eric.c.coday Text Box Project Location
Existing transformer and MDP here
New feeder.
Exact route TBD by KTR
New concrete equipment pad eric.c.coday Callout Electrical stub up to be in this approximate location eric.c.coday Line eric.c.coday Callout New communications duct. Exact route TBD by KTR eric.c.coday Highlight eric.c.coday Line eric.c.coday Callout The highlighted section of fence will be re-aligned to match the blue line shown via another task order.
eric.c.coday Line eric.c.coday Line eric.c.coday Callout Existing abandoned comm duct eric.c.coday Line eric.c.coday Callout
BLDG 9114
Line
CEC1
Existing utilities to be field verified by the KTR. Note: currently awarded construction contract is installing underground utilities in this same area.
45'
27'
10'
ISOMETRIC VIEW
EXTERIOR LIGHT
GROUNDING LUG
ANCHOR BRACKET
6"
1:70
DESCRIPTION
SHEET
DRAWN BY
DATE DRAWN
APPROVED BY
SCALE
SHEET SIZE
DRAWING NO.
APPROX. SHIPPING WT. IN LBS.
C O R P O R A T I O N LINING
SERIAL #
UNIT LENGTH
CUSTOMER
UNIT SPEC
UNIT TYPE
LOCATION
REVISION
B
1 OF
LEGEND:
KILL SWITCH
DURESS
ELECTRIC RECEPTACLE
DOUBLE STACKED
SINGLE STACKED
EMERGENCY LIGHT
TELEPHONE JACK
LAN CONNECTION
SEISMIC SENSOR
SMOKE DETECTION
PIR
BULLET TRAP
DS
EMR
P L
SS
SE
SM
PIR
BT
LEGEND CONTINUED:
THERMOSTAT
GROUND
THIS DRAWING IS THE PROPERTY OF ARMAG
CORPORATION WHO CLAIMS PROPRIETARY RIGHTS
IN THE MATERIAL DISCLOSED. IT IS ISSUED IN
CONFIDENCE FOR ENGINEERING INFORMATION
ONLY AND MAY NOT BE COPIED OR USED FOR
MANUFACTURE OF ANYTHING SHOWN WITHOUT
SPECIFIC PERMISSION FROM ARMAG CORPORATION
UNLESS OTHERWISE NOTED, TOLERANCES ARE:
MACHINED SURFACES: 125 MICRO-INCHES
THESE TOLERANCES DO NOT APPLY TO BASIC DIMS.
DRAWN TO SCALE UNLESS OTHERWISE NOTED
TK
D
UNIT WIDTH UNIT HEIGHT
QUOTE #
EXT. FINISH
S3199
02IDH
08/17/2021
10995-01 37267ADS
45' 27' 10'
ARC VAULT
ICD 705
124,000
ADS
JOINT BASE LEWIS MCCHORD, WA
ARC VAULT DUPLEX WITH (4) 24" NETWORK CABINETS, 250 A POWER
FILTER, BARD HVAC UNIT, PED LOCKER, ACOUSTIC INTERIOR DOOR,
RECEPTACLE, LAN DROP, AND EXIT DOOR
STC 50 "HAZE GRAY" - DEVTHANE 349QC
eric.c.coday
New equipment to be set in place by others
TYPICAL GROUNDING KIT
COPPER BONDING
PLATE IS BRAZED TO
1/4" MILD STEEL PLATE
GROUND CLAMP
COPPER CLAD GROUND ROD
OTHERS PER NEC REQUIREMENTS
COPPER CONDUCTOR
- 28 STRANDS OF #14 AWG
COPPER WIRE IN ROPE LAY
- 121,900 CIRCULAR MIL
CROSS SECTION
TERMINALS PRE-WIRED TO
FILTER
(4) SCREW TERMINAL LUG BLOCK
FOR UTILITY POWER CONNECTION
SCREW TERMINAL GROUND LUG
POWER TERMINAL BOX
N. T. S.
DESCRIPTION
SHEET
DRAWN BY
DATE DRAWN
APPROVED BY
SCALE
SHEET SIZE
DRAWING NO.
