION FITTINGS.

3. SEE DRAWING E-001 FOR NOTES, SYMBOLS/LEGEND AND ABBREVIATIONS.

POWER PLAN GENERAL NOTES:

ELECTRICAL CONTRACTOR SHALL VERIFY MAIN BREAKER RATING IN EXISTING PANEL, PROVIDE AND INSTALL NEW 225 AMP MAIN BREAKER IF EXISTING MAIN BREAKER RATING IS LESS THAN

225 AMP. MATCH EXISTING MANUFACTURE AND AIC RATING, DEMOLISH EXISTING 100 AMP

FEEDER AND INSTALL NEW 225 AMP FEEDER.

PROVIDE AND INSTALL 3 PHASE 60 AMP 208 VOLT MILITARY CLASS L RECEPTACLES IN NEMA 1

ENCLOSURE. INSTALL 60" AFF. FIELD VERIFY LOCATION AND RECEPTACLE PIN OUT WITH

OWNER PRIOR TO INSTALLATION.

PROVIDE AND INSTALL NEW RECEPTACLES AS SHOWN.

POWER PLAN KEYED NOTES:

12 2

TECH CONTROL

ENLARGED UPPER LEVEL RECPTACLE LOCATIONS4 1/8"=1'-0"

8'4'0 16'

EQUIPMENT GROUND

NEUTRAL

PHASE CONDUCTOR

LEGEND:

DENOTES HOME RUN

NORTH

PLAN

NORTH

PLAN

NORTH

PLAN

SHEET CONTENTS

DO NOT SCALE DRAWINGS

M&H NO.:

DATE:

DESIGNED BY:

DRAWN BY:

CHECKED BY:

C A

M P

R

IL

E A

E

LE

C

TR

IC

A

L S

E R

V

IC

E S

U P

G R

A D

E

E-103

NORTH WAREHOUSE

POWER PLAN

GGI

TDS

U S

W

AR

R E

N

TO

N , O

R

3142300-122094.01

SOUTH WAREHOUSE

S L S L

S L

JJJJ

J J J J

J

J

J

SWLP01

JJJJJJ

JJJJJJ

J S

J P

J J P

J S

S J

JJJJJJ

JJJJJJ J

S

P

SHEET CONTENTS

DO NOT SCALE DRAWINGS

M&H NO.:

DATE:

DESIGNED BY:

DRAWN BY:

CHECKED BY:

SHEET NO.

© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.

Mead & Hunt, Inc.

201 NE Park Plaza Drive, Suite 167 Vancouver, WA 98684 phone: 360-883-0047 meadhunt.com

U S

W

AR

R E

N

TO

N , O

R

C A

M P

R

IL

E A

E

LE

C

TR

IC

A

L S

E R

V

IC

E S

U P

G R

A D

E

E-104

SOUTH WAREHOUSE

LIGHTING &

POWER PLAN

GGI

TDS

ENLARGED SOUTH WAREHOUSE LIGHTING & POWER PLAN3 1/8"=1'-0"

8'4'0 16'

ENLARGED SOUTH WAREHOUSE UNDER MEZZANINE LIGHTING PLAN4 1/8"=1'-0"

8'4'0 16'

LIGHTING LEGEND:

ALUMINUM HIGH BAY LUMINAIR, 400W METAL HALIDE, WITH 4000

KELVIN LAMP, PRISMATIC LENS, AND 3' SAFETY CABLE

MHT-HBa-400E OR APPROVED EQUAL. (LOWER CASE LETTER

DENOTES SWITCH. 'NL' DENOTES NIGHT LIGHT, ALWAYS ON.)

LIGHTING KEYED NOTES:

GENERAL LIGHTING NOTES:

1. SEE DRAWING E-001 FOR NOTES, SYMBOLS/LEGENDS, AND

ABBREVIATIONS.

2. CONTRACTOR SHALL VERIFY ALL FIXTURE CATALOG NUMBERS FOR

ACCURACY. FIXTURE CATALOG NUMBERS ARE SUBJECT TO CHANGE

BY MANUFACTURER.

