Amendment_0003_-_KC46_Fuselage_Trainer_-_Specs.pdf

PDF 165 KB Posted

Attached to
KC-46A Addition/Alteration to Bldg. 3209 for Fuselage Trainer Federal contract opportunity
Solicitation number
W912DS18B0019
Issued by
Department of the Army Corps of Engineers Engineering District New York

About this file

Amendment 0003 Specs

View the file

Other files for this federal contract opportunity

Other files attached to KC-46A Addition/Alteration to Bldg. 3209 for Fuselage Trainer, newest first.
File Type Posted
Bid_Abstract-W912DS18B0019.pdf PDF
W912DS18B0019-0003.pdf PDF
Amendment_0003_-_KC46_Fuselage_Trainer_-_Plans.pdf PDF
W912DS18B0019-0002_Revised.pdf PDF
Amendment_0002_-_FuT_Specs.pdf PDF
Amendment_0002_-_FuT_Plans.pdf PDF
W912DS18B0019-0002.pdf PDF
W912DS18B0019-0001.pdf PDF
Site_Visit_Sign-In_4_SEP_18_(Fus_Trainer,_Fuel_Hydrants,_Fac_for_Mx).pdf PDF
Package_3_-_KC46_Fuselage_Trainer_-_SID.pdf PDF
W912DS18B0019.pdf PDF
Package_4-_KC46_Fuselage_Trainer_-_FFE.pdf PDF
Appendix_A_-_Bldg_3209_As-Builds.pdf PDF
Package_2_-_KC46_Fuselage_Trainer_-_Specifications.pdf PDF
Package_1_-_KC46_Fuselage_Trainer_-_Plans.pdf PDF
Appendix_B_-_Geotechnical_Report.pdf PDF
Show all 16

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

KC46A Beddown Fusel age Tr ai ner , Renovat e B. 3209 JBMDLPTFL163006 XXX Submi ssi on

SECTI ON 26 56 00

EXTERI OR LI GHTI NG ( LED)

05/13

PART 1 GENERAL

1. 1 REFERENCES

The publ i cat i ons l i s t ed bel ow f or m a par t of t hi s speci f i cat i on t o t he ext ent r ef er enced. The publ i cat i ons ar e r ef er r ed t o i n t he t ext by t he basi c desi gnat i on onl y.

AMERI CAN SOCI ETY OF HEATI NG, REFRI GERATI NG AND AI R- CONDI TI ONI NG

ENGI NEERS ( ASHRAE)

ASHRAE 90. 1 - I P ( 2013) Ener gy St andar d f or Bui l di ngs Except Low- Ri se Resi dent i al Bui l di ngs

ASTM I NTERNATI ONAL ( ASTM)

ASTM B117 ( 2016) St andar d Pr act i ce f or Oper at i ng Sal t Spr ay ( Fog) Appar at us

CALI FORNI A ENERGY COMMI SSI ON ( CEC)

CEC Ti t l e 24 ( 2016) Cal i f or ni a' s Ener gy Ef f i c i ency St andar ds f or Resi dent i al and Nonr esi dent i al Bui l di ngs

I LLUMI NATI NG ENGI NEERI NG SOCI ETY OF NORTH AMERI CA ( I ES)

I ES HB- 10 ( 2011; Er r at a 2015) I ES Li ght i ng Handbook

I ES LM- 79 ( 2008) El ect r i cal and Phot omet r i c Measur ement s of Sol i d- St at e Li ght i ng Products

I ES LM- 80 ( 2015) Measur i ng Lumen Mai nt enance of LED Li ght Sour ces

I ES RP- 16 ( 2010; Addendum A 2008; Addenda B & C 2009) Nomencl at ur e and Def i ni t i ons f or I l l umi nat i ng Engi neer i ng

I ES TM- 15 ( 2011) Lumi nai r e Cl assi f i cat i on Syst em f or Out door Lumi nai r es

I ES TM- 21 ( 2011; Addendum B 2015) Pr oj ect i ng Long Ter m Lumen Mai nt enance of LED Li ght Sour ces

I NSTI TUTE OF ELECTRI CAL AND ELECTRONI CS ENGI NEERS ( I EEE)

I EEE 100 ( 2000; Ar chi ved) The Aut hor i t at i ve Di ct i onar y of I EEE St andar ds Ter ms

I EEE C2 ( 2017) Nat i onal El ect r i cal Saf et y Code

SECTI ON 26 56 00 Page 1

09/21/18 2: 14 PM

NATI ONAL ELECTRI CAL MANUFACTURERS ASSOCI ATI ON ( NEMA)

ANSI C136. 13 ( 2004; R 2009) Amer i can Nat i onal St andar d f or Roadway Li ght i ng Equi pment , Met al Br acket s f or Wood Pol es

ANSI C136. 21 ( 2004; R 2009) Amer i can Nat i onal St andar d f or Roadway and Ar ea Li ght i ng Equi pment - Ver t i cal Tenons Used wi t h Post - Top- Mount ed Luminaires

ANSI C136. 3 ( 2014) Amer i can Nat i onal St andar d f or Roadway and Ar ea Li ght i ng Equi pment Lumi nai r e At t achment s

NEMA 250 ( 2014) Encl osur es f or El ect r i cal Equi pment ( 1000 Vol t s Maxi mum)

NEMA C136. 10 ( 2010) Amer i can Nat i onal St andar d f or Roadway and Ar ea Li ght i ng Equi pment - Locki ng- Type Phot ocont r ol Devi ces and Mat i ng Recept acl es- - Physi cal and El ect r i cal I nt er changeabi l i t y and Testing

NEMA C136. 31 ( 2010) Amer i can Nat i onal f or Roadway and Ar ea Li ght i ng Equi pment - Lumi nai r e Vibration

NEMA C82. 77 ( 2002) Har moni c Emi ssi on Li mi t s - Rel at ed Power Qual i t y Requi r ement s f or Li ght i ng Equipment

NEMA I CS 2 ( 2000; R 2005; Er r at a 2008) St andar d f or Cont r ol l er s, Cont act or s, and Over l oad Rel ays Rat ed 600 V

NEMA I EC 60529 ( 2004) Degr ees of Pr ot ect i on Pr ovi ded by Encl osur es ( I P Code)

NATI ONAL FI RE PROTECTI ON ASSOCI ATI ON ( NFPA)

NFPA 70 ( 2017) Nat i onal El ect r i cal Code

U. S. NATI ONAL ARCHI VES AND RECORDS ADMI NI STRATI ON ( NARA)

47 CFR 15 Radi o Fr equency Devi ces

UNDERWRI TERS LABORATORI ES ( UL)

UL 1310 ( 2011; Repr i nt Oct 2013) UL St andar d f or Saf et y Cl ass 2 Power Uni t s

UL 1598 ( 2008; Repr i nt Oct 2012) Lumi nai r es

UL 773 ( 2016; Repr i nt Nov 2017) St andar d f or Pl ug- I n, Locki ng Type Phot ocont r ol s f or Use wi t h Ar ea Li ght i ng

SECTI ON 26 56 00 Page 2

09/21/18 2: 14 PM

e3endtk9 Highlight

UL 773A ( 2016) St andar d f or Noni ndust r i al Phot oel ect r i c Swi t ches f or Li ght i ng Cont r ol

UL 8750 ( 2015; Repr i nt Aug 2017) UL St andar d f or Saf et y Li ght Emi t t i ng Di ode ( LED) Equi pment f or Use i n Li ght i ng Pr oduct s

UL 916 ( 2007; Repr i nt Dec 2013) St andar d f or Ener gy Management Equi pment

1. 2 DEFINITIONS

a. Unl ess ot her wi se speci f i ed or i ndi cat ed, el ect r i cal and el ect r oni cs t er ms used i n t hese speci f i cat i ons, and on t he dr awi ngs shal l be as def i ned i n I EEE 100 and I ES RP- 16.

b. For HI D, f l uor escent , and i nduct i on l umi nai r e l i ght sour ces, " Aver age Rat ed Li f e" i s t he t i me af t er whi ch 50 per cent of a l ar ge gr oup of l i ght sour ces wi l l have f ai l ed and 50 per cent wi l l have sur vi ved under nor mal oper at i ng condi t i ons.

c. For LED l umi nai r e l i ght sour ces, " Usef ul Li f e" i s t he oper at i ng hour s bef or e r eachi ng 70 per cent of t he i ni t i al r at ed l umen out put ( L70) wi t h no cat ast r ophi c f ai l ur es under nor mal oper at i ng condi t i ons. Thi s i s al so known as 70 per cent " Rat ed Lumen Mai nt enance Li f e" as def i ned in I ES LM- 80.

d. The " Gr oundl i ne Sect i on" of wood pol es i s t hat por t i on of t he pol e bet ween one f oot above, and 2 f eet bel ow t he gr oundl i ne.

