SEE ADDENDUM
(No Collect Calls)
W912ER-17-T-0013 16-Mar-2017
b. TELEPHONE NUMBER
540-665-3137
8. OFFER DUE DATE/LOCAL TIME
11:00 PM 30 Mar 2017
5. SOLICITATION NUMBER 6. SOLICITATION ISSUE DATE
AUTHORIZED FOR LOCAL REPRODUCTION
PREVIOUS EDITION IS NOT USABLE
STANDARD FORM 1449 (REV. 2/2012)
Prescribed by GSA – FAR (48 CFR) 53.212
(TYPE OR PRINT)
(SIGNATURE OF CONTRACTING OFFICER)
ADDENDA ARE
X
26. TOTAL AWARD AMOUNT (For Gov t. Use Only )
23.
CODE 10. THIS ACQUISITION IS
SUCH ADDRESS IN OFFER
17b. CHECK IF REMITTANCE IS DIFFERENT AND PUT
BELOW IS CHECKED
TELEPHONE NO. 207-256-9107
W912ER9. ISSUED BY
18b. SUBMIT INVOICES TO ADDRESS SHOWN IN BLOCK 18a. UNLESS BLOCK
W912ER17P0028 01-Jun-2017
7. FOR SOLICITATION
INFORMATION CALL:
a. NAME
DEMETRICA L JOHNSON
2. CONTRACT NO. 3. AWARD/EFFECTIVE DATE 4. ORDER NUMBER
(TYPE OR PRINT)
30b. NAME AND TITLE OF SIGNER 30c. DATE SIGNED 31b. NAME OF CONTRACTING OFFICER
30a. SIGNATURE OF OFFEROR/CONTRACTOR 31a.UNITED STATES OF AMERICA
27a. SOLICITATION INCORPORATES BY REFERENCE FAR 52.212-1. 52.212-4. FAR 52.212-3. 52.212-5 ARE ATTACHED.
X
25. ACCOUNTING AND APPROPRIATION DATA
1. REQUISITION NUMBER
20.
ADDITIONAL SHEETS SUBJECT TO THE TERMS AND CONDITIONS SPECIFIED.
OFFEROR TO COMPLETE BLOCKS 12, 17, 23, 24, AND 30
SOLICITATION/CONTRACT/ORDER FOR COMMERCIAL ITEMS
W26WKS71312470
ARE NOT ATTACHED
27b. CONTRACT/PURCHASE ORDER INCORPORATES BY REFERENCE FAR 52.212-4. FAR 52.212-5 IS ATTACHED. ADDENDA ARE ARE NOT ATTACHED
JOE L LIBBEY / Contracting Officer
See Schedule $137,050.70
(BLOCK 5), INCLUDING ANY ADDITIONS OR CHANGES WHICH ARE
SET FORTH HEREIN, IS ACCEPTED AS TO ITEMS: SEE SCHEDULE
.01-Apr-2017 YOUR OFFER ON SOLICITATION
28. CONTRACTOR IS REQUIRED TO SIGN THIS DOCUMENT AND RETURN INCON, Inc.
% FOR:SET ASIDE:UNRESTRICTED ORX
SMALL BUSINESS
17a.CONTRACTOR/ CODE 1N0S8 FACILITY
OFFEROR CODE
US ARMY CORPS OF ENGINEERS-CETAM-CT
MIDDLE EAST DISTRICT, CETAM-CT
PO BOX 2250
WINCHESTER VA 22604-1450
INCON INC.
JUSTIN H. BOUDREAU PE
10620 RIGGS HILL ROAD UNIT B
JESSUP MD 20794-9431
U.S. ARMY CORPS OF ENGINEERS FINANCE CEN
ATTN: CEFC-FP
5722 INTEGRITY DRIVE
MILLINGTON TN 38054-5005
18a. PAYMENT WILL BE MADE BY CODE W916TX
RATED ORDER UNDER
DPAS (15 CFR 700)
13a. THIS CONTRACT IS A
13b. RATING
CODE
SEE ITEM 9
15. DELIVER TO CODE W912ER 16. ADMINISTERED BY
Net 30 Days
12. DISCOUNT TERMS11. DELIVERY FOR FOB DESTINA-
TION UNLESS BLOCK IS
MARKED
SEE SCHEDULE
14. METHOD OF SOLICITATION
RFQ IFB RFPX
US ARMY CORPS OF ENGINEERS-KUWAIT
MIDDLE EAST DISTRICT
KUWAIT AREA OFFICE BLDG. T-34
CAMP ARIFJAN
APO AE 09366
FAX:
TEL: SERVICE-DISABLED
VETERAN-OWNED
SMALL BUSINESS
8(A)
HUBZONE SMALL
BUSINESS
SIZE STANDARD:
NAICS:
335313
OFFER DATED
29. AWARD OF CONTRACT: REF.
DELIVER ALL ITEMS SET FORTH OR OTHERWISE IDENTIFIED ABOVE AND ON ANY
COPIES TO ISSUING OFFICE. CONTRACTOR AGREES TO FURNISH AND
X
EMAIL: joe.l.libbey@usace.army.mil
TEL:
31c. DATE SIGNED
01-Jun-2017
SEE SCHEDULE
SCHEDULE OF SUPPLIES/ SERVICESITEM NO. QUANTITY UNIT UNIT PRICE AMOUNT
24.22.21.19.
WOMEN-OWNED SMALL BUSINESS (WOSB)
ELIGIBLE UNDER THE WOMEN-OWNED
SMALL BUSINESS PROGRAM
EDWOSB
32g. E-MAIL OF AUTHORIZED GOVERNMENT REPRESENTATIVE
SOLICITATION/CONTRACT/ORDER FOR COMMERCIAL ITEMS
(CONTINUED)
PAGE 2 OF46
ACCEPTED, AND CONFORMS TO THE CONTRACT, EXCEPT AS NOTED: ______________________________________________________
32a. QUANTITY IN COLUMN 21 HAS BEEN
RECEIVED INSPECTED
32b. SIGNATURE OF AUTHORIZED GOVERNMENT
REPRESENTATIVE
32c. DATE 32d. PRINTED NAME AND TITLE OF AUTHORIZED GOVERNMENT
REPRESENTATIVE
32e. MAILING ADDRESS OF AUTHORIZED GOVERNMENT REPRESENTATIVE 32f . TELEPHONE NUMBER OF AUTHORIZED GOVERNMENT REPRESENTATIVE
37. CHECK NUMBER
FINALPARTIALCOMPLETE
36. PAYMENT35. AMOUNT VERIFIED
CORRECT FOR
34. VOUCHER NUMBER
FINAL
33. SHIP NUMBER
PARTIAL
38. S/R ACCOUNT NUMBER 39. S/R VOUCHER NUMBER 40. PAID BY
41a. I CERTIFY THIS ACCOUNT IS CORRECT AND PROPER FOR PAYMENT
41b. SIGNATURE AND TITLE OF CERTIFYING OFFICER 41c. DATE
42a. RECEIVED BY (Print)
42b. RECEIVED AT (Location)
42c. DATE REC'D (YY/MM/DD) 42d. TOTAL CONTAINERS
STANDARD FORM 1449 (REV. 2/2012) BACK
Prescribed by GSA – FAR (48 CFR) 53.212
AUTHORIZED FOR LOCAL REPRODUCTION
PREVIOUS EDITION IS NOT USABLE
SEE SCHEDULE
20.
SCHEDULE OF SUPPLIES/ SERVICES
21.
QUANTITY UNIT
22. 23.
UNIT PRICE
24.
AMOUNT
19.
ITEM NO.
DEPARTMENT OF THE ARMY
CAMP ARIFJAN, KUWAIT
APO AE 09366
Section SF 1449 - CONTINUATION SHEET
PANELBOARD STANDARD SPECS
ELECTRIC POWER DISTRIBUTION
EQUIPMENT STANDARD
SPECIFICATION
PANELBOARDS, SWITCHBOARDS AND LOAD
CENTERS FOR NON-PERMANENT FACILITIES
Project ID: Project No. 033-16-X-P-LSA; KLZ (panelboard schedules attached)
PART 1 – GENERAL
1.1 GENERAL REQUIREMENTS FOR PANELBOARDS, SWITCHBOARDS,
LOAD CENTERS
A. This requirements document was developed to establish the minimum requirements for the Life Safety and Habitability aspects of electric power distribution systems for non- permanent facilities in support of military operations.
