INFRARED HEATING INSPECTION AND REPAIR
Solicitation number
W911KF-20-Q-0048
Issued by

About this file

This statement of work outlines requirements for a federal contract to perform inspection, maintenance, and repairs on heating equipment at Anniston Army Depot. The contractor will inspect and service approximately 560 gas-fired unit heaters, makeup air units, and infrared heaters across 48 buildings on the depot. Work includes cleaning, checking components, adjusting pressures and temperatures, troubleshooting ignition and burners, lubricating fans, and ensuring all systems meet manufacturer specifications. The contractor must have mechanical licensing and experience servicing gas heating equipment like Co-Ray-Vac systems. The one-year contract has a not-to-exceed limit for repairs that will be approved on a task order basis. The statement of work provides inspection requirements, responsibilities, schedules, safety and environmental compliance standards, and submittal requirements including inspection reports and building drawings.

View the file

Other files

File Type Posted
Amend 001.pdf PDF
Attachment 2 Wage Determination.pdf PDF
20-Q-0048.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Anniston Army Depot Directorate of Public Works Engineering Services Division Anniston, Alabama

Statement of Work

Project No. QA49-20

Infrared Heater Inspection and Repairs

Prepared by: Veronica Wilson, Project Engineer Anniston Army Depot Directorate of Public Works Engineering Services Division 7 Frankford Avenue Anniston, AL 36201

10 January 2020

Information contained in this document regarding commercial products or firms may not be used for advertising or promotional purposes and is not an endorsement of any product or firm by the Directorate of Public Works, Anniston Army Depot or the U.S. Army.

Statement of Work for Project QA49-20 Page 12

SECTION 1

GENERAL INFORMATION

1.1 DESCRIPTION OF WORK

The work to be performed under this contract consists of furnishing all plant, material, transportation, labor, equipment, coordination, planning, and supervision necessary to perform inspection, maintenance and repairs on approximately 560 Gas-Fired Unit Heaters, Make-Up Air Units, and Infrared Heaters located in approximately 48 buildings at Anniston Army Depot (ANAD). All work performed shall be completed per the manufacturer's specifications and in accordance with the contract specifications, this statement of work, drawings, and technical requirements.

1.2 LIMITATIONS

The general outline of work does not in any way limit the responsibility of the Contractor to perform all work and furnish all plant, labor, materials, and equipment required by the Statement of Work. The inclusion of any item in either the Statement of Work, the technical requirements, or the drawings shall be considered as part of the work to be done.

1.3 RESPONSIBILITIES

1.3.1 It shall be the responsibility of the Contractor to visit the site and become familiar with the job conditions at and surrounding the worksite(s) prior to mobilization. Additional items or materials which may be required for completion and finishing of the work indicated, even though such items may not be explicitly defined in the Statement of Work shall be an integral part of this contract.

1.3.2 Uniforms. Complete apparel shall be worn by all contract employees at all times. Apparel are selected by the Contractor, and shall provide a uniform appearance from one employee to the next including all visible outer clothing. Shorts are not permitted. Appropriateness of selected apparel is otherwise subject to review by the COR.

1.4 WORK SCHEDULE

1.4.1 Work shall be performed during normal Anniston Army Depot working hours, 0700 to 1630, Monday thru Thursday and 0700 to 1530 on alternate Fridays, except Building 400 and Federal Holidays.

Work in Building 400 shall be performed during working hours, 1630 to 0600. Working later in the day, Off Fridays, or weekend work shall occur only with rare exception and through Government authorization and at no additional cost to the Government.

1.4.2 DLA facilities are controlled areas and will require an escort at all times to be provided by DLA.

All work in these facilities will have to be scheduled one week (5 working days) prior to accessing the facility. No laydown area will be provided inside the building.

1.4.3 The Contractor shall prepare for approval a Work Schedule. Show in the schedule the sequence in which the Contractor proposes to perform the work and dates on which the Contractor contemplates starting and completing all schedule activities. The approved Work Schedule shall be used to measure the progress of the work and to aid in evaluating time extensions. The schedule shall be cost loaded and activity coded. The schedule will provide the basis for all progress payments.

Statement of Work for Project QA49-20 Page 13

1.5 PROTECTION OF GOVERNMENT PROPERTY AND SECURITY

During the performance of the contract, the Contractor shall provide adequate protection of all government property from damages that might occur as a result of any work being performed. Protection of the buildings shall apply to any work that is being done in or around the existing structure. Some buildings or areas for which work is to be performed is a secure work site and will therefore require a government escort at all times.

1.6 CLEANUP

The Contractor shall remove all debris and salvage items from jobsite daily and transport it to the designated disposal areas on depot. All items removed from a building remain the property of the Government.

1.7 LICENSES AND CERTIFICATIONS

All Contractors working on this contract, whether in-state or out-of-state, are required to have a state Mechanical license. The licensed Mechanical Contractor shall have experience in the installation and service of gas-fired heating equipment, specifically in Co-Ray-Vac Heating Systems. Prior to beginning work, the Contractor shall provide as a submittal, a copy of all licenses and past work history applicable to the work to be performed.

1.8 GENERAL SAFETY PROVISIONS

1.8.1 Compliance with Safety Laws and Regulations. The Contractor shall be responsible for insuring that all employees conform to the safety guidelines set forth by the Occupational Safety and Health Act, and accompanying OSHA regulations (OSHA-29CFR1926/1910), local depot safety rules and regulations, and other safety requirements as required by the specifications. This will include but not be limited to wearing eye and ear protection, safety shoes, and shirts with 4” minimum sleeves. Any violation of the safety requirements by any Contractor personnel shall be cause for removal of said personnel from the job site until violation is corrected.

1.8.2 Site Specific Safety Plan. The Contractor shall prepare and submit a Site Specific Safety Plan for this contract. This plan is a requirement of the OSHA Standard for Construction 29 CFR 1926. This plan shall show how health and safety will be managed on a specific site. The safety plan will be tailored to the project, based on the size and complexity of the work to be accomplished and shall include but not limited to fall protection and prevention program, Lock-Out Tag-Out Procedures, Personal Protective Equipment, Emergency Response Plans, Confined Space, Respiratory Protection Plan, and Hazard Communication.

One (1) electronic copy (.pdf format) of this plan shall be submitted for review and approval within two

(2) weeks after contract award.

1.8.3 Quality Control Plan. The Contractor shall prepare and submit a Quality Control Plan for executing this contract. The Quality Control Plan shall describe the way in which the Contractor will produce the deliverables, and the step-by-step approach that will be taken to ensure the quality of the services are delivered.

1.8.4 Safety Training. ANAD Safety Office will conduct visitor safety training. All Contractors performing work on Anniston Army Depot shall complete the training prior to start of work.

Statement of Work for Project QA49-20 Page 14

1.9 GENERAL ENVIRONMENTAL PROVISIONS

1.9.1 Compliance with Environmental Laws and Regulations: The Contractor shall comply with all applicable federal, state, and local environmental laws, statutes, regulations, executive orders, permits, Army regulations (with supplements), as well as Major Subordinate Command (MSC) and installation regulations and policies. The Contractor shall immediately report any conflicts between applicable federal, state, local environmental laws, statutes, executive orders, and provisions of Army Regulation 200-1, and any specifications within this contract to DRK and DPW via the COR.

1.9.2 Resource Conservation and Recovery Act (RCRA) Training. ANAD Risk Management Office (DRK) will conduct RCRA training. This training is an annual requirement. All Contractors performing work on Anniston Army Depot shall complete the training prior to start of work. This training covers the latest rules for managing the site’s hazardous waste from cradle to grave. Proof of completion of training shall be kept on site and presented upon request to the DRK representative.

