DEPARTMENT OF THE ARMY

CAMP ARIFJAN, KUWAIT

APO AE 09366

ELECTRIC POWER DISTRIBUTION

EQUIPMENT STANDARD SPECIFICATION

PANELBOARDS, SWITCHBOARDS AND LOAD CENTERS

FOR NON-PERMANENT FACILITIES

Project ID: Project No. 033-16-X-P-LSA; KLZ (panelboard schedules attached)

PART 1 – GENERAL

1.1 GENERAL REQUIREMENTS FOR PANELBOARDS, SWITCHBOARDS, LOAD

CENTERS

A. This requirements document was developed to establish the minimum requirements for the Life Safety and Habitability aspects of electric power distribution systems for non-permanent facilities in support of military operations.

B. The specification defines electric power distribution panelboards (“panelboards”) as a complete individual assembly, designed and engineered in the form of a single panel, including buses and automatic overcurrent devices, tested and manufactured to international industry standards (IEC/CE, ANSI/IEEE, UL/CUL/CSA, CSA, NEMA/IEC, BS 7671).

C. Complete panelboard assemblies shall be designed and manufactured by the same OEM; in other words, all the major components will designed and assembled by the same OEM (Enclosure, Interior/Bus, Dead Front, Cover, Main Disconnect Device, Branch devices). Panelboards assembled by an Integrator or other third party are NOT acceptable.

D. Provide electrical equipment that is the manufacturer's standard catalog products, conforming to the latest published industry and technical society standards at the date of contract award. Underwriters Laboratories (UL) listing or third-party certification is required for all basic equipment. Use of shop or field fabricated electrical equipment assemblies that are not manufacturer's standard catalog products or do not conform to the industry and technical society standards are not acceptable.

E. Electrical Components, Devices, and Accessories shall be listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.

F. Switchboard designs engineered and certified to industry standards are acceptable when the requirements exceed the ratings of an OEM’s standard panelboard design.

G. All electrical equipment and materials shall be new (new production, new-in-box).

CAMP ARIFJAN, KUWAIT

APO AE 09366

Used, re-conditioned/refurbished equipment or materials are not acceptable.

H. Enclosures:

1. Panelboard assemblies will include back box, dead front, hinged front covers, main disconnect devices, branch breakers and accessories that are engineered and tested for use as a single unit.

2. Shall be designed to be mounted against a wall, partition, or other support structure; and accessible only from the front. Vendor will provide OEM shop drawings that show mounting points.

3. Must be rated for environmental conditions specific for the installed location.

a. Ambient Temperature: Not exceeding minus 22 degrees Fahrenheit (minus 30 degrees Celsius) to plus 130 degrees Fahrenheit (plus 55 degrees Celsius).

b. b. Altitude: Not exceeding 6600 feet (2000 meters).

c. Indoor Dry and Clean Locations: NEMA250 Type 1 (IP10, per IEC 60529)

d. Outdoor/Exposed Locations:, NEMA 250 Type 3 (IP54, per IEC 60529)

NOTE: Refer to the Panelboard Schedules for site-specific panel requirements.

4. Front Cover and Door:

a. Secured to box. For surface-mounted fronts, match the box dimensions; for flush-mounted fronts, overlap the back box.

b. With door open only the circuit breaker handles shall be accessible. The dead-front shall prevent exposure to wiring and energized components.

5. Finish:

a. Panels and Trim: Steel, factory finished immediately after cleaning, pretreating and priming with manufacturer's standard enamel.

b. Back Boxes: Outdoor designs will have same finish as panels and trim.

I. System Voltage:

NOTE: Refer to the Panelboard Schedule for site-specific panel requirements.

1. 400/230vac, 3-phase, 50Hz

2. 415/240vac, 3-phase, 50Hz

3. 440/250vac, 3-phase, 50Hz

J. Incoming Main Disconnect Device:

1. Location:

a. Bottom Entry/Bottom Fed

NOTE: Refer to the Panelboard Schedule for site-specific panel requirements.

2. Overcurrent Protective Devices: Molded Case Circuit Breaker (MCCB)

CAMP ARIFJAN, KUWAIT

APO AE 09366

3. OPDs shall be manufactured by the same OEM as the panelboards and switchboards and designed for use with the corresponding panelboard or switchboard design.