3. LIGHTING PLAN IS DIAGRAMMATIC, LOCATE CONDUIT AS REQUIRED.

4. CIRCUIT BREAKERS USED TO SWITCH LIGHTS SHALL BE "SWD"/HID"

RATED.

5. RETURN REMOVED EQUIPMENT TO OWNER OR DISPOSE OF PER

OWNERS INSTRUCTIONS.

SURFACE MOUNTED FLUORESCENT FIXTURE, SAME

MANUFACTURER AND MODEL NUMBER AS EXISTING, OR APPROVED

EQUAL (LETTER DENOTES SWITCH).

MEZZANINE ABOVE

b b

LIGHTING SEQUENCE OF OPERATION

NORTH

PLAN

NORTH

PLAN

REMOVE EXISTING FEEDER TO THE SOUTH WAREHOUSE AND

REPLACE WITH NEW AS SHOWN ON THIS DRAWING. REMOVE

EXISTING DISTRIBUTION EQUIPMENT, RACEWAY, AND WIRING.

EXISTING RACEWAY AND WIRING MAY REMAIN IF REUSABLE WITH

NEW DISTRIBUTION SYSTEM.

RE-FEED EXISTING UNIT HEATER(S) FROM NEW DISTRIBUTION

PANEL. PROVIDE AND INSTALL DISCONNECT SWITCH.

PROVIDE AND INSTALL NEW 225A 120/208V 42 SPACE PANELBOARD

AND FEEDER. SEE DRAWING E-602 FOR PANEL SCHEDULE.

RE-FEED EXISING AC UNIT, LIGHT AND RECEPTACLE IN COMM

ROOM. SEE DRAWING E-602 FOR PANEL SCHEDULE.

REMOVE EXISTING HIGH BAY LIGHT FIXTURES. PROVIDE AND

INSTALL NEW INDUCTION TYPE FIXTURES. REUSE EXISTING

CONDUIT AND WIRE WHERE POSSIBLE. SEE DETAIL 4, DRAWING

E-504 FOR LIGHTING CONTROLS.

VERIFY EXISTING FIXTURE VOLTAGE, RE-FEED EXISTING LIGHTING

UNDER MEZZANINE AS REQUIRED. SEE DETAIL 4, DRAWING E-504

FOR LIGHTING CONTROLS.

PROVIDE AND INSTALL NEW FIXTURES ON MEZZANINE. SEE DETAIL

4, DRAWING E-504 FOR LIGHTING CONTROLS.

REMOVE EXISTING LIGHT SWITCHES, DISTRIBUTION, AND WIRING.

PROVIDE THREE NEW LOW VOLTAGE DIGITAL TIME SWITCHES,

WATTSTOPPER TS-400-24. SEE DRAWING E-504, DETAIL 4 FOR

LIGHTING CONTROL WIRING DIAGRAM.

REMOVE EXISTING WIRING AS REQUIRED RE-FEED EXISTING

RECEPTACLES AS SHOWN.

REMOVE EXISTING EMERGENCY LIGHT FIXTURES AND REPLACE

WITH NEW AT LOCATIONS SHOWN, SIMILAR STYLE AS EXISTING.

1 3

NL

BATTERY BACKED EMERGENCY LIGHT

P

S LIGHTING CONTROL SLAVE PACK, WATTSTOPPER S120/277/347, OR

APPROVEED EQUAL

LIGHTING CONTROL POWER PACK, WATTSTOPPER BZ-50 OR

APPROVED EQUAL

PPa POWER PACK, LOWER CASE LETTER DENOTES SWITCH.

SPa SLAVE PACK, LOWER CASE LETTER DENOTES SWITCH.

LV DENOTES LOW VOLTAGE LIGHTING CONTROL CABLE

EQUIPMENT GROUND

NEUTRAL

PHASE CONDUCTOR

LEGEND:

DENOTES HOME RUN

1. THE SOUTH WAREHOUSE CONSISTS OF THREE LIGHTING ZONES;

HIGH BAY, UNDER MEZZANINE, AND MEZZANINE.

2. EACH ZONE IS CONTROLLED VIA A TIME DELAY LIGHT SWITCH

LOCATED AT THE BUILDING ENTRANCE.