APPROX. SHIPPING WT. IN LBS.
C O R P O R A T I O N LINING
SERIAL #
UNIT LENGTH
CUSTOMER
UNIT SPEC
UNIT TYPE
LOCATION
REVISION
B
9 OF
LEGEND:
KILL SWITCH
DURESS
ELECTRIC RECEPTACLE
DOUBLE STACKED
SINGLE STACKED
EMERGENCY LIGHT
TELEPHONE JACK
LAN CONNECTION
SEISMIC SENSOR
SMOKE DETECTION
PIR
BULLET TRAP
DS
EMR
P L
SS
SE
SM
PIR
BT
LEGEND CONTINUED:
THERMOSTAT
GROUND
THIS DRAWING IS THE PROPERTY OF ARMAG
CORPORATION WHO CLAIMS PROPRIETARY RIGHTS
IN THE MATERIAL DISCLOSED. IT IS ISSUED IN
CONFIDENCE FOR ENGINEERING INFORMATION
ONLY AND MAY NOT BE COPIED OR USED FOR
MANUFACTURE OF ANYTHING SHOWN WITHOUT
SPECIFIC PERMISSION FROM ARMAG CORPORATION
UNLESS OTHERWISE NOTED, TOLERANCES ARE:
MACHINED SURFACES: 125 MICRO-INCHES
THESE TOLERANCES DO NOT APPLY TO BASIC DIMS.
DRAWN TO SCALE UNLESS OTHERWISE NOTED
TK
D
UNIT WIDTH UNIT HEIGHT
QUOTE #
EXT. FINISH
S3199
02IDH
08/17/2021
10995-01 37267ADS
45' 27' 10'
ARC VAULT
ICD 705
124,000
ADS
JOINT BASE LEWIS MCCHORD, WA
ARC VAULT DUPLEX WITH (4) 24" NETWORK CABINETS, 250 A POWER
FILTER, BARD HVAC UNIT, PED LOCKER, ACOUSTIC INTERIOR DOOR,
RECEPTACLE, LAN DROP, AND EXIT DOOR
STC 50 "HAZE GRAY" - DEVTHANE 349QC
BRK. VOLTS
AMPS /
POLES
DESCRIPTION
LOAD (VA)
DESCRIPTION
AMPS /
POLES
VOLTS BRK.
A B C
208 50/3 HVAC WA-1 (W36)
5644 / 5644
HVAC WA-2 (W36) 50/3 208
3 5644 / 5644 4
5 5644 / 5644 6
208 20/2 HAC CR (38MPR)
1560 / 520 CCTV / VESTIBULE 20/1 120 8
9 1560 / 800 LIGHTING 20/1 120 10
11 120 20/1 WA-1 WORKSTATION #1-2 1200 / 1200 WA-1 WORKSTATION #3-4 20/1 120 12
13 120 20/1 WA-1 WORKSTATION #5-6 1200 / 1200 WA-1 WORKSTATION #7-8 20/1 120 14
15 120 20/1 WA-1 WORKSTATION #9-10 1200 / 1200 WA-1 WORKSTATION #11-12 20/1 120 16
17 120 20/1 WA-2 WORKSTATION #1-3 1800 / 1200 WA-2 WORKSTATION #4-5 20/1 120 18
19 120 20/1 WA-2 WORKSTATION #6-7 1200 / 1000 NETWORK CABINET #1 20/1 120 20
21 120 20/1 NETWORK CABINET #2 1000 / 1000 NETWORK CABINET #3 20/1 120 22
23 120 20/1 NETWORK CABINET #4 1000 / 1100 CR DESK / VTC 20/1 120 24
25 120 20/1 PRINTER 1000 / 500 IDS / ACS / FIRE 20/1 120 26
27 120 20/1 SHREDDER 1700 / - SPARE 20/1 120 28
29 120 20/1 SPARE - / - SPARE 20/1 120 30
CONNECTED LOAD PER PHASE 19468 19748 18788
TOTAL CONNECTED LOAD (KVA) 58.0 (161.0 AMPS)
120/208V 3-PHASE 60 Hz
POWER DISTRIBUTION
200A MAIN BREAKER
PANELBOARD
EXTERIOR JUNCTION BOX,
PRE-WIRED TO FILTER
4-LINE 250A POWER
FILTER
eric.c.coday
New equipment electrical
SCALE: N.T.S.