4. Molded-Case Circuit-Breaker Features and Accessories: Standard frame sizes, trip ratings, and number of poles

K. Phase, Neutral, and Ground Buses:

1. Material: Hard-drawn copper, 98 percent conductivity.

L. Panelboard Short-Circuit Current Ratings: All panelboards shall be Fully Rated: Fully rated to interrupt symmetrical short-circuit current available at terminals.

NOTE: Refer to the Panelboard Schedule for site-specific panel requirements.

M. Branch Overcurrent Protective Devices:

1. Molded Case Circuit Breaker (MCCB)

2. Manufactured by the same OEM as the panelboards and switchboards and matched to the corresponding panelboard and switchboard designs

3. Molded-Case Circuit-Breaker Features and Accessories: Standard frame sizes, trip ratings, and number of poles.

PART 2 – COMPLIANCE, TRACEABILTY & SUBMITTALS

2.1 PRODUCT DOCUMENTS

A. The Vendor/Supplier shall provide the OEM’s standard documentation package including:

1. Product drawings

2. Product manuals

3. Industry compliance (certifications)

4. Product Warranty

CAMP ARIFJAN, KUWAIT

APO AE 09366

2.2 ACRONYMS and ABBREVIATIONS

A. AIC/R: Ampere Interrupt Current, Ampere Interrupt Rating

B. ANSI: American National Standards Institute

C. AWG: American Wire Gauge

D. CE: Conformité Européenne

E. Deg. C: Degrees Celsius

F. Deg. F: Degrees Fahrenheit

G. IEC: International Electrotechnical Commission

H. IEEE: Institute of Electrical and Electronic Engineers

I. LV: An electrical system having a maximum RMS voltage less than 1,000 volts

J. MB/MCB: Main Breaker/Main Circuit Breaker

K. MCCB: Molded Case Circuit Breaker

L. MDP: Main Distribution Panel/Panelboard

M. NEC: National Electrical Code (NFPA 70)

N. NEMA: National Electrical Manufacturers Association

O. NFPA: National Fire Protection Association

P. OCPD: Overcurrent Protective Devices

Q. RMS: Root-mean-square

R. SCCR: Short-Circuit Current Rating

S. SDP: Secondary Distribution Panel/Panelboard

T. SWB: Switchboard

U. UFC: Unified Facilities Criteria

V. UL: Underwriters Laboratories

W. VAC: Volts Alternating Current (AC)

X. VDC: Volts Direct Current (DC)

CAMP ARIFJAN, KUWAIT

APO AE 09366

2.3 SUBMITTALS

A. Product Data: For each type of panelboard, switchboard and overcurrent protective device, provide manufacturers' technical data on features, performance, electrical characteristics, ratings, and finishes.

B. Shop Drawings: For each panelboard and related equipment.

1. Include dimensioned plans, elevations, sections, and details. Show tabulations of installed devices, equipment features, and ratings.

2. Detail enclosure types and details for both indoor and outdoor designs [NEMA Type 1 (IP10), NEMA Type 3 (IP54)].

3. Detail bus configuration, current and voltage ratings at system operating frequency.

4. Short-circuit current rating (SCCR) of panelboards and overcurrent protective devices.

5. Detail features, characteristics, ratings, and factory settings of individual overcurrent protective devices and auxiliary components where applicable.

6. Include wiring diagrams for power, signal, and control wiring.

7. Include time-current coordination curves for each type and rating of overcurrent protective device included in panelboards. May be submit ted on translucent log-log graft paper, digitally (CD) or in OEM manuals; include selectable ranges for each type of overcurrent protective device.

C. Qualification Data: Certification and industry compliance from qualified testing agency (ies).

D. Operation and Maintenance: Provide operation, and maintenance manuals (O&M) and "Operation and Maintenance Data," include the following:

1. Manufacturer's written instructions for testing and adjusting overcurrent protective devices.

2. Time-current curves, including selectable ranges for each type of overcurrent protective device that allows adjustments.

3. Recommended Spare Parts List

2.4 QUALITY ASSURANCE

A. Provide electrical equipment that is the manufacturer’s standard catalog products, conforming to the latest published industry and technical society standards at the date of contract award. Underwriters Laboratories (UL) listing or third-party certification is required for all basic equipment. Use of shop or field fabricated electrical equipment assemblies that are not manufacturer’s standard catalog products or do not conform to the industry and technical society standards are not acceptable.