3. PRESSING THE LIGHT SWITCH TURNS ON THE FIXTURES IN THAT

ZONE AND STARTS A TIMER. WHEN THE TIMER REACHES ITS

SETTING, THE FIXTURES WILL TURN OFF.

4. DEPRESSING THE BUTTON A SECOND TIME WILL TURN THE

FIXTURES OFF.

5. DEPRESSING AND HOLDING THE LIGHT SWITCH FOR TWO SECONDS

WILL RESET THE TIME AND FIXTURES WILL REMAIN ON.

6. THE TIMER CAN BE SET FROM FIVE MINUTES TO TWELVE HOURS.

SEE INSTRUCTION MANUAL TO SET TIMER.

7. TWO HIGH BAY FIXTURES IN THE WAREHOUSE ARE DESIGNATED AS

NIGHT LIGHTS AND ARE ALWAYS ON. THEY CAN BE SWITCHED OFF

BY OPENING THE CIRCUIT'S BREAKER AT THE DISTRIBUTION PANEL.

3142300-122094.01

I:\ P

R O

JE

C

T\

\1

.0 0\

D R

A W

IN

G

S\

EL

EC

\E

-5

.D W

G

4/

/2

:0 3:

A

M (N) POWER STAND N4 & N5 ELEVATION4 (E) MID POWER STAND ELEVATION5

1 SCALE: 3/4"=1'-0"

KEYED NOTES:

PROVIDE GROUND FAULT CIRCUIT INTERRUPTER RECEPTACLE WITH

WEATHERPROOF BOX AND "EXTRA DUTY IN-USE" COVER.

NEW FUSED DISCONNECT SWITCHES SHALL BE SAME TYPE AND

MATERIAL (NON-METALIC) AS EXISTING.

GENERAL NOTES:

1. ELEVATIONS ARE DIAGRAMMATIC, VERIFY EQUIPMENT LOCATIONS PRIOR

TO INSTALLATION ON SUPPORT STRUCTURE.

2. ALL ENCLOSURES AND WIREWAY SHALL BE NONMETALLIC NEMA 4X

RATED.

3. PROVIDE SUPPORT STRUCTURE FOR NEW POWER STANDS. SEE

STRUCTURAL DRAWING

4. ALL FASTENERS: SCREWS, BOLTS, NUTS, STRUT, CLAMPS ETC. SHALL BE

STAINLESS STEEL.

5. ALL EXPOSED CONDUIT SHALL BE RIGID GALVANIZED STEEL.

6. USE APPROVED HUBS ON ALL TOP CONDUIT ENTRYS, SEALING

LOCKNUTS TO BE USED ON SIDE AND BOTTOM ENTRYS.

7. 100A EQUIPMENT RECEPTACLE(S) SHALL BE MIL-C-22992, CLASS L, SHELL

SIZE 44, THREE PHASE AC, 4-WIRE WITH 4 GROUNDS.CRIMP TYPE PINS.

8. 60A EQUIPMENT RECEPTACLE(S) SHALL BE MIL-C-22992, CLASS L, SHELL

SIZE 32, THREE PHASE AC, 4-WIRE WITH GROUND. CRIMP TYPE PINS.

(N) POWER STAND H1 ELEVATION2(E) EAST POWER STAND ELEVATION

Mead & Hunt, Inc.

201 NE Park Plaza Drive, Suite 167 Vancouver, WA 98684 phone: 360-883-0047 meadhunt.com

SHEET CONTENTS

DO NOT SCALE DRAWINGS

M&H NO.:

DATE:

DESIGNED BY:

DRAWN BY:

CHECKED BY:

SHEET NO.

U S

W

AR

R E

N

TO

N , O

R

C A

M P

R

IL

E A

E

LE

C

TR

IC

A

L S

E R

V

IC

E S

U P

G R

A D

E

E-503

ELECTRICAL

ELEVATIONS

GGI

TDS

3 (N) POWER STAND SIDE ELEVATION

(E) WEST POWER STAND ELEVATION6

SCALE: 3/4"=1'-0" SCALE: 3/4"=1'-0"

SCALE: 3/4"=1'-0" SCALE: 3/4"=1'-0" SCALE: 3/4"=1'-0"

3142300-122094.01 03-28-14

RDS

ISSUED

03-28-14 TYPE B2 FINAL

I:\ P

R O

JE

C

T\

\1

.0 0\

D R

A W

IN

G

S\

EL

EC

\E

-5

.D W

G

4/

/2

:0 3:

A

M

© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.