1.10 ELECTRICAL AND FIRE SAFETY

Work near or around any electrically energized item shall only be performed after electricity to that item has been shut off. Disconnection and reconnection of electrical power to any electrically energized item shall be done at no additional cost to the Government. Contractor shall comply with all Occupational Safety and Health Act applicable requirements regarding electrical safety.

Any hot work requirements to be performed on this or any project at the Anniston Army Depot requires the approval from the Anniston Army Depot Fire Department. Approval will be in the form of a Hot Work Permit. Hot Work Permits may be obtained from the Fire Department during normal depot working hours.

1.11 SERVICE EQUIPMENT

The Contractor shall have immediate access to all service equipment, i.e. ladders, scaffold, power hand tools, or other equipment required to complete this contract. The contractor will not be allowed to use Government-owned equipment located at the worksite. 110 volt AC electrical convenience outlets are located throughout the building and will be available for use by the contractor provided they are not in use by Government personnel.

1.12 START OF WORK MEETING

The Contractor shall attend a start of work meeting held by the government prior to starting work. Work shall NOT begin until this meeting is held. This meeting serves to answer any questions from the Contractor and to discuss building issues such as safety, storage, security, access, and working hours.

1.13 PROGRESS MEETING

The Contractor shall attend any progress meetings held by the government on a biweekly basis. This meeting is to discuss current progress, to discuss schedule and to discuss and resolve any other project related issues.

1.14 SUBMITTALS

Statement of Work for Project QA49-20 Page 15

The Contractor shall provide one hard copy and one electronic copy of all submittals to the COR with a courtesy copy forward to the Contracting Officer. Review and acceptance of submittals by the Government does not relieve the Contractor from the responsibility to meet all specifications, drawings, and other required contractual standards or regulations. The Government will require fourteen (14) calendar days for review of each submittal or resubmittal furnished by the Contractor for approval.

1.14.1 The following submittals shall be submitted to the Government:

a. Site Specific Safety Plan – 30 days prior to any work.

b. Quality Control Plan – 30 days prior to any work.

c. Safety Data Sheets (SDS) prior to commencement of work.

d. Work Schedule – Due 14 days after contract award; updates by 10th of each month.

e. Mechanical Contractor License – To be submitted with proposal

f. Inspection Reports – Due 14 days following completion of inspections.

g. Building Floor Plan Drawings – Due 14 days following completion of inspections.

1.15 STATEMENT OF WORK CHANGES

The Contractor shall not proceed with any verbal or written change(s) to the statement of work from sources other than the Contracting Officer, who will provide changes in writing.

SECTION 2

SPECIFIC TASKS

2.1 The Contractor shall provide pricing for each building separately and independently for each base and option years. No attempt is to be made to tie any item or items in with any other item or items. This Price Breakdown shall be submitted with the Contractor proposal. Pricing shall be held firm for the term of the contract.

2.2 INSPECTION AND MAINTENANCE

The Contractor shall perform inspection and maintenance on approximately 560 Gas-Fired Unit Heaters, Make-Up Air Units, and Infrared Heaters located in approximately 48 buildings located at Anniston Army Depot. A list of units and buildings are detailed in Appendix ‘A’. The Government may add and/or delete units and/or buildings at any time during the contract.

All systems shall have all periodic maintenance performed at this one time under this contract as required by the manufacturer and all repairs made to meet manufacturer factory specifications to provide maximum operating efficiency and heating capability as originally designed. The inspection, maintenance and adjustments shall include but not limited to the below requirements.

2.2.1 Gas-Fired Unit Heater Inspection and Maintenance Requirements:

a. Inspect unit heater and components for any damage.

b. Clean unit heater.

c. Check for clearances to combustibles.

d. Check for proper combustion air requirements.

e. Check to ensure mounting system is secure.

f. Check inlet gas pressures and gas pressure drops across each burner and adjust as required.

g. Inspect combustion chamber for any damage.

Statement of Work for Project QA49-20 Page 16

h. Inspect and trouble shoot ignition modules for proper ignition sequence and start-up of each burner.

i. Check all burners for gas leaks and repair as required.

j. Check unit heater fan for proper operation and lubricate if required.

k. Check power exhaust blower for proper operation.

l. Check electrical voltage and all connections and repair as require.

m. Check controls and thermostat for proper operation.

n. Inspect and clean all bird screens and exhaust caps.

o. Cycle unit heater to ensure all systems are operating properly.

2.2.2 Make-up Air Units Inspection and Maintenance Requirements:

a. Check and adjust all main blower belt tension and lubricate main bearings.

b. Check all electrical service and main blower/combustion motor amperage.

c. Remove and replace all inlet air filters and clean reusable filters.

d. Check and adjust combustion readings including CO2/O2, and heat exchanger efficiency.

e. Check heat exchanger combustion draft reads adjust as necessary.

f. Check system stack temperature and unit firing rate and temperature rise adjust as necessary.

g. Check all system safety and heat controls for proper and safe operation.

h. Check all electrical relays, contactors and motors to insure proper operation.

2.2.3 Infrared Heaters Inspection and Maintenance Requirements:

a. Inspect and troubleshoot all electrical connections including BZC control panels, check program sequence/check remote heat sensors and calibrate as necessary.

b. Mechanical inspection of each centralized combustion air fan, replace O/A filters/inspect all electrical connections including relays, motor starters and fuses.

c. Check all pre-purge and post-purge elapsed time and adjust time and replace relays as required.

d. Check inlet gas pressures and gas pressure drops across each burner and adjust as required

e. Inspect all doors and door seals on each burner housing minor repairs shall be made on site.

f. Check for proper pitch of radiant and porcelain tubes and adjust as required.

g. Inspect combustion chambers and ceramic block inserts and replace ceramic block grid as required.

h. Replace all combustion air filters, seals and spark igniter assemblies.

i. Inspect and trouble shoot ignition modules for proper ignition sequence and start-up of each burner.

j. Check for clearances to combustibles.

k. Verify that the vacuum proving switch makes and breaks with the vacuum pump running.

l. Check vacuum at the end burner after the burners have operated for 1/2 hour.

m. Inspect all radiant and porcelain tubing for corrosion.

n. Inspect all couplings for proper installation.

o. Set dampers couplings for proper vacuum pressure and balancing of system.

p. Check all burners for gas leaks and repair as required.

q. Inspect all reflectors for proper installation and ensure “U” clips are properly installed.

Reflectors that have minor damage shall be repaired on-site. Reflectors that are deemed “un-repairable” should be replaced.

r. Inspect all vacuum pumps and tailpipe for debris and remove debris as required.

s. Check and verify vacuum pump rotation and adjust as required.

t. Inspect and clean all bird screens and exhaust caps.

u. Inspect acoustical boot located on vacuum pumps and replace as required.

Statement of Work for Project QA49-20 Page 17

v. Check end-vent vacuum pressures and adjust as required.

w. Inspect condensate traps and check valves for proper operation and adjust as required.

x. Re-fire all burners to ensure proper operation.

y. Check system condensate rate and adjust as required.

z. Check radiant tube temperatures with infrared heat gun to ensure proper firing rates of each system.

aa. Conduct heating system operation training with each current building manager as required and directed by the COR.

2.3 EQUIPMENT UNIT IDENTIFICATION LABELS

The Contractor shall provide nameplates with the unit equipment number on all heater equipment being inspected. All nameplates shall be a plastic label with engraved text. All labels shall have the same features such as text, style, color, and shape. Equipment numbers shall match those listed in Appendix A.