# 4 BARS,
AT 12" O.C.
EA.WAY (TYP)
SLAB REINF.
SLAB EDGE DETAIL
TOP OF FINISHED SLAB
S3
8" CRUSHED AGGREGATE
BASE COURSE
COMPACTED TO 95%
SUBGRADE
1" SAW CUT
CONTROL JOINT REINF. W/ #4 REBAR
@ 12" O.C. EA. WAY
SCALE: N.T.S.
CROSS SECTION
S2
SCALE: N.T.S.
PLAN VIEW
S1
SAW CUT CONTROL
JOINT AT MIDDLE
OF SLAB
1" CHAMFER
4,000 PSI PORTLAND
CEMENT CONCRETE
COMPACTED
SUBGRADE
8" AGGREGATE
BASE COURSE
COMPACTED
TO 95%
WP
15"
6"
4"
2"
1 1/2" - 2X
2"
2X Ø7/8" HOLE
5 1/4" X 3 1/4" X 3/8" GUSSET
6" X 4" X 3/8" ANGLE
OPTION 6B - 15" Anchor bracket with bolts eric.c.coday
Mounting of new equipment to be completed in CLIN 0003
TThhee OOrriiggiinnaall WWeeddggee AAnncchhoorrss
MAXIMUM TENSILE AND SHEAR CAPACITY FOR STATIC LOADS
LIMESTONE UNREINFORCED STONE AGGREGATE CONCRETE UNREINFORCED
AGGREGATE ZINC PLATED CARBON STEEL LIGHTWEIGHT (IDEALITE)
Anchor Embed- 2000 psi Embed- 3000 psi 5000 psi 7000 psi Embed- 5000 psi & Hole ment Tension Shear ment Tension Shear Tension Shear Tension Shear ment Tension Shear Size (in) (lbs) (lbs) (in) (lbs) (lbs) (lbs) (lbs) (lbs) (lbs) (in) (lbs) (lbs)
1/4 1 1/8 1132 1211 1 1/8 1320 1751 1760 2316 2464 2494 1 1/2 1861 1947 1/4 1 3/4 1256 1211 1 1/2 1856 1751 2473 2316 3462 2494 • • • 5/16 1 1/4 1308 1210 1 1/4 2057 1839 2742 2530 3939 3439 1 1/2 2493 3064 5/16 2 1181 1210 1 3/4 2389 1839 3185 2530 4459 3439 • • • 3/8 1 1/4 994 1223 1 1/2 2876 4286 3834 5213 5368 5658 1 3/4 3125 4289 3/8 4 1728 1223 4 3488 4286 4650 5213 6510 5658 • • • 1/2 1 3/4 1542 3009 2 1/4 3473 7138 5789 10748 8105 11550 2 1/4 4778 9833 1/2 6 2695 3009 5 4809 7138 8015 10748 11221 11550 • • • 5/8 • • • 3 1/2 7582 10719 12636 15583 17690 16700 2 1/2 6455 12500 5/8 • • • 4 3/4 9179 10719 15299 15583 21419 16700 • • • 3/4 • • • 3 11579 15537 19299 21000 27019 23103 3 1/2 17293 19050 3/4 • • • 7 15444 15537 25740 21000 36036 23103 • • • 7/8 • • • 4 1/2 15266 • 25444 25099 33622 28718 • • • 7/8 • • • 7 16992 • 28320 25099 39648 28718 • • • 1 • • • 5 1/2 16351 • 27252 33083 38153 35700 4 1/2 21616 31666 1 • • • 7 17837 • 29728 33083 41619 35700 • • • Source 1 2 2 Sources (available upon request): 1) University of Texas, Austin, TX (using new ICBO-ES testing criteria); 1993. 2) AA Engineers & Associates, Inc., Denver, CO; 1981.
