Updated_Technical_Exhibit_B.pdf
PDF 6 MB Posted
- Attached to
- Renovate HVAC System in Bldg 33012 Federal contract opportunity
- Solicitation number
- W91151-17-B-0032
About this file
Updated Drawings for Solicitation Amendment #3
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Solicitation_Amendment_W91151_17_B_0032_0003.pdf | ||
| W9115117B0032_Solicitation_Amendment.pdf | ||
| Solicitation_Amendment__2_Change_Bid_Opening_Date.pdf | ||
| Site_Visit_Sign_In_Roster.pdf | ||
| Agenda_for__Site_Visit.pdf | ||
| AppendixA.pdf | ||
| W9115117C0032ReplaceAHU'sBLDG33012.pdf | ||
| TechnicalExhibitB.pdf | ||
| TechnicalExhibitA.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SHEET
N
1"=200’
INDEX OF DRAWINGS
HWY 84
HWY 84
HWY 36
F .M
RES.BD.
RES.BD.
R E S . B
D
RES. BD.
R E
S .B
D
KILLEEN
CANTONMENT
AREA
WEST
FORT
HOOD
GATESVILLE
NORTH
FORT
HOOD
RESERVATION
BELTON
LAKE
COPPERAS
COVE
HWY190
HWY190
FORT HOOD AREA MAP
O L
D G
E O
R G
E T
O W
N R
D
E A
S T R
A N
G E R
D
N O
LA
N R
D
FORT HOOD
W E S
T R
A N
G E R
D
C L
A R
K E R
D
H W
Y
35 37
LOCATION
PROJECT
LAREDO
CORPUS
CHRISTI
HOUSTON
AUSTIN
KILLEEN
WACO
FORT WORTH DALLAS
FORT
SMITH
OKLAHOMA
CITY
TULSA
AMARILLO
ALBUQUERUE
SANTA FE
VICINITY MAP
LOUISIANA
MEXICO
MEXICO
TEXAS
ARKANSAS
NEW
MEXICO
ELPASO
OKLAHOMA
GULF OF
SAN ANTONIO
FORT HOOD
WICHITA FALLS
N
SCALE IN MILES
1/2 1
FORT HOOD MILITARY RESERVATION
N
0 100 200
SCALE IN MILES
N
0 5 10
SCALE IN MILES
NORTH SYMBOL
GENERAL SYMBOLS
REVISION NUMBER
WALL TYPE MARK
DOOR MARKWINDOW MARK
DETAIL NUMBER
REFERENCE FROM
REFERENCE TO
G-101
C O
V E
R S
H E
E T
FORT HOOD,TEXAS
FORT HOOD DIRECTORATE OF PUBLIC WORKS-ENGINEERING DIVISION
NOTE BY SYMBOL
SHEET DESCRIPTION
A
A
N
A
A
BUILDING LEGEND (POINTS OF INTEREST)
PROJECT SITE
BUILDING 4612 (DIRECTORATE OF PUBLIC WORKS)
DARNALL ARMY HOSPITAL
III CORPS HEADQUARTERS
MAIN CANTONMENT AREA
W E S T R
A N
G E R
D
MONTAGUE VILLAGE
VILLAGEII
COMANCHE
CENTRAL DR
LANDFILL
FT.HOOD
W R
A T
T E
N
PATTON
PARK
BATTALION
NORTH
761ST
NORTH
WALKER VILLAGE
HOOD
ARMY
AIRFIELD
HILLIARD
CENTRAL
TEXAS
COLLEGE
HEIGHTS
WEST
FT.HOOD
VILLAGEIII
MURPHY
TURKEYRUN
T
H
N D
H W
Y
T
H
R
D
M U
R P
H Y
T
H
M A
R T
IN
62ND
WAINWRIGHT
TO
VILLAGEI
COMANCHE
T
H
T
H
LIBERTY VILLAGE
OLD IRONSIDES
BATTALION AVE
HELL ON WHEELSC
L
A R
K E R
O A
D C
L A
R K
E R
O A
D
C L E
A R C
R E
E K
US HIGHWAY 190
HELL ON WHEELS
OLD IRONSIDES
WARRIOR WAY
BUSINESS ROUTE 190
US HIGHWAY 190
PERSHING PARK
VENABLE VILLAGE
CHAFFEE VILLAGE
US HIGHWAY 190
RAIL HEAD
McNair Village
TANK DESTROYER RD
COPPERAS COVE RD
WEST RANGE RD
Santa Fe Av e
WAREHOUSE AVE
DESTROYER RD
TANK
COPP
ERAS
COVE
RD
O L
D G
E O
R G
R T
O W
N R
D
TURKEYRUN
C L E
A R C
R E
E K
T
H
EAST
R
AN
G E
R D
NORTH NOLAN RD
WEST RANCIER AVE
SOUTH RANGE RD
F T H
O O
D S
T
T .J
M
IL
L S B
L V
D
B P
R E
S S
E R
PROJECT NO: PX901706P
REPLACE AHUS
STRUCTURAL DETAILS IIS-502
STRUCTURAL DETAILS IS-501
ROOF FRAMING PLANS-101
STRUCTURAL NOTESS-001
MECHANICAL CONTROLSM-701
MECHANICAL SCHEDULEM-601
MECHANICAL DETAILSM-501
NEW MECHANICAL ROOM PIPING PLANM-104
MECHANICAL ROOM DUCTWORK PLANM-103
NEW MECHANICAL PIPING PLAN - AREA BM-102B
NEW MECHANICAL PIPING PLAN - AREA AM-102A
MECHANICAL DUCTWORK PLAN - AREA DM-101D
MECHANICAL DUCTWORK PLAN - AREA CM-101C
MECHANICAL DUCTWORK PLAN - AREA BM-101B
MECHANICAL DUCTWORK PLAN - AREA AM-101A
EXISTING MECHANICAL ROOM PIPING PLANMD-104
MECHANICAL ROOM DEMOLITION PLANMD-103
EXISTING MECHANICAL PIPING PLAN - AREA BMD-102B
EXISTING MECHANICAL PIPING PLAN - AREA AMD-102A
MECHANICAL DEMOLITION PLAN - AREA DMD-101D
MECHANICAL DEMOLITION PLAN - AREA CMD-101C
MECHANICAL DEMOLITION PLAN - AREA BMD-101B
MECHANICAL DEMOLITION PLAN - AREA AMD-101A
MECHANICAL NOTESM-001
COVER SHEETG-101
NUMBER
REFERENCE
SHEET
Project No.
