Binder1.pdf
PDF 2 MB Posted
- Attached to
- Rilea Electrical Repair Federal contract opportunity
- Solicitation number
- W912JV-17-B-4003
About this file
Specs and Drawings
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| A_07_Soliciation_0002.pdf | ||
| BRFI_004a.pdf | ||
| BRFI_003R_Response_Worksheet_20170207.pdf | ||
| BRFI_004.pdf | ||
| BRFI_003_Response_Worksheet_20170201.pdf | ||
| BRFI_001_Response_Worksheet_20170131.pdf | ||
| BRFI_002_Response_Worksheet_20170131.pdf | ||
| A_01_SOW_Camp_Rilea_Type_B3__SPEC_BOOK_20140414.pdf | ||
| A_01_AF_Form_66_ERWM132060_Electrical_Service_Upgrades.pdf | ||
| A_07_Solicitation.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
I:\ P
R O
JE
C
T\
\1
.0 0\
D R
A W
IN
G
S\
EL
EC
\E
-0
.D W
G
4/
/2
:0 2:
A
M
1. WORK PERFORMED INCLUDES ALL LABOR, MATERIALS, AND EQUIPMENT
REQUIRED TO INSTALL A COMPLETE ELECTRICAL SYSTEM AS
INDICATED ON THESE DRAWINGS AND AS SPECIFIED.
2. CONTRACTOR SHALL VERIFY ALL EQUIPMENT SIZES AND POWER
REQUIREMENTS FOR EQUIPMENT SUPPLIED BY OTHERS.
3. ALL ELECTRICAL WORK SHALL COMPLY WITH APPLICABLE PORTIONS OF
THE NATIONAL ELECTRIC CODE (NEC) AS WELL AS LOCAL CODES IN
FORCE AT THE TIME OF CONSTRUCTION.
4. ALL ELECTRICAL EQUIPMENT AND MATERIALS SHALL BE APPROVED BY
UNDERWRITERS LABORATORIES INC. (UL) FOR THE PURPOSE FOR
WHICH THEY ARE USED AND SHALL BEAR THEIR LABEL.
5. ALL ELECTRICAL INDUSTRIAL CONTROL PANELS SHALL BEAR THE LABEL
OF A UL 508A APPROVED PANEL SHOP.
6. ALL ELECTRICAL EQUIPMENT AND RACEWAY SHALL BE SUPPORTED/
ANCHORED/ BRACED TO MEET ALL IMPOSED GRAVITY, WIND AND/OR
SEISMIC FORCES IN ACCORDANCE WITH THE REQUIREMENTS OF THE
2010 OREGON STRUCTURAL SPECIALTY CODE. WHERE THE DESIGN OF
THESE SUPPORT SYSTEMS ARE NOT PROVIDED AS PART OF THESE
ENGINEERING DRAWINGS, THE CONTRACTOR SHALL BE RESPONSIBLE
FOR THIS DESIGN AND SHALL PROVIDE MANUFACTURERS DATA OR
CALCULATIONS PREPARED BY A STRUCTURAL ENGINEER REGISTERED
IN THE STATE OF OREGON VERIFYING COMPLIANCE WITH THESE
REQUIREMENTS.
7. PROVIDE ENGRAVED NAMEPLATES ON ALL ELECTRICAL EQUIPMENT
INDICATING SERVICE/USE.
8. ALL CONDUIT ENTRANCES INTO OUTDOOR PANELS, DEVICES,
INSTRUMENTS, ETC. SHALL BE MADE WITH UL LISTED WEATHERPROOF
CONDUIT HUBS..
9. WEATHERPROOF RECEPTACLE COVERS SHALL BE LEVITON 5997-DGY
OR APPROVED EQUAL.
10. ALL TRENCHING AND BACKFILL FOR BORING OR BURIED ELECTRICAL
CONDUITS SHALL BE BY THE CONTRACTOR UNLESS NOTED
OTHERWISE.
11. PROVIDE METALLIC TAPE ABOVE BURIED PVC CONDUIT FOR FUTURE
LOCATING.
12. CONTRACTOR, AT HIS/HER OPTION, MAY COMBINE CONDUIT RUNS FOR
BRANCH CIRCUITS PROVIDED THAT THE AMPERE RATING OF THE
CONDUCTORS IS DERATED PER ARTICLE 310, NOTE 8 TO THE AMPACITY
TABLES OF THE N.E.C.
13. DRAWINGS ARE INTENDED TO SHOW GENERAL ARRANGEMENT, DESIGN
AND EXTENT OF WORK AND ARE MORE OR LESS DIAGRAMMATIC.
DRAWINGS ARE NOT INTENDED TO SHOW EXACT LOCATIONS EXCEPT
WHERE DIMENSIONS ARE SHOWN. ELECTRICAL WORK IS SHOWN ON
PLANS USING STANDARD INDUSTRY SYMBOLS. BEFORE ORDERING
MATERIALS OR DOING WORK, THE CONTRACTOR SHALL VERIFY ALL
MEASUREMENTS PERTAINING THERETO AND ASSUME RESPONSIBILITY
THEREFOR. ANY SUBSTANTIAL DIFFERENCES EXISTING BETWEEN
DRAWINGS AND CONDITIONS IN THE FIELD SHALL BE SUBMITTED TO
THE CONTRACTING OFFICER FOR CONSIDERATION BEFORE
PROCEEDING WITH WORK.