B. The specification defines electric power distribution panelboards (“panelboards”) as a complete individual assembly, designed and engineered in the form of a single panel, including buses and automatic overcurrent devices, tested and manufactured to international industry standards (IEC/CE, ANSI/IEEE, UL/CUL/CSA, CSA, NEMA/IEC, BS 7671).
C. Complete panelboard assemblies shall be designed and manufactured by the same OEM; in other words, all the major components will designed and assembled by the same OEM (Enclosure, Interior/Bus, Dead Front, Cover, Main Disconnect Device, Branch devices). Panelboards assembled by an Integrator or other third party are NOT acceptable.
D. Provide electrical equipment that is the manufacturer's standard catalog products, conforming to the latest published industry and technical society standards at the date of contract award. Underwriters Laboratories (UL) listing or third-party certification is required for all basic equipment. Use of shop or field fabricated electrical equipment assemblies that are not manufacturer's standard catalog products or do not conform to the industry and technical society standards are not acceptable.
E. Electrical Components, Devices, and Accessories shall be listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.
F. Switchboard designs engineered and certified to industry standards are acceptable when the requirements exceed the ratings of an OEM’s standard panelboard design.
G. All electrical equipment and materials shall be new (new production, new-in-box).
Used, re-conditioned/refurbished equipment or materials are not acceptable.
H. Enclosures:
1. Panelboard assemblies will include back box, dead front, hinged front covers, main disconnect devices, branch breakers and accessories that are engineered and tested for use as a single unit.
2. Shall be designed to be mounted against a wall, partition, or other support structure; and accessible only from the front. Vendor will provide OEM shop drawings that show mounting points.
3. Must be rated for environmental conditions specific for the installed location.
a. Ambient Temperature: Not exceeding minus 22 degrees Fahrenheit (minus 30 degrees Celsius) to plus 130 degrees Fahrenheit (plus 55 degrees Celsius).
b. b. Altitude: Not exceeding 6600 feet (2000 meters).
c. Indoor Dry and Clean Locations: NEMA250 Type 1 (IP10, per IEC 60529)
d. Outdoor/Exposed Locations:, NEMA 250 Type 3 (IP54, per IEC 60529)
NOTE: Refer to the Panelboard Schedules for site-specific panel requirements.
4. Front Cover and Door:
a. Secured to box. For surface-mounted fronts, match the box dimensions; for flush-mounted fronts, overlap the back box.
b. With door open only the circuit breaker handles shall be accessible. The dead-front shall prevent exposure to wiring and energized components.
5. Finish:
a. Panels and Trim: Steel, factory finished immediately after cleaning, pretreating and priming with manufacturer's standard enamel.
b. Back Boxes: Outdoor designs will have same finish as panels and trim.
I. System Voltage:
NOTE: Refer to the Panelboard Schedule for site-specific panel requirements.
1. 400/230vac, 3-phase, 50Hz
2. 415/240vac, 3-phase, 50Hz
3. 440/250vac, 3-phase, 50Hz
J. Incoming Main Disconnect Device:
1. Location:
a. Bottom Entry/Bottom Fed
NOTE: Refer to the Panelboard Schedule for site-specific panel requirements.
2. Overcurrent Protective Devices: Molded Case Circuit Breaker (MCCB)
3. OPDs shall be manufactured by the same OEM as the panelboards and switchboards and designed for use with the corresponding panelboard or switchboard design.
4. Molded-Case Circuit-Breaker Features and Accessories: Standard frame sizes, trip ratings, and number of poles
K. Phase, Neutral, and Ground Buses:
1. Material: Hard-drawn copper, 98 percent conductivity.
L. Panelboard Short-Circuit Current Ratings: All panelboards shall be Fully Rated: Fully rated to interrupt symmetrical short-circuit current available at terminals.
NOTE: Refer to the Panelboard Schedule for site-specific panel requirements.
M. Branch Overcurrent Protective Devices:
1. Molded Case Circuit Breaker (MCCB)
2. Manufactured by the same OEM as the panelboards and switchboards and matched to the corresponding panelboard and switchboard designs
3. Molded-Case Circuit-Breaker Features and Accessories: Standard frame sizes, trip ratings, and number of poles.
PART 2 – COMPLIANCE, TRACEABILTY & SUBMITTALS
2.1 PRODUCT DOCUMENTS
A. The Vendor/Supplier shall provide the OEM’s standard documentation package including:
1. Product drawings
2. Product manuals
3. Industry compliance (certifications)
4. Product Warranty
2.2 ACRONYMS and ABBREVIATIONS
A. AIC/R: Ampere Interrupt Current, Ampere Interrupt Rating
B. ANSI: American National Standards Institute
C. AWG: American Wire Gauge
D. CE: Conformité Européenne
E. Deg. C: Degrees Celsius
F. Deg. F: Degrees Fahrenheit
G. IEC: International Electrotechnical Commission
H. IEEE: Institute of Electrical and Electronic Engineers
I. LV: An electrical system having a maximum RMS voltage less than 1,000 volts
J. MB/MCB: Main Breaker/Main Circuit Breaker
K. MCCB: Molded Case Circuit Breaker
L. MDP: Main Distribution Panel/Panelboard
M. NEC: National Electrical Code (NFPA 70)
N. NEMA: National Electrical Manufacturers Association
O. NFPA: National Fire Protection Association
P. OCPD: Overcurrent Protective Devices
Q. RMS: Root-mean-square
R. SCCR: Short-Circuit Current Rating
S. SDP: Secondary Distribution Panel/Panelboard
T. SWB: Switchboard
U. UFC: Unified Facilities Criteria
V. UL: Underwriters Laboratories
W. VAC: Volts Alternating Current (AC)
X. VDC: Volts Direct Current (DC)
A. Product Data: For each type of panelboard, switchboard and overcurrent protective device, provide manufacturers' technical data on features, performance, electrical characteristics, ratings, and finishes.
B. Shop Drawings: For each panelboard and related equipment.
1. Include dimensioned plans, elevations, sections, and details. Show tabulations of installed devices, equipment features, and ratings.
2. Detail enclosure types and details for both indoor and outdoor designs [NEMA Type 1 (IP10), NEMA Type 3 (IP54)].
3. Detail bus configuration, current and voltage ratings at system operating frequency.
4. Short-circuit current rating (SCCR) of panelboards and overcurrent protective devices.
5. Detail features, characteristics, ratings, and factory settings of individual overcurrent protective devices and auxiliary components where applicable.
6. Include wiring diagrams for power, signal, and control wiring.
7. Include time-current coordination curves for each type and rating of overcurrent protective device included in panelboards. May be submitted on translucent log-log graft paper, digitally (CD) or in OEM manuals; include selectable ranges for each type of overcurrent protective device.
C. Qualification Data: Certification and industry compliance from qualified testing agency (ies).
D. Operation and Maintenance: Provide operation, and maintenance manuals (O&M) and "Operation and Maintenance Data," include the following:
1. Manufacturer's written instructions for testing and adjusting overcurrent protective devices.
2. Time-current curves, including selectable ranges for each type of overcurrent protective device that allows adjustments.
3. Recommended Spare Parts List
2.4 QUALITY ASSURANCE
A. Provide electrical equipment that is the manufacturer’s standard catalog products, conforming to the latest published industry and technical society standards at the date of contract award. Underwriters Laboratories (UL) listing or third-party certification is required for all basic equipment. Use of shop or field fabricated electrical equipment assemblies that are not manufacturer’s standard catalog products or do not conform to the industry and technical society standards are not acceptable.
B. Electrical Components, Devices, and Accessories: Listed and labeled as defined in the UFC and NFPA 70, by a qualified testing agency, and marked for intended location and application. Comply with NEMA PB 1.
C. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.
2.3 SUBMITTALS
D. Panelboards and Switchboards considered in this document shall comply with the following industry and US GOV standards (minimum):
1. UFC 3-501-01, Electrical Engineering
2. UFC 3-520-01, Interior Electrical Systems
3. UFC 3-550-01, Exterior Electrical Power Distribution
4. UL 489, Molded-Case Circuit Breakers
5. UL 67, Standard for Panelboards
6. UL 50, Enclosures for Electrical Equipment
7. NEMA 250, Enclosures for Electrical Equipment (1000 Volts Maximum)
8. NEMA PB1, Panelboards
9. NFPA 70, National Electrical Code® (NEC®)
10. IEC 61439, Low-voltage Switchgear and Controlgear Assemblies
2.5 DELIVERY, STORAGE, AND HANDLING
A. Equipment shall be new production only (new-in-box) and delivered in the OEM factory packaging.
B. Equipment damaged in shipping is not acceptable; the Supplier and Carrier will process the Return Material Authorization and replace damaged material.