1. 3 SUBMITTALS

Gover nment appr oval i s r equi r ed f or submi t t al s wi t h a " G" desi gnat i on;

submi t t al s not havi ng a " G" desi gnat i on ar e f or Cont r act or Qual i t y Cont r ol appr oval , f or i nf or mat i on onl y, or as ot her wi se desi gnat ed. When used, a desi gnat i on f ol l owi ng t he " G" desi gnat i on i dent i f i es t he of f i ce t hat wi l l r evi ew t he submi t t al f or t he Gover nment . The f ol l owi ng shal l be submi t t ed i n accor dance wi t h Sect i on 01 33 00 SUBMI TTAL PROCEDURES:

SD- 01 Pr econst r uct i on Submi t t al s

Phot omet r i c Pl an; G, RO

LED Lumi nai r e War r ant y; G, RO

SD- 02 Shop Dr awi ngs

Lumi nai r e dr awi ngs; G, RO

SD- 03 Pr oduct Dat a

LED Lumi nai r es; G, RO

Lumi nai r e Li ght Sour ces; G, RO

Lumi nai r e Bal l ast s, Gener at or s and Power Suppl y Uni t s ( Dr i ver s) ;

G, RO

SECTI ON 26 56 00 Page 3

Li ght i ng cont act or ; G, RO

Ti me swi t ch; G, RO

Li ght i ng Cont r ol Rel ay Panel ; G, RO

Bi - l evel HI D Cont r ol l er ; G, RO

Phot ocel l ; G, RO

BRACKETS; G, RO

SD- 05 Desi gn Dat a

Desi gn Dat a f or l umi nai r es; G, RO

SD- 06 Test Repor t s

LED Lumi nai r e - I ES LM- 79 Test Repor t ; G, RO

LED Li ght Sour ce - I ES LM- 80 Test Repor t ; G, RO

Pol e, EPA, and vi br at i on damper cal cul at i ons; G, RO oper at i ng t est

Submi t oper at i ng t est r esul t s as st at ed i n par agr aph ent i t l ed " Fi el d Qual i t y Cont r ol . "

Funct i onal Per f or mance Test i ng ( FPTs) For ms; G, DO

SD- 07 Cer t i f i cat es

Lumi nai r e Usef ul Li f e Cer t i f i cat e; G, RO

Submi t cer t i f i cat i on f r om t he manuf act ur er i ndi cat i ng t he expect ed usef ul l i f e of t he l umi nai r es pr ovi ded. The usef ul l i f e shal l be di r ect l y cor r el at ed f r om t he I ES LM- 80 t est dat a usi ng pr ocedur es out l i ned i n I ES TM- 21. Ther mal pr oper t i es of t he speci f i c l umi nai r e and l ocal ambi ent oper at i ng t emper at ur e and condi t i ons shal l be t aken i nt o consi der at i on.

SD- 10 Oper at i on and Mai nt enance Dat a

El ect r oni c LED Dr i ver War r ant y

Submi t document at i on t hat i ncl udes cont act i nf or mat i on, summar y of pr ocedur es, and t he l i mi t at i ons and condi t i ons appl i cabl e t o t he pr oj ect . I ndi cat e manuf act ur er ' s commi t ment t o r ecl ai m mat er i al s f or r ecycl i ng and/ or r euse.

Oper at i onal Ser vi ce; G, RO

SECTI ON 26 56 00 Page 4

09/21/18 2: 14 PM

e3endtk9 Highlight e3endtk9 Highlight

1. 4 QUALI TY ASSURANCE

1. 4. 1 Dr awi ng Requi r ement s

1. 4. 1. 1 Lumi nai r e Dr awi ngs

I ncl ude di mensi ons, ef f ect i ve pr oj ect ed ar ea ( EPA) , accessor i es, and i nst al l at i on and const r uct i on det ai l s. Phot omet r i c dat a, i ncl udi ng zonal l umen dat a, aver age and mi ni mum r at i o, ai mi ng di agr am, and comput er i zed candl epower di st r i but i on dat a shal l accompany shop dr awi ngs.

1. 4. 2 Phot omet r i c Pl an

For LED l umi nai r es, i ncl ude comput er - gener at ed phot omet r i c anal ysi s of t he " desi gned t o" val ues f or t he " end of usef ul l i f e" of t he l umi nai r e i nst al l at i on usi ng a l i ght l oss f act or of 0. 7. For LED and al l ot her t ypes of l umi nai r es, t he submi t t al shal l i ncl ude t he f ol l owi ng:

Hor i zont al i l l umi nance measur ement s at f i ni shed gr ade, t aken at a maxi mum of ever y 10 f eet .

Ver t i cal i l l umi nance measur ement s at 5 f eet above f i ni shed gr ade.

Mi ni mum and maxi mum f oot candl e l evel s.

Aver age mai nt ai ned f oot candl e l evel .

Maxi mum t o mi ni mum r at i o f or hor i zont al i l l umi nance onl y.

1. 4. 3 Desi gn Dat a f or Lumi nai r es

a. Pr ovi de di st r i but i on dat a accor di ng t o I ES cl assi f i cat i on t ype as def i ned i n I ES HB- 10.

b. Shi el di ng as def i ned by I ES RP- 8 or B. U. G. r at i ng f or t he i nst al l ed posi t i on as def i ned by I ES TM- 15.

c. Pr ovi de saf et y cer t i f i cat i on and f i l e number f or t he l umi nai r e f ami l y. I ncl ude l i s t i ng, l abel i ng and i dent i f i cat i on per NFPA 70 ( NEC) . Appl i cabl e t est i ng bodi es ar e det er mi ned by t he US Occupat i onal Saf et y Heal t h Admi ni st r at i on ( OSHA) as Nat i onal l y Recogni zed Test i ng Labor at or i es ( NRTL) and i ncl ude: CSA ( Canadi an St andar ds Associ at i on) , ETL ( Edi son Test i ng Labor at or y) , and UL ( Under wr i t er s Labor at or i es) .

d. Pr ovi de l ong t er m l umen mai nt enance pr oj ect i ons f or each LED l umi nai r e i n accor dance wi t h I ES TM- 21. Dat a used f or pr oj ect i ons shal l be obt ai ned f r om t est i ng i n accor dance wi t h I ES LM- 80.

e. Pr ovi de wi nd l oadi ng cal cul at i ons f or l umi nai r es mount ed on pol es.

Wei ght and ef f ect i ve pr oj ect ed ar ea ( EPA) of l umi nai r es and mount i ng br acket s shal l not exceed maxi mum r at i ng of pol e as i nst al l ed i n par t i cul ar wi nd zone ar ea.

1. 4. 4 LED Lumi nai r e - I ES LM- 79 Test Repor t

Submi t t est r epor t on manuf act ur er ' s st andar d pr oduct i on model l umi nai r e.

Submi t t al shal l i ncl ude al l phot omet r i c and el ect r i cal measur ement s, as wel l as al l ot her per t i nent dat a out l i ned under " 14. 0 Test Repor t " i n

SECTI ON 26 56 00 Page 5

I ES LM- 79.

1. 4. 5 LED Li ght Sour ce - I ES LM- 80 Test Repor t

Submi t r epor t on manuf act ur er ' s st andar d pr oduct i on LED package, ar r ay, or modul e. Submi t t al shal l i ncl ude:

a. Test i ng agency, r epor t number , dat e, t ype of equi pment , and LED l i ght sour ce bei ng t est ed.

b. Al l dat a r equi r ed by I ES LM- 80.

