W911WN18B8004-0001.pdf

PDF 406 KB Posted

Attached to
Charleroi L/D Conductor Rail Replacement Federal contract opportunity
Solicitation number
W911WN18B8004
Issued by
Department of the Army Corps of Engineers Engineering District Pittsburgh

About this file

Amendment 0001

View the file

Other files for this federal contract opportunity

Other files attached to Charleroi L/D Conductor Rail Replacement, newest first.
File Type Posted
Bid_Abstract.xlsx XLSX spreadsheet
Bid_Results.pdf PDF
W911WN18B8004-0002.pdf PDF
AO37_LCH_0-121-A.pdf PDF
01_35_00.00_08.pdf PDF
AO37_LCH_11-050-A.pdf PDF
Bid_Schedule.xls XLS spreadsheet
Sign-In_Sheet,_Attendees,_Site_Visit,_7-13-18.pdf PDF
Constracting_Discussion_and_Agenda,_Site_Visit,_7-13-18.pdf PDF
Attachment_1,_Technical_Specifications,_Certified_Final,_April_2018.pdf PDF
W911WN18B8004.pdf PDF
Attachment_3,_Wage_Determination,_PA180004_06-15-2018_PA4.pdf PDF
Attachment_2,_Drawings_Certified_Final,_April_2018.pdf PDF
Show all 13

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

W81ET481104676

AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT

Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.

15A. NAME AND TITLE OF SIGNER (Type or print)

30-105-04EXCEPTION TO SF 30

APPROVED BY OIRM 11-84

STANDARD FORM 30 (Rev. 10-83) Prescribed by GSA

FAR (48 CFR) 53.243

RE: Bulkhead Hoist Conductor Rail System Replacement at Charleroi Locks and Dam, Monongahela River, Pennsylvania

This amendment is being issued to: 1) Provide responses to questions received; 2) Revise tw o (2) Draw ings; and 3) Revise the Technical Specif ications, as indicated in the Summary of Changes of this amendment.

1. CONTRACT ID CODE PAGE OF PAGES

J 1 4

16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)

16C. DATE SIGNED

BY 27-Jul-2018

16B. UNITED STATES OF AMERICA15C. DATE SIGNED15B. CONTRACTOR/OFFEROR

(Signature of Contracting Officer)(Signature of person authorized to sign)

8. NAME AND ADDRESS OF CONTRACTOR (No., Street , County, State and Zip Code) X W911WN18B8004

X 9B. DATED (SEE ITEM 11)

05-Jul-2018

10B. DATED (SEE ITEM 13)

9A. AMENDMENT OF SOLICITATION NO.

11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS

X The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offer is extended, X is not extended.

Offer must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended by one of the following methods:

(a) By completing Items 8 and 15, and returning 1 copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;

or (c) By separate letter or telegram which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN

REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.

12. ACCOUNTING AND APPROPRIATION DATA (If required)

13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS.

IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.

A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE

CONTRACT ORDER NO. IN ITEM 10A.

B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation date, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(B).

C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:

D. OTHER (Specify type of modification and authority)

E. IMPORTANT: Contractor is not, is required to sign this document and return copies to the issuing office.

14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)

10A. MOD. OF CONTRACT/ORDER NO.

2. AMENDMENT/MODIFICATION NO. 5. PROJECT NO.(If applicable)

6. ISSUED BY

3. EFFECTIVE DATE

27-Jul-2018

CODE

U.S. ARMY ENGINEER DISTRICT, PITTSBURGH

ATTN CELRP-RC-P

W S MOORHEAD FEDERAL BUILDING

1000 LIBERTY AVENUE ROOM 2203

PITTSBURGH PA 15222-4186

W911WN 7. ADMINISTERED BY (If other than item 6)

4. REQUISITION/PURCHASE REQ. NO.

CODE

See Item 6

FACILITY CODECODE

EMAIL:TEL:

W911WN18B8004

SECTION SF 30 BLOCK 14 CONTINUATION PAGE

SUMMARY OF CHANGES

SECTION SF 30 - BLOCK 14 CONTINUATION PAGE (SF 30)

The following have been added by full text:

AMENDMENT 0001

The following specification section has been revised and is attached to this amendment:

TECHNICAL SPECIFICATIONS, CERTIFIED FINAL, APRIL 2018

01 35 00.00 08 SPECIAL PROCEDURES – Revised language to clarify availability of Government auxiliary crane.