2.6 OPERATING CONDITIONS
A. Equipment Ratings:
1. Equipment shall be rated for continuous operation under the following conditions unless otherwise indicated:
a. Relative Humidity 0 to 95% non-condensing
b. Operating Frequency 47–63 Hz
c. Storage Temperature -40° to +65° C (-40° to +149° F)
d. Operating Temperature -40° to +65° C (-40° to +149° F)
e. Altitude: Not exceeding 6600 feet (2000 m)
PART 3 – LABELING
3.1 WARNINGS & IDENTIFICATION
A. Panelboard Nameplates: Label each panelboard with a nameplate complying with requirements for identification specified in Division 26 Section "Identification for Electrical Systems."
B. Multiple Power Source Warning: "DANGER - ELECTRICAL SHOCK HAZARD - EQUIPMENT HAS MULTIPLE POWER SOURCES." (where applicable per panelboard and equipment schedules)
C. Workspace/Indoor Clearance Warning: "WARNING - AREA IN FRONT OF
ELECTRICAL EQUIPMENT MUST BE KEPT CLEAR FOR 48 INCHES (1220 MM)."
(where applicable per panelboard and equipment schedules)
D. Flash Protection Field Marking: All panelboards, switchgear, switchboards, panelboards motor control centers, motor control panels and electrical control panels shall be provided with a black on yellow warning sign per ANSI Z535.4 and ISO 3864. The sign shall read: “DANGER! ARC FLASH and SHOCK HAZARD. FOLLOW ALL REQUIREMENTS IN NFPA70E FOR SAFE WORK PRACTICES and PERSONAL
PROTECTIVE EQUIPMENT.”
1. Signs shall be prominently mounted on the front of the equipment readily visible.
2. If the equipment has multiple removable front covers, a sign shall be mounted on each cover.
END OF REQUIREMENTS SECTION
APPENDIX 1
PANELBOARD CONSTRUCTION
(Reference only)
Panelboard Enclosures
(B tt F d MCB h
Fully assembled Panelboard
( h i h hi d )
Deadfront installed to
Quantity: 1 3Ø Panelboard Schedule
PANEL NO. MDP #1 Enclosure Type: OUTDOOR Bus: 400/230vac, 50Hz
3Ø 4 Wire 1600 AMP
Main C.B. 1600 AMP
Location: SOJTF OIR - S Serving: Main Distribution Panel SCCR (amps): 35,000 (minimum) Feed Thru Lugs
SubFeed Lugs
Flush Mount
Surface Mount
Top Feed
Bottom Feed ✔ Fully Rated Series Rated Iso. Gnd. Bus ✔ ✔ Load Type
Circuit Description
CONN
KVA
Circuit Breaker
PH
Circuit Breaker CONN
KVA
TypeAMP Pole CKT CKT Pole AMP
SDP 1A 600 3 1 A 2 3 600 SDP 2A
SDP 1A 600 3 3 B 4 3 600
SDP 1A 600 3 5 C 6 3 600 SDP 2A
MAINT PAD 200 3 7 A 8 3 200 SPARE
MAINT PAD 200 3 9 B 10 3 200 SPARE
MAINT PAD 200 3 11 C 12 3 200 SPARE
SPARE 125 3 13 A 14 3 125 SPARE
SPARE 125 3 15 B 16 3 125 SPARE
SPARE 125 3 17 C 18 3 125 SPARE
SPARE 200 3 19 A 20 3 200 SPARE
SPARE 200 3 21 B 22 3 200 SPARE
SPARE 200 3 23 C 24 3 200 SPARE
SPARE 400 3 25 A 26 3 600 SPARE
SPARE 400 3 27 B 28 3 600 SPARE
SPARE 400 3 29 C 30 3 600 SPARE
31 A 32
33 B 34
35 C 36
37 A 38
39 B 40
41 C 42
CONNECTED LOAD DEMAND LOAD
Total General‐Purpose Receptacle (R) Load
@ 180VA/ea. KVA
Total General‐Purpose Receptacle ( R ) Load @ 180VA/ea., 100% for first 10 KVA & 50% for remainder KVA
Total Specific‐Purpose (SP) Receptacles KVA Total Specific‐Purpose (SP) Receptacles KVA
Total Motor (M) Load KVA Total Motor (M) Load KVA
Total Lighting (L) Load @ 125% KVA Total Lighting (L) Load @ 125% KVA
Total HVAC (H) Load KVA Total HVAC (H) Load KVA
TOTAL CONNECTED LOAD KVA Largest Motor @ 125% KVA
CONNECTED AMP
Total / Phase
A B C MINIMUM FEEDER CAPACITY
KVA AMP
TOTAL DEMAND LOAD KVA
3Ø Panelboard ScheduleQuantity: 1
PANEL NO. MDP #2 Enclosure Type: OUTDOOR Bus: 400/230vac, 50Hz
Main C.B. 1600 AMP
Location: SOJTF OIR - S Serving: Main Distribution Panel SCCR (amps): 35,000 (minimum) Feed Thru Lugs
SubFeed Lugs
Flush Mount
Surface Mount
Top Feed
Bottom Feed ✔ Fully Rated Series Rated Iso. Gnd. Bus ✔ ✔
KVA
Circuit Breaker
PH
TypeAMP Pole CKT CKT Pole AMP
SDP 3A 600 3 1 A 2 3 600 SDP FUT
SDP 3A 600 3 3 B 4 3 600 SDP FUT
SDP 3A 600 3 5 C 6 3 600 SDP FUT
SPARE 200 3 7 A 8 3 200 SPARE
SPARE 200 3 9 B 10 3 200 SPARE
SPARE 200 3 11 C 12 3 200 SPARE
SPARE 125 3 13 A 14 3 125 SPARE
SPARE 125 3 15 B 16 3 125 SPARE
SPARE 125 3 17 C 18 3 125 SPARE
SPARE 200 3 19 A 20 3 200 SPARE
SPARE 200 3 21 B 22 3 200 SPARE
SPARE 200 3 23 C 24 3 200 SPARE
SPARE 400 3 25 A 26 3 600 SPARE
SPARE 400 3 27 B 28 3 600 SPARE
SPARE 400 3 29 C 30 3 600 SPARE
31 A 32
33 B 34
35 C 36
37 A 38
39 B 40
41 C 42
CONNECTED LOAD DEMAND LOAD
Total General‐Purpose Receptacle (R) Load
@ 180VA/ea. KVA
Total General‐Purpose Receptacle ( R ) Load @ 180VA/ea., 100% for first 10 KVA & 50% for remainder KVA
Total Specific‐Purpose (SP) Receptacles KVA Total Specific‐Purpose (SP) Receptacles KVA
Total Motor (M) Load KVA Total Motor (M) Load KVA
Total Lighting (L) Load @ 125% KVA Total Lighting (L) Load @ 125% KVA
Total HVAC (H) Load KVA Total HVAC (H) Load KVA
TOTAL CONNECTED LOAD KVA Largest Motor @ 125% KVA
CONNECTED AMP
Total / Phase
A B C MINIMUM FEEDER CAPACITY
PANEL NO. MDP #3 Enclosure Type: OUTDOOR Bus: 400/230vac, 50Hz
Main C.B. 1600 AMP
Location: SOJTF OIR - S Serving: Main Distribution Panel SCCR (amps): 35,000 (minimum) Feed Thru Lugs
SubFeed Lugs
Flush Mount
Surface Mount
Top Feed
Bottom Feed ✔ Fully Rated Series Rated Iso. Gnd. Bus ✔ ✔
KVA
Circuit Breaker
PH
TypeAMP Pole CKT CKT Pole AMP
MED LSA 1 400 3 1 A 2 3 400 MED LSA 2
MED LSA 1 400 3 3 B 4 3 400 MED LSA 2
MED LSA 1 400 3 5 C 6 3 400 MED LSA 2
SPARE 200 3 7 A 8 3 200 SPARE
SPARE 200 3 9 B 10 3 200 SPARE
SPARE 200 3 11 C 12 3 200 SPARE
SPARE 125 3 13 A 14 3 125 SPARE
SPARE 125 3 15 B 16 3 125 SPARE
SPARE 125 3 17 C 18 3 125 SPARE
SPARE 200 3 19 A 20 3 200 SPARE
SPARE 200 3 21 B 22 3 200 SPARE
SPARE 200 3 23 C 24 3 200 SPARE
SPARE 400 3 25 A 26 3 400 SPARE
SPARE 400 3 27 B 28 3 400 SPARE
SPARE 400 3 29 C 30 3 400 SPARE
31 A 32