1. 4. 5. 1 Test Labor at or i es

Test l abor at or i es f or t he I ES LM- 79 and I ES LM- 80 t est r epor t s shal l be one of t he f ol l owi ng:

a. Nat i onal Vol unt ar y Labor at or y Accr edi t at i on Pr ogr am ( NVLAP) accr edi t ed f or sol i d- st at e l i ght i ng t est i ng as par t of t he Ener gy- Ef f i c i ent Li ght i ng Pr oduct s l abor at or y accr edi t at i on pr ogr am.

b. One of t he qual i f i ed l abs l i s t ed on t he Depar t ment of Ener gy - Ener gy Ef f i c i ency & Renewabl e Ener gy, Sol i d- St at e Li ght i ng web si t e.

c. A manuf act ur er ' s i n- house l ab t hat meet s t he f ol l owi ng cr i t er i a:

1. Manuf act ur er has been r egul ar l y engaged i n t he desi gn and pr oduct i on of hi gh i nt ensi t y di schar ge r oadway and ar ea l umi nai r es and t he manuf act ur er ' s l ab has been successf ul l y cer t i f y i ng t hese f i xt ur es f or a mi ni mum of 15 year s.

2. Annual equi pment cal i br at i on i ncl udi ng phot omet er cal i br at i on i n accor dance wi t h Nat i onal I nst i t ut e of St andar ds and Technol ogy.

1. 4. 6 Regul at or y Requi r ement s

I n each of t he publ i cat i ons r ef er r ed t o her ei n, consi der t he advi sor y pr ovi s i ons t o be mandat or y, as t hough t he wor d, " shal l " had been subst i t ut ed f or " shoul d" wher ever i t appear s. I nt er pr et r ef er ences i n t hese publ i cat i ons t o t he " aut hor i t y havi ng j ur i sdi ct i on, " or wor ds of s i mi l ar meani ng, t o mean t he Cont r act i ng Of f i cer . Equi pment , mat er i al s, i nst al l at i on, and wor kmanshi p shal l be i n accor dance wi t h t he mandat or y and advi sor y pr ovi s i ons of NFPA 70 unl ess mor e st r i ngent r equi r ement s ar e speci f i ed or i ndi cat ed.

1. 4. 7 St andar d Pr oduct s

Pr ovi de mat er i al s and equi pment t hat ar e pr oduct s of manuf act ur er s r egul ar l y engaged i n t he pr oduct i on of such pr oduct s whi ch ar e of equal mat er i al , desi gn and wor kmanshi p. Pr oduct s shal l have been i n sat i sf act or y commer ci al or i ndust r i al use f or 2 year s pr i or t o bi d openi ng. The 2- year per i od shal l i ncl ude appl i cat i ons of equi pment and mat er i al s under s i mi l ar c i r cumst ances and of s i mi l ar s i ze. The pr oduct shal l have been on sal e on t he commer ci al mar ket t hr ough adver t i sement s, manuf act ur er s ' cat al ogs, or br ochur es dur i ng t he 2- year per i od. Wher e t wo or mor e i t ems of t he same cl ass of equi pment ar e r equi r ed, t hese i t ems shal l be pr oduct s of a s i ngl e manuf act ur er ; however , t he component par t s of t he i t em need not be t he pr oduct s of t he same manuf act ur er unl ess st at ed i n t hi s sect i on.

SECTI ON 26 56 00 Page 6

1. 4. 7. 1 Al t er nat i ve Qual i f i cat i ons

Pr oduct s havi ng l ess t han a 2- year f i el d ser vi ce r ecor d wi l l be accept abl e i f t he manuf act ur er has been r egul ar l y engaged i n t he desi gn and pr oduct i on of hi gh i nt ensi t y di schar ge r oadway and ar ea l umi nai r es f or a mi ni mum of 15 year s. Pr oduct s shal l have been i n sat i sf act or y commer ci al or i ndust r i al use f or 15 year s pr i or t o bi d openi ng. The pr oduct shal l have been on sal e on t he commer ci al mar ket t hr ough adver t i sement s, manuf act ur er s ' cat al ogs, or br ochur es dur i ng t he 15- year per i od.

1. 4. 7. 2 Mat er i al and Equi pment Manuf act ur i ng Dat e

Pr oduct s manuf act ur ed mor e t han 1 year pr i or t o dat e of del i ver y t o s i t e shal l not be used, unl ess speci f i ed ot her wi se.

1. 5 DELI VERY, STORAGE, AND HANDLI NG OF POLES

1. 5. 1 Al umi num or St eel Pol es, i f appl i cabl e

Do not st or e pol es on gr ound. Suppor t pol es so t hey ar e at l east one f oot above gr ound l evel and gr owi ng veget at i on. Do not r emove f act or y- appl i ed pol e wr appi ngs unt i l j ust bef or e i nst al l i ng pol e.

1. 5 WARRANTY

The equi pment i t ems shal l be suppor t ed by ser vi ce or gani zat i ons whi ch ar e r easonabl y conveni ent t o t he equi pment i nst al l at i on i n or der t o r ender sat i sf act or y ser vi ce t o t he equi pment on a r egul ar and emer gency basi s dur i ng t he war r ant y per i od of t he cont r act .

1. 5. 1 LED Lumi nai r e War r ant y

Pr ovi de Lumi nai r e Usef ul Li f e Cer t i f i cat e.

The equi pment i t ems shal l be suppor t ed by ser vi ce or gani zat i ons whi ch ar e r easonabl y conveni ent t o t he equi pment i nst al l at i on i n or der t o r ender sat i sf act or y ser vi ce t o t he equi pment on a r egul ar and emer gency basi s dur i ng t he war r ant y per i od of t he cont r act .

a. Pr ovi de a wr i t t en f i ve year on- si t e r epl acement war r ant y f or mat er i al , f i x t ur e f i ni sh, and wor kmanshi p. On- si t e r epl acement i ncl udes t r anspor t at i on, r emoval , and i nst al l at i on of new pr oduct s.

1. Fi ni sh war r ant y shal l i ncl ude war r ant y agai nst f ai l ur e and agai nst subst ant i al det er i or at i on such as bl i st er i ng, cr acki ng, peel i ng, chal k i ng, or f adi ng.

2. Mat er i al war r ant y shal l i ncl ude:

( a) Al l power suppl y uni t s ( LED dr i ver s) .

( b) Repl acement when mor e t han 10 per cent of LED sour ces i n any l i ght bar or subassembl y( s) ar e def ect i ve or non- st ar t i ng.

b. War r ant y per i od must begi n on dat e of benef i c i al occupancy or const r uct i on compl et i on dat e accept ance by t he Cont r act i ng Of f i cer .

Cont r act or shal l pr ovi de t he Cont r act i ng Of f i cer s i gned war r ant y cer t i f i cat es pr i or t o f i nal payment .

SECTI ON 26 56 00 Page 7

09/21/18 2: 14 PM

e3endtk9 Highlight

1. 5. 2 El ect r oni c LED Dr i ver War r ant y

Fur ni sh t he el ect r oni c LED dr i ver manuf act ur er ' s war r ant y. The war r ant y per i od shal l not be l ess t han f i ve ( 5) year s f r om t he dat e of benef i c i al occupancy or const r uct i on compl et i on dat e. The war r ant y shal l st at e t hat t he mal f unct i oni ng bal l ast shal l be exchanged by t he manuf act ur er and pr ompt l y shi pped t o t he usi ng Gover nment f aci l i t y . The r epl acement bal l ast shal l be i dent i cal t o, or an i mpr ovement upon, t he or i gi nal desi gn of t he LED dr i ver .

1. 6 OPERATI ONAL SERVI CE

Coor di nat e wi t h manuf act ur er f or mai nt enance agr eement . Col l ect i nf or mat i on f r om t he manuf act ur er about mai nt enance agr eement opt i ons, and submi t t o Cont r act i ng Of f i cer . Ser vi ces shal l r ecl ai m mat er i al s f or r ecycl i ng and/ or r euse. Ser vi ces shal l not deposi t mat er i al s i n l andf i l l s or bur n r ecl ai med mat er i al s. I ndi cat e pr ocedur es f or compl i ance wi t h r egul at i ons gover ni ng di sposal of mer cur y. When such a ser vi ce i s not avai l abl e, l ocal r ecycl er s shal l be sought af t er t o r ecl ai m t he mat er i al s.