2.4 DRAWINGS

The Contractor shall provide a floor plan for each building showing the location of all heaters to include equipment number. Floor plans shall be provided in PDF and AutoCAD formats. Equipment numbers shall match those listed in Appendix A.

2.5 INSPECTION REPORTS

Upon completion of each year inspection, the Contractor shall complete a record spreadsheet in Excel format, by building and unit number, with a list of deficiencies and/or notes and recommendations for each system. Report shall consist of (1) A Summary Sheet identifying the repair cost per building; and (2) A list of repair parts to include but not limited to the manufacturer, description of item, unit of measure, quantity, unit cost, and total cost of each part. The completed report, itemizing all recommendations to include estimated repair costs of each system, shall be given to the Government, before any additional service will be approved. Each unit inspection report shall include the following information:

2.5.1 Record spreadsheet (filled out) for each Gas-Fired Unit Heater shall include the following:

a. Building number

b. Unit number

c. Service date

d. Make & Model Number

e. Fan Motor HP

f. Power ventilator HP

g. Fan & power ventilator voltage and amps

h. Ignition checks

i. Inlet gas pressure

j. Discharge temp

k. Notes on any items replaced and comments

2.5.2 Record spreadsheet (filled out) for each Make-up Air Unit shall include the following:

a. Building number

b. Unit number

c. Service date

d. Make & Model Number

Statement of Work for Project QA49-20 Page 18

e. Fan Motor HP

f. Burner Motor HP

g. Main Blower Amps

h. Flame burner signal control voltage

i. Temp limit control settings

j. Inlet gas pressure

k. Pilot gas pressure

l. Ignition checks

m. Main disconnect voltage and amp draw

n. Notes on any items replaced and comments

2.5.3 Record spreadsheet (filled out) for each Infrared Heater shall include the following:

a. Building number

b. Unit number

c. Service date

d. Make & Model Number

e. Pump ID number

f. Motor Rotation

g. Pre & Post purge Times

h. Leaving Temp

i. Pump adjustments made and comments

j. Burner ID number

k. End Vent Vacuum

l. Ignition checks

m. Radiant tube temp

n. Notes on any items replaced and comments

2.6 REPAIRS

This contract will have a Not-to-Exceed repair budget added to the contract at the time of award; base year amount and each option year amount. Billing will be based on a Firm Fixed Price (FFP) with the Contracting Officer or his/her designated representative approval for each repair identified. The Contracting Officer or his/her designated representative will approve each proposed repair before work begins and the government will only be charged for approved services up to the Not-to-Exceed value.

2.7 TESTING AND ACCEPTANCE

Testing and acceptance of work will be in accordance with the requirements in the specifications and authorized changes. Once all items have been completed, the final inspection report is signed by all parties and final acceptance of work will be granted by the government.

SECTION 3

OTHER REQUIREMENTS

3.1 RECORDKEEPING AND REPORTING

The Contractor’s Site Manager shall provide the COR or government representative with accurate records of the performance of all assigned work – including dates and locations for each work day. This

Statement of Work for Project QA49-20 Page 19 information, in writing and in a single, legible format, shall be provided on a weekly basis - and shall identify all of the above work that took place within the previous seven days.

3.2 CONTRACTOR MANPOWER REPORTING (CMR)

The Office of the Assistant Secretary of the Army (Manpower & Reserve Affairs) operates and maintains a secure Army data collection site where the Contractor will report ALL Contractor manpower (including Sub-Contractor manpower) required for performance of this contract. The Contractor is required to completely fill in all the information in the format using the following web address:

https://Contractormanpower.army.pentagon.mil.

The required information includes:

1) Contracting Office, Contracting Officer, Contracting Officer's Technical Representative;

2) Contract number, including task and delivery order number;

3) Beginning and ending dates covered by reporting period;

4) Contractor name, address, phone number, e-mail address, identity of Contractor employee entering data;

5) Estimated direct labor hours (including sub-Contractors);

6) Estimated direct labor dollars paid this reporting period (including sub- Contractors);

7) Total payments (including sub-Contractors);

8) Predominant Federal Service Code (FSC) reflecting services provided by Contractor (and separate predominant FSC for each sub-Contractor if different);

9) Estimated data collection cost;

10) Organizational title associated with the Unit Identification Code (UIC) for the Army Requiring

Activity (the Army Requiring Activity is responsible for providing the Contractor with its UIC for the purposes of reporting this information);

11) Locations where Contractor and sub-Contractors perform the work (specified by zip code in the United States and nearest city, country, when in an overseas location, using standardized nomenclature provided on website);

12) Presence of deployment or contingency contract language; and

13) Number of Contractor, and sub-Contractor employees deployed in theater this reporting period (by country).

As part of its submission, the Contractor will also provide the estimated total cost (if any) incurred to comply with this reporting requirement. Reporting period will be the period of performance not to exceed 12 months ending September 30 of each government fiscal year and must be reported by 31 October of each calendar year. Contractors may use a direct XML data transfer to the database server or fill in the fields on the website. The XML direct transfer is a format for transferring files from a Contractor's systems to the secure web site without the need for separate data entries for each required data element at the web site. The specific formats for the XML direct transfer may be downloaded from the web site.