B. Electrical Components, Devices, and Accessories: Listed and labeled as defined in the UFC and NFPA 70, by a qualified testing agency, and marked for intended location and application. Comply with NEMA PB 1.

C. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.

collis.h.doris Highlight

CAMP ARIFJAN, KUWAIT

APO AE 09366

D. Panelboards and Switchboards considered in this document shall comply with the following industry and US GOV standards (minimum):

1. UFC 3-501-01, Electrical Engineering

2. UFC 3-520-01, Interior Electrical Systems

3. UFC 3-550-01, Exterior Electrical Power Distribution

4. UL 489, Molded-Case Circuit Breakers

5. UL 67, Standard for Panelboards

6. UL 50, Enclosures for Electrical Equipment

7. NEMA 250, Enclosures for Electrical Equipment (1000 Volts Maximum)

8. NEMA PB1, Panelboards

9. NFPA 70, National Electrical Code® (NEC®)

10. IEC 61439, Low-voltage Switchgear and Controlgear Assemblies

2.5 DELIVERY, STORAGE, AND HANDLING

A. Equipment shall be new production only (new-in-box) and delivered in the OEM factory packaging.

B. Equipment damaged in shipping is not acceptable; the Supplier and Carrier will process the Return Material Authorization and replace damaged material.

2.6 OPERATING CONDITIONS

A. Equipment Ratings:

1. Equipment shall be rated for continuous operation under the following conditions unless otherwise indicated:

a. Relative Humidity 0 to 95% non-condensing

b. Operating Frequency 47–63 Hz

c. Storage Temperature -40° to +65° C (-40° to +149° F)

d. Operating Temperature -40° to +65° C (-40° to +149° F)

e. Altitude: Not exceeding 6600 feet (2000 m)

CAMP ARIFJAN, KUWAIT

APO AE 09366

PART 3 – LABELING

3.1 WARNINGS & IDENTIFICATION

A. Panelboard Nameplates: Label each panelboard with a nameplate complying with requirements for identification specified in Division 26 Section "Identification for Electrical Systems."

B. Multiple Power Source Warning: "DANGER - ELECTRICAL SHOCK HAZARD - EQUIPMENT HAS MULTIPLE POWER SOURCES." (where applicable per panelboard and equipment schedules)

C. Workspace/Indoor Clearance Warning: "WARNING - AREA IN FRONT OF

ELECTRICAL EQUIPMENT MUST BE KEPT CLEAR FOR 48 INCHES (1220 MM)."

(where applicable per panelboard and equipment schedules)

D. Flash Protection Field Marking: All panelboards, switchgear, switchboards, panelboards motor control centers, motor control panels and electrical control panels shall be provided with a black on yellow warning sign per ANSI Z535.4 and ISO 3864. The sign shall read: “DANGER! ARC FLASH and SHOCK HAZARD. FOLLOW ALL REQUIREMENTS IN NFPA70E FOR SAFE WORK PRACTICES and PERSONAL

PROTECTIVE EQUIPMENT.”

1. Signs shall be prominently mounted on the front of the equipment readily visible.

2. If the equipment has multiple removable front covers, a sign shall be mounted on each cover.

END OF REQUIREMENTS SECTION

CAMP ARIFJAN, KUWAIT

APO AE 09366

APPENDIX 1

PANELBOARD CONSTRUCTION

(Reference only)

Panelboard Enclosures (Bottom Fed, MCB shown

Deadfront installed to prevent exposure

Fully assembled Panelboard (shown with hinged cover)

Bus: Main C.B. AMP

3Ø 4 Wire AMP

SCCR (amps): Flush Mount Top Feed

Fully Rated Surface Mount Bottom Feed

AMP Pole CKT CKT Pole AMP

1 A 2

3 B 4

5 C 6

7 A 8

9 B 10

11 C 12

13 A 14

15 B 16

17 C 18

19 A 20

21 B 22

23 C 24

25 A 26

27 B 28

29 C 30

31 A 32

33 B 34

35 C 36

37 A 38

39 B 40

41 C 42

Total General-Purpose Receptacle (R) Load Total General-Purpose Receptacle ( R ) Load @ 180VA/ea., KVA 100% for first 10 KVA & 50% for remainder KVA