PART 2 PRODUCTS

2. 1 LED LUMI NAI RES

UL 1598, NEMA C82. 77 and UL 8750. Pr ovi de l umi nai r es as i ndi cat ed i n l umi nai r e schedul e and det ai l s on pr oj ect pl ans. Pr ovi de l umi nai r es compl et e wi t h l i ght sour ces of quant i t y, t ype, and wat t age i ndi cat ed. Al l l umi nai r es of t he same t ype shal l be pr ovi ded by t he same manuf act ur er .

2. 1. 1 Gener al Requi r ement s

a. LED l umi nai r e housi ngs shal l be di e cast or ext r uded al umi num.

Housi ngs f or l umi nai r es ot her t han LED shal l be di e cast , ext r uded, or f abr i cat ed al umi num. Fabr i cat ed al umi num housi ngs shal l have al l seams and cor ner s i nt er nal l y wel ded t o r esi st weat her i ng, moi st ur e and dust.

b. LED l umi nai r es shal l be r at ed f or oper at i on wi t hi n an ambi ent t emper at ur e r ange of mi nus 40 degr ees F t o 104 degr ees F.

c. Lumi nai r es shal l be UL l i s t ed f or wet l ocat i ons per UL 1598. Opt i cal compar t ment f or LED l umi nai r es shal l be seal ed and r at ed a mi ni mum of I P65 per NEMA I EC 60529.

d. LED l umi nai r es shal l pr oduce a mi ni mum ef f i cacy as shown i n t he f ol l owi ng t abl e and as i ndi cat ed on t he l i ght i ng f i x t ur e det ai l s ( whi chever r equi r ement i s mor e st r i ngent shal l gover n) , t est ed per I ES LM- 79. Theor et i cal model s of i ni t i al r aw LED l umens per wat t ar e not accept abl e.

Application Lumi nai r e Ef f i cacy i n Lumens per Wat t

Ext er i or Wal l - Mount ed Ar ea Lumi nai r es 100

e. Lumi nai r es shal l have I ES di st r i but i on and NEMA f i el d angl e

SECTI ON 26 56 00 Page 8 cl assi f i cat i ons as i ndi cat ed i n l umi nai r e schedul e on pr oj ect pl ans per I ES HB- 10.

f . Housi ng f i ni sh shal l be baked- on enamel , anodi zed, or baked- on powder coat pai nt . Fi ni sh shal l be capabl e of sur vi v i ng ASTM B117 sal t f og envi r onment t est i ng f or 2500 hour s mi ni mum wi t hout bl i st er i ng or peeling.

g. Lumi nai r es shal l not exceed t he f ol l owi ng I ES TM- 15 Backl i ght , Upl i ght and Gl ar e ( B. U. G. ) r at i ngs:

1. Maxi mum Backl i ght ( B) r at i ng shal l be det er mi ned by l i ght i ng zone i n whi ch l umi nai r e i s pl aced and as i ndi cat ed on t he f i xt ur e details.

2. Maxi mum Upl i ght ( U) r at i ng shal l be U0.

3. Maxi mum Gl ar e ( G) r at i ng shal l be det er mi ned by l i ght i ng zone i n whi ch l umi nai r e i s pl aced and as i ndi cat ed on t he f i xt ur e det ai l s.

h. Lumi nai r es shal l be f ul l y assembl ed and el ect r i cal l y t est ed pr i or t o shi pment f r om f act or y.

i . The f i ni sh col or shal l be as i ndi cat ed i n t he l umi nai r e schedul e or det ai l on t he pr oj ect pl ans.

j . Lumi nai r e ar m bol t s shal l be 304 st ai nl ess st eel or z i nc- pl at ed st eel .

k. Lumi nai r e l enses shal l be const r uct ed of f r ost ed t emper ed gl ass or UV- r esi st ant acr yl i c. Pr ovi de pol ycar bonat e vandal - r esi st ant l enses as i ndi cat ed.

l . The wi r i ng compar t ment on pol e- mount ed, st r eet and ar ea l umi nai r es must be accessi bl e wi t hout t he use of hand t ool s t o mani pul at e smal l scr ews, bol t s, or har dwar e.

l m. I ncor por at e modul ar el ect r i cal connect i ons, and const r uct l umi nai r es t o al l ow r epl acement of al l or any par t of t he opt i cs, heat s i nks, power suppl y uni t s, bal l ast s, sur ge suppr essor s and ot her el ect r i cal component s usi ng onl y a s i mpl e t ool , such as a manual or cor dl ess el ect r i c scr ewdr i ver .

mn. Lumi nai r es shal l have a namepl at e bear i ng t he manuf act ur er ' s name, addr ess, model number , dat e of manuf act ur e, and ser i al number secur el y af f i xed i n a conspi cuous pl ace. The namepl at e of t he di st r i but i ng agent wi l l not be accept abl e.

no. Roadway and Aar ea l umi nai r es shal l have an i nt egr al t i l t adj ust ment of pl us or mi nus 5 degr ees t o al l ow t he uni t t o be l evel ed i n accor dance wi t h ANSI C136. 3.

op. Lumi nai r e must pass 3G vi br at i on t est i ng i n accor dance wi t h

NEMA C136. 31.

qp. Al l f act or y el ect r i cal connect i ons shal l be made usi ng cr i mp, l ocki ng, or l at chi ng st y l e connect or s. Twi st - st y l e wi r e nut s ar e not acceptable.

SECTI ON 26 56 00 Page 9

09/21/18 2: 14 PM

e3endtk9 Highlight

2. 1. 2 Lumi nai r e Li ght Sour ces

2. 1. 2. 1 LED Li ght Sour ces

a. Cor r el at ed Col or Temper at ur e ( CCT) shal l be i n accor dance wi t h

NEMA ANSLG C78. 377:

Nomi nal CCT: 4000K f or ar eas not cover ed by t he June 2015 Endanger ed Speci es Act . See map f or t he del i neat ed ar eas.

b. Col or Render i ng I ndex ( CRI ) shal l be:

Gr eat er t han or equal t o 70 f or 3000 and 4000 degr ees K l i ght sour ces.

c. Col or Consi st ency:

Manuf act ur er shal l ut i l i ze a maxi mum 4- st ep MacAdam el l i pse bi nni ng t ol er ance f or col or consi st ency of LEDs used i n l umi nai r es.

2. 1. 3 Lumi nai r e Power Suppl y Uni t s ( Dr i ver s)

2. 1. 3. 1 LED power Suppl y Uni t s ( Dr i ver s)

UL 1310. LED Power Suppl y Uni t s ( Dr i ver s) shal l meet t he f ol l owi ng requirements:

a. Mi ni mum ef f i c i ency shal l be 90 per cent .

b. Dr i ve cur r ent t o each i ndi v i dual LED shal l not exceed 600 mA, pl us or mi nus 10 per cent .

c. Shal l be r at ed t o oper at e bet ween ambi ent t emper at ur es of mi nus 22 degr ees F and122 degr ees F.

d. Shal l be desi gned t o oper at e on t he vol t age syst em ( br anch ci r cui t vol t age) t o whi ch t hey ar e connect ed, t ypi cal l y r angi ng f r om 120 V t o 480 V nomi nal .

e. Oper at i ng f r equency shal l be: 50 or 60 Hz.

f . Power Fact or ( PF) shal l be gr eat er t han or equal t o 0. 90.

g. Tot al Har moni c Di st or t i on ( THD) cur r ent shal l be l ess t han or equal t o 10 per cent .

h. Shal l meet r equi r ement s of 47 CFR 15, Cl ass B.

i . Shal l be RoHS- compl i ant .

j . Shal l be mount ed i nt egr al t o l umi nai r e. Remot e mount i ng of power suppl y i s not al l owed.

k. Power suppl i es i n l umi nai r es mount ed under a cover ed st r uct ur e, such as a canopy, or wher e ot her wi se appr opr i at e shal l be UL l i s t ed wi t h a sound r at i ng of A.

SECTI ON 26 56 00 Page 10 l . Shal l be di mmabl e, and compat i bl e wi t h a st andar d di mmi ng cont r ol c i r cui t of 0 - 10V or ot her appr oved di mmi ng syst em.

m. Shal l be equi pped wi t h over - t emper at ur e pr ot ect i on c i r cui t t hat t ur ns l i ght sour ce of f unt i l nor mal oper at i ng t emper at ur e i s achi eved.