14. ANY AND ALL INFORMATION SHOWN ON THESE DRAWINGS WITH
RESPECT TO EXISTING STRUCTURES, UTILITIES, AND ELECTRICAL
SYSTEMS, IS AS EXACT AS COULD BE SECURED. THE INFORMATION IS
NOT WARRANTED NOR GUARANTEED ACCURATE, FIELD VERIFY ALL
EXISTING CONDITIONS PRIOR TO PROCEEDING WITH WORK.
15. PROVIDE CLEARLY VISIBLE ARC FLASH LABELING ON NEW ELECTRICAL
EQUIPMENT TO COMPLY WITH NEC ARTICLE 110.16: "ELECTRICAL
EQUIPMENT, SUCH AS SWITCHBOARDS, PANELBOARDS, INDUSTRIAL
CONTROL PANELS, METER SOCKET ENCLOSURES AND MOTOR
CONTROL CENTERS, THAT ARE IN OTHER THAN DWELLING UNITS, AND
ARE LIKELY TO REQUIRE EXAMINATION, ADJUSTMENT, SERVICING, OR
MAINTENANCE WHILE ENERGIZED SHALL BE FIELD MARKED TO WARN
QUALIFIED PERSONS OF POTENTIAL ARC FLASH HAZARDS."
16. COORDINATE ALL POWER INTERRUPTIONS WITH OWNER. SUBMIT
POWER SHUTDOWN REQUEST NO LATER THAN 7 DAYS PRIOR TO
SCHEDULED SHUTDOWN. FOLLOW OWNERS LOCKOUT/TAGOUT
PROCEDURES.
17. ACCURATE AND LEGIBLE RECORD (AS-BUILT) DRAWINGS SHALL BE
MAINTAINED AT THE JOB SITE, AND SUBMITTED TO THE CONTRACTING
OFFICER AT PROJECT COMPLETION.
GENERAL NOTES:
FACP
H
MAGNETIC MOTOR CONTROLLER
COMBINATION STARTER
MANUAL MOTOR STARTER-3 PHASE
FIRE ALARM CONTROL PANEL
FIRE ALARM PULL STATION
HEAT DETECTOR
DUCT SMOKE DETECTOR
SMOKE DETECTOR
C
OS
OS
U
PHOTO-EYE
OS
LC
LCPx
PE
HANDHOLE
MANHOLE
H
J
M
CEILING MOUNTED EXIT FIXTURE
WALL MOUNTED EXIT FIXTURE
SURFACE OR STEM MOUNTED FIXTURE
POLE MOUNTED FIXTURE
EMERGENCY LIGHTING UNIT
WALL BRACKET MOUNTED FIXTURE
RECESSED FIXTURE
WALL BRACKET MOUNTED FLUORESCENT FIXTURE
SURFACE OR STEM MOUNTED FLUORESCENT FIXTURE
RECESSED 2 x 4 FLUORESCENT FIXTURE
RECESSED 2 x 2 FLUORESCENT FIXTURE
RECESSED 1 x 4 FLUORESCENT FIXTURE
OCCUPANCY SENSOR CEILING MOUNTED
OCCUPANCY SENSOR ULTRASONIC CEILING MOUNTED
OCCUPANCY SENSOR WALL SWITCH
LIGHTING CONTROL PANEL (x REPRESENTS PANEL DESIGNATION)
LIGHTING CONTACTOR
UNDERGROUND CONDUIT
ABOVEGROUND CONDUIT
JUNCTION BOX
CONCEALED CONDUIT IN CEILING OR WALL
WIREWAY, SIZE AND TYPE AS INDICATED ON DRAWINGS
CABLE TRAY, SIZE AND TYPE AS INDICATED ON DRAWINGS
SPECIFICATION GRADE DUPLEX RECEPTACLE
F
V
D
T
DATA OUTLET
W
VISUAL NOTIFICATION APPLIANCE
WATERFLOW SWITCH
TAMPER SWITCH
AUDIBLE/VISUAL NOTIFICATION APPLIANCE
ELECTROMAGNETIC DOOR HOLDER/CLOSER
TELEPHONE OUTLET
FLOOR MOUNTED TELEPHONE OUTLET
DATA/TELEPHONE OUTLET
TV
EQUIPMENT RACK
BROADCAST TELEVISION CABLE OUTLET
FLOOR MOUNTED DATA/TELEPHONE OUTLET
FLOOR MOUNTED DATA OUTLET
GFI
WP
S
C
SFD
SL
SPECIFICATION GRADE CEILING MOUNTED QUADRUPLEX RECEPTACLE
LOW VOLTAGE SWITCH
SPECIFICATION GRADE SINGLE POLE SWITCH
SPECIFICATION GRADE FLUORESCENT DIMMER SWITCH
SPECIFICATION GRADE SINGLE RECEPTACLE
SPECIFICATION GRADE WEATHERPROOF DUPLEX RECEPTACLE
SPECIFICATION GRADE QUADRUPLEX RECEPTACLE
SPECIFICATION GRADE GROUND FAULT INTERRUPTER DUPLEX RECEPTACLE
SPECIFICATION GRADE FLOOR MOUNTED SINGLE RECEPTACLE
SPECIFICATION GRADE FLOOR MOUNTED DUPLEX RECEPTACLE
D
SWITCHBOARD (x REPRESENTS SWITCHBOARD DESIGNATION)
WALL MOUNTED LIGHTING AND POWER TRANSFORMER-DRY TYPE
GENERAL LIGHTING AND POWER TRANSFORMER-DRY TYPE
GENERAL LIGHTING AND POWER PANELBOARD
TELEPHONE OUTLET FOR WALL MOUNTED TELEPHONE
S
S
S
ACU
LOC
MNS
V
LOUDSPEAKER
A/E
AFF
AFG
AHU
ACCU
C
ALT
CF
CHWP
DH
CUH
DO
EF
CP
DUCT HEATER
EXHAUST FAN
DOOR OPERATOR
ALTERNATE
CONDUIT
CHILLED WATER PUMP