D e s ig n e d B y
D a te
M a rk
Bldg. No.
F T
H O
O D T
E X
A S
S A
N T
A F
E E
N G
IN
E E
R D
R
B
L D
G
F O
R T H
O O
D T
E X
A S
P U
B L
IC
W
O R
K S
D
IR
E C
T O
R A
T E O
F
A B C D E F
D a te
D e s c ri p ti o n
DPW
FORT HOOD TEXAS
n oi sivi
D secivreS & gn ir ee ni g n
E
D ir ec to rat eofPublic
W o rk s
P R
O J E
C T M
A N
A G
E R
P U
R P
O S
E S O
N L
Y F
O R B
ID
D
IN
G T
E C
H N
IC
A L E
X H
IB
IT
B
/8 /2
:5
:4
P
M G E
N G
S
V C \P ro j\ P
X P B
R
E P
L A
C E A
H U
S \F lo o rp la n s
D e s ig n \G -1
C o v e r S h e e t.
d g n
33012
B P
R E
S S
E R
-A
P R -2
PX901706P
R E
P L
A C
E A
H U
S
BATTALION AVE
T
H S
T
T
H S
T
R D S
T
N D S
T
761ST TANK BATTALION AVE
33011
34011
31001 31011
31012
33012
31010
GENERAL NOTES:
WORK STAGING:
SITE CONCERNS:
M E
C H
A N
IC
A L N
O T
E S
M-001
ON AHU-4.
THIS OFFICE AND REMOVE AS MUCH OF ITS CONTENTS AS NECESSARY WHILE WORK IS BEING PERFORMED
AHU-4 IS CURRENTLY LOCATED DIRECTLY OVER A SMALL OFFICE. CUSTOMER HAS AGREED TO VACATE2.
PERFORMED OVERHEAD.
CUSTOMER HAS AGREED TO CLOSE AT LEAST ONE OF THESE REGISTERS WHILE WORK IS BEING
AHU-3 IS CURRENTLY LOCATED ABOVE TWO CASH REGISTERS IN THE EXCHANGE RETAIL SALES AREA.1.
THE GIVEN BUSINESS HOURS OR DURING ANY SCHEDULED OUTAGES.
CONTRACTOR SHALL NOTIFY THE COR 7-10 DAYS PRIOR TO ANY WORK BEING PERFORMED OUTSIDE OF4.
CLOSEDSUNDAY
1030 - 1700SATURDAY
0700 - 1900MONDAY - FRIDAY
IN THIS AREA SHALL BE PERFORMED OUTSIDE OF THESE TIMES WHENEVER POSSIBLE.
BUSINESS HOURS FOR THE 1ST CAVALRY BURGER KING ARE GIVEN IN THE FOLLOWING SCHEDULE. WORK3.
1100 - 1600SATURDAY & SUNDAY
0700 - 1900MONDAY - FRIDAY
THIS AREA SHALL BE PERFORMED OUTSIDE OF THESE TIMES WHENEVER POSSIBLE.
BUSINESS HOURS FOR THE 1ST CAVALRY EXCHANGE ARE GIVEN IN THE FOLLOWING SCHEDULE. WORK IN2.
NORMAL BUSINESS OPERATIONS.
COORDINATED WITH THE COR AND BUILDING POCS IN ADVANCE IN ORDER TO MINIMIZE THE IMPACT TO
BUILDING 33012 IS OCCUPIED DURING NORMAL BUSINESS HOURS. ALL WORK PERFORMED SHALL BE1.
B P
R E
S S
E R
AREAS.
WHILE EACH UNIT IS BEING REPLACED, CONTRACTOR SHALL PROVIDE SPOT COOLING FOR THE IMPACTED5.
REPLACEMENTS ARE AVAILABLE FOR INSTALLATION.
IN ORDER TO MINIMIZE OUTAGE TIME, EXISTING UNITS SHALL NOT BE REMOVED UNTIL THEIR4.
ANY WEEKEND THAT IS DIRECTLY PRECEDED OR FOLLOWED BY A TRAINING OR FEDERAL HOLIDAY.
A WEEKEND. IF POSSIBLE, THIS WORK SHALL BE PERFORMED DURING AN EXTENDED WEEKEND, MEANING
THE OUTAGE TO REPLACE AHU-7 SHALL NOT LAST LONGER THAN 4 CALENDAR DAYS AND SHALL INCLUDE3.
SHEETS OVER ALL TRANSFER POINTS (E.G., DOOR OPENINGS).
BUT SHALL BE ISOLATED FROM THE BLIMPIE FOOD PREP AND STORAGE AREAS BY PLACING PLASTIC
AHU-4. BURGER KING FOOD PREP AREA SHALL REMAIN OPEN WHILE THIS WORK IS BEING PERFORMED, OVERHEAD, INCLUDING THE REPLACEMENT OF BOTH AHU-7 AND THE SPECIFIED DUCTWORK SERVING
FOOD PREP AND STORAGE AREAS FOR BLIMPIE SHALL BE CLOSED WHILE WORK IS BEING PERFORMED2.