2. 1. 4 LED Lumi nai r e Sur ge Pr ot ect i on

Pr ovi de sur ge pr ot ect i on i nt egr al t o l umi nai r e t o meet C Low wavef or ms as def i ned by I EEE C62. 41. 2, Scenar i o 1, Locat i on Cat egor y C.

2. 2 EXTERI OR LUMI NAI RE CONTROLS

Cont r ol s shal l compl y wi t h Sect i on 9 of ASHRAE 90. 1 - I P, . Pr ovi de a cont r ol syst em i nt er f ace wi t hi n each l umi nai r e t hat i s compat i bl e wi t h t he ener gy management or cont r ol syst em used by t he ut i l i t y depar t ment i n char ge of t he pr oj ect ar ea f or cont r ol of s i t e l i ght i ng. Cont r ol of t he ext er i or l i ght i ng f i x t ur es shal l also capabl e of bei ng cont r ol l ed by be vi a connect i on t o t he exi st i ng base EMCs Syst em, v i a t he Bui l di ng Aut omat i on Syst em ( DDC) . Pr ovi de al l i nt er f aci ng devi ces ( r el ays, cont act or s, et c) r equi r ed t o i nt er f ace t o t he DDC Syst em. Cont r act or shal l al so be r equi r ed t o pr ovi de any pr ogr ammi ng and ot her modi f i cat i ons t o t he Bui l di ng DDC syst em r equi r ed t o i nt er f ace t o t he basewi de EMCS, t o al l ow t he r emot e cont r ol of t he ext er i or l i ght i ng f r om t he EMCS cent r al st at i on. See at t ached Bui l di ng Ext er i or Li ght i ng Det ai l and Cont r ol Sequence at t he end of t hi s speci f i cat i on sect i on f or addi t i onal requirements.

2. 2. 1 Photocell

UL 773 or UL 773A. Phot ocel l s shal l be her met i cal l y seal ed, s i l i con di ode l i ght sensor t ype, r at ed at wat t age r at i ng as r equi r ed, 277 vol t s, 50/ 60 Hz wi t h s i ngl e- pol e, s i ngl e or doubl e- t hr ow cont act s. Phot ocel l shal l be desi gned t o f ai l t o t he ON posi t i on. Housi ng shal l be const r uct ed of di e cast al umi num, r at ed t o oper at e wi t hi n a t emper at ur e r ange of mi nus 40 t o 158 degr ees F. Phot ocel l shal l have a 1/ 2 i n t hr eaded base f or mount i ng t o a j unct i on box or condui t . Pr ovi de f i xed base t ype housi ng. Phot ocel l shal l be t wi st - l ock r ecept acl e t ype conf or mi ng t o NEMA C136. 10. Pr ovi de wi t h sol i d br ass pr ongs and vol t age mar ki ngs and col or codi ng on ext er i or of housi ng. Phot ocel l shal l t ur n on at 1- 3 f oot candl es and t ur n of f at 3 t o 15 f oot candl es. A t i me del ay shal l pr event acci dent al swi t chi ng f r om t r ansi ent l i ght sour ces. Pr ovi de a di r ect i onal l ens i n f r ont of t he cel l t o pr event f i xed l i ght sour ces f r om cr eat i ng a t ur nof f condi t i on. Pr ovi de phot ocel l wi t h met al oxi de var i st or ( MOV) t ype sur ge pr ot ect i on. Phot ocel l shal l be of t ype sui t abl e f or i nst al l at i on wi t hh a l i ght i ng cont r ol syst em.

2. 2. 2 Li ght i ng Cont act or

NEMA I CS 2. Pr ovi de a el ect r i cal l y oper at ed mechani cal l y- hel d l i ght i ng cont act or housed i n a NEMA 4X encl osur e conf or mi ng t o NEMA I CS 6.

Cont act or shal l have 2 pol es, conf i gur ed as nor mal l y open NO. Cont act s shal l be r at ed 600 vol t s, 30 amper es f or a r esi st i ve l oad. Coi l oper at i ng vol t age shal l be 277 vol t s. Cont act or shal l have si l ver cadmi um oxi de doubl e- br eak cont act s and coi l c l ear i ng cont act s f or mechani cal l y hel d cont act or s and shal l r equi r e no ar ci ng cont act s. Pr ovi de cont act or wi t h hand- of f - aut omat i c sel ect or swi t ch. Pr ovi de cont act or as speci f i ed above al ong wi t h di sconnect swi t ch i n i nt egr al NEMA 4X encl osur e wi t h

SECTI ON 26 56 00 Page 11

09/21/18 2: 14 PM

e3endtk9 Highlight f l ange- mount ed handl e t o sat i sf y r equi r ement f or a " combi nat i on l i ght i ng cont act or " when speci f i ed.

2. 2. 3 Li ght i ng Cont r ol Rel ay Panel , i f r equi r ed.

Panel shal l consi st of a s i ngl e NEMA 4X sur f ace- mount ed or suppor t mount ed encl osur e wi t h t wo separ at e i nt er i or sect i ons; one f or Cl ass 1 ( br anch ci r cui t ) and one f or Cl ass 2 ( l ow vol t age) wi r i ng. Pr ovi de panel wi t h 32 r el ays. Panel shal l be desi gned as an aut omat ed cont r ol syst em i nt er f ace t ype. The Cl ass 1 sect i on shal l cont ai n t he l oad si de of al l r el ays and t he i ncomi ng br anch ci r cui t wi r i ng. The Cl ass 2 sect i on shal l cont ai n t he cont r ol power t r ansf or mer ( 24 vol t out put ) , r el ays, r el ay cont r ol modul es, and cont r ol wi r i ng, and nat i ve BACnet f i el d- pr ogr ammabl e appl i cat i on cont r ol l er f or panel s connect ed t o t he f aci l i t y aut omat ed cont r ol syst em.

Panel encl osur e shal l be const r uct ed of 14 gauge col d- r ol l ed st eel wi t h baked- on enamel f i ni sh. Panel shal l meet r equi r ement s of UL 916, ASHRAE 90. 1 - I P, CEC Ti t l e 24 and 47 CFR 15.

Rel ays shal l be 1- pol e, r at ed at 20 amper es 480 VAC wi t h r at ed l i f e of 120, 000 mechani cal oper at i ons mi ni mum.

Rel ay cont r ol modul e shal l be 24 vol t , el ect r oni c t ype and cont r ol up t o 16 4 separ at e r el ays ( 164 channel ) or pr ogr ammed gr oups of r el ays. Pr ovi de wi t h i nput s f or s i gnal s f r om devi ces such as phot ocel l s, t i mecl ocks, and mot i on sensor s. Rel ay cont r ol modul e wi t h i nt egr al t i mecl ock f unct i on shal l be 24 vol t , el ect r oni c t ype wi t h LCD di spl ay and cont r ol up t o 8 separ at e r el ays ( 8 channel ) .

2. 3 BRACKETS AND SUPPORTS

ANSI C136. 3, ANSI C136. 13, and ANSI C136. 21, as appl i cabl e. Pol e br acket s shal l be not l ess t han 1 1/ 4 i nch gal vani zed st eel pi pe or al umi num secur ed t o pol e. Sl i p- f i t t er or pi pe- t hr eaded br acket s may be used, but br acket s shal l be coor di nat ed t o l umi nai r es pr ovi ded, and br acket s f or use wi t h one t ype of l umi nai r e shal l be i dent i cal . Br acket s f or pol e- mount ed st r eet l i ght s shal l cor r ect l y posi t i on l umi nai r e no l ower t han mount i ng hei ght i ndi cat ed. Mount br acket s not l ess t han 24 f eet above st r eet .

Speci al mount i ngs or br acket s shal l be as i ndi cat ed and shal l be of met al whi ch wi l l not pr omot e gal vani c r eact i on wi t h l umi nai r e head.

2. 4 EQUI PMENT I DENTI FI CATI ON

2. 4. 1 Manuf act ur er ' s Namepl at e

Each i t em of equi pment shal l have a namepl at e bear i ng t he manuf act ur er ' s name, addr ess, model number , and ser i al number secur el y af f i xed i n a conspi cuous pl ace; t he namepl at e of t he di st r i but i ng agent wi l l not be acceptable.