Total Specific-Purpose (SP) Receptacles KVA Total Specific-Purpose (SP) Receptacles KVA

Total Motor (M) Load KVA Total Motor (M) Load KVA

Total Lighting (L) Load @ 125% KVA Total Lighting (L) Load @ 125% KVA

Total HVAC (H) Load KVA Total HVAC (H) Load KVA

KVA Largest Motor @ 125% KVA

CONNECTED AMP A B C KVA

Total / Phase KVA AMP

3Ø Panelboard Schedule

TOTAL CONNECTED LOAD

CONNECTED LOAD DEMAND LOAD

MINIMUM FEEDER CAPACITY

Load Type

Feed Thru Lugs

SubFeed Lugs Iso. Gnd. Bus

Load Type Circuit Description

CONN

KVA

Circuit Breaker

PH

Circuit Breaker CONN

KVA

Location: Serving:

PANEL NO.

Circuit Description

Series Rated

@ 180VA/ea.

TOTAL DEMAND LOAD

MDP #1

Main Distribution Panel 1600

35,000 (minimum)

SDP 1A 600 3 3 SDP 2A

3 3 SDP 2A

3 3 SDP 2A

3 3 3 3 3 3 3 3 3 3 3 3

SPARE

SPARE

SPARE

Enclosure Type: OUTDOOR 400/230vac, 50Hz

SDP 1A

SDP 1A

MAINT PAD

SPARE

SPARE

SPARE

SPARE

MAINT PAD

MAINT PAD

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

Quantity: 1

SOJTF OIR - S

Flush Mount Top Feed

Fully Rated Surface Mount Bottom Feed

AMP Pole CKT CKT Pole AMP

1 A 2

3 B 4

5 C 6

7 A 8

9 B 10

11 C 12

13 A 14

15 B 16

17 C 18

19 A 20

21 B 22

23 C 24

25 A 26

27 B 28

29 C 30

31 A 32

33 B 34

35 C 36

37 A 38

39 B 40

41 C 42

Total General-Purpose Receptacle (R) Load Total General-Purpose Receptacle ( R ) Load @ 180VA/ea., KVA 100% for first 10 KVA & 50% for remainder KVA

Total Specific-Purpose (SP) Receptacles KVA Total Specific-Purpose (SP) Receptacles KVA

Total Motor (M) Load KVA Total Motor (M) Load KVA

Total Lighting (L) Load @ 125% KVA Total Lighting (L) Load @ 125% KVA

Total HVAC (H) Load KVA Total HVAC (H) Load KVA

KVA Largest Motor @ 125% KVA

CONNECTED AMP A B C KVA

Total / Phase KVA AMP

3Ø Panelboard Schedule

TOTAL CONNECTED LOAD

CONNECTED LOAD DEMAND LOAD

MINIMUM FEEDER CAPACITY

Load Type

Feed Thru Lugs

SubFeed Lugs Iso. Gnd. Bus

Load Type Circuit Description

CONN

KVA

Circuit Breaker

PH

Circuit Breaker CONN

KVA

Location: Serving:

PANEL NO.

Circuit Description

Series Rated

@ 180VA/ea.

TOTAL DEMAND LOAD

MDP #2

Main Distribution Panel 1600

SDP 3A 600 3 3

3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3

SPARE

SPARE

SPARE

Enclosure Type: OUTDOOR 400/230vac, 50Hz

SDP 3A

SDP 3A

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SDP FUT

SDP FUT

SDP FUT

SCCR (amps): 35,000 (minimum)

Flush Mount Top Feed

Fully Rated Surface Mount Bottom Feed

AMP Pole CKT CKT Pole AMP

1 A 2

3 B 4

5 C 6

7 A 8

9 B 10

11 C 12

13 A 14

15 B 16

17 C 18

19 A 20

21 B 22

23 C 24

25 A 26

27 B 28

29 C 30

31 A 32

33 B 34

35 C 36

37 A 38

39 B 40

41 C 42

Total General-Purpose Receptacle (R) Load Total General-Purpose Receptacle ( R ) Load @ 180VA/ea., KVA 100% for first 10 KVA & 50% for remainder KVA

Total Specific-Purpose (SP) Receptacles KVA Total Specific-Purpose (SP) Receptacles KVA