CIRCULATION PUMP
CABINET UNIT HEATER
AUTONOMOUS CONTROL UNIT
LOCAL OPERATING CONSOLE
MASS NOTIFICATION SYSTEM
ARCHITECT/ENGINEER
AIR HANDLING UNIT
ABOVE FINISHED GRADE
ABOVE FINISHED FLOOR
AIR COOLED CONDENSING UNIT
CIRCULATION FAN
CEILING SPEAKER
VOLUME CONTROL
WALL MOUNTED SPEAKER
EMT
EWH
EWC
ETR
FA
FAF
GFI
GRS
FIRE ALARM
HD
HP
HWB
HVAC
IMC
IH
HWP
IEWH
HAND DRYER
HORSEPOWER
GWH
NL
NIC
NTS
NL/EL
SP
SF
RF
RCP
PVC
NIGHT LIGHT
NOT TO SCALE
RETURN FAN
SUPPLY FAN
RADIATE CEILING PANEL
SUMP PUMP
SS
TBR
TYP
UC
UH
VER
WFE
UNO
UG
TYPICAL
UNDERGROUND
UNIT HEATER
UNIT COOLER
TO BE REMOVED
MAU
HOT WATER PUMP
HOT WATER BOILER
HEATING, VENTILATION, AIR CONDITIONING
MAKE-UP AIR UNIT
INFRARED HEATER
POLYVINYL CHLORIDE
INTERMEDIATE METALLIC CONDUIT
INSTANTANEOUS ELECTRIC WATER HEATER
NOT IN CONTRACT
NIGHT LIGHT AND EMERGENCY LIGHT
STAINLESS STEEL
UNLESS NOTED OTHERWISE
WELDING FUME EXTRACTOR
VEHICLE EXHAUST REEL
EXISTING TO REMAIN
ELECTRICAL WATER HEATER
ELECTRICAL WATER COOLER
GROUND FAULT INTERRUPTER
GALVANIZED RIGID STEEL
GAS WATER HEATER
FORCED AIR FURNACE
ELECTRICAL METALLIC TUBING
WL
WP
4X 3R
WEATHERPROOF
WET LOCATION LISTED
NEMA 3R RATING
NEMA 4X RATING
EL EMERGENCY LIGHT
M
SWBD-x
GROUND ROD
G
WT
T
DISCONNECT SWITCH
FUSED DISCONNECT SWITCH
UTILITY METER SOCKET
GROUNDING CONDUCTOR
SM
3 PHASE MOTOR CONNECTION
EQUIPMENT CONNECTION
1 PHASE MOTOR CONNECTION
120/208V-3PH
MANUAL MOTOR STARTER-1 PHASE
M
1. ALL ELECTRICAL EQUIPMENT AND FIXTURES WHICH ARE NOTED TO BE
REMOVED AS PART OF ANY DEMOLITION WORK SHALL BE TURNED
OVER TO THE GOVERNMENT UNLESS DIRECTED OTHERWISE BY THE
GOVERNMENT. ALL RACEWAY AND WIRE NOT WANTED BY THE
GOVERNMENT SHALL BE DISPOSED OF BY THE CONTRACTOR.
2. REMOVAL SHALL CONSIST OF REMOVING CONNECTING EQUIPMENT OR
DEVICE(S), CONDUIT AND WIRE BACK TO THE POINT OF SERVICE.
IWH INSTANTANEOUS WATER HEATER
WALL MOUNTED ANTENNA
SM SINGLE-MODE FIBER OPTIC CABLE
MM MULTI-MODE FIBER OPTIC CABLE
MNS MASS NOTIFICATION SYSTEM
GROUND ACCESS WELL
TGB
MASS NOTIFICATION STROBE
TELEPHONE GROUNDING BUS
OS OCCUPANCY SENSOR DUAL LEVEL SWITCHING WALL SWITCH
REQ'D REQUIRED
SPECIFICATION GRADE FLOOR MOUNTED QUADRUPLEX RECEPTACLE
C SPECIFICATION GRADE CEILING MOUNTED DUPLEX RECEPTACLE
C SPECIFICATION GRADE CEILING MOUNTED SINGLE RECEPTACLE
PAD MOUNTED SWITCHPMS
ELECTRICAL SYMBOL SCHEDULE
LIGHTING FIXTURES
LIGHTING CONTROLS
RACEWAYS
RECEPTACLES
SWITCHES
COMMUNICATIONS
FIRE ALARM SYSTEM
MOTORS AND MOTOR CONTROLS
SERVICE AND DISTRIBUTION SOUND AND PAGING SYSTEM
ABBREVIATIONS
DEMOLITION NOTES:
COMBINATION SMOKE/HEAT DETECTOR
SH
INBOARD MIDDLE LAMP ON 3 LAMP FIXTURE
OUTBOARD TWO OUTSIDE LAMPS ON 3 LAMP FIXTURE
S ID SPECIFICATION GRADE INCANDESCENT DIMMER SWITCH
SIPR SIPRNET - SECRET IP ROUTER NETWORK
NIPR NIPRNET - NON-CLASSIFIED (SECURE) IP ROUTER NETWORK
TACLANE TACTICAL LOCAL AREA NETWORK ENCRYPTOR
JAFAN JOINT AIR FORCE - ARMY - NAVY
RELCAN RELEASABLE TO CANADA
MASTER CONTROL PUSH BUTTON STATION
BLUE LIGHT SYSTEM
SB SPECIFICATION GRADE BLUE LIGHT OVER RIDE SWITCH
B
B CEILING MOUNTED BLUE LIGHT
WALL MOUNTED BLUE LIGHT
ACCESS CONTROL SYSTEM
C
K
L
S
IDS
E
CARDREADER
ELECTRIC STRIKE
PIN-PAD
MAGNETIC LOCK
STATUS SENSOR
INTRUSION DETECTION SYSTEM
ACS ACCESS CONTROL SYSTEM
BMS BALANCED MAGNETIC SWITCH
M MOTION SENSORPIR
© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
Mead & Hunt, Inc.
