Attachment 1 - Specs_Equipment Locations.pdf

PDF 2 MB Posted

Attached to
SCIF In-a-Box Concrete Pad Construction Federal contract opportunity
Solicitation number
W911S822Q0002
Issued by
Department of the Army Materiel Command Mission and Installation Contracting Command Joint Base Lewis-McChord

View the file

Other files for this federal contract opportunity

Other files attached to SCIF In-a-Box Concrete Pad Construction, newest first.
File Type Posted
Contractor QA 05 APR 2022.pdf PDF
W991S822Q0002 - 0001 (Released).pdf PDF
Attachment 2 - Site Pictures_PDS.pdf PDF
W991S822Q0002 (Released).pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

eric.c.coday Text Box Project Location

Existing transformer and MDP here

New feeder.

Exact route TBD by KTR

New concrete equipment pad eric.c.coday Callout Electrical stub up to be in this approximate location eric.c.coday Line eric.c.coday Callout New communications duct. Exact route TBD by KTR eric.c.coday Highlight eric.c.coday Line eric.c.coday Callout The highlighted section of fence will be re-aligned to match the blue line shown via another task order.

eric.c.coday Line eric.c.coday Line eric.c.coday Callout Existing abandoned comm duct eric.c.coday Line eric.c.coday Callout

BLDG 9114

Line

CEC1

Existing utilities to be field verified by the KTR. Note: currently awarded construction contract is installing underground utilities in this same area.

45'

27'

10'

ISOMETRIC VIEW

EXTERIOR LIGHT

GROUNDING LUG

ANCHOR BRACKET

6"

1:70

DESCRIPTION

SHEET

DRAWN BY

DATE DRAWN

APPROVED BY

SCALE

SHEET SIZE

DRAWING NO.

APPROX. SHIPPING WT. IN LBS.

C O R P O R A T I O N LINING

SERIAL #

UNIT LENGTH

CUSTOMER

UNIT SPEC

UNIT TYPE

LOCATION

REVISION

B

1 OF

LEGEND:

KILL SWITCH

DURESS

ELECTRIC RECEPTACLE

DOUBLE STACKED

SINGLE STACKED

EMERGENCY LIGHT

TELEPHONE JACK

LAN CONNECTION

SEISMIC SENSOR

SMOKE DETECTION

PIR

BULLET TRAP

DS

EMR

P L

SS

SE

SM

PIR

BT

LEGEND CONTINUED:

THERMOSTAT

GROUND

THIS DRAWING IS THE PROPERTY OF ARMAG

CORPORATION WHO CLAIMS PROPRIETARY RIGHTS

IN THE MATERIAL DISCLOSED. IT IS ISSUED IN

CONFIDENCE FOR ENGINEERING INFORMATION

ONLY AND MAY NOT BE COPIED OR USED FOR

MANUFACTURE OF ANYTHING SHOWN WITHOUT

SPECIFIC PERMISSION FROM ARMAG CORPORATION

UNLESS OTHERWISE NOTED, TOLERANCES ARE:

MACHINED SURFACES: 125 MICRO-INCHES

THESE TOLERANCES DO NOT APPLY TO BASIC DIMS.

DRAWN TO SCALE UNLESS OTHERWISE NOTED

TK

D

UNIT WIDTH UNIT HEIGHT

QUOTE #

EXT. FINISH

S3199

02IDH

08/17/2021

10995-01 37267ADS

45' 27' 10'

ARC VAULT

ICD 705

124,000

ADS

JOINT BASE LEWIS MCCHORD, WA

ARC VAULT DUPLEX WITH (4) 24" NETWORK CABINETS, 250 A POWER

FILTER, BARD HVAC UNIT, PED LOCKER, ACOUSTIC INTERIOR DOOR,

RECEPTACLE, LAN DROP, AND EXIT DOOR

STC 50 "HAZE GRAY" - DEVTHANE 349QC

eric.c.coday

New equipment to be set in place by others

TYPICAL GROUNDING KIT

COPPER BONDING

PLATE IS BRAZED TO

1/4" MILD STEEL PLATE

GROUND CLAMP

COPPER CLAD GROUND ROD

OTHERS PER NEC REQUIREMENTS

COPPER CONDUCTOR

- 28 STRANDS OF #14 AWG

COPPER WIRE IN ROPE LAY

- 121,900 CIRCULAR MIL

CROSS SECTION

TERMINALS PRE-WIRED TO

FILTER

(4) SCREW TERMINAL LUG BLOCK

FOR UTILITY POWER CONNECTION

SCREW TERMINAL GROUND LUG

POWER TERMINAL BOX

N. T. S.

DESCRIPTION

SHEET

DRAWN BY

DATE DRAWN

APPROVED BY

SCALE

SHEET SIZE

DRAWING NO.