AHU-4 AND AHU-7 SHALL BE REPLACED WITHIN THE FIRST 60 DAYS OF THE PERFORMANCE PERIOD.1.
NUMBER
REFERENCE
SHEET
Project No.
D e s ig n e d B y
D a te
M a rk
Bldg. No.
F T
H O
O D T
E X
A S
S A
N T
A F
E E
N G
IN
E E
R D
R
B
L D
G
F O
R T H
O O
D T
E X
A S
P U
B L
IC
W
O R
K S
D
IR
E C
T O
R A
T E
D a te
D e s c ri p ti o n sivi
D secivreS & gn ir ee ni g n
E
D ir ec to rat eofPublic
W o rk s
P R
O J E
C T M
A N
A G
E R
P U
R P
O S
E S O
N L
Y F
O R B
ID
D
IN
G T
E C
H N
IC
A L E
X H
IB
IT
B
/8 /2
:5
:4
P
M G E
N G
S
V C \P ro j\ P
X P B
R
E P
L A
C E A
H U
S \F lo o rp la n s
D e s ig n \M
-0 .d g n
33012
B P
R E
S S
E R
-A
P R -2
PX901706P
R E
P L
A C
E A
H U
S
N SCALE: 3/16" = 1’ N
KEY PLAN0 4 8
SCALE (FEET)
RV
C
C
CU
RH
AHU
B P
R E
S S
E R
KEY NOTES:
AIR-HANDLING UNIT
EQUIPMENT LIST
AHU-3
RV-1
SYMBOL DESCRIPTION
C-2
C-1
CU-8
RH-3
COOLING UNIT (REFRIGERATION)
RELIEF VENT
FOR C-1
DISCONNECT
FOR C-2
DISCONNECT
GENERAL NOTES:
101A
MD-
101A
MD-
MD-
ROOF HOOD (OUTSIDE AIR)
MECHANICAL DEMOLITION PLAN - AREA A
P L
A N A
R E
A A
M E
C H
A N
IC
A L D
E M
O L
IT
IO
N
CONDENSING UNIT
CONDENSING UNIT
MATCHLINE - SEE MD-101C
M A
T C
H L
IN
E S
E E M
D -1
B
UNIT
COOLER
FROM INSIDE
DOOR BLOCKED
DEMOLISHED.
EXISTING SUPPLY DIFFUSER TO BE
DEMOLISHED.
EXISTING DUCTWORK TO BE
DUCT TO REMAIN.
38" X 14" OPENING FOR RETURN-AIR
DUCT TO BE DEMOLISHED.
38" X 14" OPENING FOR RETURN-AIR
CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING EXISTING SITE CONDITIONS.9.
OF THE CONTRACTOR UNTIL REUSED.
ITEMS INTENDED FOR REUSE ON THIS PROJECT SHALL REMAIN IN THE POSSESSION8.
ITS DISPOSAL.
BECOME THE PROPERTY OF THE CONTRACTOR, WHO SHALL BE RESPONSIBLE FOR
UNLESS NOTED OTHERWISE, ALL MATERIAL REMOVED AND NOT REUSED SHALL7.
UNITS, INCLUDING CONTROL WIRING.
CONTRACTOR SHALL DEMOLISH ALL THERMOSTATS SERVING EXISTING AIR-HANDLING6.
CONDUIT SHALL BE PRESERVED AND REUSED IF IT IS APPROPRIATELY SIZED.
EQUIPMENT SHALL REMAIN IN THE PANEL AND BE LABELED AS "SPARE". EXISTING
EXISTING ELECTRICAL PANEL. CIRCUIT BREAKERS THAT ARE NOT REUSED FOR NEW
INCLUDING DISCONNECTS, FOR DEMOLISHED HVAC EQUIPMENT BACK TO THE
CONTRACTOR SHALL DEMOLISH ALL EXISTING ELECTRICAL WIRING AND DEVICES,5.
SHALL BE DEMOLISHED.
MAINTENANCE ALONG WITH ASSOCIATED REFRIGERANT. REFRIGERANT PIPING
SERVING AHU-1 AND AHU-2, RESPECTIVELY, AND TURN THEM IN TO DPW
CONTRACTOR SHALL DISCONNECT EXISTING CONDENSING UNITS (C-1 AND C-2)4.
SHALL BE PRESERVED AND REUSED FOR THE NEW HVAC SYSTEM.
UNLESS NOTED OTHERWISE, ALL EXISTING DIFFUSERS, GRILLES, AND DUCTWORK3.
AND REUSED FOR NEW EQUIPMENT, IF POSSIBLE, OR CAPPED.
DUCTWORK SERVING AHU-3. EXISTING ROOF PENETRATION SHALL BE PRESERVED
CONTRACTOR SHALL DEMOLISH EXISTING ROOF HOOD (RH-3) AND OUTSIDE-AIR2.
DEMOLISHED IF NECESSARY TO INSTALL NEW EQUIPMENT.
ABANDONED IN PLACE. EXISTING DUCTWORK CONNECTED TO THIS UNIT MAY BE
HOT-WATER PIPING SERVING THIS UNIT SHALL BE DRAINED, CAPPED, AND
CONTRACTOR SHALL DEMOLISH EXISTING AIR-HANDLING UNIT (AHU-3). ALL EXISTING1.
NUMBER
REFERENCE
SHEET
Project No.
D e s ig n e d B y
D a te
M a rk
Bldg. No.