KEY FEATURES/BENEFITS
! Time-Tested, Proven Reliability. An industry standard for over 50 years.
! Fully Assembled and Ready to Use. Unparalleled job-site convenience.
! BOLT SIZE IS HOLE SIZE.® Allows precision placement of equipment through pre-drilled holes.
! Exclusive “Positive Wedge Connections.”
Minimizes wedge loosening due to vibratory loads.
*Drill Bits on Page 11-13
SPECIFICATIONS, APPROVALS AND LISTINGS
TYPE
Zinc Plating ASTM B-633, Type III, SCI State DOT Please call Customer Service for Approvals specific information by state.
Federal QQZ-325C, Type II, Class 3 Specifications (Clear Chromate added)
FFS-325, Group II, Type 4, Class 1 Formerly ICC-ES Legacy Report #1821* The Original Wej-it™ anchor complies with the 1997 uniform Building Code (UBC) the 2000 International Building Code (IBC), and the 2000 International Residents Code, Data Test in accordance with the ICC-ES criteria for Expansion anchors in Concrete and Masonry Elements (ACOI) dated April 2002.
Available upon Request.
NOTES:
! Information provided only for the use of a qualified design engineer. Use of technical data by persons not qualified could cause serious damage, injury, or even death.
! Ultimate values shown. For static loads, use one-fourth of the maximum tensile and shear capacities for the recommended 4:1 safety factor.
! Tested to ASTM E-488 Test Standard.
! Sources (available upon request): 1) U.S. Testing Co., Tulsa, OK
LENGTH SELECTION GUIDE
Minimum Embedment (A) + Material Thickness + (B) + Bolt Diameter + (C) = Total Anchor Length = (D)
Nut thickness = bolt diameter Material thickness
Minimum embedment
(C) (B)
(D)
(A) www.wejit.com800-343-1264 WEJ-IT FASTENING SYSTEMS - 14
Martin Highlight eric.c.coday
Mounting hardware will be provided by equipment manufacturer
INSTALLATION INSTRUCTIONS
1. Drill the hole perpendicular to the work surface with a solid carbide bit that meets ANSI B212.5 specifications. The drill bit diameter will be the same as the anchor diameter that you are installing.* To assure full holding power, do not ream the hole or allow the drill to wobble.
2. Drill the hole 1 diameter deeper than the intended embedment of the anchor, but not closer than two diameters to the bottom (opposite) surface of the concrete.
3. Clean the hole using compressed air and a nylon brush.
A clean hole is necessary for proper performance.
4. Insert anchor into hole until washer rests solidly against fixture.
5. Tighten 1 1/2 to 3 turns past hand tight position but to a maximum torque as listed below:
ORDER INFORMATION
Catalog Number Anchor Minimum Thread
Carbon Steel Diameter Embedment Length Quantity Zinc Plated & Length (in) (in) (in) Box/Carton