201 NE Park Plaza Drive, Suite 167 Vancouver, WA 98684 phone: 360-883-0047 meadhunt.com
SHEET CONTENTS
DO NOT SCALE DRAWINGS
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
ISSUED
03-28-14 TYPE B2 FINAL
SHEET NO.
U S
W
AR
R E
N
TO
N , O
R
C A
M P
R
IL
E A
E
LE
C
TR
IC
A
L S
E R
V
IC
E S
U P
G R
A D
E
E-001
3142300-122094.01
NOTES, SYMBOLS &
ABBREVIATIONS
03-28-14
RDS
GGI
TDS
© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
Mead & Hunt, Inc.
201 NE Park Plaza Drive, Suite 167 Vancouver, WA 98684 phone: 360-883-0047 meadhunt.com
SHEET CONTENTS
DO NOT SCALE DRAWINGS
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
SHEET NO.
U S
W
AR
R E
N
TO
N , O
R
C A
M P
R
IL
E A
E
LE
C
TR
IC
A
L S
E R
V
IC
E S
U P
G R
A D
E
E-013
SITE
POWER PLAN
GGI
TDS
1. CABLE AND CONDUIT SIZING BASED ON INFORMATION FROM AS-BUILT COMMUNICATIONS ELECTRONICS
TRAINING CENTER DRAWINGS, JAN-97.
2. ALL UNDERGROUND CONDUIT SHALL BE SCHEDULE 40 PVC. ALL ABOVE GROUND CONDUIT SHALL BE
RIGID GALVANIZED STEEL.
UNDERGROUND CONDUIT
(N) NEW
(E) EXISTING
SITE POWER PLAN1 1/16" = 1'-0"
NORTH
PLAN
32'16'8'0
E-104
E-104
E-103
E-103
POWER PLAN GENERAL NOTES:
POWER PLAN KEYED NOTES:
LEGEND
I:\ P
R O
JE
C
T\
\1
.0 0\
D R
A W
IN
G
S\
EL
EC
\E
-0
.D W
G
4/
/2
:0 2:
A
M
PROVIDE ELECTRICAL UPGRADES FOR NORTH WAREHOUSE, SEE DRAWING E-103
PROVIDE ELECTRICAL UPGRADES FOR SOUTH WAREHOUSE SEE DRAWING E-104
REMOVE ONE EXISTING 100A DISCONNECT SWITCH AND RECEPTACLE AND REPLACE WITH 60A FUSED DISCONNECT SWITCH AND MILITARY CLASS L RECEPTACLE. REPLACE OTHER 100A RECEPTACLE WITH MILITARY CLASS L RECEPTACLE. VERIFY RECEPTACLE PIN OUT WITH OWNER. SERVICE EXISTING
DISCONNECT AS REQUIRED.
REMOVE EXISTING RECEPTACLES AND REPLACE WITH MILITARY CLASS L RECEPTACLES. VERIFY RECEPTACLE PIN OUT WITH OWNER. PROVIDE AND INSTALL NEW FUSED DISCONNECT AND GFCI QUAD
RECEPTACLE. SERVICE EXISTING DISCONNECTS AS REQUIRED.
PROVIDE AND INSTALL NEW UNDERGROUND 225A FEEDER TO SOUTH WAREHOUSE.
PROVIDE AND INSTALL NEW POWER STANDS WITH FUSED DISCONNECT SWITCHES AND MILITARY
CLASS L RECEPTACLES. PROVIDE J-BOX FOR DATA/TELECOM. VERIFY RECEPTACLE PIN OUT WITH
OWNER. SEE SINGLE LINE DIAGRAM FOR DETAILS.
REMOVE CONDUCTORS AND REUSE EXISTING UNDERGROUND CONDUIT, RE-FEED EXISTING POWER
STANDS. SEE SINGLE LINE DIAGRAM E-704 FOR DETAILS.
INSTALL NEW UNDERGROUND CONDUIT FOR DATA/TELECOM FROM EXISTING J-BOX AT EAST POWER
STAND TO NEW POWER STANDS. PULL MAXELL INTERDUCT FOR DATA/TELECOM CABLE.
INSTALL 18" x 18" PRECAST UTILITY TRENCH WITH TRAFFIC RATED COVER. SEE CIVIL DRAWINGS FOR
DETAILS.