33 B 34
35 C 36
37 A 38
39 B 40
41 C 42
CONNECTED LOAD DEMAND LOAD
Total General‐Purpose Receptacle (R) Load
@ 180VA/ea. KVA
Total General‐Purpose Receptacle ( R ) Load @ 180VA/ea., 100% for first 10 KVA & 50% for remainder KVA
Total Specific‐Purpose (SP) Receptacles KVA Total Specific‐Purpose (SP) Receptacles KVA
Total Motor (M) Load KVA Total Motor (M) Load KVA
Total Lighting (L) Load @ 125% KVA Total Lighting (L) Load @ 125% KVA
Total HVAC (H) Load KVA Total HVAC (H) Load KVA
TOTAL CONNECTED LOAD KVA Largest Motor @ 125% KVA
CONNECTED AMP
Total / Phase
A B C MINIMUM FEEDER CAPACITY
PANEL NO. SDP 1A Enclosure Type: OUTDOOR Bus: 400/230vac, 50Hz
3Ø 4 Wire 600 AMP
Main C.B. 600 AMP
Location: SOJTF OIR - S Serving: Secondary Dist. Panel SCCR (amps): 22,000 (minimum) Feed Thru Lugs
SubFeed Lugs
Flush Mount
Surface Mount
Top Feed
Bottom Feed ✔ Fully Rated Series Rated Iso. Gnd. Bus ✔ ✔
KVA
Circuit Breaker
PH
TypeAMP Pole CKT CKT Pole AMP
CMD/DV 125 3 1 A 2 3 125 BILLET 3
CMD/DV 125 3 3 B 4 3 125 BILLET 3
CMD/DV 125 3 5 C 6 3 125 BILLET 3
BILLET 1 125 3 7 A 8 3 125 BILLET 4
BILLET 1 125 3 9 B 10 3 125 BILLET 4
BILLET 1 125 3 11 C 12 3 125 BILLET 4
BILLET 2 125 3 13 A 14 3 125 BILLET 5
BILLET 2 125 3 15 B 16 3 125 BILLET 5
BILLET 2 125 3 17 C 18 3 125 BILLET 5
SPARE 125 3 19 A 20 3 125 SPARE
SPARE 125 3 21 B 22 3 125 SPARE
SPARE 125 3 23 C 24 3 125 SPARE
SPARE 125 3 25 A 26 3 125 SPARE
SPARE 125 3 27 B 28 3 125 SPARE
SPARE 125 3 29 C 30 3 125 SPARE
SPARE 200 3 31 A 32 3 200 SPARE
SPARE 200 3 33 B 34 3 200 SPARE
SPARE 200 3 35 C 36 3 200 SPARE
SPARE 200 3 37 A 38 3 200 SPARE
SPARE 200 3 39 B 40 3 200 SPARE
SPARE 200 3 41 C 42 3 200 SPARE
CONNECTED LOAD DEMAND LOAD
Total General‐Purpose Receptacle (R) Load
@ 180VA/ea. KVA
Total General‐Purpose Receptacle ( R ) Load @ 180VA/ea., 100% for first 10 KVA & 50% for remainder KVA
Total Specific‐Purpose (SP) Receptacles KVA Total Specific‐Purpose (SP) Receptacles KVA
Total Motor (M) Load KVA Total Motor (M) Load KVA
Total Lighting (L) Load @ 125% KVA Total Lighting (L) Load @ 125% KVA
Total HVAC (H) Load KVA Total HVAC (H) Load KVA
TOTAL CONNECTED LOAD KVA Largest Motor @ 125% KVA
CONNECTED AMP
Total / Phase
A B C MINIMUM FEEDER CAPACITY
PANEL NO. SDP 2A Enclosure Type: OUTDOOR Bus: 400/230vac, 50Hz
Main C.B. 600 AMP
Location: SOJTF OIR - S Serving: Secondary Dist. Panel SCCR (amps): 22,000 (minimum) Feed Thru Lugs
SubFeed Lugs
Flush Mount
Surface Mount
Top Feed
Bottom Feed ✔ Fully Rated Series Rated Iso. Gnd. Bus ✔ ✔
KVA
Circuit Breaker
PH
TypeAMP Pole CKT CKT Pole AMP
SIG CEN 200 3 1 A 2 3 200 SUP CEN
SIG CEN 200 3 3 B 4 3 200 SUP CEN
SIG CEN 200 3 5 C 6 3 200 SUP CEN
BILLET 6 125 3 7 A 8 3 200 OP CEN
BILLET 6 125 3 9 B 10 3 200 OP CEN
BILLET 6 125 3 11 C 12 3 200 OP CEN
BILLET 7 125 3 13 A 14 3 200 SPARE
BILLET 7 125 3 15 B 16 3 200 SPARE
BILLET 7 125 3 17 C 18 3 200 SPARE
BILLET 8 125 3 19 A 20 3 125 SPARE
BILLET 8 125 3 21 B 22 3 125 SPARE
BILLET 8 125 3 23 C 24 3 125 SPARE
SPARE 200 3 25 A 26 3 125 SPARE
SPARE 200 3 27 B 28 3 125 SPARE
SPARE 200 3 29 C 30 3 125 SPARE
SPARE 125 3 31 A 32 3 125 SPARE
SPARE 125 3 33 B 34 3 125 SPARE
SPARE 125 3 35 C 36 3 125 SPARE
SPARE 125 3 37 A 38 3 125 SPARE
SPARE 125 3 39 B 40 3 125 SPARE
SPARE 125 3 41 C 42 3 125 SPARE
CONNECTED LOAD DEMAND LOAD
Total General‐Purpose Receptacle (R) Load
@ 180VA/ea. KVA
Total General‐Purpose Receptacle ( R ) Load @ 180VA/ea., 100% for first 10 KVA & 50% for remainder KVA
Total Specific‐Purpose (SP) Receptacles KVA Total Specific‐Purpose (SP) Receptacles KVA
Total Motor (M) Load KVA Total Motor (M) Load KVA
Total Lighting (L) Load @ 125% KVA Total Lighting (L) Load @ 125% KVA
Total HVAC (H) Load KVA Total HVAC (H) Load KVA
TOTAL CONNECTED LOAD KVA Largest Motor @ 125% KVA
CONNECTED AMP
Total / Phase
A B C MINIMUM FEEDER CAPACITY
PANEL NO. SDP 3A Enclosure Type: OUTDOOR Bus: 400/230vac, 50Hz
3Ø 4 Wire 600 AMP
Main C.B. 600 AMP
Location: SOJTF OIR - S Serving: Secondary Dist. Panel SCCR (amps): 22,000 (minimum) Feed Thru Lugs
SubFeed Lugs
Flush Mount
Surface Mount
Top Feed
Bottom Feed ✔ Fully Rated Series Rated Iso. Gnd. Bus ✔ ✔
KVA
Circuit Breaker
PH
TypeAMP Pole CKT CKT Pole AMP
KITCHEN 200 3 1 A 2 3 125 MWR
KITCHEN 200 3 3 B 4 3 125 MWR
KITCHEN 200 3 5 C 6 3 125 MWR
DFAC 200 3 7 A 8 3 125 LATRINE 1
DFAC 200 3 9 B 10 3 125 LATRINE 1
DFAC 200 3 11 C 12 3 125 LATRINE 1
125 3 13 A 14 3 125 LATRINE 2
SPARE 125 3 15 B 16 3 125 LATRINE 2
SPARE 125 3 17 C 18 3 125 LATRINE 2
SPARE 125 3 19 A 20 3 125 SPARE
SPARE 125 3 21 B 22 3 125 SPARE
SPARE 125 3 23 C 24 3 125 SPARE
SPARE 125 3 25 A 26 3 125 SPARE
SPARE 125 3 27 B 28 3 125 SPARE
SPARE 125 3 29 C 30 3 125 SPARE
SPARE 200 3 31 A 32 3 200 SPARE
SPARE 200 3 33 B 34 3 200 SPARE
SPARE 200 3 35 C 36 3 200 SPARE
SPARE 200 3 37 A 38 3 200 SPARE
SPARE 200 3 39 B 40 3 200 SPARE
SPARE 200 3 41 C 42 3 200 SPARE
CONNECTED LOAD DEMAND LOAD
Total General‐Purpose Receptacle (R) Load
@ 180VA/ea. KVA
Total General‐Purpose Receptacle ( R ) Load @ 180VA/ea., 100% for first 10 KVA & 50% for remainder KVA
Total Specific‐Purpose (SP) Receptacles KVA Total Specific‐Purpose (SP) Receptacles KVA
Total Motor (M) Load KVA Total Motor (M) Load KVA
Total Lighting (L) Load @ 125% KVA Total Lighting (L) Load @ 125% KVA
Total HVAC (H) Load KVA Total HVAC (H) Load KVA
TOTAL CONNECTED LOAD KVA Largest Motor @ 125% KVA
CONNECTED AMP
Total / Phase
A B C MINIMUM FEEDER CAPACITY
Quantity: 2 30PanelboardSchedule
PANEL NO. 400AMP Enclosure Type: OUTDOOR Bus: 400/230vac, 50Hz
3Ø 4 Wire 400 AMP
Main C.B. 400 AMP
Location: SOJTF OIR - S Serving: Local Distribution Panel SCCR (amps): 22,000 (minimum) Feed Thru Lugs