F T
H O
O D T
E X
A S
S A
N T
A F
E E
N G
IN
E E
R D
R
B
L D
G
F O
R T H
O O
D T
E X
A S
P U
B L
IC
W
O R
K S
D
IR
E C
T O
R A
T E
D a te
D e s c ri p ti o n sivi
D secivreS & gn ir ee ni g n
E
D ir ec to rat eofPublic
W o rk s
P R
O J E
C T M
A N
A G
E R
P U
R P
O S
E S O
N L
Y F
O R B
ID
D
IN
G T
E C
H N
IC
A L E
X H
IB
IT
B
/8 /2
:5
:4
P
M G E
N G
S
V C \P ro j\ P
X P B
R
E P
L A
C E A
H U
S \F lo o rp la n s
D e s ig n \M
D -1
A .d g n
33012
B P
R E
S S
E R
-A
P R -2
PX901706P
R E
P L
A C
E A
H U
S
20" X 16"
SUPPLY AIR
X
X
X
X
X
16" X 16"
X
9" X 8" 9" X 7" 9" X 5"
X
X
6" X 4"
9" X 7"
16" X 12"
10" VERTICAL SPLIT
6" HORIZONTAL SPLIT 6" HORIZONTAL SPLIT
SPLIT
6" HORIZONTAL
S U
P P
L Y A
IR
12" X 9" 9" X 6"
X
X
X
X
36" X 16"
SUPPLY AIR
14" X 6"
12" X 8"
3.24.1
5.1
D
E
F
G
MECHANICAL
STORAGE
LAUNDRY/
ALTERATIONS
GNC
RETAIL SALES
OFFICE
VESTIBULE
MAIN LOBBY
SHOPPETTE
RETAIL SALES
FITTING
ROOM
MECHANICAL
YARD
A B
C D
LEGEND:
T
EXISTING EQUIPMENT TO REMAIN
EXISTING EQUIPMENT TO BE DEMOLISHED
AIR FLOW DIRECTION
EXISTING ELECTRICAL DISCONNECT
EXISTING THERMOSTAT
EXISTING 1’ X 1’ EXHAUST GRILLE
EXISTING 1’ X 2’ RETURN GRILLE
EXISTING 6" X 2’ RETURN GRILLE
EXISTING 1’ X 1’ RETURN GRILLE
EXISTING 2’ X 2’ RETURN GRILLE
EXISTING 1’ X 1’ SUPPLY DIFFUSER
EXISTING 2’ X 2’ SUPPLY DIFFUSER
SCALE (FEET)
EF
AHU
RH
RV
B P
R E
S S
E R
KEY NOTES:
AIR-HANDLING UNIT
EQUIPMENT LIST
AHU-6
SYMBOL DESCRIPTION
RH-6
EF-1
RV-2
EXHAUST FAN
RELIEF VENT
GENERAL NOTES:
101B
MD-
ROOF HOOD (OUTSIDE AIR)
P L
A N A
R E
A B
M E
C H
A N
IC
A L D
E M
O L
IT
IO
N
MECHANICAL DEMOLITION PLAN - AREA B
MATCHLINE - SEE MD-101D
M A
T C
H L
IN
E S
E E M
D -1
A
TANK
WATER
GAS HOT-
EXISTING DUCTWORK TO BE DEMOLISHED.
THERMOSTAT FOR AHU-6.
CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING EXISTING SITE CONDITIONS.7.
OF THE CONTRACTOR UNTIL REUSED.
ITEMS INTENDED FOR REUSE ON THIS PROJECT SHALL REMAIN IN THE POSSESSION6.
ITS DISPOSAL.
BECOME THE PROPERTY OF THE CONTRACTOR, WHO SHALL BE RESPONSIBLE FOR
UNLESS NOTED OTHERWISE, ALL MATERIAL REMOVED AND NOT REUSED SHALL5.
UNITS, INCLUDING CONTROL WIRING.
CONTRACTOR SHALL DEMOLISH ALL THERMOSTATS SERVING EXISTING AIR-HANDLING4.
CONDUIT SHALL BE PRESERVED AND REUSED IF IT IS APPROPRIATELY SIZED.
EQUIPMENT SHALL REMAIN IN THE PANEL AND BE LABELED AS "SPARE". EXISTING
EXISTING ELECTRICAL PANEL. CIRCUIT BREAKERS THAT ARE NOT REUSED FOR NEW
INCLUDING DISCONNECTS, FOR DEMOLISHED HVAC EQUIPMENT BACK TO THE
CONTRACTOR SHALL DEMOLISH ALL EXISTING ELECTRICAL WIRING AND DEVICES,3.
SHALL BE PRESERVED AND REUSED FOR THE NEW HVAC SYSTEM.
UNLESS NOTED OTHERWISE, ALL EXISTING DIFFUSERS, GRILLES, AND DUCTWORK2.
TO THIS UNIT MAY BE DEMOLISHED IF NECESSARY TO INSTALL NEW EQUIPMENT.
PRESERVED AND REUSED FOR NEW EQUIPMENT. EXISTING DUCTWORK CONNECTED
ABANDONED IN PLACE. EXISTING ROOF HOOD (RH-6) SERVING AHU-6 SHALL BE
HOT-WATER PIPING SERVING THIS UNIT SHALL BE DRAINED, CAPPED, AND
CONTRACTOR SHALL DEMOLISH EXISTING AIR-HANDLING UNIT (AHU-6). ALL EXISTING1.
NUMBER
REFERENCE
SHEET
Project No.
D e s ig n e d B y
D a te
M a rk
Bldg. No.