REPLACE EXISTING SERVICE TO NORTH WAREHOUSE WITH NEW UNDERGROUND 225 AMP FEEDER TO EXISTING DISTRIBUTION PANEL. INSTALL NEW MAIN BREAKER IN PANEL REMOVE EXISTING FEEDER
AND ABANDON CONDUIT IN PLACE.
PROVIDE AND INSTALL NEW 3/4" X 10' GROUND ROD AND WELL, SEE DRAWING E-504.
PROVIDE AND INSTALL NEW 18" X 6" NON METALLIC CABLE TRAY AND SUPPORTS. SEE DETAIL 3, DRAWING E-504.
PROVIDE SERVICE ENTRANCE GROUND ROD AND BONDING PER NEC REQUIREMENTS.13
3142300-122094.01 03-28-14
RDS
MEZZANINEWAREHOUSE
NORTH
MEZZANINE
C
C
C
C
I:\ P
R O
JE
C
T\
\1
.0 0\
D R
A W
IN
G
S\
EL
EC
\E
-1
.D W
G
4/
/2
:0 2:
A
M
© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
Mead & Hunt, Inc.
201 NE Park Plaza Drive, Suite 167 Vancouver, WA 98684 phone: 360-883-0047 meadhunt.com
SHEET NO.
ENLARGED NORTH WAREHOUSE LOWER LEVEL POWER PLAN2 1/8"=1'-0"
8'4'0 16'
ENLARGED NORTH WAREHOUSE UPPER LEVEL POWER PLAN3 1/8"=1'-0"
8'4'0 16'
1. ALL WORK SHOWN IN BOLD IS NEW WORK OR EXISTING TO BE MODIFIED. ALL
OTHER IS EXISTING TO REMAIN.
2. INTERIOR RACEWAYS SHALL BE ELECTRICAL METALLIC TUBING WITH STEEL
COMPRESSION FITTINGS.
3. SEE DRAWING E-001 FOR NOTES, SYMBOLS/LEGEND AND ABBREVIATIONS.
POWER PLAN GENERAL NOTES:
ELECTRICAL CONTRACTOR SHALL VERIFY MAIN BREAKER RATING IN EXISTING PANEL, PROVIDE AND INSTALL NEW 225 AMP MAIN BREAKER IF EXISTING MAIN BREAKER RATING IS LESS THAN
225 AMP. MATCH EXISTING MANUFACTURE AND AIC RATING, DEMOLISH EXISTING 100 AMP
FEEDER AND INSTALL NEW 225 AMP FEEDER.
PROVIDE AND INSTALL 3 PHASE 60 AMP 208 VOLT MILITARY CLASS L RECEPTACLES IN NEMA 1
ENCLOSURE. INSTALL 60" AFF. FIELD VERIFY LOCATION AND RECEPTACLE PIN OUT WITH
OWNER PRIOR TO INSTALLATION.
PROVIDE AND INSTALL NEW RECEPTACLES AS SHOWN.
POWER PLAN KEYED NOTES:
12 2
TECH CONTROL
ENLARGED UPPER LEVEL RECPTACLE LOCATIONS4 1/8"=1'-0"
8'4'0 16'
EQUIPMENT GROUND
NEUTRAL
PHASE CONDUCTOR
LEGEND:
DENOTES HOME RUN
NORTH
PLAN
NORTH
PLAN
NORTH
PLAN
SHEET CONTENTS
DO NOT SCALE DRAWINGS
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
C A
M P
R
IL
E A
E
LE
C
TR
IC
A
L S
E R
V
IC
E S
U P
G R
A D
E
E-103
NORTH WAREHOUSE
POWER PLAN
GGI
TDS
U S
W
AR
R E
N
TO
N , O
R
3142300-122094.01
SOUTH WAREHOUSE
S L S L
S L
JJJJ
J J J J
J
J
J
SWLP01
JJJJJJ
JJJJJJ
J S
J P
J J P
J S
S J
JJJJJJ
JJJJJJ J
S
P
SHEET CONTENTS
DO NOT SCALE DRAWINGS
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
SHEET NO.
© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
Mead & Hunt, Inc.
201 NE Park Plaza Drive, Suite 167 Vancouver, WA 98684 phone: 360-883-0047 meadhunt.com
U S
W
AR
R E
N
TO
N , O
R
C A
M P
R
IL
E A
E
LE
C
TR
IC
A
L S
E R
V
IC
E S
U P
G R
A D
E
E-104
SOUTH WAREHOUSE
LIGHTING &
POWER PLAN
GGI
TDS
ENLARGED SOUTH WAREHOUSE LIGHTING & POWER PLAN3 1/8"=1'-0"
8'4'0 16'
ENLARGED SOUTH WAREHOUSE UNDER MEZZANINE LIGHTING PLAN4 1/8"=1'-0"
8'4'0 16'
LIGHTING LEGEND:
ALUMINUM HIGH BAY LUMINAIR, 400W METAL HALIDE, WITH 4000
KELVIN LAMP, PRISMATIC LENS, AND 3' SAFETY CABLE
MHT-HBa-400E OR APPROVED EQUAL. (LOWER CASE LETTER
DENOTES SWITCH. 'NL' DENOTES NIGHT LIGHT, ALWAYS ON.)
LIGHTING KEYED NOTES:
GENERAL LIGHTING NOTES:
1. SEE DRAWING E-001 FOR NOTES, SYMBOLS/LEGENDS, AND
ABBREVIATIONS.
2. CONTRACTOR SHALL VERIFY ALL FIXTURE CATALOG NUMBERS FOR
ACCURACY. FIXTURE CATALOG NUMBERS ARE SUBJECT TO CHANGE
BY MANUFACTURER.