1413 1/4 x 1 3/4 1 1/2 100/600 Z1413 20/400 1423 1/4 x 2 3/4 1 1/2 100/600 Z1423 20/400 1430 1/4 x 3 1 1/2 100/600 Z1430 20/400 5620 5/16 x 2 1 1/4 5/8 100/600 Z5620 20/400 5630 5/16 x 3 1 1/4 5/8 100/600 Z5630 20/400 3820 3/8 x 2 1 1/2 3/4 100/600 Z3820 20/400 3823 3/8 x 2 3/4 1 1/2 3/4 100/600 Z3823 20/400 3832 3/8 x 3 1/2 1 1/2 3/4 50/300 Z3832 20/200 3850 3/8 x 5 1 1/2 3/4 50/300 Z3850 20/200 3860 3/8 x 6 1 1/2 3/4 50/300 Z3860 10/200 1223 1/2 x 2 3/4 2 1 50/300 Z1223 10/200 1232 1/2 x 3 1/2 2 1 50/300 Z1232 10/200 1250 1/2 x 5 2 1 25/150 Z1250 10/100 1260 1/2 x 6 2 1 25/150 Z1260 10/100 1270 1/2 x 7 2 1 25/150 Z1270 10/1000 5832 5/8 x 3 1/2 3 1 1/4 25/150 Z5832 5/50 5842 5/8 x 4 1/2 3 1 1/4 25/150 Z5842 5/50 5850 5/8 x 5 3 1 1/4 20/120 Z5850 5/50 5860 5/8 x 6 3 1 1/4 15/90 Z5860 5/50 5870 5/8 x 7 3 1 1/4 15/90 Z5870 5/50 3440 3/4 x 4 3 1 1/2 18/108 Z3440 5/50 3450 3/4 x 5 3 1 1/2 12/72 Z3450 5/50 3460 3/4 x 6 3 1 1/2 12/72 Z3460 5/50 3470 3/4 x 7 3 1 1/2 10/60 Z3470 5/50 3482 3/4 x 8 1/2 3 1 1/2 10/30 Z3482 5/50 3410 3/4 x 10 3 1 1/2 10/30 7880 7/8 x 8 4 1/2 1 3/4 10/30 7810 7/8 x 10 4 1/2 1 3/4 10/30 7812 7/8 x 12 4 1/2 1 3/4 5/15 1080 1 x 8 5 1/2 2 10/30 1010 1 x 10 5 1/2 2 5/15 1012 1 x 12 5 1/2 2 5/15
1-2 3 4 5
Catalog Number Anchor Minimum Anchors Quantity Carded Diameter & Embedment Per Cards Per
Drill Bit Included Length (in) (in) Card Box/Carton DB1413 1/4 x 1 3/4 1 6 10/60 DB1423 1/4 x 2 3/4 1 6 10/60 DB1430 1/4 x 3 1 6 10/60 DB3820 3/8 x 2 1 1/2 4 10/60 DB3823 3/8 x 2 3/4 1 1/2 4 10/60 DB3832 3/8 x 3 1/2 1 1/2 4 10/60 DB1223 1/2 x 2 3/4 2 4 5/30 DB1232 1/2 x 3 1/2 2 2 5/30
EDGE DISTANCE AND SPACING REQUIREMENTS
Embedment (E) in Spacing Edge Anchor Diameters Distance E�6d (shallow) 3.5E 1.75E 6d�E�8d (standard) 2.00E 1.00E 8d�E (deep) 1.50E 0.75E
RECOMMENDED EDGE DISTANCE & SPACING
Edge
Anchor Embedment Distance Spacing Diameter Depth Requirements Requirements
1/4 1 1/8 1 31/32 3 15/16 1/4 1 1/2 2 5/8 5 1/4 5/16 1 1/4 2 3/16 4 3/8 5/16 1 3/4 3 1/16 6 1/8 3/8 1 1/2 2 5/8 5 1/4 3/8 4 3 6 1/2 2 1/4 3 15/16 7 7/8 1/2 5 3 3/4 7 1/2 5/8 3 1/2 6 1/8 12 1/4 5/8 4 3/4 8 5/16 16 5/8 3/4 3 5 1/4 10 1/2 3/4 7 5 1/4 10 1/2 7/8 4 1/2 7 7/8 15 3/4 7/8 7 7 14 1 5 1/2 9 5/8 19 1/4 1 7 7 14
* Always wear safety glasses. Follow drill manufacturer’s instructions.
Use only solid carbide-tipped drill bits meeting ANSI B212.15 diameter standards as listed on back cover.
TORQUE VALUES
Anchor Recommended Recommended
Diameter Setting Torque Minimum
(in) (ft lb) Embedment (in) 1/4 8 1 5/16 15 1 1/4 3/8 25 1 1/2 1/2 55 2 5/8 95 3 3/4 170 3 7/8 250 4 1/2 1 300 5 1/2 www.wejit.com 800-343-126415 - WEJ-IT FASTENING SYSTEMS
Martin Highlight
Martin Highlight
Martin Highlight
Martin Highlight
Martin Highlight
Martin Highlight
Chris Highlight