APPROX. SHIPPING WT. IN LBS.

C O R P O R A T I O N LINING

SERIAL #

UNIT LENGTH

CUSTOMER

UNIT SPEC

UNIT TYPE

LOCATION

REVISION

B

9 OF

LEGEND:

KILL SWITCH

DURESS

ELECTRIC RECEPTACLE

DOUBLE STACKED

SINGLE STACKED

EMERGENCY LIGHT

TELEPHONE JACK

LAN CONNECTION

SEISMIC SENSOR

SMOKE DETECTION

PIR

BULLET TRAP

DS

EMR

P L

SS

SE

SM

PIR

BT

LEGEND CONTINUED:

THERMOSTAT

GROUND

THIS DRAWING IS THE PROPERTY OF ARMAG

CORPORATION WHO CLAIMS PROPRIETARY RIGHTS

IN THE MATERIAL DISCLOSED. IT IS ISSUED IN

CONFIDENCE FOR ENGINEERING INFORMATION

ONLY AND MAY NOT BE COPIED OR USED FOR

MANUFACTURE OF ANYTHING SHOWN WITHOUT

SPECIFIC PERMISSION FROM ARMAG CORPORATION

UNLESS OTHERWISE NOTED, TOLERANCES ARE:

MACHINED SURFACES: 125 MICRO-INCHES

THESE TOLERANCES DO NOT APPLY TO BASIC DIMS.

DRAWN TO SCALE UNLESS OTHERWISE NOTED

TK

D

UNIT WIDTH UNIT HEIGHT

QUOTE #

EXT. FINISH

S3199

02IDH

08/17/2021

10995-01 37267ADS

45' 27' 10'

ARC VAULT

ICD 705

124,000

ADS

JOINT BASE LEWIS MCCHORD, WA

ARC VAULT DUPLEX WITH (4) 24" NETWORK CABINETS, 250 A POWER

FILTER, BARD HVAC UNIT, PED LOCKER, ACOUSTIC INTERIOR DOOR,

RECEPTACLE, LAN DROP, AND EXIT DOOR

STC 50 "HAZE GRAY" - DEVTHANE 349QC

BRK. VOLTS

AMPS /

POLES

DESCRIPTION

LOAD (VA)

DESCRIPTION

AMPS /

POLES

VOLTS BRK.

A B C

208 50/3 HVAC WA-1 (W36)

5644 / 5644

HVAC WA-2 (W36) 50/3 208

3 5644 / 5644 4

5 5644 / 5644 6

208 20/2 HAC CR (38MPR)

1560 / 520 CCTV / VESTIBULE 20/1 120 8

9 1560 / 800 LIGHTING 20/1 120 10

11 120 20/1 WA-1 WORKSTATION #1-2 1200 / 1200 WA-1 WORKSTATION #3-4 20/1 120 12

13 120 20/1 WA-1 WORKSTATION #5-6 1200 / 1200 WA-1 WORKSTATION #7-8 20/1 120 14

15 120 20/1 WA-1 WORKSTATION #9-10 1200 / 1200 WA-1 WORKSTATION #11-12 20/1 120 16

17 120 20/1 WA-2 WORKSTATION #1-3 1800 / 1200 WA-2 WORKSTATION #4-5 20/1 120 18

19 120 20/1 WA-2 WORKSTATION #6-7 1200 / 1000 NETWORK CABINET #1 20/1 120 20

21 120 20/1 NETWORK CABINET #2 1000 / 1000 NETWORK CABINET #3 20/1 120 22

23 120 20/1 NETWORK CABINET #4 1000 / 1100 CR DESK / VTC 20/1 120 24

25 120 20/1 PRINTER 1000 / 500 IDS / ACS / FIRE 20/1 120 26

27 120 20/1 SHREDDER 1700 / - SPARE 20/1 120 28

29 120 20/1 SPARE - / - SPARE 20/1 120 30

CONNECTED LOAD PER PHASE 19468 19748 18788

TOTAL CONNECTED LOAD (KVA) 58.0 (161.0 AMPS)