APPENDIX

A

UNIT INFORMATION SHEET FOR

INFRARED HEATER INSPECTION

BUILDING EQUIPMENT NO. MANUFACTURER/MODEL NO. TYPE

27 GUH-27-1 REZNOR UDAP-250 GAS UNIT HEATER

DLA GUH-27-2 REZNOR UDAP-250 GAS UNIT HEATER

GUH-27-3 REZNOR UDAP-250 GAS UNIT HEATER

GUH-27-4 REZNOR UDAP-250 GAS UNIT HEATER

GUH-27-5 REZNOR UDAP-250 GAS UNIT HEATER

GUH-27-6 REZNOR UDAP-250 GAS UNIT HEATER

102 MAU-102-1 GREENHECK ICX-HV-115-H22-H2 MAKE-UP AIR UNIT

IH-102-1 DETROIT RADIANT HLV-100N RADIANT TUBE

IH-102-2 DETROIT RADIANT HLV-100N RADIANT TUBE

IH-102-3 DETROIT RADIANT HLV-100N RADIANT TUBE

IH-102-4 DETROIT RADIANT HLV-100N RADIANT TUBE

IH-102-5 DETROIT RADIANT HLV-100N RADIANT TUBE

IH-102-6 DETROIT RADIANT HLV-100N RADIANT TUBE

IH-102-7 DETROIT RADIANT HLV-100N RADIANT TUBE

IH-102-8 DETROIT RADIANT HLV-100N RADIANT TUBE

103 IH-103-1 DETROIT RADIANT HLV-100N RADIANT TUBE

IH-103-2 DETROIT RADIANT HLV-100N RADIANT TUBE

IH-103-3 DETROIT RADIANT HLV-100N RADIANT TUBE

104 MAU-104-1 GREENHECK AR15DA-3-MG-F RADIANT TUBE

DLA DISP. MAU-104-2 GREENHECK AR15DA-3-MG-F RADIANT TUBE

108 GUH-108-1 REZNOR UDBP-175 GAS UNIT HEATER

GUH-108-2 REZNOR UDBP-175 GAS UNIT HEATER

GUH-108-3 REZNOR UDBP-175 GAS UNIT HEATER

GUH-108-4 REZNOR UDBP-175 GAS UNIT HEATER

IH-108-1 ROBERTS GORDON GORDONRAY DF-150 RADIANT TUBE

IH-108-2 ROBERTS GORDON GORDONRAY DF-150 RADIANT TUBE

IH-108-3 ROBERTS GORDON GORDONRAY DF-150 RADIANT TUBE

IH-108-4 ROBERTS GORDON GORDONRAY DF-150 RADIANT TUBE

IH-108-5 SOLARONICS VERSAMOUNT-50 RADIANT TUBE

IH-108-6 SOLARONICS VERSAMOUNT-50 RADIANT TUBE

IH-108-7 SOLARONICS VERSAMOUNT-50 RADIANT TUBE

IH-108-8 SOLARONICS VERSAMOUNT-50 RADIANT TUBE

112 GUH-112-1 REZNOR UDAP-200 GAS UNIT HEATER

DLA GUH-112-2 REZNOR UDAP-200 GAS UNIT HEATER

GUH-112-3 REZNOR UDAP-200 GAS UNIT HEATER

GUH-112-4 REZNOR UDAP-200 GAS UNIT HEATER

GUH-112-5 REZNOR UDAP-200 GAS UNIT HEATER

GUH-112-6 REZNOR UDAP-200 GAS UNIT HEATER

114 MAU-114-1 APPLIED AIR GMIFN-400-VRT MAKE-UP AIR UNIT

MAU-114-2 APPLIED AIR GMIFN-400-VRT MAKE-UP AIR UNIT

MAU-114-3 APPLIED AIR GMIFN-400-VRT MAKE-UP AIR UNIT

MAU-114-4 APPLIED AIR GMIFN-400-VRT MAKE-UP AIR UNIT

MAU-114-5 APPLIED AIR GMIFN-400-VRT MAKE-UP AIR UNIT

MAU-114-6 APPLIED AIR GMIFW-400-VRT MAKE-UP AIR UNIT

117 GUH-117-1 REZNOR UDAP-45 GAS UNIT HEATER

GUH-117-2 REZNOR UDAP-75 GAS UNIT HEATER

GUH-117-3 REZNOR UDAP-30 GAS UNIT HEATER

GUH-117-4 REZNOR UDAP-45 GAS UNIT HEATER

MAU-117-1 WEATHER RITE-ARTT218VT MAKE-UP AIR UNIT

126 GUH-126-1 REZNOR SEP-115A-4 GAS UNIT HEATER

DLA GUH-126-2 REZNOR SEP-115A-4 GAS UNIT HEATER

BAE GUH-126-3 REZNOR SEP-115A-4 GAS UNIT HEATER

GUH-126-4 REZNOR SEP-115A-4 GAS UNIT HEATER

GUH-126-5 REZNOR SEP-115A-4 GAS UNIT HEATER

GUH-126-6 REZNOR SEP-115A-4 GAS UNIT HEATER

GUH-126-7 REZNOR SEP-115A-4 GAS UNIT HEATER

GUH-126-8 REZNOR SEP-115A-4 GAS UNIT HEATER

GUH-126-9 REZNOR SEP-115A-4 GAS UNIT HEATER

GUH-126-10 REZNOR SEP-115A-4 GAS UNIT HEATER

GUH-126-11 REZNOR SEP-115A-4 GAS UNIT HEATER

GUH-126-12 REZNOR SEP-115A-4 GAS UNIT HEATER

GUH-126-13 REZNOR SEP-115A-4 GAS UNIT HEATER

GUH-126-14 REZNOR SEP-115A-4 GAS UNIT HEATER

GUH-126-15 REZNOR SEP-115A-4 GAS UNIT HEATER

GUH-126-16 REZNOR SEP-115A-4 GAS UNIT HEATER

GUH-126-17 REZNOR SEP-115A-4 GAS UNIT HEATER

GUH-126-18 REZNOR SEP-115A-4 GAS UNIT HEATER

GUH-126-19 REZNOR SEP-115A-4 GAS UNIT HEATER

GUH-126-20 REZNOR SEP-115A-4 GAS UNIT HEATER

GUH-126-21 REZNOR SEP-115A-4 GAS UNIT HEATER

GUH-126-22 REZNOR SEP-115A-4 GAS UNIT HEATER

GUH-126-23 REZNOR SEP-115A-4 GAS UNIT HEATER

GUH-126-24 REZNOR SEP-115A-4 GAS UNIT HEATER

GUH-126-25 REZNOR SEP-115A-4 GAS UNIT HEATER

GUH-126-26 REZNOR SEP-115A-4 GAS UNIT HEATER

127 MAU-127-1 GREENHECK IGX-120-H32-H2 MAKE-UP AIR UNIT

DLA MAU-127-2 GREENHECK IGX-120-H32-H2 MAKE-UP AIR UNIT

MAU-127-3 GREENHECK IGX-120-H32-H2 MAKE-UP AIR UNIT

128 GUH-128-1 REZNOR UDBP-150 GAS UNIT HEATER

GUH-128-2 REZNOR UDBP-150 GAS UNIT HEATER

GUH-128-3 REZNOR UDBP-150 GAS UNIT HEATER

GUH-128-4 REZNOR UDBP-150 GAS UNIT HEATER

GUH-128-5 REZNOR UDBP-150 GAS UNIT HEATER

GUH-128-6 REZNOR UDBP-150 GAS UNIT HEATER

GUH-128-7 REZNOR UDBP-150 GAS UNIT HEATER

GUH-128-8 REZNOR UDBP-150 GAS UNIT HEATER

GUH-128-9 REZNOR UDBP-150 GAS UNIT HEATER

GUH-128-10 REZNOR UDBP-150 GAS UNIT HEATER

GUH-128-11 REZNOR UDBP-150 GAS UNIT HEATER

GUH-128-12 REZNOR UDBP-150 GAS UNIT HEATER

GUH-128-13 REZNOR UDAP-60 GAS UNIT HEATER

GUH-128-14 REZNOR UDAP-60 GAS UNIT HEATER

GUH-128-15 REZNOR UDAP-60 GAS UNIT HEATER

GUH-128-16 REZNOR UDAP-60 GAS UNIT HEATER

GUH-128-17 REZNOR UDAP-60 GAS UNIT HEATER

GUH-128-18 REZNOR UDAP-60 GAS UNIT HEATER

MAU-128-1 GREENHECK DGX-120-H32 MAKE-UP AIR UNIT

IH-128-1 SOLARONICS VERSAMOUNT-95 RADIANT TUBE

IH-128-2 SOLARONICS VERSAMOUNT-95 RADIANT TUBE

IH-128-3 SOLARONICS VERSAMOUNT-95 RADIANT TUBE

IH-128-4 SOLARONICS VERSAMOUNT-95 RADIANT TUBE

IH-128-5 SOLARONICS VERSAMOUNT-95 RADIANT TUBE

129 GUH-129-1 REZNOR UDBP-175 GAS UNIT HEATER

GUH-129-2 REZNOR UDBP-175 GAS UNIT HEATER

GUH-129-3 REZNOR UDBP-175 GAS UNIT HEATER

GUH-129-4 REZNOR UDBP-175 GAS UNIT HEATER

GUH-129-5 REZNOR UDBP-175 GAS UNIT HEATER

GUH-129-6 REZNOR UDBP-175 GAS UNIT HEATER

GUH-129-7 REZNOR UDBP-175 GAS UNIT HEATER

GUH-129-8 REZNOR UDBP-175 GAS UNIT HEATER

GUH-129-9 REZNOR UDBP-175 GAS UNIT HEATER

GUH-129-10 REZNOR UDBP-200 GAS UNIT HEATER

GUH-129-11 REZNOR UDBP-200 GAS UNIT HEATER

GUH-129-12 REZNOR UDBP-200 GAS UNIT HEATER

GUH-129-13 REZNOR UDBP-200 GAS UNIT HEATER

GUH-129-14 REZNOR UDBP-200 GAS UNIT HEATER

GUH-129-15 REZNOR UDBP-200 GAS UNIT HEATER

GUH-129-16 REZNOR UDBP-200 GAS UNIT HEATER

GUH-129-17 REZNOR UDBP-200 GAS UNIT HEATER

GUH-129-18 REZNOR UDBP-200 GAS UNIT HEATER

GUH-129-19 REZNOR UDBP-200 GAS UNIT HEATER

GUH-129-20 REZNOR UDBP-200 GAS UNIT HEATER

GUH-129-21 REZNOR UDBP-125 GAS UNIT HEATER

GUH-129-22 REZNOR UDBP-125 GAS UNIT HEATER

IH-129-1 SOLARONICS VERSAMOUNT-80 RADIANT TUBE

IH-129-2 SOLARONICS VERSAMOUNT-80 RADIANT TUBE

IH-129-3 SOLARONICS VERSAMOUNT-80 RADIANT TUBE

IH-129-4 SOLARONICS VERSAMOUNT-80 RADIANT TUBE