3. LIGHTING PLAN IS DIAGRAMMATIC, LOCATE CONDUIT AS REQUIRED.
4. CIRCUIT BREAKERS USED TO SWITCH LIGHTS SHALL BE "SWD"/HID"
RATED.
5. RETURN REMOVED EQUIPMENT TO OWNER OR DISPOSE OF PER
OWNERS INSTRUCTIONS.
SURFACE MOUNTED FLUORESCENT FIXTURE, SAME
MANUFACTURER AND MODEL NUMBER AS EXISTING, OR APPROVED
EQUAL (LETTER DENOTES SWITCH).
MEZZANINE ABOVE
b b
LIGHTING SEQUENCE OF OPERATION
NORTH
PLAN
NORTH
PLAN
REMOVE EXISTING FEEDER TO THE SOUTH WAREHOUSE AND
REPLACE WITH NEW AS SHOWN ON THIS DRAWING. REMOVE
EXISTING DISTRIBUTION EQUIPMENT, RACEWAY, AND WIRING.
EXISTING RACEWAY AND WIRING MAY REMAIN IF REUSABLE WITH
NEW DISTRIBUTION SYSTEM.
RE-FEED EXISTING UNIT HEATER(S) FROM NEW DISTRIBUTION
PANEL. PROVIDE AND INSTALL DISCONNECT SWITCH.
PROVIDE AND INSTALL NEW 225A 120/208V 42 SPACE PANELBOARD
AND FEEDER. SEE DRAWING E-602 FOR PANEL SCHEDULE.
RE-FEED EXISING AC UNIT, LIGHT AND RECEPTACLE IN COMM
ROOM. SEE DRAWING E-602 FOR PANEL SCHEDULE.
REMOVE EXISTING HIGH BAY LIGHT FIXTURES. PROVIDE AND
INSTALL NEW INDUCTION TYPE FIXTURES. REUSE EXISTING
CONDUIT AND WIRE WHERE POSSIBLE. SEE DETAIL 4, DRAWING
E-504 FOR LIGHTING CONTROLS.
VERIFY EXISTING FIXTURE VOLTAGE, RE-FEED EXISTING LIGHTING
UNDER MEZZANINE AS REQUIRED. SEE DETAIL 4, DRAWING E-504
FOR LIGHTING CONTROLS.
PROVIDE AND INSTALL NEW FIXTURES ON MEZZANINE. SEE DETAIL
4, DRAWING E-504 FOR LIGHTING CONTROLS.
REMOVE EXISTING LIGHT SWITCHES, DISTRIBUTION, AND WIRING.
PROVIDE THREE NEW LOW VOLTAGE DIGITAL TIME SWITCHES,
WATTSTOPPER TS-400-24. SEE DRAWING E-504, DETAIL 4 FOR
LIGHTING CONTROL WIRING DIAGRAM.
REMOVE EXISTING WIRING AS REQUIRED RE-FEED EXISTING
RECEPTACLES AS SHOWN.
REMOVE EXISTING EMERGENCY LIGHT FIXTURES AND REPLACE
WITH NEW AT LOCATIONS SHOWN, SIMILAR STYLE AS EXISTING.
1 3
NL
BATTERY BACKED EMERGENCY LIGHT
P
S LIGHTING CONTROL SLAVE PACK, WATTSTOPPER S120/277/347, OR
APPROVEED EQUAL
LIGHTING CONTROL POWER PACK, WATTSTOPPER BZ-50 OR
APPROVED EQUAL
PPa POWER PACK, LOWER CASE LETTER DENOTES SWITCH.
SPa SLAVE PACK, LOWER CASE LETTER DENOTES SWITCH.
LV DENOTES LOW VOLTAGE LIGHTING CONTROL CABLE
EQUIPMENT GROUND
NEUTRAL
PHASE CONDUCTOR
LEGEND:
DENOTES HOME RUN
1. THE SOUTH WAREHOUSE CONSISTS OF THREE LIGHTING ZONES;
HIGH BAY, UNDER MEZZANINE, AND MEZZANINE.
2. EACH ZONE IS CONTROLLED VIA A TIME DELAY LIGHT SWITCH
LOCATED AT THE BUILDING ENTRANCE.
3. PRESSING THE LIGHT SWITCH TURNS ON THE FIXTURES IN THAT
ZONE AND STARTS A TIMER. WHEN THE TIMER REACHES ITS
SETTING, THE FIXTURES WILL TURN OFF.
4. DEPRESSING THE BUTTON A SECOND TIME WILL TURN THE
FIXTURES OFF.
5. DEPRESSING AND HOLDING THE LIGHT SWITCH FOR TWO SECONDS
WILL RESET THE TIME AND FIXTURES WILL REMAIN ON.
6. THE TIMER CAN BE SET FROM FIVE MINUTES TO TWELVE HOURS.
SEE INSTRUCTION MANUAL TO SET TIMER.
7. TWO HIGH BAY FIXTURES IN THE WAREHOUSE ARE DESIGNATED AS
NIGHT LIGHTS AND ARE ALWAYS ON. THEY CAN BE SWITCHED OFF
BY OPENING THE CIRCUIT'S BREAKER AT THE DISTRIBUTION PANEL.