120/208V 3-PHASE 60 Hz

POWER DISTRIBUTION

200A MAIN BREAKER

PANELBOARD

EXTERIOR JUNCTION BOX,

PRE-WIRED TO FILTER

4-LINE 250A POWER

FILTER

eric.c.coday

New equipment electrical

SCALE: N.T.S.

# 4 BARS,

AT 12" O.C.

EA.WAY (TYP)

SLAB REINF.

SLAB EDGE DETAIL

TOP OF FINISHED SLAB

S3

8" CRUSHED AGGREGATE

BASE COURSE

COMPACTED TO 95%

SUBGRADE

1" SAW CUT

CONTROL JOINT REINF. W/ #4 REBAR

@ 12" O.C. EA. WAY

SCALE: N.T.S.

CROSS SECTION

S2

SCALE: N.T.S.

PLAN VIEW

S1

SAW CUT CONTROL

JOINT AT MIDDLE

OF SLAB

1" CHAMFER

4,000 PSI PORTLAND

CEMENT CONCRETE

COMPACTED

SUBGRADE

8" AGGREGATE

BASE COURSE

COMPACTED

TO 95%

WP

15"

6"

4"

2"

1 1/2" - 2X

2"

2X Ø7/8" HOLE

5 1/4" X 3 1/4" X 3/8" GUSSET

6" X 4" X 3/8" ANGLE

OPTION 6B - 15" Anchor bracket with bolts eric.c.coday

Mounting of new equipment to be completed in CLIN 0003

TThhee OOrriiggiinnaall WWeeddggee AAnncchhoorrss

MAXIMUM TENSILE AND SHEAR CAPACITY FOR STATIC LOADS

LIMESTONE UNREINFORCED STONE AGGREGATE CONCRETE UNREINFORCED

AGGREGATE ZINC PLATED CARBON STEEL LIGHTWEIGHT (IDEALITE)

Anchor Embed- 2000 psi Embed- 3000 psi 5000 psi 7000 psi Embed- 5000 psi & Hole ment Tension Shear ment Tension Shear Tension Shear Tension Shear ment Tension Shear Size (in) (lbs) (lbs) (in) (lbs) (lbs) (lbs) (lbs) (lbs) (lbs) (in) (lbs) (lbs)

1/4 1 1/8 1132 1211 1 1/8 1320 1751 1760 2316 2464 2494 1 1/2 1861 1947 1/4 1 3/4 1256 1211 1 1/2 1856 1751 2473 2316 3462 2494 • • • 5/16 1 1/4 1308 1210 1 1/4 2057 1839 2742 2530 3939 3439 1 1/2 2493 3064 5/16 2 1181 1210 1 3/4 2389 1839 3185 2530 4459 3439 • • • 3/8 1 1/4 994 1223 1 1/2 2876 4286 3834 5213 5368 5658 1 3/4 3125 4289 3/8 4 1728 1223 4 3488 4286 4650 5213 6510 5658 • • • 1/2 1 3/4 1542 3009 2 1/4 3473 7138 5789 10748 8105 11550 2 1/4 4778 9833 1/2 6 2695 3009 5 4809 7138 8015 10748 11221 11550 • • • 5/8 • • • 3 1/2 7582 10719 12636 15583 17690 16700 2 1/2 6455 12500 5/8 • • • 4 3/4 9179 10719 15299 15583 21419 16700 • • • 3/4 • • • 3 11579 15537 19299 21000 27019 23103 3 1/2 17293 19050 3/4 • • • 7 15444 15537 25740 21000 36036 23103 • • • 7/8 • • • 4 1/2 15266 • 25444 25099 33622 28718 • • • 7/8 • • • 7 16992 • 28320 25099 39648 28718 • • • 1 • • • 5 1/2 16351 • 27252 33083 38153 35700 4 1/2 21616 31666 1 • • • 7 17837 • 29728 33083 41619 35700 • • • Source 1 2 2 Sources (available upon request): 1) University of Texas, Austin, TX (using new ICBO-ES testing criteria); 1993. 2) AA Engineers & Associates, Inc., Denver, CO; 1981.