SubFeed Lugs
Flush Mount
Surface Mount
Top Feed
Bottom Feed ✔ Fully Rated Series Rated Iso. Gnd. Bus ✔ ✔
KVA
Circuit Breaker
PH
TypeAMP Pole CKT CKT Pole AMP
HVAC 1 20 1 1 A 2 1 20 HVAC 3
HVAC 2 20 1 3 B 4 1 20 HVAC 4
Outlets GP-RCCB/GFI 20 1 5 C 6 1 20 Outlets GP-RCCB/GFI
Outlets GP-RCCB/GFI 20 1 7 A 8 1 20 Outlets GP-RCCB/GFI
Outlets GP-RCCB/GFI 20 1 9 B 10 1 20 Outlets GP-RCCB/GFI
Outlets GP-RCCB/GFI 20 1 11 C 12 1 20 Outlets GP-RCCB/GFI
Outlets GP-RCCB/GFI 20 1 13 A 14 1 Outlets GP-RCCB/GFI
Lighting 20 1 15 B 16 1 20 Lighting
Lighting 20 1 17 C 18 1 20 Lighting
Lighting 20 1 19 A 20 1 20 Lighting
SPARE 20 1 21 B 22 1 20 SPARE
SPARE 20 1 23 C 24 1 20 SPARE
SPARE 40A 3PH 40 3 25 A 26 3 40 SPARE 40A 3PH
SPARE 40A 3PH 40 3 27 B 28 3 40 SPARE 40A 3PH
SPARE 40A 3PH 40 3 29 C 30 3 40 SPARE 40A 3PH
SPARE 63A 3PH 63 3 31 A 32 3 63 SPARE 63A 3PH
SPARE 63A 3PH 63 3 33 B 34 3 63 SPARE 63A 3PH
SPARE 63A 3PH 63 3 35 C 36 3 63 SPARE 63A 3PH
SPARE 100A 3PH 100 3 37 A 38 3 100 SPARE 100A 3PH
SPARE 100A 3PH 100 3 39 B 40 3 100 SPARE 100A 3PH
SPARE 100A 3PH 100 3 41 C 42 3 100 SPARE 100A 3PH
CONNECTED LOAD DEMAND LOAD
Total General‐Purpose Receptacle (R) Load
@ 180VA/ea. KVA
Total General‐Purpose Receptacle ( R ) Load @ 180VA/ea., 100% for first 10 KVA & 50% for remainder KVA
Total Specific‐Purpose (SP) Receptacles KVA Total Specific‐Purpose (SP) Receptacles KVA
Total Motor (M) Load KVA Total Motor (M) Load KVA
Total Lighting (L) Load @ 125% KVA Total Lighting (L) Load @ 125% KVA
Total HVAC (H) Load KVA Total HVAC (H) Load KVA
TOTAL CONNECTED LOAD KVA Largest Motor @ 125% KVA
CONNECTED AMP
Total / Phase
A B C MINIMUM FEEDER CAPACITY
Quantity: 2 30PanelboardSchedule
PANEL NO. 200AMP Enclosure Type: OUTDOOR Bus: 400/220vac, 50Hz
3Ø 4 Wire 200 AMP
Main C.B. 200 AMP
Location: SOJTF OIR - S Serving: Local Distribution Panel SCCR (amps): 22,000 (minimum) Feed Thru Lugs
SubFeed Lugs
Flush Mount
Surface Mount
Top Feed
Bottom Feed ✔ Fully Rated Series Rated Iso. Gnd. Bus ✔ ✔
KVA
Circuit Breaker
PH
TypeAMP Pole CKT CKT Pole AMP
HVAC 1 20 1 1 A 2 1 20 HVAC 3
HVAC 2 20 1 3 B 4 1 20 HVAC 4
Outlets GP-RCCB/GFI 20 1 5 C 6 1 20 Outlets GP-RCCB/GFI
Outlets GP-RCCB/GFI 20 1 7 A 8 1 20 Outlets GP-RCCB/GFI
Outlets GP-RCCB/GFI 20 1 9 B 10 1 20 Outlets GP-RCCB/GFI
Outlets GP-RCCB/GFI 20 1 11 C 12 1 20 Outlets GP-RCCB/GFI
Outlets GP-RCCB/GFI 20 1 13 A 14 1 Outlets GP-RCCB/GFI
Lighting 20 1 15 B 16 1 20 Lighting
Lighting 20 1 17 C 18 1 20 Lighting
Lighting 20 1 19 A 20 1 20 Lighting
SPARE 20 1 21 B 22 1 20 SPARE
SPARE 20 1 23 C 24 1 20 SPARE
SPARE 20 1 25 A 26 1 20 SPARE
SPARE 20 1 27 B 28 1 20 SPARE
SPARE 20 1 29 C 30 1 20 SPARE
SPARE 40A 3PH 40 3 31 A 32 3 40 SPARE 40A 3PH
SPARE 40A 3PH 40 3 33 B 34 3 40 SPARE 40A 3PH
SPARE 40A 3PH 40 3 35 C 36 3 40 SPARE 40A 3PH
SPARE 63A 3PH 63 3 37 A 38 3 63 SPARE 63A 3PH
SPARE 63A 3PH 63 3 39 B 40 3 63 SPARE 63A 3PH
SPARE 63A 3PH 63 3 41 C 42 3 63 SPARE 63A 3PH
CONNECTED LOAD DEMAND LOAD
Total General‐Purpose Receptacle (R) Load
@ 180VA/ea. KVA
Total General‐Purpose Receptacle ( R ) Load @ 180VA/ea., 100% for first 10 KVA & 50% for remainder KVA
Total Specific‐Purpose (SP) Receptacles KVA Total Specific‐Purpose (SP) Receptacles KVA
Total Motor (M) Load KVA Total Motor (M) Load KVA
Total Lighting (L) Load @ 125% KVA Total Lighting (L) Load @ 125% KVA
Total HVAC (H) Load KVA Total HVAC (H) Load KVA
TOTAL CONNECTED LOAD KVA Largest Motor @ 125% KVA
CONNECTED AMP
Total / Phase
A B C MINIMUM FEEDER CAPACITY
W912ER17P0028
PANEL NO. 125AMP Enclosure Type: OUTDOOR Bus: 400/230vac, 50Hz
3Ø 4 Wire 125 AMP
Main C.B. 125 AM Location: SOJTF OIR - S Serving: Local Distribution Panel SCCR (amps): 22,000 (minimum) Feed Thru Lugs
SubFeed Lugs
Flush Mount
Surface Mount
Top Feed
Bottom Feed ✔ Fully Rated Series Rated Iso. Gnd. Bus ✔ ✔
KVA
Circuit Breaker
PH
Lo TyAMP Pole CKT CKT Pole AMP
HVAC 1 20 1 1 A 2 1 20 HVAC 3
HVAC 2 20 1 3 B 4 1 20 HVAC 4
Outlets GP-RCCB/GFI 20 1 5 C 6 1 20 Outlets GP-RCCB/GFI
Outlets GP-RCCB/GFI 20 1 7 A 8 1 20 Outlets GP-RCCB/GFI
Outlets GP-RCCB/GFI 20 1 9 B 10 1 20 Outlets GP-RCCB/GFI
Outlets GP-RCCB/GFI 20 1 11 C 12 1 20 Outlets GP-RCCB/GFI
Outlets GP-RCCB/GFI 20 1 13 A 14 1 Outlets GP-RCCB/GFI
Lighting 20 1 15 B 16 1 20 Lighting
Lighting 20 1 17 C 18 1 20 Lighting
Lighting 20 1 19 A 20 1 20 Lighting
SPARE 20 1 21 B 22 1 20 SPARE
SPARE 20 1 23 C 24 1 20 SPARE
SPARE 30A 3ph 30 3 25 A 26 3 40 SPARE 40A 3ph
SPARE 30A 3ph 30 3 27 B 28 3 40 SPARE 40A 3ph
SPARE 30A 3ph 30 3 29 C 30 3 40 SPARE 40A 3ph
31 A 32 3
33 B 34 3
35 C 36 3
37 A 38 3
39 B 40 3
41 C 42 3
CONNECTED LOAD DEMAND LOAD
Total General‐Purpose Receptacle (R) Load
@ 180VA/ea. KVA
Total General‐Purpose Receptacle ( R ) Load @ 180VA/ea., 100% for first 10 KVA & 50% for remainder K
Total Specific‐Purpose (SP) Receptacles KVA Total Specific‐Purpose (SP) Receptacles K
Total Motor (M) Load KVA Total Motor (M) Load K
Total Lighting (L) Load @ 125% KVA Total Lighting (L) Load @ 125% K
Total HVAC (H) Load KVA Total HVAC (H) Load K
TOTAL CONNECTED LOAD KVA Largest Motor @ 125% K
CONNECTED AMP
Total / Phase
A B C MINIMUM FEEDER CAPACITY
TOTAL DEMAND LOAD K
ITEM NO SUPPLIES/SERVICES QUANTITY UNIT UNIT PRICE AMOUNT
0001 1 Each $15,679.01 $15,679.01 Panelboard 1600 amp panel no. MDP #1 KLZ
FFP
Panelboard 1600 amp panel no. MDP #1for KLZ, Kuwait, see SOW for installation and guidance as it setforth herein.Complete panelboard assemblies shall be designed and manufactured by the same OEM; in other words, all the major components will designed and assembled by the same OEM (Enclosure, Interior/Bus, Dead Front, Cover, Main Disconnect Device, Branch devices).