3142300-122094.01
I:\ P
R O
JE
C
T\
\1
.0 0\
D R
A W
IN
G
S\
EL
EC
\E
-5
.D W
G
4/
/2
:0 3:
A
M (N) POWER STAND N4 & N5 ELEVATION4 (E) MID POWER STAND ELEVATION5
1 SCALE: 3/4"=1'-0"
KEYED NOTES:
PROVIDE GROUND FAULT CIRCUIT INTERRUPTER RECEPTACLE WITH
WEATHERPROOF BOX AND "EXTRA DUTY IN-USE" COVER.
NEW FUSED DISCONNECT SWITCHES SHALL BE SAME TYPE AND
MATERIAL (NON-METALIC) AS EXISTING.
GENERAL NOTES:
1. ELEVATIONS ARE DIAGRAMMATIC, VERIFY EQUIPMENT LOCATIONS PRIOR
TO INSTALLATION ON SUPPORT STRUCTURE.
2. ALL ENCLOSURES AND WIREWAY SHALL BE NONMETALLIC NEMA 4X
RATED.
3. PROVIDE SUPPORT STRUCTURE FOR NEW POWER STANDS. SEE
STRUCTURAL DRAWING
4. ALL FASTENERS: SCREWS, BOLTS, NUTS, STRUT, CLAMPS ETC. SHALL BE
STAINLESS STEEL.
5. ALL EXPOSED CONDUIT SHALL BE RIGID GALVANIZED STEEL.
6. USE APPROVED HUBS ON ALL TOP CONDUIT ENTRYS, SEALING
LOCKNUTS TO BE USED ON SIDE AND BOTTOM ENTRYS.
7. 100A EQUIPMENT RECEPTACLE(S) SHALL BE MIL-C-22992, CLASS L, SHELL
SIZE 44, THREE PHASE AC, 4-WIRE WITH 4 GROUNDS.CRIMP TYPE PINS.
8. 60A EQUIPMENT RECEPTACLE(S) SHALL BE MIL-C-22992, CLASS L, SHELL
SIZE 32, THREE PHASE AC, 4-WIRE WITH GROUND. CRIMP TYPE PINS.
(N) POWER STAND H1 ELEVATION2(E) EAST POWER STAND ELEVATION
Mead & Hunt, Inc.
201 NE Park Plaza Drive, Suite 167 Vancouver, WA 98684 phone: 360-883-0047 meadhunt.com
SHEET CONTENTS
DO NOT SCALE DRAWINGS
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
SHEET NO.
U S
W
AR
R E
N
TO
N , O
R
C A
M P
R
IL
E A
E
LE
C
TR
IC
A
L S
E R
V
IC
E S
U P
G R
A D
E
E-503
ELECTRICAL
ELEVATIONS
GGI
TDS
3 (N) POWER STAND SIDE ELEVATION
(E) WEST POWER STAND ELEVATION6
SCALE: 3/4"=1'-0" SCALE: 3/4"=1'-0"
SCALE: 3/4"=1'-0" SCALE: 3/4"=1'-0" SCALE: 3/4"=1'-0"
3142300-122094.01 03-28-14
RDS
ISSUED
03-28-14 TYPE B2 FINAL
I:\ P
R O
JE
C
T\
\1
.0 0\
D R
A W
IN
G
S\
EL
EC
\E
-5
.D W
G
4/
/2
:0 3:
A
M
© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
Mead & Hunt, Inc.
201 NE Park Plaza Drive, Suite 167 Vancouver, WA 98684 phone: 360-883-0047 meadhunt.com
SHEET CONTENTS
DO NOT SCALE DRAWINGS
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
SHEET NO.
U S
W
AR
R E
N
TO
N , O
R
C A
M P
R
IL
E A
E
LE
C
TR
IC
A
L S
E R
V
IC
E S
U P
G R
A D
E
E-504
ELECTRICAL DETAILS
TRW
TDS
KEYED NOTES:
SEE STRUCTURAL DRAWING FOR DETAILS.
INSTALL TOP OF TRAY 18" MAXIMUM ABOVE GRADE.
GENERAL NOTES:
1. NOT USED
3142300-122094.01 03-28-14
RDS
ISSUED
03-28-14 TYPE B2 FINAL
SHEET CONTENTS
DO NOT SCALE DRAWINGS
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
SHEET NO.
U S
W
AR
R E
N
TO
N , O
R
C A
M P
R
IL
E A
E
LE
C
TR
IC
A
L S
E R
V
IC
E S
U P
G R
A D
E
E-602
PANEL SCHEDULES
TRW
TDS
KEYED NOTES:
REPLACE EXISTING MAIN CIRCUIT BREAKER WITH 225A
BREAKER. SAME MANUFACTURER, MODEL, AND RATING AS
EXISTING.
GENERAL NOTES:
1. NOT USED.
PROVIDE AND INSTALL NEW CIRCUIT BREAKER. SAME
MANUFACTURER, MODEL, AND RATING AS EXISTING. REVISE
PANEL SCHEDULES.
© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
Mead & Hunt, Inc.
201 NE Park Plaza Drive, Suite 167 Vancouver, WA 98684 phone: 360-883-0047 meadhunt.com
3142300-122094.01
REMOVE EXISTING RECEPTACLE.2
SINGLE LINE DIAGRAM KEYED NOTES:
4 REMOVE EXISTING 60 AMP RECEPTACLES A, B, AND C; CONDUIT, WIRING..
© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
Mead & Hunt, Inc.
201 NE Park Plaza Drive, Suite 167 Vancouver, WA 98684 phone: 360-883-0047 meadhunt.com
SINGLE LINE DRAGRAM (REMOVAL)1 NO SCALE
SHEET CONTENTS
DO NOT SCALE DRAWINGS
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
SHEET NO.