KEY FEATURES/BENEFITS

! Time-Tested, Proven Reliability. An industry standard for over 50 years.

! Fully Assembled and Ready to Use. Unparalleled job-site convenience.

! BOLT SIZE IS HOLE SIZE.® Allows precision placement of equipment through pre-drilled holes.

! Exclusive “Positive Wedge Connections.”

Minimizes wedge loosening due to vibratory loads.

*Drill Bits on Page 11-13

SPECIFICATIONS, APPROVALS AND LISTINGS

TYPE

Zinc Plating ASTM B-633, Type III, SCI State DOT Please call Customer Service for Approvals specific information by state.

Federal QQZ-325C, Type II, Class 3 Specifications (Clear Chromate added)

FFS-325, Group II, Type 4, Class 1 Formerly ICC-ES Legacy Report #1821* The Original Wej-it™ anchor complies with the 1997 uniform Building Code (UBC) the 2000 International Building Code (IBC), and the 2000 International Residents Code, Data Test in accordance with the ICC-ES criteria for Expansion anchors in Concrete and Masonry Elements (ACOI) dated April 2002.

Available upon Request.

NOTES:

! Information provided only for the use of a qualified design engineer. Use of technical data by persons not qualified could cause serious damage, injury, or even death.

! Ultimate values shown. For static loads, use one-fourth of the maximum tensile and shear capacities for the recommended 4:1 safety factor.

! Tested to ASTM E-488 Test Standard.

! Sources (available upon request): 1) U.S. Testing Co., Tulsa, OK

LENGTH SELECTION GUIDE

Minimum Embedment (A) + Material Thickness + (B) + Bolt Diameter + (C) = Total Anchor Length = (D)

Nut thickness = bolt diameter Material thickness

Minimum embedment

(C) (B)

(D)

(A) www.wejit.com800-343-1264 WEJ-IT FASTENING SYSTEMS - 14

Martin Highlight eric.c.coday

Mounting hardware will be provided by equipment manufacturer

INSTALLATION INSTRUCTIONS

1. Drill the hole perpendicular to the work surface with a solid carbide bit that meets ANSI B212.5 specifications. The drill bit diameter will be the same as the anchor diameter that you are installing.* To assure full holding power, do not ream the hole or allow the drill to wobble.

2. Drill the hole 1 diameter deeper than the intended embedment of the anchor, but not closer than two diameters to the bottom (opposite) surface of the concrete.

3. Clean the hole using compressed air and a nylon brush.

A clean hole is necessary for proper performance.

4. Insert anchor into hole until washer rests solidly against fixture.

5. Tighten 1 1/2 to 3 turns past hand tight position but to a maximum torque as listed below:

ORDER INFORMATION

Catalog Number Anchor Minimum Thread

Carbon Steel Diameter Embedment Length Quantity Zinc Plated & Length (in) (in) (in) Box/Carton