Total Motor (M) Load KVA Total Motor (M) Load KVA

Total Lighting (L) Load @ 125% KVA Total Lighting (L) Load @ 125% KVA

Total HVAC (H) Load KVA Total HVAC (H) Load KVA

KVA Largest Motor @ 125% KVA

CONNECTED AMP A B C KVA

Total / Phase KVA AMP

3Ø Panelboard Schedule

TOTAL CONNECTED LOAD

CONNECTED LOAD DEMAND LOAD

MINIMUM FEEDER CAPACITY

Load Type

Feed Thru Lugs

SubFeed Lugs Iso. Gnd. Bus

Load Type Circuit Description

CONN

KVA

Circuit Breaker

PH

Circuit Breaker CONN

KVA

Location: Serving:

PANEL NO.

Circuit Description

Series Rated

@ 180VA/ea.

TOTAL DEMAND LOAD

MDP #3

Main Distribution Panel 1600

MED LSA 1 400 3 3

3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3

SPARE

SPARE

SPARE

Enclosure Type: OUTDOOR 400/230vac, 50Hz

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

MED LSA 1

MED LSA 1

MED LSA 2

MED LSA 2

MED LSA 2

SCCR (amps): 35,000 (minimum)

Flush Mount Top Feed

Fully Rated Surface Mount Bottom Feed

AMP Pole CKT CKT Pole AMP

1 A 2

3 B 4

5 C 6

7 A 8

9 B 10

11 C 12

13 A 14

15 B 16

17 C 18

19 A 20

21 B 22

23 C 24

25 A 26

27 B 28

29 C 30

31 A 32

33 B 34

35 C 36

37 A 38

39 B 40

41 C 42

Total General-Purpose Receptacle (R) Load Total General-Purpose Receptacle ( R ) Load @ 180VA/ea., KVA 100% for first 10 KVA & 50% for remainder KVA

Total Specific-Purpose (SP) Receptacles KVA Total Specific-Purpose (SP) Receptacles KVA

Total Motor (M) Load KVA Total Motor (M) Load KVA

Total Lighting (L) Load @ 125% KVA Total Lighting (L) Load @ 125% KVA

Total HVAC (H) Load KVA Total HVAC (H) Load KVA

KVA Largest Motor @ 125% KVA

CONNECTED AMP A B C KVA

Total / Phase KVA AMP

3Ø Panelboard Schedule

TOTAL CONNECTED LOAD

CONNECTED LOAD DEMAND LOAD

MINIMUM FEEDER CAPACITY

Load Type

Feed Thru Lugs

SubFeed Lugs Iso. Gnd. Bus

Load Type Circuit Description

CONN

KVA

Circuit Breaker

PH

Circuit Breaker CONN

KVA

Location: Serving:

PANEL NO.

Circuit Description

Series Rated

@ 180VA/ea.

TOTAL DEMAND LOAD

SDP 1A

Secondary Dist. Panel 600

CMD/DV 125 3 3

3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3

BILLET 4

BILLET 4

BILLET 4

Enclosure Type: OUTDOOR 400/230vac, 50Hz

BILLET 1

BILLET 2

BILLET 1

BILLET 1

BILLET 2

BILLET 2

BILLET 3

BILLET 3

BILLET 3

CMD/DV

CMD/DV

BILLET 5

BILLET 5

BILLET 5

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SCCR (amps): 22,000 (minimum)

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SCCR (amps): Flush Mount Top Feed

Fully Rated Surface Mount Bottom Feed

AMP Pole CKT CKT Pole AMP

1 A 2

3 B 4

5 C 6

7 A 8

9 B 10

11 C 12

13 A 14

15 B 16

17 C 18

19 A 20

21 B 22

23 C 24

25 A 26

27 B 28

29 C 30

31 A 32

33 B 34

35 C 36

37 A 38

39 B 40

41 C 42

Total General-Purpose Receptacle (R) Load Total General-Purpose Receptacle ( R ) Load @ 180VA/ea., KVA 100% for first 10 KVA & 50% for remainder KVA

Total Specific-Purpose (SP) Receptacles KVA Total Specific-Purpose (SP) Receptacles KVA

Total Motor (M) Load KVA Total Motor (M) Load KVA

Total Lighting (L) Load @ 125% KVA Total Lighting (L) Load @ 125% KVA

Total HVAC (H) Load KVA Total HVAC (H) Load KVA

KVA Largest Motor @ 125% KVA

CONNECTED AMP A B C KVA

Total / Phase KVA AMP

3Ø Panelboard Schedule

TOTAL CONNECTED LOAD

CONNECTED LOAD DEMAND LOAD

MINIMUM FEEDER CAPACITY

Load Type

Feed Thru Lugs

SubFeed Lugs Iso. Gnd. Bus

Load Type Circuit Description

CONN

KVA

Circuit Breaker

PH

Circuit Breaker CONN

KVA

Location: Serving:

PANEL NO.