130 GUH-130-1 REZNOR UDBP-150 GAS UNIT HEATER

GUH-130-2 REZNOR UDBP-150 GAS UNIT HEATER

GUH-130-3 REZNOR UDBP-200 GAS UNIT HEATER

GUH-130-4 REZNOR UDBP-200 GAS UNIT HEATER

GUH-130-5 REZNOR UDBP-200 GAS UNIT HEATER

GUH-130-6 REZNOR UDBP-200 GAS UNIT HEATER

GUH-130-7 REZNOR UDBP-200 GAS UNIT HEATER

GUH-130-8 REZNOR UDBP-200 GAS UNIT HEATER

GUH-130-9 REZNOR UDBP-200 GAS UNIT HEATER

GUH-130-10 REZNOR UDBP-200 GAS UNIT HEATER

GUH-130-11 REZNOR UDBP-200 GAS UNIT HEATER

GUH-130-12 REZNOR UDBP-200 GAS UNIT HEATER

GUH-130-13 REZNOR UDBP-200 GAS UNIT HEATER

GUH-130-14 REZNOR UDBP-150 GAS UNIT HEATER

GUH-130-15 REZNOR UDBP-150 GAS UNIT HEATER

131 MAU-131-1 GREENHECK IGX-HV-120-H32-HZ MAKE-UP AIR UNIT

MAU-131-2 GREENHECK IGX-HV-120-H32-HZ MAKE-UP AIR UNIT

MAU-131-3 GREENHECK IGX-HV-120-H32-HZ MAKE-UP AIR UNIT

MAU-131-4 GREENHECK IGX-HV-120-H32-HZ MAKE-UP AIR UNIT

132 MAU-132-1 GREENHECK IGX-HV-120-H32-HZ MAKE-UP AIR UNIT

MAU-132-2 GREENHECK IGX-HV-120-H32-HZ MAKE-UP AIR UNIT

MAU-132-3 GREENHECK IGX-HV-120-H32-HZ MAKE-UP AIR UNIT

MAU-132-4 GREENHECK IGX-HV-120-H32-HZ MAKE-UP AIR UNIT

MAU-132-5 GREENHECK IGX-HV-120-H32-HZ MAKE-UP AIR UNIT

MAU-132-6 GREENHECK IGX-HV-120-H32-HZ MAKE-UP AIR UNIT

133 GUH-133-1 REZNOR UDBP-200 GAS UNIT HEATER

GUH-133-2 REZNOR UDBP-200 GAS UNIT HEATER

GUH-133-3 REZNOR UDBP-200 GAS UNIT HEATER

GUH-133-4 REZNOR UDBP-200 GAS UNIT HEATER

GUH-133-5 REZNOR UDBP-200 GAS UNIT HEATER

GUH-133-6 REZNOR UDBP-200 GAS UNIT HEATER

GUH-133-7 REZNOR UDBP-200 GAS UNIT HEATER

GUH-133-8 REZNOR UDBP-200 GAS UNIT HEATER

GUH-133-9 REZNOR UDBP-200 GAS UNIT HEATER

GUH-133-10 REZNOR UDBP-200 GAS UNIT HEATER

GUH-133-11 REZNOR UDBP-200 GAS UNIT HEATER

GUH-133-12 REZNOR UDBP-200 GAS UNIT HEATER

GUH-133-13 REZNOR UDBP-200 GAS UNIT HEATER

GUH-133-14 REZNOR UDBP-100 GAS UNIT HEATER

GUH-133-15 REZNOR UDBP-100 GAS UNIT HEATER

143 IH-143-1 ROBERTS GORDON RADIANT TUBE

IH-143-2 ROBERTS GORDON RADIANT TUBE

IH-143-3 ROBERTS GORDON RADIANT TUBE

IH-143-4 ROBERTS GORDON RADIANT TUBE

IH-143-5 ROBERTS GORDON RADIANT TUBE

IH-143-6 ROBERTS GORDON RADIANT TUBE

IH-143-7 ROBERTS GORDON RADIANT TUBE

IH-143-8 ROBERTS GORDON RADIANT TUBE

145 GUH-145-1 REZNOR UDBP-150 GAS UNIT HEATER

GUH-145-2 REZNOR UDBP-100 GAS UNIT HEATER

GUH-145-3 REZNOR UDBP-100 GAS UNIT HEATER

GUH-145-4 REZNOR UDBP-150 GAS UNIT HEATER

GUH-145-5 REZNOR UDBP-150 GAS UNIT HEATER

GUH-145-6 REZNOR UDBP-150 GAS UNIT HEATER

GUH-145-7 REZNOR UDBP-150 GAS UNIT HEATER

GUH-145-8 REZNOR UDBP-150 GAS UNIT HEATER

GUH-145-9 REZNOR UDBP-100 GAS UNIT HEATER

GUH-145-10 REZNOR UDBP-150 GAS UNIT HEATER

GUH-145-11 REZNOR UDBP-150 GAS UNIT HEATER

147 GUH-147-1 REZNOR UDAP-60 GAS UNIT HEATER

GUH-147-2 REZNOR UDBP-150 GAS UNIT HEATER

GUH-147-3 REZNOR UDBP-150 GAS UNIT HEATER

GUH-147-4 REZNOR UDBP-150 GAS UNIT HEATER

GUH-147-5 REZNOR UDBP-150 GAS UNIT HEATER

GUH-147-6 REZNOR UDBP-150 GAS UNIT HEATER

GUH-147-7 REZNOR UDBP-175 GAS UNIT HEATER

GUH-147-8 REZNOR UDBP-175 GAS UNIT HEATER

161 IH-161-1 N/A RADIANT TUBE

IH-161-2 N/A RADIANT TUBE

IH-161-3 N/A RADIANT TUBE

IH-161-4 N/A RADIANT TUBE

163 GUH-163-1 REZNOR GAS UNIT HEATER

169 IH-169-1 ROBERTS GORDON RADIANT TUBE

IH-169-2 ROBERTS GORDON RADIANT TUBE

IH-169-3 ROBERTS GORDON RADIANT TUBE

170 IH-170-1 ROBERTS GORDON RADIANT TUBE

IH-170-2 ROBERTS GORDON RADIANT TUBE

IH-170-3 ROBERTS GORDON RADIANT TUBE

IH-170-4 ROBERTS GORDON RADIANT TUBE

182 GUH-182-1 REZNOR UDAP-60 GAS UNIT HEATER

GUH-182-2 REZNOR UDAP-60 GAS UNIT HEATER

IH-182-1 SOLARONICS VERSAMOUNT-150 RADIANT TUBE

184 IH-184-1 SOLARONICS VERSAMOUNT-150 RADIANT TUBE

IH-184-2 SOLARONICS VERSAMOUNT-100 RADIANT TUBE

226 GUH-226-1 REZNOR UDAP-75 GAS UNIT HEATER

GUH-226-2 REZNOR UDAP-75 GAS UNIT HEATER

268 MAU-268-1 GREENHECK IGX-120-H32-H2 MAKE-UP AIR UNIT

MAU-268-2 GREENHECK IGX-120-H32-H2 MAKE-UP AIR UNIT

360 GUH-360-1 MODINE SEP-230A-3 GAS UNIT HEATER

DLA GUH-360-2 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-360-3 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-360-4 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-360-5 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-360-6 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-360-7 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-360-8 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-360-9 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-360-10 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-360-11 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-360-12 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-360-13 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-360-14 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-360-15 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-360-16 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-360-17 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-360-18 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-360-19 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-360-20 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-360-21 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-360-22 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-360-23 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-360-24 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-360-25 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-360-26 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-360-27 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-360-28 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-360-29 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-360-30 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-360-31 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-360-32 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-360-33 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-360-34 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-360-35 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-360-36 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-360-37 