1413 1/4 x 1 3/4 1 1/2 100/600 Z1413 20/400 1423 1/4 x 2 3/4 1 1/2 100/600 Z1423 20/400 1430 1/4 x 3 1 1/2 100/600 Z1430 20/400 5620 5/16 x 2 1 1/4 5/8 100/600 Z5620 20/400 5630 5/16 x 3 1 1/4 5/8 100/600 Z5630 20/400 3820 3/8 x 2 1 1/2 3/4 100/600 Z3820 20/400 3823 3/8 x 2 3/4 1 1/2 3/4 100/600 Z3823 20/400 3832 3/8 x 3 1/2 1 1/2 3/4 50/300 Z3832 20/200 3850 3/8 x 5 1 1/2 3/4 50/300 Z3850 20/200 3860 3/8 x 6 1 1/2 3/4 50/300 Z3860 10/200 1223 1/2 x 2 3/4 2 1 50/300 Z1223 10/200 1232 1/2 x 3 1/2 2 1 50/300 Z1232 10/200 1250 1/2 x 5 2 1 25/150 Z1250 10/100 1260 1/2 x 6 2 1 25/150 Z1260 10/100 1270 1/2 x 7 2 1 25/150 Z1270 10/1000 5832 5/8 x 3 1/2 3 1 1/4 25/150 Z5832 5/50 5842 5/8 x 4 1/2 3 1 1/4 25/150 Z5842 5/50 5850 5/8 x 5 3 1 1/4 20/120 Z5850 5/50 5860 5/8 x 6 3 1 1/4 15/90 Z5860 5/50 5870 5/8 x 7 3 1 1/4 15/90 Z5870 5/50 3440 3/4 x 4 3 1 1/2 18/108 Z3440 5/50 3450 3/4 x 5 3 1 1/2 12/72 Z3450 5/50 3460 3/4 x 6 3 1 1/2 12/72 Z3460 5/50 3470 3/4 x 7 3 1 1/2 10/60 Z3470 5/50 3482 3/4 x 8 1/2 3 1 1/2 10/30 Z3482 5/50 3410 3/4 x 10 3 1 1/2 10/30 7880 7/8 x 8 4 1/2 1 3/4 10/30 7810 7/8 x 10 4 1/2 1 3/4 10/30 7812 7/8 x 12 4 1/2 1 3/4 5/15 1080 1 x 8 5 1/2 2 10/30 1010 1 x 10 5 1/2 2 5/15 1012 1 x 12 5 1/2 2 5/15

1-2 3 4 5

Catalog Number Anchor Minimum Anchors Quantity Carded Diameter & Embedment Per Cards Per

Drill Bit Included Length (in) (in) Card Box/Carton DB1413 1/4 x 1 3/4 1 6 10/60 DB1423 1/4 x 2 3/4 1 6 10/60 DB1430 1/4 x 3 1 6 10/60 DB3820 3/8 x 2 1 1/2 4 10/60 DB3823 3/8 x 2 3/4 1 1/2 4 10/60 DB3832 3/8 x 3 1/2 1 1/2 4 10/60 DB1223 1/2 x 2 3/4 2 4 5/30 DB1232 1/2 x 3 1/2 2 2 5/30

EDGE DISTANCE AND SPACING REQUIREMENTS

Embedment (E) in Spacing Edge Anchor Diameters Distance E�6d (shallow) 3.5E 1.75E 6d�E�8d (standard) 2.00E 1.00E 8d�E (deep) 1.50E 0.75E

RECOMMENDED EDGE DISTANCE & SPACING

Edge

Anchor Embedment Distance Spacing Diameter Depth Requirements Requirements

1/4 1 1/8 1 31/32 3 15/16 1/4 1 1/2 2 5/8 5 1/4 5/16 1 1/4 2 3/16 4 3/8 5/16 1 3/4 3 1/16 6 1/8 3/8 1 1/2 2 5/8 5 1/4 3/8 4 3 6 1/2 2 1/4 3 15/16 7 7/8 1/2 5 3 3/4 7 1/2 5/8 3 1/2 6 1/8 12 1/4 5/8 4 3/4 8 5/16 16 5/8 3/4 3 5 1/4 10 1/2 3/4 7 5 1/4 10 1/2 7/8 4 1/2 7 7/8 15 3/4 7/8 7 7 14 1 5 1/2 9 5/8 19 1/4 1 7 7 14

* Always wear safety glasses. Follow drill manufacturer’s instructions.

Use only solid carbide-tipped drill bits meeting ANSI B212.15 diameter standards as listed on back cover.

TORQUE VALUES

Anchor Recommended Recommended

Diameter Setting Torque Minimum

(in) (ft lb) Embedment (in) 1/4 8 1 5/16 15 1 1/4 3/8 25 1 1/2 1/2 55 2 5/8 95 3 3/4 170 3 7/8 250 4 1/2 1 300 5 1/2 www.wejit.com 800-343-126415 - WEJ-IT FASTENING SYSTEMS

Martin Highlight

Martin Highlight

Martin Highlight

Martin Highlight

Martin Highlight

Martin Highlight

Chris Highlight

Slide Number 1
Slide Number 2