2. 4. 2 Labels

Pr ovi de l abel ed l umi nai r es i n accor dance wi t h UL 1598 r equi r ement s.

Lumi nai r es shal l be c l ear l y mar ked f or oper at i on of speci f i c l i ght sour ces and bal l ast s accor di ng t o pr oper l i ght sour ce t ype. The f ol l owi ng l i ght sour ce char act er i st i cs shal l be not ed i n t he f or mat " Use Onl y _____" :

a. Cor r el at ed col or t emper at ur e ( CCT) and col or r ender i ng i ndex ( CRI ) f or al l l umi nai r es.

b. Wat t age and vol t age of l umi nai r e.

SECTI ON 26 56 00 Page 12

09/21/18 2: 14 PM

e3endtk9 Highlight

Mar ki ngs r el at ed t o l amp t ype shal l be c l ear and l ocat ed t o be r eadi l y v i s i bl e t o ser vi ce per sonnel , but unseen f r om nor mal v i ewi ng angl es when l amps ar e i n pl ace. Bal l ast s or dr i ver s shal l have cl ear mar ki ngs i ndi cat i ng mul t i - l evel out put s and i ndi cat e pr oper t er mi nal s f or t he var i ous out put s.

2. 5 FACTORY APPLI ED FI NI SH

El ect r i cal equi pment shal l have f act or y- appl i ed pai nt i ng syst ems whi ch shal l , as a mi ni mum, meet t he r equi r ement s of NEMA 250 cor r osi on- r esi st ance t est .

PART 3 EXECUTI ON

3. 1 INSTALLATION

El ect r i cal i nst al l at i ons shal l conf or m t o I EEE C2, NFPA 70, and t o t he r equi r ement s speci f i ed her ei n.

3. 1. 1 Phot ocel l Swi t ch Ai mi ng

Ai m swi t ch accor di ng t o manuf act ur er ' s r ecommendat i ons. Mount swi t ch on or besi de each l umi nai r e when swi t ch i s pr ovi ded i n cast weat her pr oof al umi num housi ng wi t h swi vel ar m.

3. 1. 2 GROUNDING

Gr ound noncur r ent - car r y i ng par t s of equi pment i ncl udi ng met al pol es, l umi nai r es, mount i ng ar ms, br acket s, and met al l i c encl osur es v i a an dr i v i en gr ound r od gr oudi ng el ect r ode and t o t he equi pment gr oundi ng conduct or i n t he br anch ci r cui t . Wher e copper gr oundi ng conduct or i s connect ed t o a met al ot her t han copper , pr ovi de speci al l y t r eat ed or l i ned connect or s sui t abl e f or t hi s pur pose.

3. 1. 3 FI ELD APPLI ED PAI NTI NG

Pai nt el ect r i cal equi pment as r equi r ed t o mat ch f i ni sh of adj acent sur f aces or t o meet t he i ndi cat ed or speci f i ed saf et y cr i t er i a.

3. 2 FI ELD QUALI TY CONTROL

Upon compl et i on of i nst al l at i on, ver i f y t hat equi pment i s pr oper l y i nst al l ed, connect ed, and adj ust ed. Conduct an oper at i ng t est af t er 100 hour s of bur n- i n t i me t o show t hat t he equi pment oper at es i n accor dance wi t h t he r equi r ement s of t hi s sect i on.

- - End of Sect i on - - f

SECTI ON 26 56 00 Page 13

SECTI ON 31 00 00

EARTHWORK

08/08

PART 1 GENERAL

1. 1 CRI TERI A FOR BI DDI NG

Base bi ds on t he f ol l owi ng cr i t er i a:

a. Sur f ace el evat i ons ar e as i ndi cat ed.

b. Pi pes or ot her ar t i f i c i al obst r uct i ons, except t hose i ndi cat ed, wi l l not be encount er ed.

c. Gr ound wat er el evat i ons i ndi cat ed by t he bor i ng l og wer e t hose exi st i ng at t he t i me subsur f ace i nvest i gat i ons wer e made and do not necessar i l y r epr esent gr ound wat er el evat i on at t he t i me of construction.

d. Mat er i al char act er i s i ndi cat ed by t he bor i ng l ogs.

1. 2 REFERENCES

The publ i cat i ons l i s t ed bel ow f or m a par t of t hi s speci f i cat i on t o t he ext ent r ef er enced. The publ i cat i ons ar e r ef er r ed t o wi t hi n t he t ext by t he basi c desi gnat i on onl y.

AMERI CAN ASSOCI ATI ON OF STATE HI GHWAY AND TRANSPORTATI ON OFFI CI ALS

(AASHTO)

AASHTO T 180 ( 2017) St andar d Met hod of Test f or Moi st ur e- Densi t y Rel at i ons of Soi l s Usi ng a 4. 54- kg ( 10- l b) Rammer and a 457- mm ( 18- i n. ) Dr op

AASHTO T 224 ( 2010) St andar d Met hod of Test f or Cor r ect i on f or Coar se Par t i c l es i n t he Soi l Compact i on Test

ASTM I NTERNATI ONAL ( ASTM)

ASTM C136/ C136M ( 2014) St andar d Test Met hod f or Si eve Anal ysi s of Fi ne and Coar se Aggr egat es

ASTM C33/ C33M ( 2016) St andar d Speci f i cat i on f or Concr et e Aggregates

ASTM D1140 ( 2017) St andar d Test Met hods f or Det er mi ni ng t he Amount of Mat er i al Fi ner t han 75- µm ( No. 200) Si eve i n Soi l s by Washing

ASTM D1556/ D1556M ( 2015; E 2016) St andar d Test Met hod f or Densi t y and Uni t Wei ght of Soi l i n Pl ace by Sand- Cone Met hod

SECTI ON 31 00 00 Page 1

09/21/18 1: 11 PM

ASTM D1557 ( 2012; E 2015) St andar d Test Met hods f or Labor at or y Compact i on Char act er i st i cs of Soi l Usi ng Modi f i ed Ef f or t ( 56, 000 f t - l bf / f t 3) ( 2700 kN- m/ m3)

ASTM D2487 ( 2011) Soi l s f or Engi neer i ng Pur poses ( Uni f i ed Soi l Cl assi f i cat i on Syst em)

ASTM D4318 ( 2017) St andar d Test Met hods f or Li qui d Li mi t , Pl ast i c Li mi t , and Pl ast i c i t y I ndex of Soi l s

ASTM D6938 ( 2017) St andar d Test Met hod f or I n- Pl ace Densi t y and Wat er Cont ent of Soi l and Soi l - Aggr egat e by Nucl ear Met hods ( Shal l ow Depth)

ASTM D698 ( 2012; E 2014; E 2015) Labor at or y Compact i on Char act er i st i cs of Soi l Usi ng St andar d Ef f or t ( 12, 400 f t - l bf / cu. f t .

( 600 kN- m/ cu. m. ) )

1. 3 DEFINITIONS

1. 3. 1 Sat i sf act or y Mat er i al s

Sat i sf act or y mat er i al s compr i se any mat er i al s c l assi f i ed by ASTM D2487 as GW, GP, SW, SP, SM, SW- SM, SP- SM. Sat i sf act or y mat er i al s f or gr adi ng compr i se st ones l ess t han 8 i nches, except f or f i l l mat er i al f or pavement s and r ai l r oads whi ch compr i se st ones l ess t han 3 i nches i n any di mensi on.

1. 3. 2 Unsat i sf act or y Mat er i al s

Mat er i al s whi ch do not compl y wi t h t he r equi r ement s f or sat i sf act or y mat er i al s ar e unsat i sf act or y. Unsat i sf act or y mat er i al s al so i ncl ude man- made f i l l s ; t r ash; r ef use; backf i l l s f r om pr evi ous const r uct i on; and mat er i al c l assi f i ed as sat i sf act or y whi ch cont ai ns r oot and ot her or gani c mat t er or f r ozen mat er i al . Not i f y t he Cont r act i ng Of f i cer when encount er i ng any cont ami nat ed mat er i al s.