F T
H O
O D T
E X
A S
S A
N T
A F
E E
N G
IN
E E
R D
R
B
L D
G
F O
R T H
O O
D T
E X
A S
P U
B L
IC
W
O R
K S
D
IR
E C
T O
R A
T E
D a te
D e s c ri p ti o n sivi
D secivreS & gn ir ee ni g n
E
D ir ec to rat eofPublic
W o rk s
P R
O J E
C T M
A N
A G
E R
P U
R P
O S
E S O
N L
Y F
O R B
ID
D
IN
G T
E C
H N
IC
A L E
X H
IB
IT
B
/8 /2
:5
:5
P
M G E
N G
S
V C \P ro j\ P
X P B
R
E P
L A
C E A
H U
S \F lo o rp la n s
D e s ig n \M
D -1
B .d g n
33012
B P
R E
S S
E R
-A
P R -2
PX901706P
R E
P L
A C
E A
H U
S
T
16" X 12"16" X 12"
X
X
12" X 6" 12" X 6"
12" X 12"
SPLIT
HORIZONTAL
EQUAL
SPLIT
4" HORIZONTAL
X
X
6" X 4"
7" X 5"
14" X 16"
24" X 16"
X
14" X 10" 14" X 10"14" X 6" 14" X 6"
14" X 16" 14" X 10"
X
S U
P P
L Y A
IR
X
X
T
12" X 8" 12" X 12" 16" X 12"
X
18" X 18"
X
12" X 6"
12" X 6"
X
X
THIS AREA
DIFFUSER (TYP)
18" X 12" SUPPLY
2 1
2.13.2
D
E
F
G
OFFICE
BARBER SHOP
WOMEN
DINING AREA
JANITOR
MEN
SODA
STORAGE
DINING AREA
MAIN LOBBY
A B
C D
LEGEND:
T
EXISTING EQUIPMENT TO REMAIN
EXISTING EQUIPMENT TO BE DEMOLISHED
AIR FLOW DIRECTION
EXISTING ELECTRICAL DISCONNECT
EXISTING THERMOSTAT
EXISTING 1’ X 1’ EXHAUST GRILLE
EXISTING 1’ X 2’ RETURN GRILLE
EXISTING 6" X 2’ RETURN GRILLE
EXISTING 1’ X 1’ RETURN GRILLE
EXISTING 2’ X 2’ RETURN GRILLE
SCALE (FEET)
AHU
EF
CU
CU
CU
CU
4A
C
4B
C
CU
CU
C
C
AHU
RH
B P
R E
S S
E R
KEY NOTES:
101C
MD-
PANEL "L"
PANEL "C"
(SHUT OFF)
FOR C-4A
DISCONNECT
FOR CU-1
DISCONNECT
FOR CU-2
DISCONNECT
FOR C-4B
DISCONNECT
REFRIGERATION UNIT
DISCONNECT FOR
FOR C-5
DISCONNECT
(NOT USED)
DISCONNECT
FOR ICE MAKER
LOCATED ON ROOF
GENERAL NOTES:
AIR-HANDLING UNITAHU-4
SYMBOL DESCRIPTION
C-3
RV-1 RELIEF VENT
AIR-HANDLING UNITAHU-5
RH-4
C-4A
C-4B
C-5
EF-5 EXHAUST FAN
SYMBOL DESCRIPTION
CU-2
CU-6
CU-7
CU-1
CU-8
CU-11
EQUIPMENT LIST (HVAC)
EQUIPMENT LIST (REFRIGERATION)
COOLING UNIT
COOLING UNIT (ON ROOF)
COOLING UNIT
COOLING UNIT
COOLING UNIT
COOLING UNIT
(NOT USED)
DISCONNECT
4 5
ROOF HOOD (OUTSIDE AIR)
P L
A N A
R E
A C
M E
C H
A N
IC
A L D
E M
O L
IT
IO
N
MECHANICAL DEMOLITION PLAN - AREA C
CONDENSING UNIT
CONDENSING UNIT
CONDENSING UNIT
CONDENSING UNIT
M A
T C
H L
IN
E S
E E M
D -1
D
MATCHLINE - SEE MD-101A
CONCRETE SLABS
TANK
GAS HOT-WATER
SLAB
4" CONCRETE
WATER TANK
ELECTRIC HOT-
(ICE)
FREEZER UNIT
UNIT
COOLER
UNIT
COOLER
UNIT
COOLER
ROOF
LADDER TO
FREEZERS
DOCK
LOADING
10" X 6"
16" X 8" OUTSIDE-AIR LOUVER.
THERMOSTAT FOR AHU-5.
THERMOSTAT FOR AHU-3.
DEMOLISHED.
EXISTING SUPPLY DIFFUSER TO BE
DEMOLISHED.
EXISTING DUCTWORK TO BE
CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING EXISTING SITE CONDITIONS.9.
OF THE CONTRACTOR UNTIL REUSED.
ITEMS INTENDED FOR REUSE ON THIS PROJECT SHALL REMAIN IN THE POSSESSION8.
ITS DISPOSAL.
BECOME THE PROPERTY OF THE CONTRACTOR, WHO SHALL BE RESPONSIBLE FOR
UNLESS NOTED OTHERWISE, ALL MATERIAL REMOVED AND NOT REUSED SHALL7.
UNITS, INCLUDING CONTROL WIRING.
CONTRACTOR SHALL DEMOLISH ALL THERMOSTATS SERVING EXISTING AIR-HANDLING6.
CONDUIT SHALL BE PRESERVED AND REUSED IF IT IS APPROPRIATELY SIZED.