Circuit Description

Series Rated

@ 180VA/ea.

TOTAL DEMAND LOAD

SDP 2A

Secondary Dist. Panel 1600

22,000 (minimum)

3 3 SUP CEN

3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3

Enclosure Type: OUTDOOR 400/230vac, 50Hz

OP CEN

OP CEN

OP CEN

SIG CEN

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SUP CEN

SUP CEN

BILLET 7

BILLET 7

BILLET 7

BILLET 8

BILLET 8

BILLET 8

SIG CEN

SIG CEN

BILLET 6

BILLET 6

BILLET 6

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

Flush Mount Top Feed

Fully Rated Surface Mount Bottom Feed

AMP Pole CKT CKT Pole AMP

1 A 2

3 B 4

5 C 6

7 A 8

9 B 10

11 C 12

13 A 14

15 B 16

17 C 18

19 A 20

21 B 22

23 C 24

25 A 26

27 B 28

29 C 30

31 A 32

33 B 34

35 C 36

37 A 38

39 B 40

41 C 42

Total General-Purpose Receptacle (R) Load Total General-Purpose Receptacle ( R ) Load @ 180VA/ea., KVA 100% for first 10 KVA & 50% for remainder KVA

Total Specific-Purpose (SP) Receptacles KVA Total Specific-Purpose (SP) Receptacles KVA

Total Motor (M) Load KVA Total Motor (M) Load KVA

Total Lighting (L) Load @ 125% KVA Total Lighting (L) Load @ 125% KVA

Total HVAC (H) Load KVA Total HVAC (H) Load KVA

KVA Largest Motor @ 125% KVA

CONNECTED AMP A B C KVA

Total / Phase KVA AMP

3Ø Panelboard Schedule

TOTAL CONNECTED LOAD

CONNECTED LOAD DEMAND LOAD

MINIMUM FEEDER CAPACITY

Load Type

Feed Thru Lugs

SubFeed Lugs Iso. Gnd. Bus

Load Type Circuit Description

CONN

KVA

Circuit Breaker

PH

Circuit Breaker CONN

KVA

Location: Serving:

PANEL NO.

Circuit Description

Series Rated

@ 180VA/ea.

TOTAL DEMAND LOAD

SDP 3A

Secondary Dist. Panel 600

KITCHEN 200 3 3

3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3

LATRINE 1

LATRINE 1

LATRINE 1

Enclosure Type: OUTDOOR 400/230vac, 50Hz

DFAC

SPARE

DFAC

DFAC

SPARE

SPARE

MWR

MWR

MWR

KITCHEN

KITCHEN

LATRINE 2

LATRINE 2

LATRINE 2

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SCCR (amps): 22,000 (minimum)

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

AMP

SCCR (amps): Flush Mount Top Feed

Fully Rated Surface Mount Bottom Feed

AMP Pole CKT CKT Pole AMP

1 A 2

3 B 4

5 C 6

7 A 8

9 B 10

11 C 12

13 A 14

15 B 16

17 C 18

19 A 20

21 B 22

23 C 24

25 A 26

27 B 28

29 C 30

31 A 32

33 B 34

35 C 36

37 A 38

39 B 40

41 C 42

Total General-Purpose Receptacle (R) Load Total General-Purpose Receptacle ( R ) Load @ 180VA/ea., KVA 100% for first 10 KVA & 50% for remainder KVA

Total Specific-Purpose (SP) Receptacles KVA Total Specific-Purpose (SP) Receptacles KVA

Total Motor (M) Load KVA Total Motor (M) Load KVA

Total Lighting (L) Load @ 125% KVA Total Lighting (L) Load @ 125% KVA

Total HVAC (H) Load KVA Total HVAC (H) Load KVA

KVA Largest Motor @ 125% KVA

CONNECTED AMP A B C KVA

Total / Phase KVA AMP

TOTAL CONNECTED LOAD

CONNECTED LOAD DEMAND LOAD

MINIMUM FEEDER CAPACITY

Load Type

Feed Thru Lugs

SubFeed Lugs Iso. Gnd. Bus

Load Type Circuit Description

CONN

KVA

Circuit Breaker

PH

Circuit Breaker CONN

KVA

Location: Serving:

PANEL NO.