1. 3. 3 Cohesi onl ess and Cohesi ve Mat er i al s

Cohesi onl ess mat er i al s i ncl ude mat er i al s c l assi f i ed i n ASTM D2487 as GW, GP, SW, and SP. Cohesi ve mat er i al s i ncl ude mat er i al s c l assi f i ed as GC, SC, ML, CL, MH, and CH. Mat er i al s c l assi f i ed as GM and SM wi l l be i dent i f i ed as cohesi onl ess onl y when t he f i nes ar e nonpl ast i c. Per f or m t est i ng, r equi r ed f or c l assi f y i ng mat er i al s, i n accor dance wi t h ASTM D4318, ASTM C136/ C136M and ASTM D1140.

1. 3. 4 Degr ee of Compact i on

Degr ee of compact i on r equi r ed, except as not ed i n t he second sent ence, i s expr essed as a per cent age of t he maxi mum densi t y obt ai ned by t he t est pr ocedur e pr esent ed i n ASTM D1557 abbr evi at ed as a per cent of l abor at or y maxi mum densi t y. Si nce ASTM D1557 appl i es onl y t o soi l s t hat have 30 per cent or l ess by wei ght of t hei r par t i c l es r et ai ned on t he 3/ 4 i nch si eve, expr ess t he degr ee of compact i on f or mat er i al havi ng mor e t han 30 per cent by wei ght of t hei r par t i c l es r et ai ned on t he 3/ 4 i nch si eve as a

SECTI ON 31 00 00 Page 2 per cent age of t he maxi mum densi t y i n accor dance wi t h AASHTO T 180 and cor r ect ed wi t h AASHTO T 224. To mai nt ai n t he same per cent age of coar se mat er i al , use t he " r emove and r epl ace" pr ocedur e as descr i bed i n NOTE 8 of Par agr aph 7. 2 i n AASHTO T 180.

1. 3. 5 Topsoil

Mat er i al sui t abl e f or t opsoi l s obt ai ned f r om Of f s i t e ar ea i s def i ned as:

Nat ur al , f r i abl e soi l r epr esent at i ve of pr oduct i ve, wel l - dr ai ned soi l s i n t he ar ea, f r ee of subsoi l , st umps, r ocks l ar ger t han one i nch di amet er , br ush, weeds, t oxi c subst ances, and ot her mat er i al det r i ment al t o pl ant gr owt h. Amend t opsoi l pH r ange t o obt ai n a pH of 5. 5 t o 7.

1. 3. 6 Unst abl e Mat er i al ( St r uct ur al Fi l l )

Unst abl e mat er i al s ar e t oo wet t o pr oper l y suppor t t he ut i l i t y pi pe, condui t , or appur t enant st r uct ur e.

1. 3. 7 Sel ect Gr anul ar Mat er i al

1. 3. 7. 1 Gener al Requi r ement s

Sel ect gr anul ar mat er i al ( St r uct ur al f i l l ) consi st of mat er i al s c l assi f i ed as GW, GP, SW, SP, by ASTM D2487 wher e i ndi cat ed. The l i qui d l i mi t of such mat er i al must not exceed 35 per cent when t est ed i n accor dance wi t h ASTM D4318. The pl ast i c i t y i ndex must not be gr eat er t han 12 per cent when t est ed i n accor dance wi t h ASTM D4318, and not mor e t han 10 per cent by wei ght may be f i ner t han No. 200 si eve when t est ed i n accor dance wi t h

ASTM D1140.

1. 4 SYSTEM DESCRI PTI ON

Subsur f ace soi l bor i ng l ogs ar e appended t o t he SPECI AL CONTRACT REQUI REMENTS. These dat a r epr esent t he best subsur f ace i nf or mat i on avai l abl e; however , var i at i ons may exi st i n t he subsur f ace bet ween bor i ng locations.

1. 4. 1 Cl assi f i cat i on of Excavat i on

No consi der at i on wi l l be gi ven t o t he nat ur e of t he mat er i al s, and al l excavat i on wi l l be desi gnat ed as uncl assi f i ed excavat i on.

1. 4. 2 Dewat er i ng Wor k Pl an

Submi t pr ocedur es f or accompl i shi ng dewat er i ng wor k.

1. 5 SUBMITTALS

Gover nment appr oval i s r equi r ed f or submi t t al s wi t h a " G" desi gnat i on;

submi t t al s not havi ng a " G" desi gnat i on ar e f or i nf or mat i on onl y. When used, a desi gnat i on f ol l owi ng t he " G" desi gnat i on i dent i f i es t he of f i ce t hat wi l l r evi ew t he submi t t al f or t he Gover nment . Submi t t al s wi t h an " S" ar e f or i ncl usi on i n t he Sust ai nabi l i t y eNot ebook, i n conf or mance t o Sect i on 01 33 29 SUSTAI NABI LI TY REPORTI NG. Submi t t he f ol l owi ng i n accor dance wi t h Sect i on 01 33 00 SUBMI TTAL PROCEDURES:

SD- 01 Pr econst r uct i on Submi t t al s

Shor i ng; G, RO

SECTI ON 31 00 00 Page 3

Dewat er i ng Wor k Pl an; G, RO

SD- 03 Pr oduct Dat a

Ut i l i zat i on of Excavat ed Mat er i al s; G, RO Openi ng of any Excavat i on or Bor r ow Pi t ; G, RO

SD- 06 Test Repor t s

Test i ng; G, RO

Bor r ow Si t e Test i ng; G, RO

Wi t hi n 24 hour s of concl usi on of physi cal t est s, submi t 2 copi es of t est r esul t s, i ncl udi ng cal i br at i on cur ves and r esul t s of cal i br at i on t est s.

SD- 07 Cer t i f i cat es

Test i ng; G, RO

PART 2 PRODUCTS

2. 1 REQUI REMENTS FOR OFFSI TE SOI LS

Test of f s i t e soi l s br ought i n f or use as backf i l l f or Tot al Pet r ol eum Hydr ocar bons ( TPH) , Benzene, Tol uene, Et hyl Benzene, and Xyl ene ( BTEX) and f ul l Toxi c i t y Char act er i st i c Leachi ng Pr ocedur e ( TCLP) i ncl udi ng i gni t abi l i t y , cor r osi v i t y and r eact i v i t y. Backf i l l shal l cont ai n a maxi mum of 100 par t s per mi l l i on ( ppm) of t ot al pet r ol eum hydr ocar bons ( TPH) and a maxi mum of 10 ppm of t he sum of Benzene, Tol uene, Et hyl Benzene, and Xyl ene ( BTEX) and shal l pass t he TCPL t est . Det er mi ne TPH concent r at i ons by usi ng EPA 600/ 4- 79/ 020 Met hod 418. 1. Det er mi ne BTEX concent r at i ons by usi ng EPA SW- 846. 3- 3 Met hod 5030/ 8020. Per f or m TCLP i n accor dance wi t h EPA SW- 846. 3- 3 Met hod 1311. Pr ovi de Bor r ow Si t e Test i ng f or TPH, BTEX and TCLP f r om a composi t e sampl e of mat er i al f r om t he bor r ow si t e, wi t h at l east one t est f r om each bor r ow si t e. Do not br i ng mat er i al onsi t e unt i l t est s have been appr oved by t he Cont r act i ng Of f i cer .

2. 2 BURI ED WARNI NG AND I DENTI FI CATI ON TAPE

Pr ovi de pol yet hyl ene pl ast i c war ni ng t ape manuf act ur ed speci f i cal l y f or war ni ng and i dent i f i cat i on of bur i ed ut i l i t y l i nes. Pr ovi de t ape on r ol l s, 3 i nches mi ni mum wi dt h, col or coded as speci f i ed bel ow f or t he i nt ended ut i l i t y wi t h war ni ng and i dent i f i cat i on i mpr i nt ed i n bol d bl ack l et t er s cont i nuousl y over t he ent i r e t ape l engt h. War ni ng and i dent i f i cat i on t o r ead, " CAUTI ON, BURI ED ( i nt ended ser vi ce) LI NE BELOW" or s i mi l ar wor di ng. Pr ovi de per manent col or and pr i nt i ng, unaf f ect ed by moi st ur e or soi l .