EQUIPMENT SHALL REMAIN IN THE PANEL AND BE LABELED AS "SPARE". EXISTING
EXISTING ELECTRICAL PANEL. CIRCUIT BREAKERS THAT ARE NOT REUSED FOR NEW
INCLUDING DISCONNECTS, FOR DEMOLISHED HVAC EQUIPMENT BACK TO THE
CONTRACTOR SHALL DEMOLISH ALL EXISTING ELECTRICAL WIRING AND DEVICES,5.
TURNED IN TO THE DPW CLASSIFICATION UNIT PER SPECS (01 57 20.00 10)
C-5) AND ASSOCIATED REFRIGERANT PIPING. ALL EXISTING REFRIGERANT SHALL BE
CONTRACTOR SHALL DEMOLISH EXISTING CONDENSING UNITS (C-3, C-4A, C-4B, AND4.
SHALL BE PRESERVED AND REUSED FOR THE NEW HVAC SYSTEM.
UNLESS NOTED OTHERWISE, ALL EXISTING DIFFUSERS, GRILLES, AND DUCTWORK3.
LOUVER SERVING AHU-5 SHALL BE PRESERVED AND REUSED FOR NEW EQUIPMENT.
AND REUSED FOR NEW EQUIPMENT, IF POSSIBLE, OR CAPPED. EXISTING OUTSIDE-AIR
DUCTWORK SERVING AHU-4. EXISTING ROOF PENETRATION SHALL BE PRESERVED
CONTRACTOR SHALL DEMOLISH EXISTING ROOF HOOD (RH-4) AND OUTSIDE-AIR2.
NECESSARY TO INSTALL NEW EQUIPMENT.
PLACE. EXISTING DUCTWORK CONNECTED TO THESE UNITS MAY BE DEMOLISHED IF
PIPING SERVING THESE UNITS SHALL BE DRAINED, CAPPED, AND ABANDONED IN
INCLUDING THE EXTERNAL HEATING COIL SERVING AHU-5. ALL EXISTING HOT-WATER
CONTRACTOR SHALL DEMOLISH EXISTING AIR-HANDLING UNITS (AHU-4 AND AHU-5),1.
NUMBER
REFERENCE
SHEET
Project No.
D e s ig n e d B y
D a te
M a rk
Bldg. No.
F T
H O
O D T
E X
A S
S A
N T
A F
E E
N G
IN
E E
R D
R
B
L D
G
F O
R T H
O O
D T
E X
A S
P U
B L
IC
W
O R
K S
D
IR
E C
T O
R A
T E
D a te
D e s c ri p ti o n sivi
D secivreS & gn ir ee ni g n
E
D ir ec to rat eofPublic
W o rk s
P R
O J E
C T M
A N
A G
E R
P U
R P
O S
E S O
N L
Y F
O R B
ID
D
IN
G T
E C
H N
IC
A L E
X H
IB
IT
B
/8 /2
:5
:5
P
M G E
N G
S
V C \P ro j\ P
X P B
R
E P
L A
C E A
H U
S \F lo o rp la n s
D e s ig n \M
D -1
C .d g n
33012
B P
R E
S S
E R
-A
P R -2
PX901706P
R E
P L
A C
E A
H U
S
T
T
SPLIT
4" HORIZONTAL
SPLIT
5" HORIZONTAL
SPLIT
5" VERTICAL
SPLIT
6" HORIZONTAL
10" X 8"
9" X 6" 9" X 6"
X
12" X 10" 12" X 6"
9" X 6" 9" X 6" 9" X 6"
6" X 6"
14" X 10"
14" X 6"
14" X 6"
36" X 14"
SUPPLY AIR
6" X 6"
6" X 6"
9" X 5"
12" X 10"12" X 5" T
26" X 14"
18" X 18"
RETURN AIR
T
FD
56 4.2
3.5
A
B
C
D
OFFICE
OFFICE
OFFICE
COOLER
SHOPPETTE
STORAGE
EMPLOYEE
BREAK AREA
WOMEN
JANITOR
MEN
SHOPPETTE
RETAIL SALES
MECHANICAL
YARD
LEGEND:
T
EXISTING EQUIPMENT TO REMAIN
EXISTING EQUIPMENT TO BE DOMOLISHED
AIR FLOW DIRECTION
EXISTING ELECTRICAL DISCONNECT
EXISTING THERMOSTAT
EXISTING 1’ X 1’ EXHAUST GRILLE
EXISTING 1’ X 2’ RETURN GRILLE
EXISTING 6" X 2’ RETURN GRILLE
EXISTING 1’ X 1’ RETURN GRILLE
EXISTING 2’ X 2’ RETURN GRILLE
SCALE (FEET)
CU
C
CU
CU
CU
H
EF
EF
H
EF
H
AHU
RV
P
R E
S S
E R
KEY NOTES:
SYMBOL DESCRIPTION
CU-9
CU-5
CU-4
CU-10
EF-2
SYMBOL DESCRIPTION
EXHAUST FAN
H-1
RV-2 RELIEF VENT
C-6
EF-3 EXHAUST FAN
EF-4 EXHAUST FAN
HOOD VENT UNIT
H-2 HOOD VENT UNIT
H-3 HOOD VENT UNIT
AHU-7
EQUIPMENT LIST (HVAC)
EQUIPMENT LIST (REFRIGERATION)
COOLING UNIT
COOLING UNIT
COOLING UNIT
COOLING UNIT
GENERAL NOTES:
AIR-HANDLING UNIT (ON ROOF)
FED FROM PANEL PK3
PANEL "PK2 - SECTION 1"
FED FROM PANEL PK3
PANEL "PK2 - SECTION 2"
PANEL "PK4"
PANEL "PK1"
PANEL NOT USED
PANEL "PK3"
101D
MD-
EXISTING DUCTWORK TO BE DEMOLISHED.
THERMOSTAT FOR AHU-7.