Panelboards assembled by an Integrator or other third party are NOT acceptable.
See SOW for addtional details. Delivery information: SOJTF-OIR J4 Attention: Mr. Kolditz/Chief Burkett Phone#700-786-6500 Kuwait City, Kuwait 09309 NOTE: The requirements in DFARS 252.211-7003, Item Identification and Valuation, are applicable for this line item. The contractor shall provide DoD unique identification or a DoD recognized unique identification equivalent.
FOB: Destination
MILSTRIP: W26WKS71312470
PURCHASE REQUEST NUMBER: W26WKS71312470
NET AMT $15,679.01
ACRN AA
CIN: W26WKS713124700001
$15,679.01
0002 1 Each $15,679.01 $15,679.01 Panelboard 1600 amp panel no. MDP#2 KLZ
FFP
Panelboard 1600 amp panel no. MDP #2 for KLZ Kuwait. Complete panelboard assemblies shall be designed and manufactured by the same OEM; in other words, all the major components will designed and assembled by the same OEM (Enclosure, Interior/Bus, Dead Front, Cover, Main Disconnect Device, Branch devices). Panelboards assembled by an Integrator or other third party are NOT acceptable. See SOW for additional details.
NOTE: The requirements in DFARS 252.211-7003, Item Identification and Valuation, are applicable for this line item. The contractor shall provide DoD unique identification or a DoD recognized unique identification equivalent.
FOB: Destination
NET AMT $15,679.01
CIN: W26WKS713124700002
$15,679.01
0003 1 Each $15,191.25 $15,191.25 Panelboard 1600 amp panel no. MDP#3 KLZ
FFP
Panelboard 1600 amp panel no. MDP#3 for KLZ, Kuwait.Complete panelboard assemblies shall be designed and manufactured by the same OEM; in other words, all the major components will designed and assembled by the same OEM (Enclosure, Interior/Bus, Dead Front, Cover, Main Disconnect Device, Branch devices). Panelboards assembled by an Integrator or other third party are NOT acceptable. See SOW for additional details.
Delivery information:
SOJTF-OIR J4
Attention: Mr. Kolditz/Chief Burkett Phone#700-786-6500 Kuwait City, Kuwait 09309
NOTE: The requirements in DFARS 252.211-7003, Item Identification and Valuation, are applicable for this line item. The contractor shall provide DoD unique identification or a DoD recognized unique identification equivalent.
NET AMT $15,191.25
CIN: W26WKS713124700003
$15,191.25
0004 1 Each $5,001.11 $5,001.11 Panelboard 600 amp panel no. SDP-1A ,KLZ
FFP
Panelboard 600 amp panel no. SDP-1A for KLZ, Kuwait. Complete panelboard assemblies shall be designed and manufactured by the same OEM; in other words, all the major components will designed and assembled by the same OEM (Enclosure, Interior/Bus, Dead Front, Cover, Main Disconnect Device, Branch devices). Panelboards assembled by an Integrator or other third party are NOT acceptable. See SOW for additional details.
Delivery information:
SOJTF-OIR J4
Attention: Mr. Kolditz/Chief Burkett Phone#700-786-6500 Kuwait City, Kuwait 09309
NOTE: The requirements in DFARS 252.211-7003, Item Identification and Valuation, are applicable for this line item. The contractor shall provide DoD unique identification or a DoD recognized unique identification equivalent.
NET AMT $5,001.11
CIN: W26WKS713124700004
$5,001.11
0005 1 Each $5,231.73 $5,231.73 Panelboard 600 amp panel no. SDP-2A, KLZ
FFP
Panelboard 600 amp panel no. SDP-2A for KLZ, Kuwait. Complete panelboard assemblies shall be designed and manufactured by the same OEM; in other words, all the major components will designed and assembled by the same OEM (Enclosure, Interior/Bus, Dead Front, Cover, Main Disconnect Device, Branch devices). Panelboards assembled by an Integrator or other third party are NOT acceptable. See SOW for additional details.
Delivery information:
SOJTF-OIR J4
Attention: Mr. Kolditz/Chief Burkett Phone#700-786-6500 Kuwait City, Kuwait 09309
NOTE: The requirements in DFARS 252.211-7003, Item Identification and Valuation, are applicable for this line item. The contractor shall provide DoD unique identification or a DoD recognized unique identification equivalent.
NET AMT $5,231.73
CIN: W26WKS713124700005
$5,231.73
0006 1 Each $5,431.87 $5,431.87 Panelboard 600 amp panel no. SDP-3A, KLZ
FFP
Panelboard 600 amp panel no. SDP-3A for KLZ, Kuwait.Complete panelboard assemblies shall be designed and manufactured by the same OEM; in other words, all the major components will designed and assembled by the same OEM (Enclosure, Interior/Bus, Dead Front, Cover, Main Disconnect Device, Branch devices). Panelboards assembled by an Integrator or other third party are NOT acceptable. See SOW for additional details.
Delivery information:
SOJTF-OIR J4
Attention: Mr. Kolditz/Chief Burkett Phone#700-786-6500 Kuwait City, Kuwait 09309
NOTE: The requirements in DFARS 252.211-7003, Item Identification and Valuation, are applicable for this line item. The contractor shall provide DoD unique identification or a DoD recognized unique identification equivalent.
NET AMT $5,431.87
CIN: W26WKS713124700006
$5,431.87
0007 2 Each $2,575.07 $5,150.14 Panelboard 400 amp panel no. 400AMP, KLZ
FFP
Panelboard 400 amp panel no. 400AMP for KLZ, Kuwait. Complete panelboard assemblies shall be designed and manufactured by the same OEM; in other words, all the major components will designed and assembled by the same OEM (Enclosure, Interior/Bus, Dead Front, Cover, Main Disconnect Device, Branch devices). Panelboards assembled by an Integrator or other third party are NOT acceptable. See SOW for additional details.
Delivery information:
SOJTF-OIR J4
Attention: Mr. Kolditz/Chief Burkett Phone#700-786-6500 Kuwait City, Kuwait 09309
NOTE: The requirements in DFARS 252.211-7003, Item Identification and Valuation, are applicable for this line item. The contractor shall provide DoD unique identification or a DoD recognized unique identification equivalent.
