Fort_Peck_Transformer_Supply_Drawings_2016.pdf

PDF 27 MB Posted

Attached to
Supply Transformers Federal contract opportunity
Solicitation number
W9128F-16-T-0001
Issued by
Department of the Army Corps of Engineers Engineering District Omaha

About this file

Fort Peck Transformer drawings 2016

View the file

Other files for this federal contract opportunity

Other files attached to Supply Transformers, newest first.
File Type Posted
SPS_Amd_0005.pdf PDF
SPS_Amd_0004.pdf PDF
Amd_0004_Specs.pdf PDF
SPS_Amd_0003.pdf PDF
Amd_0003_Combined.pdf PDF
AMD002.pdf PDF
Amendment_1.pdf PDF
Approved_Solicitation.pdf PDF
PPQ.pdf PDF
Fort_Peck_GSU_Station_Service_Transformer_Specs.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

A E C

O N

T R

A C

T O

R I

D

F P

P -5 .3

-0 -0 /2

U .S

A R

M Y C

O R

P S O

F E

N G

IN

E E

R S

P O

R T

L A

N D

O R

E G

O N

H Y

D R

O E

L E

C T

R

IC

D

E S

IG

N C

E N

T E

R

U .S

A R

M Y C

O R

P S O

F E

N G

IN

E E

R S

O M

A H

A

N E

B R

A S

K A

O M

A H

A D

IS

T R

IC

T

OMAHA DISTRICT

S

E V

E N R

M

IL

E S ,P .E

F P

P .3

G

X X

X .d g n

G

H D

C D

D F

D F

IL

R

IN

D E

X T

O D

R A

W

IN

G

G-002

A

N S

F O

R M

E R S

U P

P L

Y

M

IS

S O

U R I

R

IV

E R

W F -1

-T -0

F O

R T P

E C

K D

A M

A N

S I

D

G

H D

C B J B

/0

/2

INDEX TO DRAWINGS

CONTRACT DRAWINGS

GENERAL

ELECTRICAL

FOR INFORMATION ONLY

MECHANICAL

TITLE TITLE

MFP-OPN93E111.1

MFP-OPN93E109.1

MFP-OPN93E106.1

MFP-OPN93E103.6

SWITCHYARD 1, SECTIONS 9 & 10

SWITCHYARD 1, SECTIONS 6 & 7

SWITCHYARD 1, SECTIONS 1 & 2

SWITCHYARD 1, LOWER LEVEL BUSSES

IDENTIFICATION

SHEET

G-008

G-007

G-006

G-005

G-004

G-003

G-002

G-001

M-201

M-101

25,000 / 33,333 KVA GSU TRANS. (OPTIONAL), FALL PROTECTION SYSTEM DETAILS

60,000 / 80,000 KVA GSU TRANSFORMER, FALL PROTECTION SYSTEM DETAILS

3,000 KVA STATION SERVICE TRANSFORMER REQUIREMENTS SUMMARY SHEET

25,000 / 33,333 KVA GSU TRANS. (OPTIONAL), REQUIREMENTS SUMMARY SHEET

60,000 / 80,000 KVA GSU TRANSFORMER, REQUIREMENTS SUMMARY SHEET

SWITCHYARD NO. 2 SITE PLAN AND STATION SERVICE TRANSFORMER DELIVERY LOCATION

SWITCHYARD NO. 1 SITE PLAN AND TRANSFORMER DELIVERY LOCATION

FORT PECK DAM VICINITY MAP

INDEX TO DRAWINGS

COVER PAGE, PROJECT LOCATION AND VICINITY MAPS

E-307

E-306

E-305

E-304

E-303

E-302

E-301

E-208

E-207

E-206

E-205

E-204

E-203

E-202

E-201

E-109

E-108

E-107

E-106

E-105

E-104

E-103

E-102

E-101

3,000 KVA STATION SERVICE TRANS., CONTROL CABINET EXTERNAL CONNECTIONS

3,000 KVA STATION SERVICE TRANS., 125 VDC CONTROLS AND ANNUNCIATION

3,000 KVA STATION SERVICE TRANS., 120 VAC CONTROLS SCHEMATIC

3,000 KVA STATION SERVICE TRANS., CONTROL CABINET LAYOUT

3,000 KVA STATION SERVICE TRANS., CONTROL CABINET

3,000 KVA STATION SERVICE TRANS., LAYOUT SHEET 2

3,000 KVA STATION SERVICE TRANS., LAYOUT SHEET 1

25,000 / 33,333 KVA GSU TRANS. (OPTIONAL), CONTROL AND POWER CABINETS EXT. CONNECTIONS

25,000 / 33,333 KVA GSU TRANS. (OPTIONAL), ELECTRONIC TEMPERATURE MONITOR CONNECTIONS

25,000 / 33,333 KVA GSU TRANS. (OPTIONAL), CONTROL CABINET 125VDC CONTROL,ANNUNCIATION

25,000 / 33,333 KVA GSU TRANS. (OPTIONAL), 240VAC COOLING POWER, 120 VAC CONTROL SCHEM.

25,000 / 33,333 KVA GSU TRANS. (OPTIONAL), 240VAC POWER CABINET LAYOUT

25,000 / 33,333 KVA GSU TRANS. (OPTIONAL), CONTROL CABINET LAYOUT

25,000 / 33,333 KVA GSU TRANS. (OPTIONAL), POWER AND CONTROL CABINETS

25,000 / 33,333 KVA GSU TRANS. (OPTIONAL), LAYOUT AND LIMITING DIMENSIONS

GSU TRANSFORMERS, MISCELLANEOUS DETAILS

60,000 / 80,000 KVA GSU TRANSFORMER, CONTROL AND POWER CABINETS EXT. CONNECTIONS

60,000 / 80,000 KVA GSU TRANSFORMER, ELECTRONIC TEMPERATURE MONITOR CONNECTIONS

60,000 / 80,000 KVA GSU TRANSFORMER, CONTROL CABINET 125VDC CONTROL, ANNUNCIATION

60,000 / 80,000 KVA GSU TRANSFORMER, 240VAC COOLING POWER, 120 VAC CONTROL SCHEM.

60,000 / 80,000 KVA GSU TRANSFORMER, 240VAC POWER CABINET LAYOUT

60,000 / 80,000 KVA GSU TRANSFORMER, CONTROL CABINET LAYOUT

60,000 / 80,000 KVA GSU TRANSFORMER, POWER AND CONTROL CABINETS

60,000 / 80,000 KVA GSU TRANSFORMER, LAYOUT AND LIMITING DIMENSIONS

DRAWING FILE NUMBER

FPP-5.301-0-0/8

FPP-5.301-0-0/7

FPP-5.301-0-0/6

FPP-5.301-0-0/5

FPP-5.301-0-0/4

FPP-5.301-0-0/3

FPP-5.301-0-0/2

FPP-5.301-0-0/1

FPP-5.301-6-01A/24

FPP-5.301-6-01A/23

FPP-5.301-6-01A/22

FPP-5.301-6-01A/21

FPP-5.301-6-01A/20

FPP-5.301-6-01A/19

FPP-5.301-6-01A/18

FPP-5.301-6-01A/17

FPP-5.301-6-01A/16

FPP-5.301-6-01A/15

FPP-5.301-6-01A/14

FPP-5.301-6-01A/13

FPP-5.301-6-01A/12

FPP-5.301-6-01A/11

FPP-5.301-6-01A/10

FPP-5.301-6-01A/9

FPP-5.301-6-01A/8

FPP-5.301-6-01A/7

FPP-5.301-6-01A/6

FPP-5.301-6-01A/5

FPP-5.301-6-01A/4

FPP-5.301-6-01A/3

FPP-5.301-6-01A/2

FPP-5.301-6-01A/1

FPP-5.301-3-0/2

FPP-5.301-3-0/1

DRAWING FILE NUMBER

S O

L

IC

IT

A T

IO

N N

O

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

T

IO

N M

A R

K

S

IZ

E

S U

B M

IT

T E

D B

Y

P L

O T S

C A

L E

IDENTIFICATION

SHEET

D A

T E

A P

P R

D R

A W

IN

G N

U M

B E

R of Engineers

US Army Corps

P L

O T D

A T

E

54321

D

C

B

A

/8 /2

DRAWING PLOT SIZE: ANSI D DATE AND TIME PLOTTED: 2/8/2016 10:15:39 AM BY USERNAME: g2hdcevh SHEET NAME: G-002

D E

S

IG

N F

IL

E n w d \n w p \E

T D

S \C

A D

D -W o rk s p a c e s \N

W P \W o rk

S p a c e \p ro je c ts \L o c a l R e s o u rc e

C O

N T

R A

C T N

O

F

IL

E N

A M

E

D A

T

NOTES:

SWITCHYARD NO. 2, TO THE LOCATION INDICATED ON SHEET G-005.

THE OTHER STATION SERVICE TRANSFORMER SHALL BE DELIVERED TO3.

ENGINEER.

SUPERVISION OF THE TRANSFORMER MANUFACTURER'S ERECTING

FORMERS AND PLACE THEM ON THE MOUNTING PADS UNDER THE

THE SEPARATE INSTALLATIONS CONTRACTOR WILL MOVE THE TRANS-

TRANSFORMER'S PERMANENT OPERATING LOCATION IS MADE AVAILABLE,

AVAILABLE BY THE SEPARATE INSTALLATIONS CONTRACTOR. AS EACH

SUCH TIME THAT THEIR PERMANENT OPERATING LOCATIONS ARE MADE

TRANSFORMERS WILL BE TEMPORARILY STORED IN THIS LOCATION UNTIL

TEMPORARY STORAGE LOCATION AND PLACED ON CRIBBING. THE

STATION SERVICE TRANSFORMER SHALL BE DELIVERED TO THE INDICATED

THE OPTIONAL 25,000/33,333 KVA GSU TRANSFORMER AND ONE 3,000 KVA2.

AVAILABLE BY THE SEPARATE INSTALLATIONS CONTRACTOR.

OFF-LOADED TO ITS PERMANENT OPERATING LOCATION, AS MADE

THE 60,000/80,000 KVA GSU TRANSFORMER SHALL BE DELIVERED AND1.