Mead & Hunt, Inc.

201 NE Park Plaza Drive, Suite 167 Vancouver, WA 98684 phone: 360-883-0047 meadhunt.com

SHEET CONTENTS

DO NOT SCALE DRAWINGS

M&H NO.:

DATE:

DESIGNED BY:

DRAWN BY:

CHECKED BY:

SHEET NO.

U S

W

AR

R E

N

TO

N , O

R

C A

M P

R

IL

E A

E

LE

C

TR

IC

A

L S

E R

V

IC

E S

U P

G R

A D

E

E-504

ELECTRICAL DETAILS

TRW

TDS

KEYED NOTES:

SEE STRUCTURAL DRAWING FOR DETAILS.

INSTALL TOP OF TRAY 18" MAXIMUM ABOVE GRADE.

GENERAL NOTES:

1. NOT USED

3142300-122094.01 03-28-14

RDS

ISSUED

03-28-14 TYPE B2 FINAL

SHEET CONTENTS

DO NOT SCALE DRAWINGS

M&H NO.:

DATE:

DESIGNED BY:

DRAWN BY:

CHECKED BY:

SHEET NO.

U S

W

AR

R E

N

TO

N , O

R

C A

M P

R

IL

E A

E

LE

C

TR

IC

A

L S

E R

V

IC

E S

U P

G R

A D

E

E-602

PANEL SCHEDULES

TRW

TDS

KEYED NOTES:

REPLACE EXISTING MAIN CIRCUIT BREAKER WITH 225A

BREAKER. SAME MANUFACTURER, MODEL, AND RATING AS

EXISTING.

GENERAL NOTES:

1. NOT USED.

PROVIDE AND INSTALL NEW CIRCUIT BREAKER. SAME

MANUFACTURER, MODEL, AND RATING AS EXISTING. REVISE

PANEL SCHEDULES.

© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.

Mead & Hunt, Inc.

201 NE Park Plaza Drive, Suite 167 Vancouver, WA 98684 phone: 360-883-0047 meadhunt.com

3142300-122094.01

REMOVE EXISTING RECEPTACLE.2

SINGLE LINE DIAGRAM KEYED NOTES:

4 REMOVE EXISTING 60 AMP RECEPTACLES A, B, AND C; CONDUIT, WIRING..

© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.

Mead & Hunt, Inc.

201 NE Park Plaza Drive, Suite 167 Vancouver, WA 98684 phone: 360-883-0047 meadhunt.com

SINGLE LINE DRAGRAM (REMOVAL)1 NO SCALE

SHEET CONTENTS

DO NOT SCALE DRAWINGS

M&H NO.:

DATE:

DESIGNED BY:

DRAWN BY:

CHECKED BY:

SHEET NO.

U S

W

AR

R E

N

TO

N , O

R

C A

M P

R

IL

E A

E

LE

C

TR

IC

A

L S

E R

V

IC

E S

U P

G R

A D

E

E-703

SINGLE LINE DIAGRAM

REMOVAL

GGI

TDS

1. CABLE AND CONDUIT SIZING BASED ON INFORMATION FROM AS-BUILT

COMMUNICATIONS ELECTRONICS TRAINING CENTER DRAWINGS, JAN-97.

2. SEE DRAWING E-001 FOR NOTES, SYMBOLS/LEGENDS, AND ABBREVIATIONS.

SINGLE LINE DIAGRAM GENERAL NOTES:

4 4

5 REMOVE 200A RECEPTACLE D, CONDUIT, AND WIRING.

3 3

REMOVE RECEPTACLES AND FEEDER CABLE BACK TO SOURCE. CONDUIT TO BE REUSED.3

REMOVE 100 AMP RECEPTACLE.1

DEMO

(N) NEW

(E) EXISTING

LEGEND

6 REMOVE EXISTING 60 AMP DISCONNECT, RECEPTACLE, J-BOX AND WIRING.

3142300-122094.01

© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.