Circuit Description

Series Rated

@ 180VA/ea.

TOTAL DEMAND LOAD

400AMP

Local Distribution Panel 400

22,000 (minimum)

1 20 1 20 1 20

20 1 1 20 20 1 1 20 20 1 1 20 20 1 1 20 20 1 1 20 20 1 1 20 20 1 1 20 20 1 1 20

1 20

Lighting

SPARE 63A 3PH 63 3

63 3

Enclosure Type: OUTDOOR 400/230vac, 50Hz 3Ø 4 Wire

HVAC 2

20 1

20 1

HVAC 1

HVAC 4

HVAC 3

Lighting Lighting

SPARE 63A 3PH

SPARE 63A 3PH

SPARE 63A 3PH

SPARE 63A 3PH

SPARE 63A 3PH

Lighting Lighting Lighting

SPARE 40A 3PH

SPARE 40A 3PH

SPARE 40A 3PH

SPARE 40A 3PH

SPARE 40A 3PH

SPARE 40A 3PH

SPARE

SPARE

SPARE

SPARE

20 1

SPARE 100A 3PH

SPARE 100A 3PH

SPARE 100A 3PH

SPARE 100A 3PH

SPARE 100A 3PH

SPARE 100A 3PH

Quantity: 2

Outlets GP-RCCB/GFI Outlets GP-RCCB/GFI Outlets GP-RCCB/GFI Outlets GP-RCCB/GFI Outlets GP-RCCB/GFI

Outlets GP-RCCB/GFI Outlets GP-RCCB/GFI Outlets GP-RCCB/GFI Outlets GP-RCCB/GFI Outlets GP-RCCB/GFI

SCCR (amps): Flush Mount Top Feed

Fully Rated Surface Mount Bottom Feed

AMP Pole CKT CKT Pole AMP

1 A 2

3 B 4

5 C 6

7 A 8

9 B 10

11 C 12

13 A 14

15 B 16

17 C 18

19 A 20

21 B 22

23 C 24

25 A 26

27 B 28

29 C 30

31 A 32

33 B 34

35 C 36

37 A 38

39 B 40

41 C 42

Total General-Purpose Receptacle (R) Load Total General-Purpose Receptacle ( R ) Load @ 180VA/ea., KVA 100% for first 10 KVA & 50% for remainder KVA

Total Specific-Purpose (SP) Receptacles KVA Total Specific-Purpose (SP) Receptacles KVA

Total Motor (M) Load KVA Total Motor (M) Load KVA

Total Lighting (L) Load @ 125% KVA Total Lighting (L) Load @ 125% KVA

Total HVAC (H) Load KVA Total HVAC (H) Load KVA

KVA Largest Motor @ 125% KVA

CONNECTED AMP A B C KVA

Total / Phase KVA AMP

TOTAL CONNECTED LOAD

CONNECTED LOAD DEMAND LOAD

MINIMUM FEEDER CAPACITY

Load Type

Feed Thru Lugs

SubFeed Lugs Iso. Gnd. Bus

Load Type Circuit Description

CONN

KVA

Circuit Breaker

PH

Circuit Breaker CONN

KVA

Location: Serving:

PANEL NO.

Circuit Description

Series Rated

@ 180VA/ea.