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-360-38 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-360-39 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-360-40 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-360-41 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-360-42 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-360-43 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-360-44 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-360-45 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-360-46 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-360-47 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-360-48 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-360-49 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-360-50 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-360-51 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-360-52 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-360-53 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-360-54 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-360-55 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-360-56 MODINE SEP-230A-3 GAS UNIT HEATER

361 GUH-361-1 MODINE SEP-230A-3 GAS UNIT HEATER

DLA GUH-361-2 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-361-3 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-361-4 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-361-5 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-361-6 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-361-7 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-361-8 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-361-9 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-361-10 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-361-11 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-361-12 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-361-13 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-361-14 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-361-15 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-361-16 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-361-17 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-361-18 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-361-19 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-361-20 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-361-21 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-361-22 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-361-23 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-361-24 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-361-25 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-361-26 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-361-27 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-361-28 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-361-29 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-361-30 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-361-31 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-361-32 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-361-33 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-361-34 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-361-35 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-361-36 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-361-37 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-361-38 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-361-39 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-361-40 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-361-41 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-361-42 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-361-43 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-361-44 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-361-45 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-361-46 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-361-47 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-361-48 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-361-49 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-361-50 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-361-51 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-361-52 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-361-53 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-361-54 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-361-55 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-361-56 MODINE SEP-230A-3 GAS UNIT HEATER

362 GUH-362-1 MODINE SEP-230A-3 GAS UNIT HEATER

DLA GUH-362-2 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-362-3 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-362-4 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-362-5 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-362-6 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-362-7 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-362-8 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-362-9 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-362-10 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-362-11 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-362-12 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-362-13 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-362-14 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-362-15 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-362-16 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-362-17 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-362-18 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-362-19 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-362-20 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-362-21 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-362-22 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-362-23 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-362-24 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-362-25 MODINE SEP-230A-3 GAS UNIT HEATER