A E C

O N

T R

A C

T O

R I

D

F P

P -5 .3

-0 -0 /4

U .S

A R

M Y C

O R

P S O

F E

N G

IN

E E

R S

P O

R T

L A

N D

O R

E G

O N

H Y

D R

O E

L E

C T

R

IC

D

E S

IG

N C

E N

T E

R

U .S

A R

M Y C

O R

P S O

F E

N G

IN

E E

R S

O M

A H

A

N E

B R

A S

K A

O M

A H

A D

IS

T R

IC

E V

E N R

M

IL

E S ,P .E

F P

P .3

G

X X

X .d g n

G

H D

C D

D F

D F

IL

E R

D E

L

IV

E R

Y L

O C

A T

IO

N S

IT

E P

L A

N A

N D T

R A

N S

F O

R M

E R

S W

IT

C H

Y A

R D N

O

G-004

A

N S

F O

R M

E R S

U P

P L

Y

M

IS

S O

U R I

R

IV

E R

W F -1

-T -0

R T P

E C

K D

A M

A N

S I

D

G

H D

C B J B

/0

/2

TRANSFORMER DELIVERY / STORAGE LOCATION

SWITCHYARD 1 SITE PLAN AND

SEE NOTE 2

S O

L

IC

IT

A T

IO

N N

O

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

T

IO

N M

A R

K

S

IZ

E

S U

B M

IT

T E

D B

Y

P L

O T S

C A

L E

IDENTIFICATION

SHEET

D A

T E

A P

P R

D R

A W

IN

G N

U M

B E

R of Engineers

US Army Corps

P L

O T D

A T

E

54321

D

C

B

A

/8 /2

DRAWING PLOT SIZE: ANSI D DATE AND TIME PLOTTED: 2/8/2016 10:27:50 AM BY USERNAME: g2hdcevh SHEET NAME: G-004

D E

S

IG

N F

IL

E n w d \n w p \E

T D

S \C

A D

D -W o rk s p a c e s \N

W P \W o rk

S p a c e \p ro je c ts \L o c a l R e s o u rc e

C O

N T

R A

C T N

O

F

IL

E N

A M

E

D A

T

INDICATED ON SHEET G-004.

DELIVERED TO SWITCHYARD NO. 1, O THE LOCATION

THE OTHER STATION SERVICE TRANSFORMER SHALL BE2.

ERECTING ENGINEER.

THE SUPERVISION OF THE TRANSFORMER MANUFACTURER'S

TRANSFORMER AND PLACE ITON THE MOUNTING PAD UNDER

SEPARATE INSTALLATIONS CONTRACTOR WILL MOVE THE

PERMANENT OPERATING LOCATION IS MADE AVAILABLE, THE

INSTALLATIONS CONTRACTOR. WHEN THE TRANSFORMER'S

OPERATING LOCATION IS MADE AVAILABLE BY THE SEPARATE

LOCATION UNTIL SUCH TIME THAT THE PERMANENT

TRANSFORMER WILL BE TEMPORARILY STORED IN THIS

SWITCHYARD NO. 2, AND PLACED PLACED ON CRIBBING. THE

SHALL BE DELIVERED TO THE INDICATED LOCATION IN

ONE OF THE 3,000 KVA STATION SERVICE TRANSFORMERS1.

A E C

O N

T R

A C

T O

R I

D

/0

/2

F P

P -5 .3

-0 -0 /5

U .S

A R

M Y C

O R

P S O

F E

N G

IN

E E

R S

P O

R T

L A

N D

O R

E G

O N

H Y

D R

O E

L E

C T

R

IC

D

E S

IG

N C

E N

T E

R

U .S

A R

M Y C

O R

P S O

F E

N G

IN

E E

R S

O M

A H

A

N E

B R

A S

K A

O M

A H

A D

IS

T R

IC

E V

E N R

M

IL

E S ,P .E

F P

P .3

G

X X

X .d g n

G

H D

C D

D F

D F

IL

E R

T R

A N

S F

O R

M E

R D

E L

IV

E R

Y L

O C

A T

IO

N S

IT

E P

L A

N A

N D S

T A

T

IO

N S

E R

V

IC

E

S W

IT

C H

Y A

R D N

O

G-005

A

N S

F O

R M

E R S

U P

P L

Y

M

IS

S O

U R I

R

IV

E R

W F -1

-T -0

R T P

E C

K D

A M

A N

S I

D

G

H D

C B J B

TRANSFORMER DELIVERY / STORAGE LOCATION

SWITCHYARD 2 SITE PLAN AND STATION SERVICE

SEE NOTE 1

S O

L

IC

IT

A T

IO

N N

O

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

T

IO

N M

A R

K

S

IZ

E

S U

B M

IT

T E

D B

Y

P L

O T S

C A

L E

IDENTIFICATION

SHEET

D A

T E

A P

P R

D R

A W

IN

G N

U M

B E

R of Engineers

US Army Corps

P L

O T D

A T

E

54321

D

C

B

A

/8 /2

DRAWING PLOT SIZE: ANSI D DATE AND TIME PLOTTED: 2/8/2016 10:06:26 AM BY USERNAME: g2hdcevh SHEET NAME: G-005

D E

S

IG

N F

IL

E n w d \n w p \E

T D

S \C

A D

D -W o rk s p a c e s \N

W P \W o rk

S p a c e \p ro je c ts \L o c a l R e s o u rc e

C O

N T

R A

C T N

O

F

IL

E N

A M

E

D A

T

C

O N

T R

A C

T O

R I

D

/0

/2

F P

P -5 .3

-0 -0 /6

U .S

A R

M Y C

O R

P S O

F E

N G

IN

E E

R S

P O

R T

L A

N D

O R

E G

O N

H Y

D R

O E

L E

C T

R

IC

D

E S

IG

N C

E N

T E

R

U .S

A R

M Y C

O R

P S O

F E

N G

IN

E E

R S

O M

A H

A

N E

B R

A S

K A

O M

A H

A D

IS

T R

IC

E V

E N R

M

IL

E S ,P .E

F P

P .3

G

X X

X .d g n

G

H D

C D

D F

D F

IL

Q

U

IR

E M

E N

T S S

U M

M A

R Y S

H E

E T

,0

,0

K

V A G

S U T

R A

N S

F O

R M

E

G-006

A

N S

F O

R M

E R S

U P

P L

Y

M

IS

S O

U R I

R

IV

E R

W F -1

-T -0

R T P

E C

K D

A M

A N

S I

D

G

H D

C B J B

(REFERENCE SPECIFICATION SECTION 48 19 23.04)

NAMEPLATE DATA:

TANK AND CONSTRUCTION:

ACCESSORIES:

BUSHINGS:

SURGE ARRESTERS:

INSULATING OIL:

∙ Napthenic base - ASTM D 3487 Type II; 0.3% by mass of oxidation inhibitor

SEPARATE CONTROL AND POWER CABINETS:

SPARE PARTS:

FACTORY ASSEMBLY AND PAINT:

(4) Completely assembled and witnessing of factory acceptance tests

(3) Completed core/coil assembly, but prior to tanking

(2) After completion of windings but prior to landing on core

(1) Design Review Meeting

∙ INSPECTIONS: Government inspections performed during to oil filling.

∙ INTERIOR PAINT: Primer coat, oil-resistant finish coat - White. Allow to cure for one week prior to receive a non-slip coating.

gloss. Corrosion resistant surfaces, and stainless steel cabinets, shall remain unpainted. Cover

∙ EXTERIOR PAINT: Primer coat, epoxy base coat, polyurethane top coat - Munsell 5BG 7/0.4 high-of reassembly.

∙ ASSEMBLY: Transformer to be fully assembled, with removable components match-marked for ease

FACTORY ACCEPTANCE TESTS (F.A.T.):

∙ FREQUENCY: 60 Hz

∙ MAXIMUM LOAD LOSSES: 150 kW

∙ MAXIMUM NO-LOAD LOSSES: 45 kW

∙ MAXIMUM SOUND LEVEL (ONAF): 68 dB

∙ OIL PRESERVATION SYSTEM: Constant Oil Pressure System (COPS) tank

∙ TEMPERATURE RISE: 65 ºC

∙ SECONDARY WINDING (H) DETC: 5 taps; 2 @ +2.5%, 2 @ -2.5%

∙ IMPEDANCE: 8.0% (H-X)

∙ PHASING: Three-Phase

∙ BIL LEVELS, kV: 550 (H) / 110 (X) / 150 (H0)

∙ VOLTAGE RATINGS: 115,000 GrdY (H) - 13,800 Delta (X)

∙ KVA RATING: 60,000 / 80,000

∙ COOLING CLASS: ONAN/ONAF

∙ TYPE: Class II GSU Power Transformer

∙ SFRA TEST SHIPPING BUSHING: 2.5 kV Class, 45 kV BIL, 100 Amp

∙ CORE GROUNDS: 2.5 kV Class, 45 kV BIL, 100 Amp relaying accuracy) impregnated paper condenser core (One 200:5 CT, 0.3B-1.8 metering accuracy, C400

∙ NEUTRAL (H0): 34.5 kV Class, 200 kV BIL, 800 Amp, composite exterior with resin-relaying accuracy) temperature rise rating (One 4,000:5 MRCT, 0.3B-1.8 metering accuracy, C400

∙ PRIMARY WINDING (X): 25 kV Class, 150 kV BIL, 4,000 Amp, light contamination, 125 ºC accuracy, C400 relaying accuracy) resin-impregnated paper condenser core (Two 600:5 MRCT, 0.3B-1.8 metering

∙ SECONDARY WINDING (H): 138 kV Class, 650 kV BIL, 800 Amp, composite exterior with

∙ Analog temperature gage functional verification

∙ Bushing current transformer routine tests power factor tests during transformer F.A.T.

∙ Each high-voltage and high-voltage neutral bushing shall undergo capacitance and

∙ All electrical and electo-mechanical devices shall be functionally tested

∙ De-energized tap changer mechanical operational test (5 complete cycles)

- One SFRA test to be performed with the transformer in the shipping configuration

- One SFRA test to be performed with the transformer fully assembled and oil filled

- Cable integrity test required

∙ Sweep Frequency Response Analysis (with electronic data files)

∙ Leakage reactance (with electronic data files)

One hour level: 300 pC

∙ Induced voltage test acceptance criteria: 7,200 cycle enhancement level: 500 pC;

∙ Audible sound level tests

∙ Lightning impulse tests

∙ Temperature rise tests shall be performed at each cooling stage

∙ All 'Routine' tests (IEEE C57.12.00, Table 18)

REQUIREMENTS SUMMARY SHEET

FORT PECK DAM 60,000 / 80,000 KVA GSU TRANSFORMER

∙ (Qty 1): Fuse of each type and rating

∙ (Qty 3): Fiber optic extension cable

∙ (Qty 1): Buchholz relay

∙ (Qty 2): Cooling fan complete with motor

∙ (Qty 1): Bushing current transformer of each type and rating

∙ (Qty 1): Oil temperature indicator

∙ (Qty 1): Winding temperature indicator

∙ (Qty 1): Liquid level indicator

∙ (Qty 1): Electronic pressure monitor and one pressure transducer

∙ (Qty 1): Pressure relief device

∙ (Qty 1): Relay and contactor of each type

∙ (Qty 3): Annunciator relay modules and LEDs

∙ (Qty 1): Complete gasket set

∙ (Qty 1): Set of gaskets for transformer re assembly

∙ (Qty 1): 25 kV low-voltage winding bushing

∙ (Qty 1): 34.5 kV high-voltage neutral bushing

∙ (Qty 1): 138 kV high-voltage winding bushing

(Western Safety Products, Model 16691)

∙ Portable fall arrest system anchor post with Davik Arm

∙ Gas and oil actuated Buchholz relay

∙ Maintenance-free dehydrating breather (Messko Reinhausen MTraB, Type DB 200 Gamma)

∙ Electronic pressure monitor, with three sensors on main tank (Qualitrol 930) measurement (Qualitrol 509ITM DW-200)

∙ Electronic Temperature Monitor with cooling controls and fiber-optic winding temperature

∙ On-line dissolved gas and moisture content monitor (Serveron TM8)

∙ Directed-flow pressure relief device with discharge piping (Qualitrol XPRD)

∙ Oil level indicator on conservator tank

∙ WTI and OTI gauges with RTDs at transformer base.

∙ GROUNDING: #4/0 AWG insulated grounding conductors from arresters to ground pad

∙ MOUNTING: Removable brackets on top of transformer

∙ RATINGS: 70 kV MCOV; 90 kV duty-cycle

∙ RADIATORS: Hot-dip galvanized.

Maximum design flux density of 1.75 Tesla. Step-lap construction.

∙ CORE: Laminations maximum thickness of 0.270mm, cold-rolled, grain-oriented steel.

∙ LOW-VOLTAGE BUSHING THROATS: Low-voltage bushing throat flange.

∙ SEISMIC: Seismic calculations required for main tank and all major components.

∙ LIFTING EYES: Design loads for each eye shall be two times the actual load.

∙ BASE: Designed for pad mounting with seismic welding to steel plates.

designed for use with Western Safety Products fall arrest anchor post Model 16691.

∙ PORTABLE FALL ARREST ANCHOR POST MOUNTING PLATE: Uni-anchor plate and lug, posts with red vinyl coated wire rope rails; non-slip surface on tank cover.

∙ PERSONAL FALL ARREST SYSTEM: Removable yellow powder-coated aluminum safety base of tank.

∙ GROUNDING: #4/0 insulated copper conductor from neutral bushing to tank ground pad at

∙ VALVES: Stainless steel ball-type (with the exception of butterfly valves) used for gasket grooves of rectangular cross-section.

∙ GASKETS: Nitrile NBR (Buna-N), Duro 50-60, 25% compression. O-ring gaskets shall not be

∙ MAN-HOLE: 24-inch diameter (minimum one) steel with engraved black lettering.

control and power cabinets shall be anodized aluminum approximately 1/8 inch thick or stainless low-voltage bushings made of stainless steel with black lettering. Device nameplates within the also be provided. Equipment nameplates shall be provided for the high-voltage bushings and calculated X/R ratio. An additional diagram nameplate for sling locations and lift positions shall plant location, Government contract number, pressure and vacuum the tank will withstand, and

∙ NAMEPLATES: Cast bronze or stainless steel; IEEE C57.12.00, Table 7, including manufacturing date,

- Fold-down maintenance tray on inside of control cabinet door.

thermostat control.

- PTC resistor design enclosure heaters with integral fans, and NEMA 4X rated industrial grade

- 120 V ac, 20 A hospital grade GFCI receptacle mounted inside the control cabinet.

- 120 V ac, 1,000 Lumen LED Type A19 lamps with door-actuated switch.

- All circuits, wiring and equipment rated greater than 120 V ac to be mounted in power cabinet.

weatherproof window provided in cabinet door for viewing.

- Electronic Temperature Monitor mounted on swing panel within control cabinet, with weatherproof window provided in cabinet door for viewing.

- 12 pt. annunciator (Seekirk B1001A-S78) mounted on swing panel within control cabinet, with

- Lockout relay with trip coil monitoring and indicators (Electroswitch Series 24)

∙ SPECIAL FEATURES:

- 125 and 250 V dc circuits - Rated 125/250 or 250 V dc, and 10,000 A interrupting

- 120 V ac circuits - Rated 250 V dc and 120/240 or 240 V ac, and 10,000 A interrupting

- 240 V ac circuits - Rated 600 V ac and 22,000 A interrupting

∙ MOLDED-CASE CIRCUIT BREAKERS:

120 V ac circuits - 10 A

- Single-break inductive load interrupting rating: 125 V dc circuits - 1.5 A;

- Rated for 600 V ac or 250 V dc

∙ SWITCHES:

120 V ac circuits - 6.0 A

- Single-contact inductive load interrupting capacity: 125 V dc circuits - 1.0 A;

- Rated for 125 V dc or 120 V ac; meets requirements of NEMA ICS5; 10 A contacts

∙ AUXILIARY RELAYS:

∙ TERMINAL BLOCKS: 600 V, 30 A minimum, 90 ºC rated terminations.

boxes shall be cast aluminum with cast covers and liquid-tight hubs.

All conduit threaded joints shall have a conductive joint compound applied. Outlet and junction

∙ CONDUIT: All wiring to be run in conduit. Wire runs through tank reinforcing channels not allowed.

Phase C - Blue; Grounded neutral - White; Insulated ground - Green/Yellow

∙ WIRING: XLPE; 3-phase power conductors color coded: Phase A - Black; Phase B - Red;

Cooling fans - 240 V ac, 3-wire, 3-phase, 60 Hz

∙ GOVERNMENT-FURNISHED POWER: Control power - 125 V dc; Annunciation power - 125 V dc;

side panels of enclosures.

viewing Qualitrol 509 DW and annunciator in control cabinet. Solar shielding on top, front and

∙ CABINET MATERIAL: Weather-proof Type 304 stainless steel with locking provisions. Windows for

S O

L

IC

IT

A T

IO

N N

O

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

T

IO

N M

A R

K

S

IZ

E

S U

B M

IT

T E

D B

Y

P L

O T S

C A

L E

IDENTIFICATION

SHEET

D A

T E

A P

P R

D R

A W

IN

G N

U M

B E

R of Engineers

US Army Corps

P L

O T D

A T

E

54321

D

C

B

A

/8 /2

DRAWING PLOT SIZE: ANSI D DATE AND TIME PLOTTED: 2/8/2016 10:33:12 AM BY USERNAME: g2hdcevh SHEET NAME: G-006

D E

S

IG

N F

IL

E n w d \n w p \E

T D

S \C

A D

D -W o rk s p a c e s \N

W P \W o rk

S p a c e \p ro je c ts \L o c a l R e s o u rc e

C O

N T

R A

C T N

O

F

IL

E N

A M

E

D A

T

C

O N

T R

A C

T O

R I

D

/0

/2

F P

P -5 .3

-0 -0 /7

U .S

A R

M Y C

O R

P S O

F E

N G

IN

E E

R S

P O

R T

L A

N D

O R

E G

O N

H Y

D R

O E

L E

C T

R

IC

D

E S

IG

N C

E N

T E

R

U .S

A R

M Y C

O R

P S O

F E

N G

IN

E E

R S

O M

A H

A

N E

B R

A S

K A

O M

A H

A D

IS

T R

IC

E V

E N R

M

IL

E S ,P .E

F P

P .3

G

X X

X .d g n

G

H D

C D

D F

D F

IL

Q

U

IR

E M

E N

T S S

U M

M A

R Y S

H E

E T

,0

,3

K

V A G

S U T

R A

N S (O

P T

IO

N A

L

G-007

A

N S

F O

R M

E R S

U P

P L

Y

M

IS

S O

U R I

R

IV

E R

W F -1

-T -0

R T P

E C

K D

A M

A N

S I

D

G

H D

C B J B

(REFERENCE SPECIFICATION SECTION 48 19 23.01)

NAMEPLATE DATA:

TANK AND CONSTRUCTION:

ACCESSORIES:

BUSHINGS:

∙ SFRA TEST SHIPPING BUSHING: 2.5 kV Class, 45 kV BIL, 100 Amp

∙ CORE GROUNDS: 2.5 kV Class, 45 kV BIL, 100 Amp relaying accuracy) impregnated paper condenser core (One 200:5 CT, 0.3B-1.8 metering accuracy, C400

∙ NEUTRAL (H0): 34.5 kV Class, 200 kV BIL, 400 Amp, composite exterior with resin-relaying accuracy) temperature rise rating (One 2,000:5 MRCT, 0.3B-1.8 metering accuracy, C400

∙ PRIMARY WINDING (X): 25 kV Class, 150 kV BIL, 2,000 Amp, light contamination, 125 ºC accuracy, C400 relaying accuracy) resin-impregnated paper condenser core (Two 400:5 MRCT, 0.3B-1.8 metering

∙ SECONDARY WINDING (H): 69 kV Class, 350 kV BIL, 400 Amp, composite exterior with

SURGE ARRESTERS:

INSULATING OIL:

∙ Napthenic base - ASTM D 3487 Type II; 0.3% by mass of oxidation inhibitor

SEPARATE CONTROL AND POWER CABINETS:

SPARE PARTS:

FACTORY ASSEMBLY AND PAINT:

(4) Completely assembled and witnessing of factory acceptance tests

(3) Completed core/coil assembly, but prior to tanking

(2) After completion of windings but prior to landing on core

(1) Design Review Meeting

∙ INSPECTIONS: Government inspections performed during to oil filling.

∙ INTERIOR PAINT: Primer coat, oil-resistant finish coat - White. Allow to cure for one week prior to receive a non-slip coating.

gloss. Corrosion resistant surfaces, and stainless steel cabinets, shall remain unpainted. Cover

∙ EXTERIOR PAINT: Primer coat, epoxy base coat, polyurethane top coat - Munsell 5BG 7/0.4 high-of reassembly.

∙ ASSEMBLY: Transformer to be fully assembled, with removable components match-marked for ease

FACTORY ACCEPTANCE TESTS (F.A.T.):

∙ FREQUENCY: 60 Hz

∙ MAXIMUM LOAD LOSSES: 95 kW

∙ MAXIMUM NO-LOAD LOSSES: 30 kW

∙ MAXIMUM SOUND LEVEL (ONAF): 68 dB

∙ OIL PRESERVATION SYSTEM: Constant Oil Pressure System (COPS) tank

∙ TEMPERATURE RISE: 65 ºC

∙ SECONDARY WINDING (H) DETC: 5 taps; 2 @ +2.5%, 2 @ -2.5%

∙ IMPEDANCE: 7.0% (H-X)

∙ PHASING: Three-Phase

∙ BIL LEVELS, kV: 350 (H) / 110 (X) / 150 (H0)

∙ VOLTAGE RATINGS: 69,000 GrdY (H) - 13,800 Delta (X)

∙ KVA RATING: 25,000 / 33,333

∙ COOLING CLASS: ONAN/ONAF

∙ TYPE: Class I GSU Power Transformer

REQUIREMENTS SUMMARY SHEET

FORT PECK DAM 25,000 / 33,333 KVA GSU TRANSFORMER (OPTIONAL)

∙ Analog temperature gage functional verification

∙ Bushing current transformer routine tests

∙ Low-frequency dielectric test on auxiliary devices

∙ Insulation power factor and capacitance

∙ Core insulation resistance

∙ Winding insulation resistance

∙ Dissolved gas-in-oil analysis

∙ Zero-phase sequence impedance

∙ Control and cooling losses power factor tests during transformer F.A.T.

∙ Each high-voltage and high-voltage neutral bushing shall undergo capacitance and

∙ All electrical and electo-mechanical devices shall be functionally tested

∙ De-energized tap changer mechanical operational test (5 complete cycles)

- One SFRA test to be performed with the transformer in the shipping configuration

- One SFRA test to be performed with the transformer fully assembled and oil filled

- Cable integrity test required

∙ Sweep Frequency Response Analysis (with electronic data files)

∙ Leakage reactance (with electronic data files)

∙ Induced voltage test acceptance criteria: 7,200 cycle enhancement level: 500 pC

∙ Audible sound level tests

∙ Lightning impulse tests

∙ Temperature rise tests shall be performed at each cooling stage

∙ All 'Routine' tests (IEEE C57.12.00, Table 18)

∙ (Qty 1): Fuse of each type and rating

∙ (Qty 3): Fiber optic extension cable

∙ (Qty 1): Buchholz relay

∙ (Qty 2): Cooling fan complete with motor

∙ (Qty 1): Bushing current transformer of each type and rating

∙ (Qty 1): Oil temperature indicator

∙ (Qty 1): Winding temperature indicator

∙ (Qty 1): Liquid level indicator

∙ (Qty 1): Electronic pressure monitor and one pressure transducer

∙ (Qty 1): Pressure relief device

∙ (Qty 1): Relay and contactor of each type

∙ (Qty 3): Annunciator relay modules and LEDs

∙ (Qty 1): Complete gasket set

∙ (Qty 1): Set of gaskets for transformer re assembly

∙ (Qty 1): 25 kV low-voltage winding bushing

∙ (Qty 1): 34.5 kV high-voltage neutral bushing

∙ (Qty 1): 69 kV high-voltage winding bushing

∙ Gas and oil actuated Buchholz relay

∙ Maintenance-free dehydrating breather (Messko Reinhausen MTraB, Type DB 200 Gamma)

∙ Electronic pressure monitor, with three sensors on main tank (Qualitrol 930) temperature measurement (Qualitrol 509ITM DW-200)

∙ Electronic Temperature Monitor with cooling controls and fiber-optic winding

∙ On-line dissolved gas and moisture content monitor (Serveron TM8)

∙ Directed-flow pressure relief device with discharge piping (Qualitrol XPRD)

∙ Oil level indicator on conservator tank

∙ WTI and OTI gauges with RTDs at transformer base.

∙ GROUNDING: #4/0 AWG insulated grounding conductors from arresters to ground pad

∙ MOUNTING: Removable brackets on top of transformer

∙ RATINGS: 48 kV MCOV; 60 kV duty-cycle

∙ RADIATORS: Hot-dip galvanized.

Maximum design flux density of 1.75 Tesla. Step-lap construction.

∙ CORE: Laminations maximum thickness of 0.270mm, cold-rolled, grain-oriented steel.

∙ LOW-VOLTAGE BUSHING THROATS: Low-voltage bushing throat flange.

∙ SEISMIC: Seismic calculations required for main tank and all major components.

∙ LIFTING EYES: Design loads for each eye shall be two times the actual load.

∙ BASE: Designed for pad mounting with seismic welding to steel plates.

designed for use with Western Safety Products fall arrest anchor post Model 16691.

∙ PORTABLE FALL ARREST ANCHOR POST MOUNTING PLATE: Uni-anchor plate and lug, posts with red vinyl coated wire rope rails; non-slip surface on tank cover.

∙ PERSONAL FALL ARREST SYSTEM: Removable yellow powder-coated aluminum safety base of tank.

∙ GROUNDING: #4/0 insulated copper conductor from neutral bushing to tank ground pad at

∙ VALVES: Stainless steel ball-type (with the exception of butterfly valves) used for gasket grooves of rectangular cross-section.

∙ GASKETS: Nitrile NBR (Buna-N), Duro 50-60, 25% compression. O-ring gaskets shall not be

∙ MAN-HOLE: 24-inch diameter (minimum one) control cabinet shall be anodized aluminum or stainless steel with engraved black lettering.

low-voltage bushings made of stainless steel with black lettering. Device nameplates within the also be provided. Equipment nameplates shall be provided for the high-voltage bushings and calculated X/R ratio. An additional diagram nameplate for sling locations and lift positions shall plant location, Government contract number, pressure and vacuum the tank will withstand, and

∙ NAMEPLATES: Cast bronze or stainless steel; IEEE C57.12.00, Table 7, including manufacturing date,

- Fold-down maintenance tray on inside of control cabinet door.

thermostat control.

- PTC resistor design enclosure heaters with integral fans, and NEMA 4X rated industrial grade

- 120 V ac, 20 A hospital grade GFCI receptacle mounted inside the control cabinet.

- 120 V ac, 1,000 Lumen LED Type A19 lamps with door-actuated switch.

- All circuits, wiring and equipment rated greater than 120 V ac to be mounted in power cabinet.

weatherproof window provided in control cabinet door for viewing.

- Electronic Temperature Monitor mounted on swing panel within control cabinet, with weatherproof window provided in control cabinet door for viewing.

- 12 pt. annunciator (Seekirk B1001A-S78) mounted on swing panel within control cabinet, with

∙ SPECIAL FEATURES:

- 125 and 250 V dc circuits - Rated 125/250 or 250 V dc, and 10,000 A interrupting

- 120 V ac circuits - Rated 250 V dc and 120/240 or 240 V ac, and 10,000 A interrupting

- 240 V ac circuits - Rated 600 V ac and 22,000 A interrupting

∙ MOLDED-CASE CIRCUIT BREAKERS:

120 V ac circuits - 10 A

- Single-break inductive load interrupting rating: 125 V dc circuits - 1.5 A;

- Rated for 600 V ac or 250 V dc

∙ SWITCHES:

120 V ac circuits - 6.0 A

- Single-contact inductive load interrupting capacity: 125 V dc circuits - 1.0 A;

- Rated for 125 V dc or 120 V ac; meets requirements of NEMA ICS5; 10 A contacts

∙ AUXILIARY RELAYS:

∙ TERMINAL BLOCKS: 600 V, 30 A minimum, 90 ºC rated terminations.

boxes shall be cast aluminum with cast covers and liquid-tight hubs.

All conduit threaded joints shall have a conductive joint compound applied. Outlet and junction

∙ CONDUIT: All wiring to be run in conduit. Wire runs through tank reinforcing channels not allowed.

Phase C - Blue; Grounded neutral - White; Insulated ground - Green/Yellow

∙ WIRING: XLPE; 3-phase power conductors color coded: Phase A - Black; Phase B - Red;

Cooling fans - 240 V ac, 3-wire, 3-phase, 60 Hz

∙ GOVERNMENT-FURNISHED POWER: Control power - 125 V dc; Annunciation power - 125 V dc;

side panels of enclosures.

viewing Qualitrol 509 DW and annunciator in control cabinet. Solar shielding on top, front and

∙ CABINET MATERIAL: Weather-proof Type 304 stainless steel with locking provisions. Windows for

S O

L

IC

IT

A T

IO

N N

O

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

T

IO

N M

A R

K

S

IZ

E

S U

B M

IT

T E

D B

Y

P L

O T S

C A

L E

IDENTIFICATION

SHEET

D A

T E

A P

P R

D R

A W

IN

G N

U M

B E

R of Engineers

US Army Corps

P L

O T D

A T

E

54321

D

C

B

A

/8 /2

DRAWING PLOT SIZE: ANSI D DATE AND TIME PLOTTED: 2/8/2016 10:38:36 AM BY USERNAME: g2hdcevh SHEET NAME: G-007

D E

S

IG

N F

IL

E n w d \n w p \E

T D

S \C

A D

D -W o rk s p a c e s \N

W P \W o rk

S p a c e \p ro je c ts \L o c a l R e s o u rc e

C O

N T

R A

C T N

O

F

IL

E N

A M

E

D A

T

C

O N

T R

A C

T O

R I

D

/0

/2

F P

P -5 .3

-0 -0 /8

U .S

A R

M Y C

O R

P S O

F E

N G

IN

E E

R S

P O

R T

L A

N D

O R

E G

O N

H Y

D R

O E

L E

C T

R

IC

D

E S

IG

N C

E N

T E

R

U .S

A R

M Y C

O R

P S O

F E

N G

IN

E E

R S

O M

A H

A

N E

B R

A S

K A

O M

A H

A D

IS

T R

IC

E V

E N R

M

IL

E S ,P .E

F P

P .3

G

X X

X .d g n

G

H D

C D

D F

D F

IL

Q

U

IR

E M

E N

T S S

U M

M A

R Y S

H E

E T

,0

K

V A S

T A

T

IO

N S

E R

V

IC

E T

R A

N S

G-008

A

N S

F O

R M

E R S

U P

P L

Y

M

IS

S O

U R I

R

IV

E R

W F -1

-T -0

R T P

E C

K D

A M

A N

S I

D

G

H D

C B J B

(REFERENCE SPECIFICATION SECTION 48 19 23.02)

NAMEPLATE DATA:

TANK AND CONSTRUCTION:

ACCESSORIES:

BUSHINGS:

SURGE ARRESTERS:

INSULATING OIL:

∙ Napthenic base - ASTM D 3487 Type II; 0.3% by mass of oxidation inhibitor

SPARE PARTS:

FACTORY ASSEMBLY AND PAINT:

FACTORY ACCEPTANCE TESTS (F.A.T.):

REQUIREMENTS SUMMARY SHEET

FORT PECK 3,000 KVA STATION SERVICE TRANSFORMER

∙ FREQUENCY: 60 Hz

∙ MAXIMUM LOAD LOSSES: 28 kW

∙ MAXIMUM NO-LOAD LOSSES: 5 kW

∙ MAXIMUM SOUND LEVEL (ONAF): 63 dB

∙ OIL PRESERVATION SYSTEM: Nitrogen Blanket

∙ TEMPERATURE RISE: 65 ºC

0.625%; 16 steps above and 16 steps below rated voltage

∙ LOW-VOLTAGE WINDING (X) OLTC: +/- 10% in steps of

∙ IMPEDANCE: 7.0% (H-X)

∙ PHASING: Three-Phase

∙ BIL LEVELS, kV: 110 (H) / 75 (X) / 75 (X0)

∙ VOLTAGE RATINGS: 13,800 Delta (H) - 4,160 GrdY (X)

∙ KVA RATING: 3,000

∙ COOLING CLASS: ONAN

∙ TYPE: Class I GSU Power Transformer

∙ SFRA TEST SHIPPING BUSHING: 2.5 kV Class, 45 kV BIL, 100 Amp

∙ CORE GROUNDS: 2.5 kV Class, 45 kV BIL, 100 Amp

0.3B-1.8 metering accuracy, C400 relaying accuracy)

∙ NEUTRAL (X0): 5 kV Class, 75 kV BIL, 500 Amp (One 100:5 CT, ∙ SECONDARY WINDING (X): 5 kV Class, 75 kV BIL, 500 Amp

∙ PRIMARY WINDING (H): 25 kV Class, 150 kV BIL, 400 Amp

CONTROL CABINET:

(4) Completely assembled and witnessing of factory acceptance tests

(3) Completed core/coil assembly, but prior to tanking

(2) After completion of windings but prior to landing on core

(1) Design Review Meeting

∙ INSPECTIONS: Government inspections performed during to oil filling.

∙ INTERIOR PAINT: Primer coat, oil-resistant finish coat - White. Allow to cure for one week prior to receive a non-slip coating.

gloss. Corrosion resistant surfaces, and stainless steel cabinets, shall remain unpainted. Cover

∙ EXTERIOR PAINT: Primer coat, epoxy base coat, polyurethane top coat - Munsell 5BG 7/0.4 high-of reassembly.

∙ ASSEMBLY: Transformers to be fully assembled, with removable components match-marked for ease

∙ (Qty 1): Fuse of each type and rating

∙ (Qty 3): Fiber optic extension cable

∙ (Qty 1): Oil temperature indicator

∙ (Qty 1): Winding temperature indicator

∙ (Qty 1): Liquid level indicator

∙ (Qty 1): Electronic pressure monitor and one pressure transducer

∙ (Qty 1): Pressure relief device

∙ (Qty 1): Relay and contactor of each type

∙ (Qty 3): Annunciator relay modules and LEDs

∙ (Qty 1): Complete gasket set

∙ (Qty 1): Set of gaskets for transformer re assembly

∙ (Qty 1): 5 kV low-voltage and neutral winding bushing

∙ (Qty 1): 25 kV high-voltage winding bushing

∙ Analog temperature gage functional verification

∙ Bushing current transformer routine tests

∙ Low-frequency dielectric test on auxiliary devices

∙ OLTC design and routine tests (IEEE C57.131, paragraphs 5.2 and 5.3)

∙ Insulation power factor and capacitance

∙ Core insulation resistance

∙ Winding insulation resistance

∙ Dissolved gas-in-oil analysis

∙ Zero-phase sequence impedance transformer F.A.T.

∙ Each high-voltage bushing shall undergo capacitance and power factor tests during

∙ All electrical and electo-mechanical devices shall be functionally tested

- One SFRA test to be performed with the transformer in the shipping configuration

- One SFRA test to be performed with the transformer fully assembled and oil filled

- Cable integrity test required

∙ Sweep Frequency Response Analysis (with electronic data files)

∙ Leakage reactance (with electronic data files)

∙ Induced voltage test acceptance criteria: 7,200 cycle enhancement level: 500 pC

∙ Audible sound level test

∙ Lightning impulse tests

∙ Temperature rise test

∙ All 'Routine' tests (IEEE C57.12.00, Table 18) at transformer base.

∙ GROUNDING: #4/0 AWG insulated grounding conductors from arresters to ground pad

∙ MOUNTING: Removable brackets on top of transformer

∙ RATINGS: 8.4 kV MCOV; 60 kV duty-cycle

∙ RADIATORS: Hot-dip galvanized.

Maximum design flux density of 1.75 Tesla. Step-lap construction.

∙ CORE: Laminations maximum thickness of 0.270mm, cold-rolled, grain-oriented steel.

bushing housing enclosure.

∙ LOW-VOLTAGE BUSHING HOUSING: Flanged low-voltage bushing throat with removable

∙ SEISMIC: Seismic calculations required for main tank and all major components.

∙ LIFTING EYES: Design loads for each eye shall be two times the actual load.

∙ BASE: Designed for pad mounting with seismic welding to steel plates.

designed for use with Western Safety Products fall arrest anchor post Model 16691.

∙ PORTABLE FALL ARREST ANCHOR POST MOUNTING PLATE: Uni-anchor plate and lug, ground pad at base of tank, routed through conduit.

∙ GROUNDING: A #4/0 insulated copper conductor from low-voltage neutral bushing to tank

25 degrees Celsius.

∙ OIL LEVEL MARKING: Operating oil level marking on the tank for an oil temperature of

∙ VALVES: Stainless steel ball-type (with the exception of butterfly valves) used for gasket grooves of rectangular cross-section.

∙ GASKETS: Nitrile NBR (Buna-N), Duro 50-60, 25% compression. O-ring gaskets shall not be

∙ MAN-HOLE: 24-inch diameter (minimum one)

∙ OLTC maintenance-free dehydrating breather (Messko Reinhausen MTraB, Type DB 100)

∙ Electronic pressure monitor, with one sensor on the OLTC (Qualitrol 930)

∙ Electronic pressure monitor, with three sensors on the main tank (Qualitrol 930)

∙ Fiber-optic temperature monitor (Qualitrol 408)

∙ Nitrogen gas generation system (Waukesha N2GEN-210)

(Reinhausen Tapcon 250).

controls (Reinhausen Tapmotion MD-III) and automatic voltage controller

∙ On-load tap changer (Reinhausen VACUTAP RMV-II), with motor drive enclosure and

∙ On-line dissolved Hydrogen and moisture content monitor (Serveron TM1)

OLTC (Qualitrol XPRD)

∙ Directed-flow pressure relief device with discharge piping for main tank and

∙ Oil level indicator

∙ WTI and OTI gauges with RTDs control cabinet shall be anodized aluminum or stainless steel with engraved black lettering.

low-voltage bushings made of stainless steel with black lettering. Device nameplates within the also be provided. Equipment nameplates shall be provided for the high-voltage bushings and calculated X/R ratio. An additional diagram nameplate for sling locations and lift positions shall plant location, Government contract number, pressure and vacuum the tank will withstand, and

∙ NAMEPLATES: Cast bronze or stainless steel; IEEE C57.12.00, Table 7, including manufacturing date,

- Fold-down maintenance tray on inside of control cabinet door.

thermostat control.

- PTC resistor design enclosure heaters with integral fans, and NEMA 4X rated industrial grade

- 120 V ac, 20 A hospital grade GFCI receptacle.

- 120 V ac, 1,000 Lumen LED Type A19 lamps with door-actuated switch.

weatherproof window provided in cabinet door for viewing.

- Fiber-optic temperature monitor mounted on swing panel within control cabinet, with weatherproof window provided in cabinet door for viewing.

- 12 pt. annunciator (Seekirk B1001A-S78) mounted on swing panel within control cabinet, with

∙ SPECIAL FEATURES:

- 125 and 250 V dc circuits - Rated 125/250 or 250 V dc, and 10,000 A interrupting

- 120 V ac circuits - Rated 250 V dc and 120/240 or 240 V ac, and 10,000 A interrupting

- 240 V ac circuits - Rated 600 V ac and 22,000 A interrupting

∙ MOLDED-CASE CIRCUIT BREAKERS:

120 V ac circuits - 10 A

- Single-break inductive load interrupting rating: 125 V dc circuits - 1.5 A;

- Rated for 600 V ac or 250 V dc

∙ SWITCHES:

120 V ac circuits - 6.0 A

- Single-contact inductive load interrupting capacity: 125 V dc circuits - 1.0 A;

- Rated for 125 V dc or 120 V ac; meets requirements of NEMA ICS5; 10 A contacts

∙ AUXILIARY RELAYS:

∙ TERMINAL BLOCKS: 600 V, 30 A minimum, 90 ºC rated terminations.

boxes shall be cast aluminum with cast covers and liquid-tight hubs.

All conduit threaded joints shall have a conductive joint compound applied. Outlet and junction

∙ CONDUIT: All wiring to be run in conduit. Wire runs through tank reinforcing channels not allowed.

Phase C - Blue; Grounded neutral - White; Insulated ground - Green/Yellow

∙ WIRING: XLPE; 3-phase power conductors color coded: Phase A - Black; Phase B - Red;

OLTC motor drive power - 208/120 V ac

∙ GOVERNMENT-FURNISHED POWER: Control power - 125 V dc; Annunciation power - 125 V dc;

side panels of enclosures.

viewing Qualitrol 408 and annunciator in cabinet doors. Solar shielding on top, front and

∙ CABINET MATERIAL: Weather-proof Type 304 stainless steel with locking provisions. Windows for

S O

L

IC

IT

A T

IO

N N

O

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

T

IO

N M

A R

K

S

IZ

E

S U

B M

IT

T E

D B

Y

P L

O T S

C A

L E

IDENTIFICATION

SHEET

D A

T E

A P

P R

D R

A W

IN

G N

U M

B E

R of Engineers

US Army Corps

P L

O T D

A T

E

54321

D

C

B

A

/8 /2

DRAWING PLOT SIZE: ANSI D DATE AND TIME PLOTTED: 2/8/2016 10:43:12 AM BY USERNAME: g2hdcevh SHEET NAME: G-008

D E

S

IG

N F

IL

E n w d \n w p \E

T D

S \C

A D

D -W o rk s p a c e s \N

W P \W o rk

S p a c e \p ro je c ts \L o c a l R e s o u rc e

C O

N T

R A

C T N

O

F

IL

E N

A M

E

D A

T

SURGE ARRESTER

BUCHHOLZ RELAY

PRESSURE RELIEF DEVICE WITH DISCHARGE PIPING

ANNUNCIATOR

OIL LEVEL GAUGE

COOLING FAN (TYPICAL)

CONSTANT OIL PRESSURE SYSTEM (COPS) TANK

LIFTING EYE (TYPICAL)

SKID-TYPE STRUCTURAL BASE

FALL PROTECTION SYSTEM STORAGE BOX

FALL PROTECTION POST POCKET (TYPICAL)

14 1

ANALOG TEMPERATURE GAUGES

CONTROL CABINET (SEE SHEETS E-102 & E-103)

POWER CABINET (SEE SHEETS E-102 & E-104)

36 3 MOUNTING PROVISIONS FOR BUSHING POTENTIAL DEVICE

ELECTRONIC DEHYDRATING BREATHER FOR CONSERVATOR

LOW-VOLTAGE (X) BUSHING

HIGH-VOLTAGE (H) BUSHING

HIGH-VOLTAGE NEUTRAL (H0) BUSHING

2 BUCHHOLZ RELAY ISOLATION VALVE

RADIATOR ISOLATION VALVE

29 4 JACK PAD (TYPICAL)

3-INCH MAIN OIL DRAIN VALVE

3-INCH VACUUM VALVE

2-INCH LOWER FILTER VALVE

2-INCH UPPER FILTER VALVE

2 1.5-INCH SERVERON VALVE

1 SERVERON OIL MONITORING EQUIPMENT

25 1 SERVERON EQUIPMENT MOUNTING UNISTRUT

26 1 SERVERON EQUIPMENT HELIUM CYLINDER LOCATION

AS DES.

AS DES.

AS DES.

AS DES.

33 THERMOWELLSAS DES.

35 1 MOUNTING LOCATION FOR NAMEPLATES

837 STRUCTURAL BASE CHANNELS FOR WELDING BASE TO PAD

ELECTRONIC PRESSURE MONITOR TRANSDUCER (SEE NOTE 6)

CORE & CORE FRAME GROUND BUSHINGS (FIG. 1, SH. 109)

BILL OF MATERIALS

DESCRIPTIONQTYITEMDESCRIPTIONQTYITEM

38 1 ELECTRONIC PRESSURE MONITOR

ELECTRONIC TEMPERATURE MONITOR

RADIATOR (TYPICAL) (SEE NOTE 5)

NOTES:

BY THE MANUFACTURER.

TRANSDUCER MANIFOLD, IN A LOCATION AS RECOMMENDED

ON THE TANK UTILIZING A QUALTROL THREE-PORT

TRANSDUCERS SHALL BE INSTALLED ON A FLANGED VALVE

A TOTAL OF THREE ELECTRONIC PRESSURE MONITOR6.

QUANTITY REQUIREMENTS.

FLOW, AND ARE NOT INTENDED TO INDICATE THE ACTUAL

THE PERMISSIBLE LOCATIONS AND DIRECTION OF FAN AIR

THE RADIATORS AS DEPICTED ON THIS DRAWING SHOW5.

DOES NOT SHOW SOME DEVICES LOCATED ON THE COVER.

FOR THE PURPOSES OF DRAWING CLARITY, THE SIDE VIEW4.

SURGE ARRESTERS OR ASSOCIATED SUPPORT STRUCTURE.

VIEW DOES NOT SHOW THE LOW-VOLTAGE BUSHINGS,

FOR THE PURPOSES OF DRAWING CLARITY, THE ELEVATION3.

LOCATED BENEATH THE CONSERVATOR TANK.

DOES NOT SHOW THE RADIATORS, FANS, OR VALVES

FOR THE PURPOSES OF DRAWING CLARITY, THE PLAN VIEW2.

JACKING PADS AND STRUCTURAL BASE CHANNELS

ANCILLARY DEVICES

CONTROL AND POWER CABINETS

COPS TANK

SURGE ARRESTERS

HIGH-VOLTAGE AND LOW-VOLTAGE BUSHINGS

CRITICAL TO ASSURE PROPER INTERCONNECTION:

FOLLOWING ANCILLARY EQUIPMENT ARE CONSIDERED

THE EXISTING POWERPLANT. THE LOCATIONS OF THE

THE TRANSFORMER FOR PROPER INTERCONNECTION TO

PROVIDED FOR THE MANUFACTURERS USE IN DESIGNING

THE TRANSFORMER LAYOUT AND DIMENSIONS HAVE BEEN1.

A E C

O N

T R

A C

T O

R I

D

/0

/2

U .S

A R

M Y C

O R

P S O

F E

N G

IN

E E

R S

P O

R T

L A

N D

O R

E G

O N

H Y

D R

O E

L E

C T

R

IC

D

E S

IG

N C

E N

T E

R

U .S

A R

M Y C

O R

P S O

F E

N G

IN

E E

R S

O M

A H

A

N E

B R

A S

K A

O M

A H

A D

IS

T R

IC

E V

E N R

M

IL

E S ,P .E

F P

P .3

E

X X

X .d g n

G

H D

C D

D F

D F

IL

L

Y

O U

T A

N D L

IM

IT

IN

G D

IM

E N

S

IO

N S

,0

,0

K

V A G

S U T

R A

N S

F O

R M

E

E-101

A

N S

F O

R M

E R S

U P

P L

Y

M

IS

S O

U R I

R

IV

E R

W F -1

-T -0

F P

P -5 .3

-6 -0

A /1

F O

R T P

E C

K D

A M

A N

S I

D

G

H D

C B J B

(SEE NOTE 2)

TRANSFORMER PLAN VIEW

(SEE NOTE 3)

TRANSFORMER ELEVATION VIEW

(SEE NOTE 4)

TRANSFORMER SIDE VIEW

M A

X

IM

U M

48"

66"

48"

66"

28" 28" 16"

60,000 / 80,000 KVA GSU TRANSFORMER

16 2

22 21

14 13

41" MINIMUM

285" (MAXIMUM)

M A

X

IM

U M

S O

L

IC

IT

A T

IO

N N

O

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

T

IO

N M

A R

K

S

IZ

E

S U

B M

IT

T E

D B

Y

P L

O T S

C A

L E

IDENTIFICATION

SHEET

D A

T E

A P

P R

D R

A W

IN

G N

U M

B E

R of Engineers

US Army Corps

P L

O T D

A T

E

54321

D

C

B

A

/8 /2

DRAWING PLOT SIZE: ANSI D DATE AND TIME PLOTTED: 2/8/2016 10:49:17 AM BY USERNAME: g2hdcevh SHEET NAME: E-101

D E

S

IG

N F

IL

E n w d \n w p \E

T D

S \C

A D

D -W o rk s p a c e s \N

W P \W o rk

S p a c e \p ro je c ts \L o c a l R e s o u rc e

C O

N T

R A

C T N

O

F

IL

E N

A M

E

D A

T E

H0

H2H1 H3

X2

520.5091520.5091520.5091

520.5091520.5091520.5091

X3X1H0

H1 H2 H3

TERMINAL BOX

TO SERVERON

240 VAC POWER CABINET 120 VAC & 125 VDC CONTROL CABINET

43TF 86T

COMPUTER TRAY

FOLD-DOWN

(SEE DETAIL "A")

ANN.

ETM

NOT TO SCALE

CONTROL AND POWER CABINETS

NOT TO SCALE

CONNECTIONS AND GROUNDING

DETAIL OF ENCLOSURE CONDUIT

NOT TO SCALE

SIDE VIEW

DETAIL OF VIBRATION ISOLATION MOUNTS

NOT TO SCALE

DETAIL OF TYPICAL CABINET DOOR SEAL

DETAIL "A"

WINDOW SEAL

TYPICAL CLAYTONRITE-TYPE

RAIN AND DRIP SHIELD

GASKET SEAL

CABINET DOOR

DRIP CHANNEL

SECURING STRIP

FRAMEWORK

CABINET MOUNTING

TRANSFORMER TANK

TEMPERED GLASS

RUBBER SEAL

CLAYTONRITE-TYPE

PANEL FACE

NOTE 1

NOTE 1

AND GROUNDING SCREW

WITH A CAPTIVE O-RING GASKET

SHALL BE A MYERS SCRU-TITE,

ALL CONDUIT HUB FITTINGS

DRAWINGS POCKET

O&M MANUAL

LEGEND:

MOUNTS (TYPICAL)

VIBRATION ISOLATION

ELECTRONIC TEMPERATURE MONITORETM

ANNUNCIATOR PANELANN.

LOCKOUT RELAY86T

COOLLING GROUP ON-OFF-AUTO SELECTOR SWITCH43TF

CABINETS

CONTROL

POWER AND

A E C

O N

T R

A C

T O

R I

D

/0

/2

U .S

A R

M Y C

O R

P S O

F E

N G

IN

E E

R S

P O

R T

L A

N D

O R

E G

O N

H Y

D R

O E

L E

C T

R

IC

D

E S

IG

N C

E N

T E

R

U .S

A R

M Y C

O R

P S O

F E

N G

IN

E E

R S

O M

A H

A

N E

B R

A S

K A

O M

A H

A D

IS

T R

IC

E V

E N R

M

IL

E S ,P .E

F P

P .3

E

X X

X .d g n

G

H D

C D

D F

D F

IL

P

W

E R A

N D C

O N

T R

O L C

A B

IN

E T

,0

,0

K

V A G

S U T

R A

N S

F O

R M

E

E-102

A

N S

F O

R M

E R S

U P

P L

Y

M

IS

S O

U R I

R

IV

E R

W F -1

-T -0

F P

P -5 .3

-6 -0

A /2

F O

R T P

E C

K D

A M

A N

S I

D

G

H D

C B J B

60,000 / 80,000 KVA GSU TRANSFORMER

NOTES:

GROUND WIRE

ENCLOSURE

EQUIPMENT

O&M MANUAL DRAWINGS.

LEFT DOOR SHALL HAVE A POCKET SIZED TO HOLD THE

FOR LATCHING THE TRAY WHEN STOWED. THEA MEANS

TRAY IN A HORIZONTAL POSITION WHEN LOWERED, AND

SHALL INCLUDE FOLDING HINGES WHICH SECURE THE

TRAY MOUNTED ON THE INSIDE OF THE DOOR. THE TRAY

THE RIGHT DOOR SHALL HAVE A DROP DOWN LAPTOP6.

PARA. 2.15.2.

PER THE REQUIREMENTS OF SECTION 48 19 23.04,

THE TRANSFORMER TANK USING VIBRATION ISOLATORS,

TO A FRAME STRUCTURE, WHICH SHALL BE MOUNTED TO

THE CONTROL AND POWER CABINETS SHALL BE MOUNTED5.

OF THE TRANSFORMER.

DEVICES ARE APPROXIMATELY 60 INCHES ABOVE THE BASE

ANNUNCIATOR PANELS SHALL BE MOUNTED SO THAT THE

THE ELECTRONIC TEMPERATURE MONITOR AND4.

ENTER EACH CABINET THROUGH THE BASE.

TO THE CONTROL AND POWER CABINETS SHALL ONLY

ALL CONDUIT ROUTING FROM THE TRANSFORMER DEVICES3.

OF SECTION 48 19 23.04, PARA. 2.15.2.

OF FIELD FITTING OF CONDUIT PER THE REQUIREMENTS

HAVE GASKETED REMOVABLE PLATES FOR THE PURPOSES

SIZES WILL VARY. THE BASE OF EACH CABINET SHALL

WILL BE INSTALLED BY OTHERS. ACTUAL QUANTITIES AND

IS SHOWN FOR REPRESENTATIVE PURPOSES ONLY, AND

EXTERNAL CONDUIT CONNECTIONS TO THE POWER PLANT2.

GOVERNMENT).

SPACE FOR ARC FLASH LABEL (PROVIDED BY THE1.

S O

L

IC

IT

A T

IO

N N

O

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

T

IO

N M

A R

K

S

IZ

E

S U

B M

IT

T E

D B

Y

P L

O T S

C A

L E

IDENTIFICATION

SHEET

D A

T E

A P

P R

D R

A W

IN

G N

U M

B E

R of Engineers

US Army Corps

P L

O T D

A T

E

54321

D

C

B

A

/8 /2

DRAWING PLOT SIZE: ANSI D DATE AND TIME PLOTTED: 2/8/2016 10:50:30 AM BY USERNAME: g2hdcevh SHEET NAME: E-102

D E

S

IG

N F

IL

E n w d \n w p \E

T D

S \C

A D

D -W o rk s p a c e s \N

W P \W o rk

S p a c e \p ro je c ts \L o c a l R e s o u rc e

C O

N T

R A

C T N

O

F

IL

E N

A M

E

D A

T

10 GAUGE, MINIMUM.

THE REMOVABLE BOTTOM PLATE THICKNESS SHALL BE3.

INSIDE THE CONTROL CABINET.

THE GFCI OUTLET SHALL BE ACCESSIBLE ONLY FROM2.

MAY BE MODIFIED BY THE CONTRACTOR.

ILLUSTRATIVE PURPOSES ONLY. THE ACTUAL LAYOUT

THE CONTROL CABINET LAYOUT AS SHOWN IS FOR1.

GFCI OUTLET 120VAC, 20AOUTL

CABINET LIGHTLT

CABINET HEATERHTR

GROUND BUSGND

ELECTRONIC TEMPERATURE MONITORETM

DOOR SWITCHDS

ANNUNCIATION PANELANN

LOCKOUT RELAY (HAND RESET)86T

COOLING GROUP ON-OFF-AUTO SELECTOR SWITCH43TF

INDUSTRIAL GRADE THERMOSTAT23

A E C

O N

T R

A C

T O

R I

D

/0

/2

U .S

A R

M Y C

O R

P S O

F E

N G

IN

E E

R S

P O

R T

L A

N D

O R

E G

O N

H Y

D R

O E

L E

C T

R

IC

D

E S

IG

N C

E N

T E

R

U .S

A R

M Y C

O R

P S O

F E

N G

IN

E E

R S

O M

A H

A

N E

B R

A S

K A

O M

A H

A D

IS

T R

IC

E V

E N R

M

IL

E S ,P .E

F P

P .3

E

X X

X .d g n

G

H D

C D

D F

D F

IL

C

N

T R

O L C

A B

IN

E T L

A Y

O U

T

,0

,0

K

V A G

S U T

R A

N S

F O

R M

E

E-103

A

N S

F O

R M

E R S

U P

P L

Y

M

IS

S O

U R I

R

IV

E R

W F -1

-T -0

F P

P -5 .3

-6 -0

A /3

F O

R T P

E C

K D

A M

A N

S I

D

G

H D

C B J B

NOT TO SCALE

CONTROL CABINET LAYOUT

60,000 / 80,000 KVA GSU TRANSFORMER

(FRONT VIEW)

LEFT SWING PANEL

LH SIDE PANEL LH BACK PANEL RH BACK PANEL RH SIDE PANEL

(FRONT VIEW)

RIGHT SWING PANEL

ANN

BLOCKS

TERMINAL

23-1

RESISTORS

CALIBRATION

ANALOG WTI

LTLT

BLOCKS

TERMINAL

BLOCKS

TERMINAL

BLOCKS

TERMINAL

TRANSFORMER

CURRENT

43TF 86T

HTR BLOCKS

TERMINAL

BREAKERS

CIRCUIT

DEVICES

RELAYS AND

AUXILIARY

OUTL

HTR

WIRING TO POWER CABINET

BUSHING FOR 120VAC

WIREWAY HOLE WITH

INSTALLATION

FOR FUTURE CONDUIT

GASKETED BOTTOM PLATE

REMOVABLE BOLTED AND

TRANSFORMER MOUNTED CONDUIT

AREA FOR INSTALLATION OF

SEE NOTE 2

DS1 DS2

GND

BOTTOM PANEL

ETM

DEVICES

ASSOCIATED

ETM

S O

L

IC

IT

A T

IO

N N

O

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

T

IO

N M

A R

K

S

IZ

E

S U

B M

IT

T E

D B

Y

P L

O T S

C A

L E

IDENTIFICATION

SHEET

D A

T E

A P

P R

D R

A W

IN

G N

U M

B E

R of Engineers

US Army Corps

P L

O T D

A T

E

54321

D

C

B

A

/8 /2

DRAWING PLOT SIZE: ANSI D DATE AND TIME PLOTTED: 2/8/2016 10:51:37 AM BY USERNAME: g2hdcevh SHEET NAME: E-103

D E

S

IG

N F

IL

E n w d \n w p \E

T D

S \C

A D

D -W o rk s p a c e s \N

W P \W o rk

S p a c e \p ro je c ts \L o c a l R e s o u rc e

C O

N T

R A

C T N

O

F

IL

E N

A M

E

D A

T

INDUSTRIAL GRADE THERMOSTAT23

CABINET LIGHTLT

CABINET HEATERHTR

GROUND BUSGND

DOOR SWITCHDS

NOTES:

10 GAUGE, MINIMUM.

THE REMOVABLE BOTTOM PLATE THICKNESS SHALL BE3.

CABINET.

BLOCKS SHALL BE MOUNTED IN THE 240 VAC POWER

CIRCUIT BREAKERS, CONTACTORS AND POWER TERMINAL

THE COOLING FANS, INCLUDING THE MOLDED-CASE

ALL 240 VAC PROTECTIVE AND CONTROL EQUIPMENT FOR2.

CONTRACTOR.

ONLY. THE LAYOUT MAY BE MODIFIED BY THE

THE LAYOUT SHOWN IS FOR ILLUSTRATIVE PURPOSES1.

