APPENDIX

B

Pump Data

Appendix B Page 1 of 3

The Grundfos PIP series vortex pumps are designed for pumping water or sewage in non-hazardous applications where explosion-proof motors are not required. The all cast iron construction of the pump makes it extremely durable against corrosion. The pumps vortex impeller allows it to pass up to 2 inch solids and can handle stringy trash without clogging the impeller.

Commercial Sump, Sewage & Effluent Pumps

GRUNDFOS PIP

Discharge 2” NPT, Vertical, Bolt-on Flange

Liquid Temperature 104°F (40° C) Intermittent

Motor Housing Cast Iron ASTM A-48, Class 30

Volute Cast Iron ASTM A-48, Class 30

Seal Plate Cast Iron ASTM A-48, Class 30

Impeller Design Vortex, Open with Pump Out

Vanes on Back Side. Dynamically Balanced, ISO G6.3

Impeller Material 85-5-5-5 Cast Iron

Shaft 416 Stainless Steel

Square Rings Buna-N

Hardware 300 Series Stainless Steel

Paint Air Dry Enamel, Top Coat

Seal Design Single Mechanical, or Tandem

Mechanical with Oil Filled Reservoir

Seal Material

Rotating Faces - Carbon

Stationary Faces - Ceramic

Elastomer - Buna-N

Hardware - 300 Series Stainless Steel

Cord Entry 2” NPT - 20 FT. (6.1m)

Custom Molded for Sealing and Strain Relief

Speed 3450 RPM, 60Hz (Nominal)

Upper Bearing Design Single Row, Ball, Oil Lubricated

Upper Bearing Load Radial

Lower Bearing Design Single Row, Ball, Oil Lubricated

Lower Bearing Load Radial & Thrust

Motor Design

NEMA L, Single Phase, NEMA B, Three Phase Torque Curve, Oil Filled Squirrel Cage Induction

Motor Insulation Class B Class F on Selected Models

Single Phase Permanent Split Capacitor (PSC)

Three Phase

200-240/480 is Tri-Voltage Motor.

600V Requires Overload Protection to be Included in

Control Panel

PUMP SPECIFICATIONS

GRUNDFOS PIP 1-1/2 HP to 2 HP

Appendix B Page 2 of 3

Grundfos 2001 Butterfield Rd, Ste 1700 Downers Grove, IL 60515

Th e na m e G ru nd fo s, th e

G ru nd fo s l og o, a nd b e th in k in no va te a re re gi st er ed tr ad em ar ks o w ne d by G ru nd fo s H ol di ng A

/S o r G ru nd fo s A /S

, D en m ar k.

A ll rig ht s r es er ve d w or ld w id e.

L- G

P-

SL

-0

R ev

. 0 1-www.grundfos.us www.grundfos.ca www.grundfos.mx inches (mm)

PIPXXX-L SERIES

Plugs for 120 Volt and .5Hp, 240 Volt Single Phase Models.

PUMP MODEL NO.

PUMP SERIAL NO.

IMPORTANT !

1.) Pump may be operated “dry” for extended periods without damage to motor and/or seals.

2.) This pump is appropriate for those applications specified as class I division II hazardous locations.

3.) This pump is not appropriate for those applications specified as class I division i hazardous locations.

4.) Installations such as decorative fountains or water features provided for visual enjoyment must be installed in accordance with the national electric code ANSI/NFPA 70 and/or the authority having jurisdiction.

This pump is not intended for use in swimming pools, recreational water parks, or installations in which human contact with pumped media is a common occurrence.

Winding Resistance ± 5%, measured from terminal block. Pump rated for operation at ± 10% voltage at motor.

Optional - Moisture sensor cord for DS models is 18/5 SOW, 0.47 ± .02 O.D.

Optional - Temperature sensor cord for 3 phase models is 14/3 SOW, 0.53 ± .02 O.D.

Optional - Moisture & Temperature sensor cord for 3 phase DS models is 18/5 SOW, 0.47 ± .02 O.D.

GRUNDFOS PIP Technical Data – 1-1/2 HP to 2 HP

MODEL HP VOLT PH/Hz RPM (Nom)

NEMA

START

CODE

INSUL.

CLASS

FULL

LOAD

AMPS

LOCKED

ROTOR

AMPS

CORD

SIZE

CODE

TYPE

CORD O.D.

± .02 (.5) in

(mm)

WINDING

RESISTANCE

MAIN -- START

PIP1522L 1.5 240 1/60 3450 A F 13.5 31.5 12/3 SOW 0.61 (15.5) 2.15 -- 12.49

PIP1592L 1.5 200/240 3/60 3450 C F 10.8/9.8 27 14/4 SOW 0.60 (15.2) 4.22

PIP1542L 1.5 480 3/60 3450 F F 4.9 13.5 14/4 SOW 0.60 (15.2) 17.0

PIP1552L 1.5 600 3/60 3450 F B 3.9 11 14/4 SOW 0.60 (15.2) 22.2

PIP2022L 2 240 1/60 3450 C F 16 42 12/3 SOW 0.61 (15.5) 1.26 -- 55.34

PIP2092L 2 200/240 3/60 3450 J F 13.2/12 30 14/4 SOW 0.60 (15.2) 3.08

PIP2042L 2 480 3/60 3450 J F 6 15 14/4 SOW 0.60 (15.2) 12.30

PIP2052L 2 600 3/60 3450 J B 4.8 12 14/4 SOW 0.60 (15.2) 19.70

Appendix B Page 3 of 3 rmiller Highlight