GUH-362-26 MODINE SEP-230A-3 GAS UNIT HEATER

398 GUH-398-1 REZNOR UDBP-100 GAS UNIT HEATER

DLA GUH-398-2 REZNOR UDBP-100 GAS UNIT HEATER

GUH-398-3 REZNOR UDBP-100 GAS UNIT HEATER

GUH-398-4 REZNOR UDBP-100 GAS UNIT HEATER

400 MAU-400-1 APPLIED AIR GMIF-175-VH MAKE-UP AIR UNIT

MAU-400-2 APPLIED AIR GMIF-175-VH MAKE-UP AIR UNIT

MAU-400-3 APPLIED AIR GMIF-175-VH MAKE-UP AIR UNIT

MAU-400-4 APPLIED AIR GMIF-175-VH MAKE-UP AIR UNIT

MAU-400-5 APPLIED AIR GMIF-175-VH MAKE-UP AIR UNIT

MAU-400-6 APPLIED AIR GMIF-175-VH MAKE-UP AIR UNIT

MAU-400-7 APPLIED AIR GMIF-175-VH MAKE-UP AIR UNIT

MAU-400-8 APPLIED AIR GMIF-175-VH MAKE-UP AIR UNIT

MAU-400-9 APPLIED AIR GMIF-175-VH MAKE-UP AIR UNIT

MAU-400-10 APPLIED AIR GMIF-175-VH MAKE-UP AIR UNIT

MAU-400-11 APPLIED AIR GMIF-175-VH MAKE-UP AIR UNIT

MAU-400-12 APPLIED AIR GMIF-175-VH MAKE-UP AIR UNIT

MAU-400-13 APPLIED AIR GMIF-175-VH MAKE-UP AIR UNIT

MAU-400-14 APPLIED AIR GMIF-175-VH MAKE-UP AIR UNIT

MAU-400-15 APPLIED AIR GMIF-175-VH MAKE-UP AIR UNIT

MAU-400-16 APPLIED AIR GMIF-175-VH MAKE-UP AIR UNIT

MAU-400-17 APPLIED AIR GMIF-175-VH MAKE-UP AIR UNIT

MAU-400-18 APPLIED AIR GMIF-175-VH MAKE-UP AIR UNIT

MAU-400-19 APPLIED AIR GMIF-175-VH MAKE-UP AIR UNIT

MAU-400-20 APPLIED AIR GMIF-175-VH MAKE-UP AIR UNIT

MAU-400-21 APPLIED AIR GMIF-175-VRT MAKE-UP AIR UNIT

MAU-400-22 APPLIED AIR GMIF-175-VRT MAKE-UP AIR UNIT

MAU-400-23 APPLIED AIR GMIF-175-VRT MAKE-UP AIR UNIT

MAU-400-24 APPLIED AIR GMIF-175-VRT MAKE-UP AIR UNIT

MAU-400-25 APPLIED AIR GMIF-175-VRT MAKE-UP AIR UNIT

MAU-400-26 APPLIED AIR GMIF-175-VRT MAKE-UP AIR UNIT

IH-400-1 ROBERTS GORDON RADIANT TUBE

IH-400-2 ROBERTS GORDON RADIANT TUBE

IH-400-3 ROBERTS GORDON RADIANT TUBE

IH-400-4 ROBERTS GORDON RADIANT TUBE

IH-400-5 ROBERTS GORDON RADIANT TUBE

IH-400-6 ROBERTS GORDON RADIANT TUBE

IH-400-7 ROBERTS GORDON RADIANT TUBE

IH-400-8 ROBERTS GORDON RADIANT TUBE

IH-400-9 ROBERTS GORDON RADIANT TUBE

IH-400-10 ROBERTS GORDON RADIANT TUBE

IH-400-11 ROBERTS GORDON RADIANT TUBE

IH-400-12 ROBERTS GORDON RADIANT TUBE

IH-400-13 ROBERTS GORDON RADIANT TUBE

402 GUH-402-1 REZNOR UDBP-125 GAS UNIT HEATER

GUH-402-2 REZNOR UDBP-125 GAS UNIT HEATER

409 GUH-409-1 REZNOR UDBP-150 GAS UNIT HEATER

GUH-409-2 REZNOR UDBP-150 GAS UNIT HEATER

GUH-409-3 REZNOR UDBP-150 GAS UNIT HEATER

GUH-409-4 REZNOR UDBP-150 GAS UNIT HEATER

GUH-409-5 REZNOR UDBP-150 GAS UNIT HEATER

MAU-409-1 GREENHECK DGX-130-H38-DB MAKE-UP AIR UNIT

MAU-409-2 GREENHECK DGX-130-H38-DB MAKE-UP AIR UNIT

MAU-409-3 GREENHECK DGX-130-H38-DB MAKE-UP AIR UNIT

MAU-409-4 GREENHECK DGX-120-H32-DB MAKE-UP AIR UNIT

MAU-409-5 GREENHECK DGX-136-H42-DB MAKE-UP AIR UNIT

MAU-409-6 GREENHECK DGX-136-H42-DB MAKE-UP AIR UNIT

MAU-409-7 GREENHECK DGX-112-H22-DB-10 MAKE-UP AIR UNIT

MAU-409-8 GREENHECK IGX-120-H32-H2 MAKE-UP AIR UNIT

IH-409-1 ROBERTS GORDON RADIANT TUBE

IH-409-2 ROBERTS GORDON RADIANT TUBE

IH-409-3 ROBERTS GORDON RADIANT TUBE

IH-409-4 ROBERTS GORDON RADIANT TUBE

IH-409-5 ROBERTS GORDON RADIANT TUBE

IH-409-6 ROBERTS GORDON RADIANT TUBE

IH-409-7 ROBERTS GORDON RADIANT TUBE

410 GUH-410-1 REZNOR UDAP-200 GAS UNIT HEATER

GUH-410-2 REZNOR UDAP-200 GAS UNIT HEATER

GUH-410-3 REZNOR UDAP-200 GAS UNIT HEATER

GUH-410-4 REZNOR UDAP-200 GAS UNIT HEATER

GUH-410-5 REZNOR UDAP-60 GAS UNIT HEATER

GUH-410-6 REZNOR UDAP-60 GAS UNIT HEATER

414 MAU-414-1 GREENHECK IGX-120-H32-HZ MAKE-UP AIR UNIT

MAU-414-2 GREENHECK IGX-120-H32-HZ MAKE-UP AIR UNIT

MAU-414-3 GREENHECK IGX-120-H32-HZ MAKE-UP AIR UNIT

MAU-414-4 GREENHECK IGX-120-H32-HZ MAKE-UP AIR UNIT

MAU-414-5 GREENHECK IGX-120-H32-HZ MAKE-UP AIR UNIT

MAU-414-6 GREENHECK IGX-120-H32-HZ MAKE-UP AIR UNIT

MAU-414-7 GREENHECK IGX-120-H32-HZ MAKE-UP AIR UNIT

MAU-414-8 GREENHECK IGX-120-H32-HZ MAKE-UP AIR UNIT

421 GUH-421-1 REZNOR UDBP-125 GAS UNIT HEATER

GUH-421-2 REZNOR UDBP-125 GAS UNIT HEATER

IH-421-1 SOLARONICS VERSAMOUNT-150 RADIANT TUBE

IH-421-2 SOLARONICS VERSAMOUNT-150 RADIANT TUBE

422 GUH-422-1 REZNOR UDBP-150 GAS UNIT HEATER

GUH-422-2 REZNOR UDBP-100 GAS UNIT HEATER

GUH-422-3 REZNOR UDBP-100 GAS UNIT HEATER

GUH-422-4 REZNOR UDBP-200 GAS UNIT HEATER

423 IH-423-1 SOLARONICS VERSAMOUNT-100 RADIANT TUBE

IH-423-2 SOLARONICS VERSAMOUNT-100 RADIANT TUBE

IH-423-3 SOLARONICS VERSAMOUNT-100 RADIANT TUBE

IH-423-4 SOLARONICS VERSAMOUNT-100 RADIANT TUBE

IH-423-5 SOLARONICS VERSAMOUNT-100 RADIANT TUBE

IH-423-6 SOLARONICS VERSAMOUNT-100 RADIANT TUBE

IH-423-7 SOLARONICS VERSAMOUNT-100 RADIANT TUBE

IH-423-8 SOLARONICS VERSAMOUNT-100 RADIANT TUBE

IH-423-9 SOLARONICS VERSAMOUNT-100 RADIANT TUBE

IH-423-10 SOLARONICS VERSAMOUNT-100 RADIANT TUBE

IH-423-11 SOLARONICS VERSAMOUNT-100 RADIANT TUBE

IH-423-12 SOLARONICS VERSAMOUNT-100 RADIANT TUBE

432 MAU-432-1 GREENHECK ICX-HV-115-H22-H2 MAKE-UP AIR UNIT

433 MAU-433-1 GREENHECK PCB-200-HBL MAKE-UP AIR UNIT

MAU-433-2 GREENHECK IGX-115-H22-HZ MAKE-UP AIR UNIT

MAU-433-RT-PB-1 GREENHECK TSU-230-H50-HZ MAKE-UP AIR UNIT

MAU-433-RT-PB-2 GREENHECK TSU-230-H50-HZ MAKE-UP AIR UNIT

MAU-433-RT-PB-3 GREENHECK TSU-230-H50-HZ MAKE-UP AIR UNIT

MAU-433-RT-PB-4 GREENHECK TSU-230-H50-HZ MAKE-UP AIR UNIT

IH-433-1 ROBERTS GORDON RADIANT TUBE

IH-433-2 ROBERTS GORDON RADIANT TUBE

IH-433-3 ROBERTS GORDON RADIANT TUBE

IH-433-4 ROBERTS GORDON RADIANT TUBE

IH-433-5 ROBERTS GORDON RADIANT TUBE

434 GUH-434-1 REZNOR UDAP-75 GAS UNIT HEATER

GUH-434-2 REZNOR UDAP-75 GAS UNIT HEATER

GUH-434-3 REZNOR UDAP-75 GAS UNIT HEATER

GUH-434-4 REZNOR UDAP-75 GAS UNIT HEATER

GUH-434-5 REZNOR UDAP-75 GAS UNIT HEATER

GUH-434-6 REZNOR UDAP-75 GAS UNIT HEATER

GUH-434-7 REZNOR UDAP-75 GAS UNIT HEATER

GUH-434-8 REZNOR UDAP-75 GAS UNIT HEATER

GUH-434-9 REZNOR UDAP-100 GAS UNIT HEATER

GUH-434-10 REZNOR UDAP-150 GAS UNIT HEATER

GUH-434-11 REZNOR UDBP-150 GAS UNIT HEATER

GUH-434-12 REZNOR UDBP-150 GAS UNIT HEATER

IH-434-1 SOLARONICS VERSAMOUNT-125 RADIANT TUBE

IH-434-2 SOLARONICS VERSAMOUNT-125 RADIANT TUBE

451 MAU-451-1 FLOAIRE EIN-RT80A1B01B61R2AB3K5 MAKE-UP AIR UNIT

MAU-451-2 FLOAIRE EIN-RT80A1B01B61R2AB3K6 MAKE-UP AIR UNIT

MAU-451-3 FLOAIRE EIN-RT80A1B01B61R2AB3K7 MAKE-UP AIR UNIT

MAU-451-4 FLOAIRE EIN-RT80A1B01B61R2AB3K8 MAKE-UP AIR UNIT

456 IH-456-1 SOLARONICS VERSAMOUNT-150 RADIANT TUBE

IH-456-2 SOLARONICS VERSAMOUNT-150 RADIANT TUBE

459 IH-459-1 SOLARONICS VERSAMOUNT-175 RADIANT TUBE

IH-459-2 SOLARONICS VERSAMOUNT-175 RADIANT TUBE

IH-459-3 SOLARONICS VERSAMOUNT-175 RADIANT TUBE

IH-459-4 SOLARONICS VERSAMOUNT-175 RADIANT TUBE

474 MAU-474-1 GREENHECK SFhFF404PA00C59D01ABZ00G0K MAKE-UP AIR UNIT MAU-474-2 GREENHECK SFhFF404PA00C59D01ABZ00G0K MAKE-UP AIR UNIT