War ni ng Tape Col or Codes

Red Electric

Yellow Gas, Oi l ; Danger ous Mat er i al s

SECTI ON 31 00 00 Page 4

War ni ng Tape Col or Codes

Orange Tel ephone and Ot her Communi cat i ons

Blue Wat er Syst ems

Green Sewer Syst ems

White St eam Syst ems

Gray Compr essed Ai r

2. 3 Beddi ng Mat er i al

Pr ovi de beddi ng mat er i al consi st i ng of sand, gr avel , or cr ushed r ock, wel l gr aded, wi t h a maxi mum par t i c l e s i ze of 2 i nches. Compose mat er i al of t ough, dur abl e par t i c l es. Al l ow f i nes passi ng t he No. 200 st andar d s i eve wi t h a pl ast i c i t y i ndex l ess t han si x.

2. 4 CAPI LLARY WATER BARRI ER

Pr ovi de capi l l ar y wat er bar r i er of c l ean, poor l y gr aded cr ushed r ock, cr ushed gr avel , or uncr ushed gr avel pl aced beneat h a bui l di ng s l ab.

Conf or m t o ASTM C33/ C33M f or f i ne aggr egat e gr adi ng wi t h a maxi mum of 3 per cent by wei ght passi ng ASTM D1140, No. 200 si eve.

PART 3 EXECUTI ON

3. 1 STRI PPI NG OF TOPSOI L

Wher e i ndi cat ed or di r ect ed, st r i p t opsoi l t o a dept h of 4 i nches. Spr ead t opsoi l on ar eas al r eady gr aded and pr epar ed f or t opsoi l , or t r anspor t ed and deposi t ed i n st ockpi l es conveni ent t o ar eas t hat ar e t o r ecei ve appl i cat i on of t he t opsoi l l at er , or at l ocat i ons i ndi cat ed or speci f i ed.

Keep t opsoi l separ at e f r om ot her excavat ed mat er i al s, br ush, l i t t er , obj ect i onabl e weeds, r oot s, st ones l ar ger t han 2 i nches i n di amet er , and ot her mat er i al s t hat woul d i nt er f er e wi t h pl ant i ng and mai nt enance oper at i ons. Remove f r om t he si t e any sur pl us of t opsoi l f r om excavat i ons and gr adi ngs.

3. 2 GENERAL EXCAVATI ON

Per f or m excavat i on of ever y t ype of mat er i al encount er ed wi t hi n t he l i mi t s of t he pr oj ect t o t he l i nes, gr ades, and el evat i ons i ndi cat ed and as speci f i ed. Per f or m t he gr adi ng i n accor dance wi t h t he t ypi cal sect i ons shown and t he t ol er ances speci f i ed i n par agr aph FI NI SHI NG. Tr anspor t sat i sf act or y excavat ed mat er i al s and pl ace i n f i l l wi t hi n t he l i mi t s of t he wor k. Excavat e unsat i sf act or y mat er i al s encount er ed wi t hi n t he l i mi t s of t he wor k bel ow gr ade and r epl ace wi t h sat i sf act or y mat er i al s as di r ect ed. I ncl ude such excavat ed mat er i al and t he sat i sf act or y mat er i al or der ed as r epl acement i n excavat i on. Di spose sur pl us sat i sf act or y excavat ed mat er i al not r equi r ed f or f i l l i n ar eas appr oved f or sur pl us mat er i al st or age or desi gnat ed wast e ar eas. Di spose unsat i sf act or y excavat ed mat er i al i n desi gnat ed wast e or spoi l ar eas. Dur i ng const r uct i on, per f or m excavat i on and f i l l i n a manner and sequence t hat wi l l pr ovi de pr oper dr ai nage at al l t i mes. Excavat e mat er i al r equi r ed f or

SECTI ON 31 00 00 Page 5 f i l l or embankment i n excess of t hat pr oduced by excavat i on wi t hi n t he gr adi ng l i mi t s f r om t he bor r ow ar eas i ndi cat ed or f r om ot her appr oved ar eas sel ect ed by t he Cont r act or as speci f i ed.

3. 2. 1 Dr ai nage St r uct ur es

Make excavat i ons t o t he l i nes, gr ades, and el evat i ons shown, or as di r ect ed. Pr ovi de t r enches and f oundat i on pi t s of suf f i c i ent s i ze t o per mi t t he pl acement and r emoval of f or ms f or t he f ul l l engt h and wi dt h of st r uct ur e f oot i ngs and f oundat i ons as shown. Do not di st ur b t he bot t om of t he excavat i on when concr et e or masonr y i s t o be pl aced i n an excavat ed ar ea. Do not excavat e t o t he f i nal gr ade l evel unt i l j ust bef or e t he concr et e or masonr y i s t o be pl aced.

3. 2. 2 Drainage

Pr ovi de f or t he col l ect i on and di sposal of sur f ace and subsur f ace wat er encount er ed dur i ng const r uct i on. Compl et el y dr ai n const r uct i on s i t e dur i ng per i ods of const r uct i on t o keep soi l mat er i al s suf f i c i ent l y dr y.

Const r uct st or m dr ai nage f eat ur es at t he ear l i est st ages of s i t e devel opment , and t hr oughout const r uct i on gr ade t he const r uct i on ar ea t o pr ovi de posi t i ve sur f ace wat er r unof f away f r om t he const r uct i on act i v i t y or pr ovi de t empor ar y di t ches, swal es, and ot her dr ai nage f eat ur es and equi pment as r equi r ed t o mai nt ai n dr y soi l s. When unsui t abl e wor ki ng pl at f or ms f or equi pment oper at i on and unsui t abl e soi l suppor t f or subsequent const r uct i on f eat ur es devel op, r emove unsui t abl e mat er i al and pr ovi de new soi l mat er i al as speci f i ed her ei n. I t i s t he r esponsi bi l i t y of t he Cont r act or t o assess t he soi l and gr ound wat er condi t i ons pr esent ed by t he pl ans and speci f i cat i ons and t o empl oy necessar y measur es t o per mi t const r uct i on t o pr oceed.

3. 2. 3 Dewatering

Cont r ol gr oundwat er f l owi ng t owar d or i nt o excavat i ons t o pr event s l oughi ng of excavat i on s l opes and wal l s, boi l s, upl i f t and heave i n t he excavat i on and t o el i mi nat e i nt er f er ence wi t h or der l y pr ogr ess of const r uct i on. Do not per mi t Fr ench dr ai ns, sumps, di t ches or t r enches wi t hi n 3 f eet of t he f oundat i on of any st r uct ur e, except wi t h speci f i c wr i t t en appr oval , and af t er speci f i c cont r act ual pr ovi s i ons f or r est or at i on of t he f oundat i on ar ea have been made. Take cont r ol measur es by t he t i me t he excavat i on r eaches t he wat er l evel i n or der t o mai nt ai n t he i nt egr i t y of t he i n s i t u mat er i al . Whi l e t he excavat i on i s open, mai nt ai n t he wat er l evel cont i nuousl y, at l east 2 f eet bel ow t he wor ki ng l evel . Oper at e dewat er i ng syst em cont i nuousl y unt i l const r uct i on wor k bel ow exi st i ng wat er l evel s i s compl et e. Submi t per f or mance r ecor ds weekly.

3. 2. 4 Tr ench Excavat i on Requi r ement s

Excavat e t he t r ench as r ecommended by t he manuf act ur er of t he pi pe t o be i nst al l ed. Sl ope t r ench wal l s bel ow t he t op of t he pi pe, or make ver t i cal , and of such wi dt h as r ecommended i n t he manuf act ur er ' s pr i nt ed i nst al l at i on manual . Pr ovi de ver t i cal t r ench wal l s wher e no manuf act ur er ' s pr i nt ed i nst al l at i on manual i s avai l abl e. Shor e t r ench wal l s mor e t han 2 f eet hi gh, or as r equi r ed by OSHA excavat i on r egul at i ons or cut back t o a st abl e s l ope, or pr ovi de wi t h equi val ent means of pr ot ect i on f or empl oyees who may be exposed t o movi ng gr ound or cave i n.

Excavat e t r ench wal l s whi ch ar e cut back t o at l east t he angl e of r epose of t he soi l . Gi ve speci al at t ent i on t o s l opes whi ch may be adver sel y

SECTI ON 31 00 00 Page 6 af f ect ed by weat her or moi st ur e cont ent .