Mead & Hunt, Inc.

201 NE Park Plaza Drive, Suite 167 Vancouver, WA 98684 phone: 360-883-0047 meadhunt.com

SINGLE LINE DRAGRAM1 NO SCALE

SHEET CONTENTS

DO NOT SCALE DRAWINGS

M&H NO.:

DATE:

DESIGNED BY:

DRAWN BY:

CHECKED BY:

SHEET NO.

U S

W

AR

R E

N

TO

N , O

R

C A

M P

R

IL

E A

E

LE

C

TR

IC

A

L S

E R

V

IC

E S

U P

G R

A D

E

E-704

SINGLE LINE DIAGRAM

GGI

TDS

PROVIDE AND INSTALL NEW FEEDER, MILITARY CLASS L RECEPTACLES, QUAD RECEPTACLE

AND DISCONNECT SWITCH AS REQUIRED . REUSE EXISTING FUSED DISCONNECT SWITCHES AS

SHOWN.

REMOVE EXISTING #1 CONDUCTORS AND REUSED EXISTING 4" UNDERGROUND CONDUIT. PULL

IN NEW 200 AMP, #4/0 POWER STAND FEEDER.

PROVIDE NEW POWER STANDS WITH FUSED DISCONNECT SWITCHES,MILITARY CLASS L

RECEPTACLES, AND QUAD RECEPTACLE AS SHOWN.

REPLACE EXISTING RECEPTACLE WITH A MILITARY CLASS L RECEPTACLE.

PROVIDE NEW 200 AMP SERVICE TO SOUTH WAREHOUSE.

REPLACE EXISTING WAREHOUSE FEEDER WITH NEW 225 AMP SERVICE.

REPLACE EXISTING SWITCHBOARD CIRCUIT BREAKERS TO AGREE WITH NEW DISTRIBUTION.

SAME MANUFACTURE, MODEL NUMBER, AND RATING AS EXISTING.

SINGLE LINE DIAGRAM KEYED NOTES:

1. CABLE AND CONDUIT SIZING BASED ON INFORMATION FROM AS-BUILT

COMMUNICATIONS ELECTRONICS TRAINING CENTER DRAWINGS, JAN-97.

2. SEE DRAWING E-001 FOR NOTES, SYMBOLS/LEGENDS, AND ABBREVIATIONS.

SINGLE LINE DIAGRAM GENERAL NOTES:

(N) NEW

(E) EXISTING

LEGEND

LOAD SUMMARY

PER 208V SWITCHBOARD POWER METER READINGS COLLECTED ON 1/14/13,

THE MAXIMUM DEMAND RECORDED THE PREVIOUS SIX MONTHS WAS:

A-PHASE: 240A, B-PHASE: 238A, C-PHASE: 252A.

THE METER'S SLIDING WINDOW SETTING WAS THE DEFAULT VALUE OF

AVERAGE DEMAND OVER A 10 MINUTE PERIOD. THIS MAXIMUM DEMAND

OCCURRED OVER THE WEEKEND OF 1/12/13 AND WAS CONFIRMED BY THE

OWNER TO BE THE MAXIMUM RECEPTACLE LOAD EXPECTED FOR THE NEW

ELECTRICAL DISTRIBUTION SYSTEM CONFIGURATION.

BASED ON THIS RECORDED LOAD, THE DESIGN MAXIMUM DEMAND FOR THE

208V SWITCHBOARD IS ESTIMATED TO BE:

245 AMPS; 88 KVA.

3142300-122094.01

A 01 S&D 01
A 01 S&D 02
A 01 S&D 30.09-1 13304 B Final 041114
E-001
E-001
E-013
E-013 SITE POWER PLAN
E-103
E-103
E-104
E-104 SOUTH WAREHOUSE LIGHTING & POWER PLAN
E-503
E-503 ELECTRICAL ELEVATIONS
E-504
E-504 ELECTRICAL DETAILS
E-602
E-602 PANEL SCHEDULES
E-703
E-703 SINGLE-LINE DIAGRAM REMOVAL
E-704
E-704 SINGLE-LINE DIAGRAM

File details come from the government source that posted it. Updated .