NET AMT $5,150.14
CIN: W26WKS713124700007
$5,150.14
0008 2 Each $2,236.55 $4,473.10 Panelboard 200 amp panel no. 200AMP, KLZ
FFP
Panelboard 200 amp panel no. 200AMP for KLZ, Kuwait. Complete panelboard assemblies shall be designed and manufactured by the same OEM; in other words, all the major components will designed and assembled by the same OEM (Enclosure, Interior/Bus, Dead Front, Cover, Main Disconnect Device, Branch devices). Panelboards assembled by an Integrator or other third party are NOT acceptable. See SOW for additional details.
Delivery information:
SOJTF-OIR J4
Attention: Mr. Kolditz/Chief Burkett Phone#700-786-6500 Kuwait City, Kuwait 09309
NOTE: The requirements in DFARS 252.211-7003, Item Identification and Valuation, are applicable for this line item. The contractor shall provide DoD unique identification or a DoD recognized unique identification equivalent.
NET AMT $4,473.10
CIN: W26WKS713124700008
$4,473.10
0009 12 Each $1,664.65 $19,975.80 Panelboard 125 amp panel no. 125AMP, KLZ
FFP
Panelboard 125 amp panel no. 125 AMP for KLZ, Kuwait. Complete panelboard assemblies shall be designed and manufactured by the same OEM; in other words, all the major components will designed and assembled by the same OEM (Enclosure, Interior/Bus, Dead Front, Cover, Main Disconnect Device, Branch devices). Panelboards assembled by an Integrator or other third party are NOT acceptable. See SOW for additional details.
Delivery information:
SOJTF-OIR J4
Attention: Mr. Kolditz/Chief Burkett Phone#700-786-6500 Kuwait City, Kuwait 09309
NOTE: The requirements in DFARS 252.211-7003, Item Identification and Valuation, are applicable for this line item. The contractor shall provide DoD unique identification or a DoD recognized unique identification equivalent.
NET AMT $19,975.80
CIN: W26WKS713124700009
$19,975.80
0010 3 Each $14,363.66 $43,090.98 Transfer Switch 1000 Volts Maximum, KLZ
FFP
Transfer Switch 1000 Volts Maximum for KLZ, Kuwait. Complete panelboard assemblies shall be designed and manufactured by the same OEM; in other words, all the major components will designed and assembled by the same OEM (Enclosure, Interior/Bus, Dead Front, Cover, Main Disconnect Device, Branch devices). Panelboards assembled by an Integrator or other third party are NOT acceptable. See SOW for additional details.
Delivery information:
SOJTF-OIR J4
Attention: Mr. Kolditz/Chief Burkett Phone#700-786-6500 Kuwait City, Kuwait 09309
NOTE: The requirements in DFARS 252.211-7003, Item Identification and Valuation, are applicable for this line item. The contractor shall provide DoD unique identification or a DoD recognized unique identification equivalent.
NET AMT $43,090.98
CIN: W26WKS713124700010
$43,090.98
0011 1 Unit $2,146.70 $2,146.70
SHIPPING
FFP
Delivery information:
SOJTF-OIR J4
Attention: Mr. Kolditz/Chief Burkett Phone#700-786-6500 Kuwait City, Kuwait 09309
NOTE: The requirements in DFARS 252.211-7003, Item Identification and Valuation, are applicable for this line item. The contractor shall provide DoD unique identification or a DoD recognized unique identification equivalent.
NET AMT $2,146.70
CIN: W26WKS713124700011
$2,146.70
INSPECTION AND ACCEPTANCE TERMS
Supplies/services will be inspected/accepted at:
CLIN INSPECT AT INSPECT BY ACCEPT AT ACCEPT BY
0001 Destination Government Destination Government 0002 Destination Government Destination Government 0003 Destination Government Destination Government 0004 Destination Government Destination Government 0005 Destination Government Destination Government 0006 Destination Government Destination Government 0007 Destination Government Destination Government 0008 Destination Government Destination Government 0009 Destination Government Destination Government 0010 Destination Government Destination Government 0011 Destination Government Destination Government
DELIVERY INFORMATION
CLIN DELIVERY DATE QUANTITY SHIP TO ADDRESS DODAAC /
CAGE
0001 30-AUG-2017 1 US ARMY CORPS OF ENGINEERS-
KUWAIT
MIDDLE EAST DISTRICT
KUWAIT AREA OFFICE BLDG. T-34
CAMP ARIFJAN
APO AE 09366
965 - 9876 8901
W912ER
0002 30-AUG-2017 1 (SAME AS PREVIOUS LOCATION)
0003 30-AUG-2017 1 (SAME AS PREVIOUS LOCATION)
0004 30-AUG-2017 1 (SAME AS PREVIOUS LOCATION)
0005 30-AUG-2017 1 (SAME AS PREVIOUS LOCATION)
0006 30-AUG-2017 1 (SAME AS PREVIOUS LOCATION)
0007 30-AUG-2017 2 (SAME AS PREVIOUS LOCATION)
0008 30-AUG-2017 2 (SAME AS PREVIOUS LOCATION)
0009 30-AUG-2017 12 (SAME AS PREVIOUS LOCATION)
0010 30-AUG-2017 3 (SAME AS PREVIOUS LOCATION)
0011 30-AUG-2017 1 (SAME AS PREVIOUS LOCATION)
ACCOUNTING AND APPROPRIATION DATA
AA: 021 NA 2020 2017 0000 NA 2017 NA 0000 21001 13519770000
AMOUNT: $137,050.70
ACRN CLIN/SLIN CIN AMOUNT
AA 0001 W26WKS713124700001 $15,679.01
0002 W26WKS713124700002 $15,679.01
0003 W26WKS713124700003 $15,191.25
0004 W26WKS713124700004 $5,001.11
0005 W26WKS713124700005 $5,231.73
0006 W26WKS713124700006 $5,431.87
0007 W26WKS713124700007 $5,150.14
0008 W26WKS713124700008 $4,473.10
0009 W26WKS713124700009 $19,975.80
0010 W26WKS713124700010 $43,090.98
0011 W26WKS713124700011 $2,146.70
CLAUSES INCORPORATED BY REFERENCE
52.203-7 Anti-Kickback Procedures MAY 2014 52.204-19 Incorporation by Reference of Representations and
Certifications.
DEC 2014
52.209-10 Prohibition on Contracting With Inverted Domestic Corporations
NOV 2015
52.212-4 Contract Terms and Conditions--Commercial Items JAN 2017 52.225-13 Restrictions on Certain Foreign Purchases JUN 2008 52.246-16 Responsibility For Supplies APR 1984 52.247-34 F.O.B. Destination NOV 1991 252.203-7000 Requirements Relating to Compensation of Former DoD
Officials
SEP 2011
252.232-7003 Electronic Submission of Payment Requests and Receiving Reports
JUN 2012
CLAUSES INCORPORATED BY FULL TEXT
52.212-5 CONTRACT TERMS AND CONDITIONS REQUIRED TO IMPLEMENT STATUTES OR
EXECUTIVE ORDERS--COMMERCIAL ITEMS (JAN 2017)
(a) The Contractor shall comply with the following Federal Acquisition Regulation (FAR) clauses, which are incorporated in this contract by reference, to implement provisions of law or Executive orders applicable to acquisitions of commercial items:
(1) 52.203-19, Prohibition on Requiring Certain Internal Confidentiality Agreements or Statements (JAN 2017) (section 743 of Division E, Title VII, of the Consolidated and Further Continuing Appropriations Act, 2015 (Pub. L.
113-235) and its successor provisions in subsequent appropriations acts (and as extended in continuing resolutions)).
(2) 52.209-10, Prohibition on Contracting with Inverted Domestic Corporations (Nov 2015).
(3) 52.233-3, Protest After Award (AUG 1996) (31 U.S.C. 3553).
(4) 52.233-4, Applicable Law for Breach of Contract Claim (OCT 2004) (Public Laws 108-77 and 108-78 (19 U.S.C. 3805 note)).
(b) The Contractor shall comply with the FAR clauses in this paragraph (b) that the Contracting Officer has indicated as being incorporated in this contract by reference to implement provisions of law or Executive orders applicable to acquisitions of commercial items: (Contracting Officer check as appropriate.)
___ (1) 52.203-6, Restrictions on Subcontractor Sales to the Government (Sept 2006), with Alternate I (Oct 1995) (41 U.S.C. 4704 and 10 U.S.C. 2402).
____ (2) 52.203-13, Contractor Code of Business Ethics and Conduct (Oct 2015) (41 U.S.C. 3509).
____ (3) 52.203-15, Whistleblower Protections under the American Recovery and Reinvestment Act of 2009 (June 2010) (Section 1553 of Pub. L. 111-5). (Applies to contracts funded by the American Recovery and Reinvestment Act of 2009.)