The following contract drawings have been revised and are attached to this amendment:

DRAWINGS, CERTIFIED FINAL, APRIL 2018

037-LCH-0/121-A – CONTRACT AND REFERENCE DRAWINGS INDEX – Revised to indicate

Amendment 1.

037-LCH-11/050-A – CONTRACTOR WORK LIMITS – PLAN – Revised to incorporate parking along dam abutment access road.

SECTION 00 21 00 - INSTRUCTIONS

The following have been added by full text:

QUESTIONS AND ANSWERS

RESPONSES TO QUESTIONS RECEIVED (1-10)

Q1: Does the project Site Superintendent have to be a direct employ of the prime contractor, or may this rule be performed by an employee of a subcontractor?

A1: The project site superintendent can be employed by a subcontractor if that subcontractor is performing the majority of the work.

Q2: Can the Site Superintendent also fill the role of the CQC Electrical Technician?

A2: No, the CQC Electrical Technician cannot be the Site Superintendent. This position must be filled by a QC person with no other production duties. We would allow the CQC-SM to also be the Electrical Technician if the requisite experience and training is satisfied.

Q3: Is it necessary for the CQC Electrical Technician to be on-site at all times, or is it acceptable if the Electrical Technician made scheduled visits to inspect the progress of electrical work and to be present for all testing activities?

A3: The CQC Electrical Technician must be on site when electrical work is being performed.

Q4: Is Longshoreman’s insurance required? The solicitation section “Required Insurance” (00 73 00-3.c), states that “Longshoreman Insurance MAY be required for this work. Please consult with your insurance carrier and applicable statutes”. Our insurance provider would need to know if this work is considered over a navigable waterway. Does USACE consider this work to be performed over a navigable waterway?

A4: Work on this project is considered to be performed over a navigable waterway.

Q5: To access all the work area, it appears the bulkhead crane will need to be relocated during the project so that the rail can be accessed. Will temporary backup generator power be operational and available for use so that the crane can be relocated by USACE personnel after the existing rail conductor system is removed?

A5: The crane can be relocated only by the USACE personnel as needed per contract. It is expected that generator power will be complete and operational by the time of award and notice to proceed is issued.

Q6: Spec 01 35 26 – paragraph 3.1.2 states lead paint is to be removed from the bulkhead hoist work platform and “miscellaneous ferrous metal items which may be encountered in the performance of the work”. Would these miscellaneous items include each existing Z-bracket installed along the length of the bridge’s current conductor rail support system that is to have the bottom 4” demo’ed?

A6: The work for bottom 4-inch demolition on the existing Z-bracket shall be performed as requirement in accordance with CFR 1926.62 for lead paint removal.

Q7: On drawing sheet 57/17, General Note 4 refers the bidder to Detail 5. Detail 5 is missing from this drawing. Please clarify your intent.

A7: In general note 4 on drawing 57/17, replace FROM “Detail 5” TO “Detail 2”.

Q8: Contractor laydown area seems small for parking, jobsite trailer and material laydown area. Would it be acceptable if cars parked along the edge of the access road to the dam abutment?

A8: Contractor may park up to 5 vehicles along the abutment access road. The asphalt pavement averages around 12 feet wide. Contractor should plan on grading the shoulder areas at no extra cost to the government in order to provide a suitable parking along the road. The Contractor shall provide details to the Contracting Officer for review and approval prior to performing any changes and restore the area as directed by the Contracting Officer at the end of the contract.

Q9: Detail 1 on drawing sheet 56/56 seems to indicate that the C-channel attached to the existing Z-bar may be existing. However, upon review in the field, this c-channel does not exist. Please confirm that the contractor is to furnish and install a new c-channel along the length of the crane rail (approximately 430LF) under this contract. If the c-channel is to be provided under this contract, please clarify the desired finish (hot-dipped galvanized, painted, etc.).

A9: All C-channels shall be furnished and installed by the contractor as required and shown on the structural drawings 57/16 and 57/17. Paint in accordance with specification section 05 51 36 CONDUCTOR RAIL

SUPPORTS AND MAINTENANCE PLATFORM.

Q10: The specification repeatedly refers to the presence of lead-based paint on existing features of the work. Please confirm that the Contractor shall include the cost of developing and implementing a lead compliance plan meeting the requirements of EM-385 06.C.02 for modifications and demolition of these existing features of the work.

A10: Yes. Cost for meeting the requirement of EM-385 06.C.02 shall be included in this contract.

(End of Summary of Changes)