MAU-474-3 GREENHECK YCD150D4H0BB MAKE-UP AIR UNIT

MAU-474-4 GREENHECK SFJ3-18A MAKE-UP AIR UNIT

MAU-474-5 GREENHECK SFJ3-18A MAKE-UP AIR UNIT

MAU-474-6 GREENHECK SFJ5-25 MAKE-UP AIR UNIT

MAU-474-7 GREENHECK SFJ4-18A MAKE-UP AIR UNIT

MAU-474-8 GREENHECK SFJ4-20 MAKE-UP AIR UNIT

MAU-474-9 GREENHECK SFJ4-20 MAKE-UP AIR UNIT

MAU-474-10 GREENHECK PA12 MAKE-UP AIR UNIT

MAU-474-11 GREENHECK PA12 MAKE-UP AIR UNIT

MAU-474-12 GREENHECK BAJ4-1000-303040 MAKE-UP AIR UNIT

MAU-474-13 GREENHECK PAJ5-1200-404040 MAKE-UP AIR UNIT

MAU-474-14 GREENHECK PAJ4-1200-404040 MAKE-UP AIR UNIT

MAU-474-15 GREENHECK PAJ1-150 MAKE-UP AIR UNIT

MAU-474-16 GREENHECK YCD210C4L0EA MAKE-UP AIR UNIT

MAU-474-17 GREENHECK C10J04878 MAKE-UP AIR UNIT

475 MAU-475-1 GREENHECK SFJ3-18A MAKE-UP AIR UNIT

MAU-475-2 GREENHECK SFJ5-25 MAKE-UP AIR UNIT

MAU-475-3 GREENHECK SFJ3-18A MAKE-UP AIR UNIT

MAU-475-4 GREENHECK SFHGC904J3J8EEED01ABC000K000RT0060 MAKE-UP AIR UNIT

MAU-475-5 GREENHECK YCD150D4LBBB MAKE-UP AIR UNIT

MAU-475-6 GREENHECK SFHFF754GA88E9BD7C01AB20000K0000T008600 MAKE-UP AIR UNIT

MAU-475-7 GREENHECK SFHFF754GA88E9BD7C01AB20000K0000T008600 MAKE-UP AIR UNIT

MAU-475-8 GREENHECK SFHFF754GA88E9BD7C01AB20000K0000T008600 MAKE-UP AIR UNIT

MAU-475-9 GREENHECK SFHFF754GA88E9BD7C01AB20000K0000T008600 MAKE-UP AIR UNIT

MAU-475-10 GREENHECK SFHFF754GA88E9BD7C01AB20000K0000T008600 MAKE-UP AIR UNIT

MAU-475-11 GREENHECK YSC120A4RXA2R0000C1B00200 MAKE-UP AIR UNIT

MAU-475-12 GREENHECK SFHFF754GA88E9BD7C01AB20000K0000T008600 MAKE-UP AIR UNIT

MAU-475-13 GREENHECK SFHGC904J3J8EEED5D01ABC000K000RT0060 MAKE-UP AIR UNIT

MAU-475-14 GREENHECK YCD240B4HBJB MAKE-UP AIR UNIT

MAU-475-15 GREENHECK YCD240B4HBJB MAKE-UP AIR UNIT

MAU-475-16 GREENHECK SFHFF754GA88E9BD7C01AB20000K0000T008600 MAKE-UP AIR UNIT

513 IH-513-1 ROBERTS GORDON TF-380 RADIANT TUBE

DLA IH-513-2 ROBERTS GORDON TF-380 RADIANT TUBE

IH-513-3 REVERBERAY DX2-30-100N RADIANT TUBE

IH-513-4 REVERBERAY DX2-30-100N RADIANT TUBE

IH-513-5 REVERBERAY DX2-30-100N RADIANT TUBE

IH-513-6 REVERBERAY DX2-30-100N RADIANT TUBE

IH-513-7 REVERBERAY DX2-30-100N RADIANT TUBE

IH-513-8 REVERBERAY DX2-30-100N RADIANT TUBE

HIUH-513-1 REVERBERAY DR45DMPS HIGH INTENSITY UNIT HEATER

HIUH-513-2 REVERBERAY DR45DMPS HIGH INTENSITY UNIT HEATER

HIUH-513-3 REVERBERAY DR45DMPS HIGH INTENSITY UNIT HEATER

HIUH-513-4 REVERBERAY DR45DMPS HIGH INTENSITY UNIT HEATER

HIUH-513-5 REVERBERAY DR45DMPS HIGH INTENSITY UNIT HEATER

HIUH-513-6 REVERBERAY DR45DMPS HIGH INTENSITY UNIT HEATER

HIUH-513-7 REVERBERAY DR45DMPS HIGH INTENSITY UNIT HEATER

HIUH-513-8 REVERBERAY DR45DMPS HIGH INTENSITY UNIT HEATER

HIUH-513-9 REVERBERAY DR45DMPS HIGH INTENSITY UNIT HEATER

HIUH-513-10 REVERBERAY DR45DMPS HIGH INTENSITY UNIT HEATER

HIUH-513-11 REVERBERAY DR45DMPS HIGH INTENSITY UNIT HEATER

HIUH-513-12 REVERBERAY DR45DMPS HIGH INTENSITY UNIT HEATER

HIUH-513-13 REVERBERAY DR45DMPS HIGH INTENSITY UNIT HEATER

HIUH-513-14 REVERBERAY DR45DMPS HIGH INTENSITY UNIT HEATER

HIUH-513-15 REVERBERAY DR45DMPS HIGH INTENSITY UNIT HEATER

HIUH-513-16 REVERBERAY DR45DMPS HIGH INTENSITY UNIT HEATER

HIUH-513-17 REVERBERAY DR45DMPS HIGH INTENSITY UNIT HEATER

HIUH-513-18 REVERBERAY DR45DMPS HIGH INTENSITY UNIT HEATER

HIUH-513-19 REVERBERAY DR45DMPS HIGH INTENSITY UNIT HEATER

HIUH-513-20 REVERBERAY DR45DMPS HIGH INTENSITY UNIT HEATER

HIUH-513-21 REVERBERAY DR45DMPS HIGH INTENSITY UNIT HEATER

HIUH-513-22 REVERBERAY DR45DMPS HIGH INTENSITY UNIT HEATER

HIUH-513-23 REVERBERAY DR45DMPS HIGH INTENSITY UNIT HEATER

HIUH-513-24 REVERBERAY DR45DMPS HIGH INTENSITY UNIT HEATER

HIUH-513-25 REVERBERAY DR45DMPS HIGH INTENSITY UNIT HEATER

HIUH-513-26 REVERBERAY DR45DMPS HIGH INTENSITY UNIT HEATER

HIUH-513-27 REVERBERAY DR45DMPS HIGH INTENSITY UNIT HEATER

Binder1.pdf
IR Heater Statement of Work.pdf
Q977-19 Statement of Work 8.pdf
IR Heaters List.pdf
Heater Schedule