THERMOSTAT FOR AHU-4.
MECHANICAL DEMOLITION PLAN - AREA D
P L
A N A
R E
A D
M E
C H
A N
IC
A L D
E M
O L
IT
IO
N
MATCHLINE - SEE MD-101B
M A
T C
H L
IN
E S
E E M
D -1
C
S E
E M
D -1
C
M A
T C
H L
IN
E
CONDENSING UNIT
DOCK
LOADING
FINISHED FLOOR
WALL IS 84" ABOVE
LOWER PART OF
SWITCH C-6
DISCONNECT
CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING EXISTING SITE CONDITIONS.8.
OF THE CONTRACTOR UNTIL REUSED.
ITEMS INTENDED FOR REUSE ON THIS PROJECT SHALL REMAIN IN THE POSSESSION7.
ITS DISPOSAL.
BECOME THE PROPERTY OF THE CONTRACTOR, WHO SHALL BE RESPONSIBLE FOR
UNLESS NOTED OTHERWISE, ALL MATERIAL REMOVED AND NOT REUSED SHALL6.
UNITS, INCLUDING CONTROL WIRING.
CONTRACTOR SHALL DEMOLISH ALL THERMOSTATS SERVING EXISTING AIR-HANDLING5.
CONDUIT SHALL BE PRESERVED AND REUSED IF IT IS APPROPRIATELY SIZED.
EQUIPMENT SHALL REMAIN IN THE PANEL AND BE LABELED AS "SPARE". EXISTING
EXISTING ELECTRICAL PANEL. CIRCUIT BREAKERS THAT ARE NOT REUSED FOR NEW
INCLUDING DISCONNECTS, FOR DEMOLISHED HVAC EQUIPMENT BACK TO THE
CONTRACTOR SHALL DEMOLISH ALL EXISTING ELECTRICAL WIRING AND DEVICES,4.
DPW CLASSIFICATION UNIT PER SPECS (01 57 20.00 10)
REFRIGERANT PIPING. ALL EXISTING REFRIGERANT SHALL BE TURNED IN TO THE
CONTRACTOR SHALL DEMOLISH EXISTING CONDENSING UNIT (C-6) AND ASSOCIATED3.
SHALL BE PRESERVED AND REUSED FOR THE NEW HVAC SYSTEM.
UNLESS NOTED OTHERWISE, ALL EXISTING DIFFUSERS, GRILLES, AND DUCTWORK2.
TO INSTALL NEW EQUIPMENT.
EXISTING DUCTWORK CONNECTED TO THIS UNIT MAY BE DEMOLISHED IF NECESSARY
CONTRACTOR SHALL DEMOLISH EXISTING AIR-HANDLING UNIT (AHU-7) ON ROOF.1.
NUMBER
REFERENCE
SHEET
Project No.
D e s ig n e d B y
D a te
M a rk
Bldg. No.
F T
H O
O D T
E X
A S
S A
N T
A F
E E
N G
IN
E E
R D
R
B
L D
G
F O
R T H
O O
D T
E X
A S
P U
B L
IC
W
O R
K S
D
IR
E C
T O
R A
T E
D a te
D e s c ri p ti o n sivi
D secivreS & gn ir ee ni g n
E
D ir ec to rat eofPublic
W o rk s
P R
O J E
C T M
A N
A G
E R
P U
R P
O S
E S O
N L
Y F
O R B
ID
D
IN
G T
E C
H N
IC
A L E
X H
IB
IT
B
/8 /2
:5
:5
P
M G E
N G
S
V C \P ro j\ P
X P B
R
E P
L A
C E A
H U
S \F lo o rp la n s
D e s ig n \M
D -1
D .d g n
33012
B P
R E
S S
E R
-A
P R -2
PX901706P
R E
P L
A C
E A
H U
S
T
T
X
X
X
X
X
6" X 6"
6" X 6"
30" X 14" 26" X 14"
X
X
X
12" X 5"
12" X 5"
14" X 6"
14" X 6"
X
14" X 6"
9" X 6"
X
X
10" X 8"
X
14" X 6"
14" X 6"
T
T
10" X 8"
24" X 12"
24" X 24"
SUPPLY AIR
3.5 3.1
A
B
C
D
C.1
COOLER
STORAGE
FREEZER
DINING AREA
BLIMPIE
SUBS
BURGER
KING
FOOD
PREP
FOOD PREP
FREEZER
FREEZER
A B
C D
LEGEND:
T
EXISTING EQUIPMENT TO REMAIN
EXISTING EQUIPMENT TO BE DEMOLISHED
AIR FLOW DIRECTION
EXISTING ELECTRICAL DISCONNECT
EXISTING THERMOSTAT
EXISTING 1’ X 1’ EXHAUST GRILLE
EXISTING 1’ X 2’ RETURN GRILLE
EXISTING 6" X 2’ RETURN GRILLE
EXISTING 1’ X 1’ RETURN GRILLE
EXISTING 2’ X 2’ RETURN GRILLE
KEY PLAN
SCALE: 1/8" = 1’
SCALE (FEET)
0 8 164
MATCHLINE - SEE MD-102B MATCHLINE - SEE MD-102B
KEY NOTES:
EQUIPMENT LIST
SYMBOL DESCRIPTION
AIR-HANDLING UNITAHU-6
C-2
C-1 CONDENSING UNIT
CONDENSING UNIT
AIR-HANDLING UNITAHU-3
EXISTING MECHANICAL PIPING PLAN - AREA A
P
IP
IN
G P
L A
N A
R E
A A
E X
IS
T
IN
G M
E C
H A
N
IC
A L
102A
MD-
102A
MD-
MD-
CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING EXISTING SITE CONDITIONS.5.