_X__ (4) 52.204-10, Reporting Executive Compensation and First-Tier Subcontract Awards (Oct 2016) (Pub. L.
109-282) (31 U.S.C. 6101 note).
___ (5) [Reserved]
___ (6) 52.204-14, Service Contract Reporting Requirements (Oct 2016) (Pub. L. 111-117, section 743 of Div.
C).
___ (7) 52.204-15, Service Contract Reporting Requirements for Indefinite-Delivery Contracts (Oct 2016) (Pub.
L. 111-117, section 743 of Div. C).
___ (8) 52.209-6, Protecting the Government's Interest When Subcontracting with Contractors Debarred, Suspended, or Proposed for Debarment. (Oct 2015) (31 U.S.C. 6101 note).
____ (9) 52.209-9, Updates of Publicly Available Information Regarding Responsibility Matters (July 2013) (41 U.S.C. 2313).
____ (10) [Reserved]
____ (11)(i) 52.219-3, Notice of HUBZone Set-Aside or Sole-Source Award (NOV 2011) (15 U.S.C. 657a).
____ (ii) Alternate I (NOV 2011) of 52.219-3.
____ (12) (i) 52.219-4, Notice of Price Evaluation Preference for HUBZone Small Business Concerns (OCT 2014) (if the offeror elects to waive the preference, it shall so indicate in its offer) (15 U.S.C. 657a).
____ (ii) Alternate I (JAN 2011) of 52.219-4.
____ (13) [Reserved]
____ (14)(i) 52.219-6, Notice of Total Small Business Set-Aside (NOV 2011) (15 U.S.C. 644).
____ (ii) Alternate I (NOV 2011).
____ (iii) Alternate II (NOV 2011).
____ (15)(i) 52.219-7, Notice of Partial Small Business Set-Aside (June 2003) (15 U.S.C. 644).
____ (ii) Alternate I (Oct 1995) of 52.219-7.
____ (iii) Alternate II (Mar 2004) of 52.219-7.
____ (16) 52.219-8, Utilization of Small Business Concerns (Nov 2016) (15 U.S.C. 637(d)(2) and (3)).
____ (17)(i) 52.219-9, Small Business Subcontracting Plan (Jan 2017) (15 U.S.C. 637(d)(4)).
____ (ii) Alternate I (Nov 2016) of 52.219-9.
____ (iii) Alternate II (Nov 2016) of 52.219-9.
____ (iv) Alternate III (Nov 2016) of 52.219-9.
____ (v) Alternate IV (Nov 2016) of 52.219-9.
____ (18) 52.219-13, Notice of Set-Aside of Orders (NOV 2011) (15 U.S.C. 644(r)).
____ (19) 52.219-14, Limitations on Subcontracting (JAN 2017) (15 U.S.C. 637(a)(14)).
____ (20) 52.219-16, Liquidated Damages—Subcon-tracting Plan (Jan 1999) (15 U.S.C. 637(d)(4)(F)(i)).
____ (21) 52.219-27, Notice of Service-Disabled Veteran-Owned Small Business Set-Aside (NOV 2011) (15 U.S.C.
657f).
____ (22) 52.219-28, Post Award Small Business Program Rerepresentation (July 2013) (15 U.S.C. 632(a)(2)).
____ (23) 52.219-29, Notice of Set-Aside for, or Sole Source Award to, Economically Disadvantaged Women- Owned Small Business Concerns (Dec 2015) (15 U.S.C. 637(m)).
____(24) 52.219-30, Notice of Set-Aside for, or Sole Source Award to, Women-Owned Small Business Concerns Eligible Under the Women-Owned Small Business Program (Dec 2015) (15 U.S.C. 637(m)).
__X__ (25) 52.222-3, Convict Labor (June 2003) (E.O. 11755).
__X__(26) 52.222-19, Child Labor--Cooperation with Authorities and Remedies (Oct 2016) (E.O. 13126).
__X__ (27) 52.222-21, Prohibition of Segregated Facilities (Apr 2015).
____ (28) 52.222-26, Equal Opportunity (Sept 2016) (E.O. 11246).
____ (29) 52.222-35, Equal Opportunity for Veterans (Oct 2015) (38 U.S.C. 4212).
____ (30) 52.222-36, Equal Opportunity for Workers with Disabilities (July 2014) (29 U.S.C. 793).
____ (31) 52.222-37, Employment Reports on Veterans (FEB 2016) (38 U.S.C. 4212).
____ (32) 52.222-40, Notification of Employee Rights Under the National Labor Relations Act (Dec 2010) (E.O.
13496).
__X__ (33)(i) 52.222-50, Combating Trafficking in Persons (March 2, 2015) (22 U.S.C. chapter 78 and E.O.
13627).
____ (ii) Alternate I (March 2, 2015) of 52.222-50 (22 U.S.C. chapter 78 and E.O. 13627).
____ (34) 52.222-54, Employment Eligibility Verification (Oct 2015). (E. O. 12989). (Not applicable to the acquisition of commercially available off-the-shelf items or certain other types of commercial items as prescribed in 22.1803.)
____ (35) 52.222-59, Compliance with Labor Laws (Executive Order 13673) (OCT 2016). (Applies at $50 million for solicitations and resultant contracts issued from October 25, 2016 through April 24, 2017; applies at $500,000 for solicitations and resultant contracts issued after April 24, 2017).
Note to paragraph (b)(35): By a court order issued on October 24, 2016, 52.222-59 is enjoined indefinitely as of the date of the order. The enjoined paragraph will become effective immediately if the court terminates the injunction. At that time, DoD, GSA, and NASA will publish a document in the Federal Register advising the public of the termination of the injunction.
____ (36) 52.222-60, Paycheck Transparency (Executive Order 13673) (OCT 2016).
____ (37)(i) 52.223-9, Estimate of Percentage of Recovered Material Content for EPA–Designated Items (May 2008) (42 U.S.C. 6962(c)(3)(A)(ii)). (Not applicable to the acquisition of commercially available off-the-shelf items.)
____ (ii) Alternate I (May 2008) of 52.223-9 (42 U.S.C. 6962(i)(2)(C)). (Not applicable to the acquisition of commercially available off-the-shelf items.)
____ (38) 52.223-11, Ozone-Depleting Substances and High Global Warming Potential Hydrofluorocarbons (June, 2016) (E.O. 13693).
____ (39) 52.223-12, Maintenance, Service, Repair, or Disposal of Refrigeration Equipment and Air Conditioners (June, 2016) (E.O. 13693).
____ (40) (i) 52.223-13, Acquisition of EPEAT® Registered Imaging Equipment (Jun 2014) (E.O.s 13423 and 13514).
____ (ii) Alternate I (OCT 2015) of 52.223-13.
____ (41)(i) 52.223-14, Acquisition of EPEAT® Registered Televisions (Jun 2014) (E.O.s 13423 and 13514).
____ (ii) Alternate I (Jun 2014) of 52.223-14.
____ (42) 52.223-15, Energy Efficiency in Energy-Consuming Products (Dec 2007) (42 U.S.C. 8259b).
____ (43)(i) 52.223-16, Acquisition of EPEAT[supreg]-Registered Personal Computer Products (OCT 2015) (E.O.s 13423 and 13514).
____ (ii) Alternate I (Jun 2014) of 52.223-16.
_X___ (44) 52.223-18, Encouraging Contractor Policies to Ban Text Messaging While Driving (Aug 2011) (E.O.
13513).
____ (45) 52.223-20, Aerosols (June, 2016) (E.O. 13693).
____ (46) 52.223-21, Foams (June, 2016) (E.O. 13693).
____ (47)(i) 52.224-3, Privacy Training (JAN 2017) (5 U.S.C. 552a).
____ (ii) Alternate I (JAN 2017) of 52.224-3.
____ (48) 52.225-1, Buy American--Supplies (May 2014) (41 U.S.C. chapter 83).
____(49) (i) 52.225-3, Buy American--Free Trade Agreements--Israeli Trade Act (May 2014) (41 U.S.C. chapter 83, 19 U.S.C. 3301 note, 19 U.S.C. 2112 note, 19 U.S.C. 3805 note, 19 U.S.C. 4001 note, Pub. L.
103-182, 108-77, 108-78, 108-286, 108-302, 109-53, 109-169, 109-283, 110-138, 112-41, 112-42, and 112-43.
____ (ii) Alternate I…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .