B3_Solicitation_Amendment-2_W9126G-17-R-0084.pdf
PDF 569 KB Posted
- Attached to
- Automated Infantry Platoon Battle Course (IPBC)
- Solicitation number
- W9126G-17-R-0084
About this file
Amendment 0002, Solicitation W9126G-17-R-0084
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.
15A. NAME AND TITLE OF SIGNER (Type or print)
30-105-04EXCEPTION TO SF 30
APPROVED BY OIRM 11-84
STANDARD FORM 30 (Rev. 10-83) Prescribed by GSA
FAR (48 CFR) 53.243
The Solicitation for Automated Infantry Platoon Battle Course (IPBC); Fort Hood, Texas is amended as follows:
See SF30 Continuation Sheet(s)
NOTE: Proposal Receipt date will be, 17 July 2017, at 12:00 p.m. Central Time.
1. CONTRACT ID CODE PAGE OF PAGES
J 1 2
16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)
16C. DATE SIGNED
BY
16B. UNITED STATES OF AMERICA15C. DATE SIGNED15B. CONTRACTOR/OFFEROR
(Signature of Contracting Officer)(Signature of person authorized to sign)
8. NAME AND ADDRESS OF CONTRACTOR (No., Street, County, State and Zip Code) X 9A. AMENDMENT OF SOLICITATION NO.
W9126G-17-R-0084
X 9B. DATED (SEE ITEM 11)
14-July-2017
10B. DATED (SEE ITEM 13)
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
X The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offer is extended, X is not extended.
Offer must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended by one of the following methods:
(a) By completing Items 8 and 15, and returning copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;
or (c) By separate letter or telegram which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN
REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
12. ACCOUNTING AND APPROPRIATION DATA (If required)
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS.
IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.
A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE
CONTRACT ORDER NO. IN ITEM 10A.
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation date, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(B).
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER (Specify type of modification and authority)
E. IMPORTANT: Contractor is not, is required to sign this document and return copies to the issuing office.
14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
10A. MOD. OF CONTRACT/ORDER NO.
2. AMENDMENT/MODIFICATION NO. 5. PROJECT NO.(If applicable)
6. ISSUED BY
3. EFFECTIVE DATE
14-July-2017
CODE
US ARMY ENGINEER DISTRICT, FORT WORTH
ATTN: CESWF-CT
819 TAYLOR ST, ROOM 2A19
P.O. BOX 17300
FORT WORTH TX 76102-0300
W9126G 7. ADMINISTERED BY (If other than item 6)
4. REQUISITION/PURCHASE REQ. NO.
CODE
See Item 6
FACILITY CODECODE
EMAIL:TEL:
X 1
W9126G-17-R-0084
SECTION SF 30 BLOCK 14 CONTINUATION PAGE
SUMMARY OF CHANGES
1. New Sections: Replace the following section with the accompanying new section of the same number and title bearing the notation “W9126G-17-R-0084, Amendment No. 0002".
03 40 00.00 10 PLANT-PRECAST CONCRETE PRODUCTS FOR BELOW GRADE CONSTRUCTION
End of Summary of Changes
YTC Pre-Cast Spec YTCPRECAST
SECTION 03 40 00.00 10
PLANT-PRECAST CONCRETE PRODUCTS FOR BELOW GRADE CONSTRUCTION
08/06
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
ACI INTERNATIONAL (ACI)
ACI 211.1 (1991; R 2009) Standard Practice for Selecting Proportions for Normal, Heavyweight and Mass Concrete
ACI 211.2 (1998; R 2004) Standard Practice for Selecting Proportions for Structural Lightweight Concrete
ACI 305R (2010) Specification for Hot Weather Concreting
ACI 306.1 (1990; R 2002) Standard Specification for Cold Weather Concreting
ACI 318 (2008; Errata 2010; Errata 2010) Building Code Requirements for Structural Concrete and Commentary
AMERICAN CONCRETE PIPE ASSOCIATION (ACPA)
ACPA 01-102 (2000) Concrete Pipe Handbook
ACPA QPC (2005; Ver 3.0) QCast Plant Certification Manual
AMERICAN WELDING SOCIETY (AWS)
AWS D1.1/D1.1M (2010) Structural Welding Code - Steel
AWS D1.4/D1.4M (2005; Errata 2005) Structural Welding Code - Reinforcing Steel
ASTM INTERNATIONAL (ASTM)
ASTM A153/A153M (2009) Standard Specification for Zinc Coating (Hot-Dip) on Iron and Steel Hardware
ASTM A185/A185M (2007) Standard Specification for Steel Welded Wire Reinforcement, Plain, for Concrete
SECTION 03 40 00.00 10 Page 1
W9126G-17-R-0084, Amendment No. 0002
ASTM A36/A36M (2008) Standard Specification for Carbon Structural Steel
ASTM A496/A496M (2007) Standard Specification for Steel Wire, Deformed, for Concrete Reinforcement
ASTM A497/A497M (2007) Standard Specification for Steel Welded Wire Reinforcement, Deformed, for Concrete
ASTM A615/A615M (2009b) Standard Specification for Deformed and Plain Carbon-Steel Bars for Concrete Reinforcement
ASTM A706/A706M (2009b) Standard Specification for Low-Alloy Steel Deformed and Plain Bars for Concrete Reinforcement
ASTM A775/A775M (2007b) Standard Specification for Epoxy-Coated Steel Reinforcing Bars
ASTM A82/A82M (2007) Standard Specification for Steel Wire, Plain, for Concrete Reinforcement
ASTM A884/A884M (2006) Standard Specification for Epoxy-Coated Steel Wire and Welded Wire Reinforcement
ASTM C 1064/C 1064M (2008) Standard Test Method for Temperature of Freshly Mixed Hydraulic-Cement Concrete
ASTM C 138/C 138M (2010b) Standard Test Method for Density ("Unit Weight"), Yield, and Air Content (Gravimetric) of Concrete
ASTM C 143/C 143M (2010) Standard Test Method for Slump of Hydraulic-Cement Concrete
ASTM C 150/C 150M (2009) Standard Specification for Portland Cement
ASTM C 171 (2007) Standard Specification for Sheet Materials for Curing Concrete
ASTM C 173/C 173M (2010b) Standard Test Method for Air Content of Freshly Mixed Concrete by the Volumetric Method
ASTM C 192/C 192M (2007) Standard Practice for Making and Curing Concrete Test Specimens in the Laboratory
ASTM C 309 (2007) Standard Specification for Liquid Membrane-Forming Compounds for Curing Concrete
ASTM C 31/C 31M (2010) Standard Practice for Making and Curing Concrete Test Specimens in the Field
SECTION 03 40 00.00 10 Page 2
ASTM C 33/C 33M (2011) Standard Specification for Concrete Aggregates
ASTM C 39/C 39M (2010) Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
ASTM C 595/C 595M (2010) Standard Specification for Blended Hydraulic Cements
ASTM C 618 (2008a) Standard Specification for Coal Fly Ash and Raw or Calcined Natural Pozzolan for Use in Concrete
ASTM C 891 (2011) Installation of Underground Precast Concrete Utility Structures
ASTM C231/C231M (2010) Standard Test Method for Air Content of Freshly Mixed Concrete by the Pressure Method
ASTM C260/C260M (2010a) Standard Specification for Air-Entraining Admixtures for Concrete
CSA STANDARDS (CSA)
CSA A23.4 (2009; Update 2010) Precast Concrete - Materials and Construction
NATIONAL PRECAST CONCRETE ASSOCIATION (NPCA)
NPCA QC Manual (2005; R 2006) Quality Control Manual for Precast Plants
1.2 SYSTEM DESCRIPTION
Furnish precast concrete units designed and fabricated by an experienced and acceptable precast concrete manufacturer who has been, for at least 3 years, regularly and continuously engaged in the manufacture of precast concrete work similar to that indicated on the drawings. Coordinate precast work with the work of other trades. Precast units shall include Stationary Infantry Target and Moving Infantry Target concrete emplacements.
1.2.1 Standard Precast Units
Design standard precast concrete units to withstand indicated design load conditions in accordance with applicable industry design standards ACI 318, ASTM, ACPA 01-102, Chapter 7-Design for Sulfide Control. Design shall also consider stresses induced during handling, shipping and installation as to avoid product cracking or other handling damage. Indicate design loads for precast concrete units on the shop drawings. Submit drawings for standard precast concrete units furnished by the precast concrete producer for approval by the Contracting Officer. These drawings shall demonstrate that the applicable industry design standards have been met. Include installation and construction information on shop drawings. Include details of steel reinforcement size and placement as well as supporting design calculations, if appropriate. Produce precast concrete units in accordance with the approved drawings. Submit cut sheets, for standard
SECTION 03 40 00.00 10 Page 3 precast concrete units, showing conformance to project drawings and requirements, and to applicable industry design standards listed in this specification.
1.2.2 Custom-Made Precast Units
Submit design calculations for custom-made precast units, prepared and sealed by a registered professional engineer, for approval prior to fabrication. Include in the calculations the analysis of units for lifting stresses and the sizing of lifting devices. Submit drawings furnished by the precast concrete producer for approval by the Contracting Officer.
Show on these drawings complete design, installation, and construction information in such detail as to enable the Contracting Officer to determine the adequacy of the proposed units for the intended purpose.
Include details of steel reinforcement size and placement as well as supporting design calculations, if appropriate. Produce precast concrete units in accordance with the approved drawings.
1.2.3 Joints and Sealants
Provide joints and sealants between adjacent units of the type and configuration indicated on shop drawings meeting specified design and performance requirements.
1.2.4 Concrete Mix Design
1.2.4.1 Concrete Mix Proportions
Base selection of proportions for concrete on the methodology presented in ACI 211.1 for normal weight concrete and ACI 211.2 for lightweight concrete. Develop the concrete proportions using the same type and brand of cement, the same type and brand of pozzolan, the same type and gradation of aggregates, and the same type and brand of admixture that will be used in the manufacture of precast concrete units for the project. Do not use calcium chloride in precast concrete containing reinforcing steel or other embedded metal items. At a minimum of thirty days prior to precast concrete unit manufacturing, the precast concrete producer will submit a mix design and proportions for each strength and type of concrete that will be used. Furnish a complete list of materials, including quantity, type, brand and applicable data sheets for all mix design constituents as well as applicable reference specifications. The use of self-consolidating concrete is permitted, provided that mix design proportions and constituents meet the requirements of this specification.
1.2.4.2 Concrete Strength
Provide precast concrete units with a 28-day compressive strength (f'c) of 4000_____ psi unless otherwise noted..
1.2.4.3 Water-to-Cement Ratio
Furnish concrete, that will be exposed to freezing and thawing, containing entrained air and with water-cement ratios of 0.45 or less. Furnish concrete which will not be exposed to freezing, but which is required to be watertight, with a water-cement ratio of 0.48 or less if the concrete is exposed to fresh water, or 0.45 or less if exposed to brackish water or sea water.
SECTION 03 40 00.00 10 Page 4
1.2.4.4 Air Content
The air content of concrete that will be exposed to freezing conditions shall be within the limits given below.
NOMINAL MAXIMUM AIR CONTENT %
AGGREGATE SIZE SEVERE EXPOSURE MODERATE EXPOSURE
10 mm (3/8 inch) 6.0 to 9.0 4.5 to 7.5 13 mm (1/2 inch) 5.5 to 8.5 4.0 to 7.0 19 mm (3/4 inch) 4.5 to 7.5 3.5 to 6.5 25 mm (1.0 inch) 4.5 to 7.5 3.0 to 6.0 38 mm (1.5 inch) 4.5 to 7.0 3.0 to 6.0
Note: For specified compressive strengths greater than 5000 psi, air content may be reduced 1 percent
1.3 SUBMITTALS
All submittals are the responsibility of the precast concrete producer.
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for information only. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
SD-01 Preconstruction Submittals
Quality Control Procedures
SD-02 Shop Drawings
Standard Precast Units; G Custom-Made Precast Units; G
SD-03 Product Data
Standard Precast Units
Embedded Items
SD-05 Design Data
Design Calculations Concrete Mix Proportions
SD-06 Test Reports
Test Reports
SD-07 Certificates
Quality Control Procedures
1.4 QUALITY ASSURANCE
Demonstrate adherence to the standards set forth in NPCA QC Manual and/or ACPA QPC. Meet requirements written in the subparagraphs below.
SECTION 03 40 00.00 10 Page 5
1.4.1 NPCA and ACPA Plant Certification
The precast concrete producer shall be certified by the National Precast Concrete Association's and/or the American Concrete Pipe Association's Plant Certification Program prior to and during production of the products for this project.
1.4.2 Qualifications, Quality Control and Inspection
1.4.2.1 Qualifications
Select a precast concrete producer that has been in the business of producing precast concrete units similar to those specified for a minimum of 3 years. The precast concrete producer shall maintain a permanent quality control department or retain an independent testing agency on a continuing basis.
1.4.2.2 Quality Control Procedures
Submit quality control procedures established by the precast manufacturer in accordance with NPCA QC Manual and/or ACPA QPC. Show that the following QC tests are performed as required and in accordance with the ASTM standards indicated.
a. Slump: Perform a slump test for each 150 cu yd of concrete produced, or once a day, whichever comes first. Perform slump tests in accordance with ASTM C 143/C 143M.
b. Temperature: Measure the temperature of fresh concrete when slump or air content tests are made and when compressive test specimens are made in accordance with ASTM C 1064/C 1064M.
c. Compressive Strength: Make at least four compressive strength specimens for each 150 cubic yards of concrete of each mix in accordance with the following Standards: ASTM C 31/C 31M, ASTM C 192/C 192M, ASTM C 39/C 39M.
d. Air Content: Perform tests for air content on air-entrained, wet-cast concrete for each 150 cu yd of concrete, but not less often than once each day when air-entrained concrete is used. Determine the air content in accordance with either ASTM C231/C231M or ASTM C 173/C 173M for normal weight aggregates and ASTM C 173/C 173M for lightweight aggregates.
e. Unit Weight: Perform tests for unit weight a minimum of once per week to verify the yield of batch mixes. Perform unit weight tests for each 100 cu yd of lightweight concrete in accordance with
ASTM C 138/C 138M.
Submit test reports as Follows:
a. Copies of material certifications and/or laboratory test reports, including mill tests and all other test data, for portland cement, blended cement, pozzolans, ground granulated blast furnace slag, silica fume, aggregate, admixtures, and curing compound proposed for use on this project.
b. Copies of test reports showing that the mix has been successfully tested to produce concrete with the properties
SECTION 03 40 00.00 10 Page 6 specified and will be suitable for the job conditions. Such tests may include compressive strength, flexural strength, plastic or hardened air content, freeze thaw durability, abrasion and absorption. Clearly detail in the specifications special tests for precast concrete or cast-in items.
c. Sufficient documentation, when the use of self-consolidating concrete (SCC) is proposed, showing a minimum of 30-days production track records demonstrating that SCC is appropriate for casting of the product.
d. Copies of in-plant QA/QC inspection reports, upon the request of the Contracting Officer.
1.5 DELIVERY, STORAGE, AND HANDLING
1.5.1 Delivery
Deliver precast units to the site in accordance with the delivery schedule to avoid excessive build-up of units in storage at the site. Upon delivery to the jobsite, all precast concrete units will be inspected by the Contracting Officer for quality and final acceptance.
1.5.2 Storage
Store units off the ground or in a manner that will minimize potential damage.
1.5.3 Handling
Handle, transport, and store products in a manner to minimize damage.
Lifting devices or holes shall be consistent with industry standards.
Perform lifting with methods or devices intended for this purpose as indicated on shop drawings.
PART 2 PRODUCTS
2.1 MATERIALS
Except as otherwise specified in the following paragraphs, conform material to Section 03 30 00 CAST-IN-PLACE CONCRETE.
2.1.1 Cement
Furnish cement conforming to ASTM C 150/C 150M, Type I, II, III or V.
Furnish blended cements that conform to ASTM C 595/C 595M.
2.1.2 Fly Ash and Pozzolans
Fly ash is used as a supplementary cementitious material (SCM) conforming to ASTM C 618, Class C or F with 4 percent maximum loss on ignition and 35 percent maximum cement replacement by weight.
2.1.3 Water
Furnish water potable or free of deleterious substances in amounts harmful to concrete or embedded metals.
SECTION 03 40 00.00 10 Page 7
2.1.4 Aggregates
2.1.4.1 Selection
Furnish aggregates conforming to ASTM C 33/C 33M. Provide aggregates not containing any substance, which may be deleteriously reactive with the alkalies in the cement.
2.1.5 Admixtures
2.1.5.1 Air-Entraining
ASTM C260/C260M
2.1.6 Reinforcement
2.1.6.1 Reinforcing Bars
a. Deformed Billet-steel: ASTM A615/A615M
b. Deformed Low-alloy steel: ASTM A706/A706M
2.1.6.2 Reinforcing Wire
a. Plain Wire: ASTM A82/A82M
b. Deformed Wire: ASTM A496/A496M
2.1.6.3 Welded Wire Fabric
a. Plain Wire: ASTM A185/A185M
b. Deformed Wire: ASTM A497/A497M
2.1.6.4 Epoxy Coated Reinforcement
a. Reinforcing Bars: ASTM A775/A775M
b. Wires and Fabric: ASTM A884/A884M
2.1.7 Inserts and Embedded Metal
All items embedded in concrete shall be of the type required for the intended task, and meet the following standards.
a. Structural Steel Plates, Angles, etc.: ASTM A36/A36M
b. Hot-dipped Galvanized: ASTM A153/A153M
PART 3 EXECUTION
3.1 FABRICATION AND PLACEMENT
Perform fabrication in accordance with NPCA QC Manual and/or ACPA QPC unless specified otherwise.
3.1.1 Forms
Use forms, for manufacturing precast concrete products, of the type and design consistent with industry standards and practices. They should be capable of consistently providing uniform products and dimensions.
Construct forms so that the forces and vibrations to which the forms will be subjected can cause no product damage. Clean forms of concrete build-up
SECTION 03 40 00.00 10 Page 8 after each use. Apply form release agents according to the manufacturers recommendations and do not allow to build up on the form casting surfaces.
3.1.2 Reinforcement
Follow applicable ASTM Standard or ACI 318 for placement and splicing.
Fabricate cages of reinforcement either by tying the bars, wires or welded wire fabric into rigid assemblies or by welding, where permissible, in accordance with AWS D1.4/D1.4M. Position reinforcing as specified by the design and so that the concrete cover conforms to requirements. The tolerance on concrete cover shall be one-third of that specified but not more than 1/2 inch. Provide concrete cover not less than 1/2 inch. Take positive means to assure that the reinforcement does not move significantly during the casting operations.
3.1.3 Embedded Items
Position embedded items at locations specified in the design documents.
Perform welding in accordance with AWS D1.1/D1.1M when necessary. Hold rigidly in place inserts, plates, weldments, lifting devices and other items to be imbedded in precast concrete products so that they do not move significantly during casting operations. Submit product data sheets and proper installation instruction for anchors, lifting inserts and other devices. Clearly indicate the products dimensions and safe working load.
3.2 CONCRETE
3.2.1 Concrete Mixing
Mixing operations shall produce batch-to-batch uniformity of strength, consistency, and appearance.
3.2.2 Concrete Placing
Deposit concrete into forms as near to its final location as practical.
Keep the free fall of the concrete to a minimum. Consolidate concrete in such a manner that segregation of the concrete is minimized and honeycombed areas are kept to a minimum. Use vibrators to consolidate concrete with frequencies and amplitudes sufficient to produce well consolidated concrete.
3.2.2.1 Cold Weather Concreting
Perform cold weather concreting in accordance with ACI 306.1.
a. Provide adequate equipment for heating concrete materials and protecting concrete during freezing or near-freezing weather.
b. Free from frost all concrete materials and all reinforcement, forms, fillers, and ground with which concrete is to come in contact.
c. Do not use frozen materials or materials containing ice.
d. In cold weather the temperature of concrete at the time of placing shall not be below 45 degrees F. Discard concrete that freezes before its compressive strength reaches 500 psi.
3.2.2.2 Hot Weather Concreting
Recommendations for hot weather concreting are given in detail in ACI 305R.
SECTION 03 40 00.00 10 Page 9
During hot weather, give proper attention to constituents, production methods, handling, placing, protection, and curing to prevent excessive concrete temperatures or water evaporation that could impair required strength or serviceability of the member or structure. The temperature of concrete at the time of placing shall not exceed 90 degrees F.
3.2.3 Concrete Curing
Commence curing immediately following the initial set and completion of surface finishing.
3.2.3.1 Curing by Moisture Retention
Prevent moisture evaporation from exposed surfaces until adequate strength for stripping is reached by one of the following methods:
a. Cover with polyethylene sheets a minimum of 6 mils thick in accordance with ASTM C 171.
b. Cover with burlap or other absorptive material and keep continually moist.
c. Use of a membrane-curing compound applied at a rate not to exceed 200 square ft/gallon, or in accordance with manufacturers' recommendations according to ASTM C 309.
3.2.3.2 Curing with Heat and Moisture
Do not subject concrete to steam or hot air until after the concrete has attained its initial set. Apply steam, if used, within a suitable enclosure, which permits free circulation of the steam in accordance with CSA A23.4. If hot air is used for curing, take precautions to prevent moisture loss from the concrete. The temperature of the concrete shall not be permitted to exceed 150 degrees F. These requirements do not apply to products cured with steam under pressure in an autoclave.
3.2.4 Surface Finish
Finish unformed surfaces of wet-cast precast concrete products as specified. If no finishing procedure is specified, finish such surfaces using a strike-off to level the concrete with the top of the form.
3.2.4.1 Formed Non-Architectural Surfaces
Cast surfaces against approved forms following industry practices in cleaning forms, designing concrete mixes, placing and curing concrete.
Normal color variations, form joint marks, small surface holes caused by air bubbles, and minor chips and spalls will be accepted but no major imperfections, honeycombs or other major defects will be permitted.
3.2.4.2 Unformed Surfaces
Finish unformed surfaces with a vibrating screed, or by hand with a float.
Normal color variations, minor indentations, minor chips and spalls will be accepted but no major imperfections, honeycombs, or other major defects shall be permitted.
SECTION 03 40 00.00 10 Page 10
3.2.4.3 Special Finishes
Troweled, broom or other finishes shall be according to the requirements of project documents and performed in accordance with industry standards or supplier specifications. Submit finishes for approval when required by the project documents. The sample finishes shall be approved prior to the start of production.
3.2.5 Stripping Products from Forms
Do not remove products from the forms until the concrete reaches the compressive strength for stripping required by the design. If no such requirement exists, products may be removed from the forms after the final set of concrete provided that stripping damage is minimal.
3.2.6 Patching and Repair
No repair is required to formed surfaces that are relatively free of air voids and honeycombed areas, unless the surfaces are required by the design to be finished.
3.2.6.1 Repairing Minor Defects
Defects that will not impair the functional use or expected life of a precast concrete product may be repaired by any method that does not impair the product.
3.2.6.2 Repairing Honeycombed Areas
When honeycombed areas are to be repaired, remove all loose material and cut back the areas into essentially horizontal or vertical planes to a depth at which coarse aggregate particles break under chipping rather than being dislodged. Use proprietary repair materials in accordance with the manufacturer's instructions. If a proprietary repair material is not used, saturate the area with water. Immediately prior to repair, the area should be damp, but free of excess water. Apply a cement-sand grout or an approved bonding agent to the chipped surfaces, followed immediately by consolidating an appropriate repair material into the cavity.
3.2.6.3 Repairing Major Defects
Evaluate, by qualified personnel, defects in precast concrete products which impair the functional use or the expected life of products to determine if repairs are feasible and, if so, to establish the repair procedure.
3.2.7 Shipping Products
Do not ship products until they are at least 5 days old, unless it can be shown that the concrete strength has reached at least 75 percent of the specified 28-day strength, or that damage will not result, impairing the performance of the product.
3.3 INSTALLATION
3.3.1 Site Access
It is the Contractor's responsibility to provide adequate access to the site to facilitate hauling, storage and proper handling of the precast
SECTION 03 40 00.00 10 Page 11 concrete products.
3.3.2 General Requirements
a. Install precast concrete products to the lines and grades shown in the contract documents or otherwise specified.
b. Lift products by suitable lifting devices at points provided by the precast concrete producer.
c. Install products in accordance with the precast concrete producer's instructions. In the absence of such instructions, install underground utility structures in accordance with ASTM C 891. Install pipe and manhole sections in accordance with the procedures outlined by the American Concrete Pipe Association.
d. Field modifications to the product will relieve the precast producer of liability even if such modifications result in the failure of the product.
-- End of Section --