U S
W
AR
R E
N
TO
N , O
R
C A
M P
R
IL
E A
E
LE
C
TR
IC
A
L S
E R
V
IC
E S
U P
G R
A D
E
E-703
SINGLE LINE DIAGRAM
REMOVAL
GGI
TDS
1. CABLE AND CONDUIT SIZING BASED ON INFORMATION FROM AS-BUILT
COMMUNICATIONS ELECTRONICS TRAINING CENTER DRAWINGS, JAN-97.
2. SEE DRAWING E-001 FOR NOTES, SYMBOLS/LEGENDS, AND ABBREVIATIONS.
SINGLE LINE DIAGRAM GENERAL NOTES:
4 4
5 REMOVE 200A RECEPTACLE D, CONDUIT, AND WIRING.
3 3
REMOVE RECEPTACLES AND FEEDER CABLE BACK TO SOURCE. CONDUIT TO BE REUSED.3
REMOVE 100 AMP RECEPTACLE.1
DEMO
(N) NEW
(E) EXISTING
LEGEND
6 REMOVE EXISTING 60 AMP DISCONNECT, RECEPTACLE, J-BOX AND WIRING.
3142300-122094.01
© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
Mead & Hunt, Inc.
201 NE Park Plaza Drive, Suite 167 Vancouver, WA 98684 phone: 360-883-0047 meadhunt.com
SINGLE LINE DRAGRAM1 NO SCALE
SHEET CONTENTS
DO NOT SCALE DRAWINGS
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
SHEET NO.
U S
W
AR
R E
N
TO
N , O
R
C A
M P
R
IL
E A
E
LE
C
TR
IC
A
L S
E R
V
IC
E S
U P
G R
A D
E
E-704
SINGLE LINE DIAGRAM
GGI
TDS
PROVIDE AND INSTALL NEW FEEDER, MILITARY CLASS L RECEPTACLES, QUAD RECEPTACLE
AND DISCONNECT SWITCH AS REQUIRED . REUSE EXISTING FUSED DISCONNECT SWITCHES AS
SHOWN.
REMOVE EXISTING #1 CONDUCTORS AND REUSED EXISTING 4" UNDERGROUND CONDUIT. PULL
IN NEW 200 AMP, #4/0 POWER STAND FEEDER.
PROVIDE NEW POWER STANDS WITH FUSED DISCONNECT SWITCHES,MILITARY CLASS L
RECEPTACLES, AND QUAD RECEPTACLE AS SHOWN.
REPLACE EXISTING RECEPTACLE WITH A MILITARY CLASS L RECEPTACLE.
PROVIDE NEW 200 AMP SERVICE TO SOUTH WAREHOUSE.
REPLACE EXISTING WAREHOUSE FEEDER WITH NEW 225 AMP SERVICE.
REPLACE EXISTING SWITCHBOARD CIRCUIT BREAKERS TO AGREE WITH NEW DISTRIBUTION.
SAME MANUFACTURE, MODEL NUMBER, AND RATING AS EXISTING.
SINGLE LINE DIAGRAM KEYED NOTES:
1. CABLE AND CONDUIT SIZING BASED ON INFORMATION FROM AS-BUILT
COMMUNICATIONS ELECTRONICS TRAINING CENTER DRAWINGS, JAN-97.
2. SEE DRAWING E-001 FOR NOTES, SYMBOLS/LEGENDS, AND ABBREVIATIONS.
SINGLE LINE DIAGRAM GENERAL NOTES:
(N) NEW
(E) EXISTING
LEGEND
LOAD SUMMARY
PER 208V SWITCHBOARD POWER METER READINGS COLLECTED ON 1/14/13,
THE MAXIMUM DEMAND RECORDED THE PREVIOUS SIX MONTHS WAS:
A-PHASE: 240A, B-PHASE: 238A, C-PHASE: 252A.
THE METER'S SLIDING WINDOW SETTING WAS THE DEFAULT VALUE OF
AVERAGE DEMAND OVER A 10 MINUTE PERIOD. THIS MAXIMUM DEMAND
OCCURRED OVER THE WEEKEND OF 1/12/13 AND WAS CONFIRMED BY THE
OWNER TO BE THE MAXIMUM RECEPTACLE LOAD EXPECTED FOR THE NEW
ELECTRICAL DISTRIBUTION SYSTEM CONFIGURATION.
BASED ON THIS RECORDED LOAD, THE DESIGN MAXIMUM DEMAND FOR THE
208V SWITCHBOARD IS ESTIMATED TO BE:
245 AMPS; 88 KVA.
3142300-122094.01
| A 01 S&D 01 |
| A 01 S&D 02 |
| A 01 S&D 30.09-1 13304 B Final 041114 |
| E-001 |
| E-001 |
| E-013 |
| E-013 SITE POWER PLAN |
| E-103 |
| E-103 |
| E-104 |
| E-104 SOUTH WAREHOUSE LIGHTING & POWER PLAN |
| E-503 |
| E-503 ELECTRICAL ELEVATIONS |
| E-504 |
| E-504 ELECTRICAL DETAILS |
| E-602 |
| E-602 PANEL SCHEDULES |
| E-703 |
| E-703 SINGLE-LINE DIAGRAM REMOVAL |
| E-704 |
| E-704 SINGLE-LINE DIAGRAM |
File details come from the government source that posted it. Updated .