TOTAL DEMAND LOAD

200AMP

Local Distribution Panel 200

22,000 (minimum)

1 20 1 20 1 20

20 1 1 20 20 1 1 20 20 1 1 20 20 1 1 20 20 1 1 20 20 1 1 20 20 1 1 20 20 1 1 20 20 1 1 20 20 1 1 20 20 1 1 20 20 1 1 20

Lighting

SPARE 63A 3PH 63 3

63 3

Enclosure Type: OUTDOOR 400/220vac, 50Hz 3Ø 4 Wire

HVAC 2

20 1

20 1

HVAC 1

HVAC 4

HVAC 3

Lighting Lighting

SPARE 63A 3PH

SPARE 63A 3PH

SPARE 63A 3PH

SPARE 63A 3PH

SPARE 63A 3PH

3 63

Lighting Lighting Lighting

SPARE 40A 3PH

SPARE 40A 3PH

SPARE 40A 3PH

63 3

SPARE 40A 3PH

SPARE 40A 3PH

SPARE 40A 3PH

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

Quantity: 2

Outlets GP-RCCB/GFI Outlets GP-RCCB/GFI Outlets GP-RCCB/GFI Outlets GP-RCCB/GFI Outlets GP-RCCB/GFI

Outlets GP-RCCB/GFI Outlets GP-RCCB/GFI Outlets GP-RCCB/GFI Outlets GP-RCCB/GFI

SCCR (amps): Flush Mount Top Feed Fully Rated Surface Mount Bottom Feed

AMP Pole CKT CKT Pole AMP

1 A 2

3 B 4

5 C 6

7 A 8

9 B 10

11 C 12

13 A 14

15 B 16

17 C 18

19 A 20

21 B 22

23 C 24

25 A 26

27 B 28

29 C 30

31 A 32

33 B 34

35 C 36

37 A 38

39 B 40

41 C 42

Total General-Purpose Receptacle (R) Load Total General-Purpose Receptacle ( R ) Load @ 180VA/ea., KVA 100% for first 10 KVA & 50% for remainder KVA

Total Specific-Purpose (SP) Receptacles KVA Total Specific-Purpose (SP) Receptacles KVA

Total Motor (M) Load KVA Total Motor (M) Load KVA

Total Lighting (L) Load @ 125% KVA Total Lighting (L) Load @ 125% KVA

Total HVAC (H) Load KVA Total HVAC (H) Load KVA

KVA Largest Motor @ 125% KVA

CONNECTED AMP A B C KVA

Total / Phase KVA AMP

TOTAL CONNECTED LOAD

CONNECTED LOAD DEMAND LOAD

MINIMUM FEEDER CAPACITY

Load Type

Feed Thru Lugs

SubFeed Lugs Iso. Gnd. Bus

Load Type Circuit Description

CONN

KVA

Circuit Breaker

PH

Circuit Breaker CONN

KVA

Location: Serving:

PANEL NO.

Circuit Description

Series Rated

@ 180VA/ea.

TOTAL DEMAND LOAD

125AMP

SOJTF OIR - S Local Distribution Panel 125

22,000 (minimum)

1 20 1 20 1 20

20 1 1 20 20 1 1 20 20 1 1 20 20 1 1 20 20 1 1 20 20 1 1 20 20 1 1 20 20 1 1 20

1 20

Lighting

Enclosure Type: OUTDOOR 400/230vac, 50Hz 3Ø 4 Wire

HVAC 2

20 1

20 1

HVAC 1

HVAC 4

HVAC 3

Outlets GP-RCCB/GFI

Lighting Lighting

Lighting Lighting

SPARE 30A 3ph SPARE 30A 3ph SPARE 30A 3ph

SPARE 40A 3ph SPARE 40A 3ph SPARE 40A 3ph

SPARE

SPARE SPARE20 1

Lighting

SPARE

Quantity: 12

Outlets GP-RCCB/GFI Outlets GP-RCCB/GFI Outlets GP-RCCB/GFI Outlets GP-RCCB/GFI

Outlets GP-RCCB/GFI Outlets GP-RCCB/GFI Outlets GP-RCCB/GFI

KLZ Specifications
Panelboard Specification
PART 1 – GENERAL
PART 2 – COMPLIANCE, TRACEABILTY & SUBMITTALS
PART 3 – LABELING
KLZ Panelboard Schedules
MDP 1 1600amp KFC North rg1
MDP 2 1600amp KFC North rg1
MDP 3 1600amp KFC North rg1
SDP 1A 600amp KFC North rg1
SDP 2A 600amp KFC North rg1
SDP 3A 600amp KFC North rg1
LDP 400amp Generic Panelboard With RCCB GFI rg1
LDP 200amp Generic Panelboard With RCCB GFI rg1
LDP 125amp Generic Panelboard With RCCB GFI rg1