A E C

O N

T R

A C

T O

R I

D

/0

/2

U .S

A R

M Y C

O R

P S O

F E

N G

IN

E E

R S

P O

R T

L A

N D

O R

E G

O N

H Y

D R

O E

L E

C T

R

IC

D

E S

IG

N C

E N

T E

R

U .S

A R

M Y C

O R

P S O

F E

N G

IN

E E

R S

O M

A H

A

N E

B R

A S

K A

O M

A H

A D

IS

T R

IC

E V

E N R

M

IL

E S ,P .E

F P

P .3

E

X X

X .d g n

G

H D

C D

D F

D F

IL

V A

C P

O W

E R C

A B

IN

E T L

A Y

O U

T

,0

,0

K

V A G

S U T

R A

N S

F O

R M

E

E-104

A

N S

F O

R M

E R S

U P

P L

Y

M

IS

S O

U R I

R

IV

E R

W F -1

-T -0

F P

P -5 .3

-6 -0

A /4

F O

R T P

E C

K D

A M

A N

S I

D

G

H D

C B J B

NOT TO SCALE

POWER CABINET LAYOUT

60,000 / 80,000 KVA GSU TRANSFORMER

DS1

LH SIDE PANEL RH SIDE PANEL

BLOCKS

TERMINAL

INSTALLATION

FOR FUTURE CONDUIT

GASKETED BOTTOM PLATE

REMOVABLE BOLTED AND

23-2

AND FAN CONTROL)

LIGHTS, HEATER

(WIRING FOR

BLOCKS

TERMINAL

120 VAC

BACK PANEL

GND

CABINET

WIRING TO CONTROL

BUSHING FOR 120VAC

WIREWAY HOLE WITH

BOTTOM PANEL

LT

TRANSFORMER MOUNTED CONDUIT

AREA FOR INSTALLATION OF

CONTACTORS

FAN MOTOR

BREAKERS AND

CIRCUIT

TRANSFORMER

POWER

AUXILIARY

HTR

BLOCKS

TERMINAL

S O

L

IC

IT

A T

IO

N N

O

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

T

IO

N M

A R

K

S

IZ

E

S U

B M

IT

T E

D B

Y

P L

O T S

C A

L E

IDENTIFICATION

SHEET

D A

T E

A P

P R

D R

A W

IN

G N

U M

B E

R of Engineers

US Army Corps

P L

O T D

A T

E

54321

D

C

B

A

/8 /2

DRAWING PLOT SIZE: ANSI D DATE AND TIME PLOTTED: 2/8/2016 10:52:44 AM BY USERNAME: g2hdcevh SHEET NAME: E-104

D E

S

IG

N F

IL

E n w d \n w p \E

T D

S \C

A D

D -W o rk s p a c e s \N

W P \W o rk

S p a c e \p ro je c ts \L o c a l R e s o u rc e

C O

N T

R A

C T N

O

F

IL

E N

A M

E

D A

T

LP738(+)

LP738(-)

52-1

TO ETM

CURRENT

FAN

GROUP

COOLING

FCT

(POWER PANEL 7, CIRCUIT 3)

240 VAC, 3-PHASE, 60 HZ

GOVERNMENT SUPPLIED POWER

PDB1

P

P

A

P

P

B

P

P

C

H1

H2

H3

H4

DS-1

H T

R

1 2

86T

LT1 LT2

43TF

23-1

NC NO

DS-2

NC NO

H T

R

LT3

23-2

DS-3

NC NO

POWER CABINET

LOCATED IN 240 VAC

POWER CABINET

LOCATED IN 240 VAC

LIGHTS

CABINET

CONTROL

52-6

HEATER

CABINET

CONTROL

52-7

OFF POSITION

O F F

X

X

CONTACTS (

O

N

A

U T

O

ON AUTO

43TF

20A

GFCI

OUTLET

P D

B

RECEPTACLE

CABINET

CONTROL

52-8

27-1

27-1

ANN.

POWER CABINET

LOCATED IN 240 VAC

FUSES

X1

X2

X3

X4

240 X 480V - 120/240V

TRANSFORMER

POWER

AUXILIARY

V

V

LIGHT

CABINET

POWER

52-3

HEATER

CABINET

POWER

52-4

L

IG

H T

IN

G P

A N

E L

C

IR

C U

IT

V

A C -P

H A

S E H

Z

G O

V E

R N

M E

N T S

U P

P L

IE

D C

O N

T R

O L P

O W

E R

P D

B

ANN.52-2

120 VAC

POWER

BREATHER

DEHYDRATING

RLY 1)

(ETM

49T1

MONITOR

GAS-IN-OIL

52-9

120 VAC

(DEV. 45M)

POWER

MONITOR

GAS-IN-OIL

FAN MOTOR88

TRANSFORMER LOCKOUT RELAY86T

AC MOLDED-CASE CIRCUIT BREAKER52

WINDING TEMPERATURE49T_

COOLING GROUP ON-OFF-AUTO SELECTOR SWITCH43TF

COOLING GROUP MOTOR CONTACTOR42

UNDERVOLTAGE RELAY27

INDUSTRIAL GRADE THERMOSTAT23

CABINET LIGHTLT

POWER DISTRIBUTION BLOCKPDB

CABINET HEATERHTR

GROUND FAULT CIRCUIT INTERRUPTERGFCI

FAN CURRENT TRANSFORMERFCT

ELECTRONIC TEMPERATURE MONITORETM

CABINET DOOR SWITCHDS

ANNUNCIATIONANN

BREATHER

DEHYDRATING

52-5

SHOWN WITH THE ETM IN THE ENERGIZED STATE.

THE ETM RELAY CONTACT 1 IS A FAILSAFE CONTACT7.

ALL FANS SHALL HAVE BUILT-IN OVERLOAD PROTECTION.6.

AUXILIARY POWER TRANSFORMER.

TO REDUCE THE REQUIRED RATING AND SIZE OF THE

GOVERNMENT FURNISHED 120VAC LIGHTING PANEL 7

THE GFCI RECEPTACLE IS SOURCED FROM THE5.

PROVIDED BY THE ETM MANUFACTURER.

THE FAN CURRENT TRANSFORMER SHOWN SHALL BE4.

FURNISHED.

INDICATED IN THE DASHED BOXES ARE GOVERNMENT

INDICATED. THE 240VAC AND 120VAC POWER SOURCES

THE CONTRACTOR SHALL PROVIDE ALL EQUIPMENT AS3.

OF THE ACTUAL CONFIGURATION PROVIDED.

REPRESENTATION ONLY AND MAY NOT BE INDICATIVE

CONTACTORS AS SHOWN ARE FOR SCHEMATIC

THE QUANTITY AND GROUPING OF COOLING FANS AND2.

ROUTED THROUGH THE MAIN CONTROL CABINET.

ASSOCIATED WIRING SHALL BE INSTALLED INSIDE OR

240 VAC POWER CABINET. NO 240 VAC EQUIPMENT OR

ALL EQUIPMENT SHOWN SHALL BE INSTALLED IN THE1.

C

O N

T R

A C

T O

R I

D

/0

/2

U .S

A R

M Y C

O R

P S O

F E

N G

IN

E E

R S

P O

R T

L A

N D

O R

E G

O N

H Y

D R

O E

L E

C T

R

IC

D

E S

IG

N C

E N

T E

R

U .S

A R

M Y C

O R

P S O

F E

N G

IN

E E

R S

O M

A H

A

N E

B R

A S

K A

O M

A H

A D

IS

T R

IC

E V

E N R

M

IL

E S ,P .E

F P

P .3

E

X X

X .d g n

G

H D

C D

D F

D F

IL

E R

V

A C C

O N

T R

O L S

C H

E M

A T

IC

S V

A C C

O O

L

IN

G P

O W

E R A

N D

,0

,0

K

V A G

S U T

R A

N S

F O

R M

E

E-105

A

N S

F O

R M

E R S

U P

P L

Y

M

IS

S O

U R I

R

IV

E R

W F -1

-T -0

F P

P -5 .3

-6 -0

A /5

F O

R T P

E C

K D

A M

A N

S I

D

G

H D

C B J B

60,000 / 80,000 KVA GSU TRANSFORMER

S O

L

IC

IT

A T

IO

N N

O

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

T

IO

N M

A R

K

S

IZ

E

S U

B M

IT

T E

D B

Y

P L

O T S

C A

L E

IDENTIFICATION

SHEET

D A

T E

A P

P R

D R

A W

IN

G N

U M

B E

R of Engineers

US Army Corps

P L

O T D

A T

E

54321

D

C

B

A

/8 /2

DRAWING PLOT SIZE: ANSI D DATE AND TIME PLOTTED: 2/8/2016 10:53:50 AM BY USERNAME: g2hdcevh SHEET NAME: E-105

D E

S

IG

N F

IL

E n w d \n w p \E

T D

S \C

A D

D -W o rk s p a c e s \N

W P \W o rk

S p a c e \p ro je c ts \L o c a l R e s o u rc e

C O

N T

R A

C T N

O

F

IL

E N

A M

E

D A

T

ANALOG WINDING TEMPERATURE INDICATORWTI

TOGGLE SWITCH (ANNUNCIATOR)TS

POWER DISTRIBUTION BLOCKPDB

INDICATING LIGHT (ANNUNCIATOR)L

HAND RESET (DEVICE 86T)HR

ELECTRONIC TEMPERATURE MONITORETM

TRIP AUXILIARY RELAY94X

LOCKOUT RELAY (HAND RESET)86T

DC MOLDED-CASE CIRCUIT BREAKER72

OIL LEVEL GAUGE (CONSERVATOR TANK)71QL

ELECTRONIC PRESSURE MONITOR63PM

PRESSURE RELIEF DEVICE63PR

BUCHHOLZ RELAY LOW OIL LEVEL63BL

BUCHHOLZ RELAY GAS DETECTION63BG

COOLING GROUP AC MOLDED CASE CIRCUIT BREAKER52-2

WINDING TEMPERATURE49T

TRANSFORMER GAS-IN-OIL MONITOR45M

COOLING GROUP MOTOR CONTACTOR42

COOLING CONTROL UNDERVOLTAGE RELAY27-1

OIL HIGH TEMPERATURE (509DW)26Q

CONTACTS.

SOLENOID EXCEEDS THE RATING OF THESE DEVICE

CONTACTS, AS THE BURDEN OF THE…