OF THE CONTRACTOR UNTIL REUSED.
ITEMS INTENDED FOR REUSE ON THIS PROJECT SHALL REMAIN IN THE POSSESSION4.
ITS DISPOSAL.
BECOME THE PROPERTY OF THE CONTRACTOR, WHO SHALL BE RESPONSIBLE FOR
UNLESS NOTED OTHERWISE, ALL MATERIAL REMOVED AND NOT REUSED SHALL3.
CAPPED, AND ABANDONED IN PLACE.
EXISTING REFRIGERANT PIPING FOR AHU-3 (NOT SHOWN) SHALL BE DRAINED,2.
INSTALL NEW PIPING TO SERVE NEW EQUIPMENT.
CONTRACTOR SHALL DEMOLISH EXISTING REFRIGERANT PIPING FOR AHU-6 AND1.
EXISTING NATURAL-GAS HOT-WATER TANK WITH 6" FLUE TO REMAIN.
EXISTING NATURAL-GAS METER AND REGULATOR TO REMAIN.
GENERAL NOTES:
B P
R E
S S
E R
NUMBER
REFERENCE
SHEET
Project No.
D e s ig n e d B y
D a te
M a rk
Bldg. No.
F T
H O
O D T
E X
A S
S A
N T
A F
E E
N G
IN
E E
R D
R
B
L D
G
F O
R T H
O O
D T
E X
A S
P U
B L
IC
W
O R
K S
D
IR
E C
T O
R A
T E
D a te
D e s c ri p ti o n sivi
D secivreS & gn ir ee ni g n
E
D ir ec to rat eofPublic
W o rk s
P R
O J E
C T M
A N
A G
E R
P U
R P
O S
E S O
N L
Y F
O R B
ID
D
IN
G T
E C
H N
IC
A L E
X H
IB
IT
B
/8 /2
:5
:5
P
M G E
N G
S
V C \P ro j\ P
X P B
R
E P
L A
C E A
H U
S \F lo o rp la n s
D e s ig n \M
D -1
A .d g n
33012
B P
R E
S S
E R
-A
P R -2
PX901706P
R E
P L
A C
E A
H U
S
C
C
AHU 6
AHU
UNDERGROUND
NATURAL-GAS MAIN
HIGH-PRESSURE
ON ROOF2" Ø
ON ROOF2" Ø
AND CAPPED
2 1/2" Ø THROUGH WALL
2" Ø
2" Ø
2" Ø
1" Ø 3/4" Ø
2 1
2.13.24.1
5.1
D
E
F
G
D
E
F
G
MECHANICAL
STORAGE
LAUNDRY/
ALTERATIONS
GNC
RETAIL SALES
OFFICE
OFFICE
BARBER SHOP
VESTIBULE
MAIN LOBBY
WOMEN
DINING AREA
JANITOR
MEN
SODA
STORAGE
DINING AREA
SHOPPETTE
RETAIL SALES
4 3
ROOM
MAIN LOBBY
A
LEGEND:
EXISTING REFRIGERANT LINE
EXISTING NATURAL-GAS SUPPLY LINE
SCALE: 1/8" = 1’
SCALE (FEET)
0 8 164
MATCHLINE - SEE MD-102A MATCHLINE - SEE MD-102A
KEY NOTES:
AIR-HANDLING UNIT
EQUIPMENT LIST
AHU-4
SYMBOL DESCRIPTION
C-5
C-4B
CONDENSING UNIT
CONDENSING UNIT
AIR-HANDLING UNITAHU-7
AIR-HANDLING UNITAHU-5
C-6
C-3
EXISTING MECHANICAL PIPING PLAN - AREA B
P
IP
IN
G P
L A
N A
R E
A B
E X
IS
T
IN
G M
E C
H A
N
IC
A L
102B
MD-
C-4A
CONDENSING UNIT
CONDENSING UNIT
CONDENSING UNIT
N
CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING EXISTING SITE CONDITIONS.5.
OF THE CONTRACTOR UNTIL REUSED.
ITEMS INTENDED FOR REUSE ON THIS PROJECT SHALL REMAIN IN THE POSSESSION4.
ITS DISPOSAL.
BECOME THE PROPERTY OF THE CONTRACTOR, WHO SHALL BE RESPONSIBLE FOR
UNLESS NOTED OTHERWISE, ALL MATERIAL REMOVED AND NOT REUSED SHALL3.
DRAINED, CAPPED, AND ABANDONED IN PLACE.
EXISTING REFRIGERANT PIPING FOR AHU-4 AND AHU-7 (NOT SHOWN) SHALL BE2.
INSTALL NEW PIPING TO SERVE NEW EQUIPMENT.
CONTRACTOR SHALL DEMOLISH EXISTING REFRIGERANT PIPING FOR AHU-5 AND1.
EXISTING NATURAL-GAS HOT-WATER TANK WITH 6" FLUE TO REMAIN.
PIPING CONTINUES THROUGH ROOF TO KITCHEN EQUIPMENT.
GENERAL NOTES:
B P
R E
S S
E R
NUMBER
REFERENCE
SHEET
Project No.
D e s ig n e d B y
D a te
M a rk
Bldg. No.
F T
H O
O D T
E X
A S
S A
N T
A F
E E
N G
IN
E E
R D
R
B
L D
G
F O
R T H
O O
D T
E X
A S
P U
B L
IC
W
O R
K S
D
IR
E C
T O
R A
T E
D a te
D e s c ri p ti o n sivi
D secivreS & gn ir ee ni g n
E
D ir ec to rat eofPublic
W o rk s
P R
O J E
C T M
A N
A G
E R
P U
R P
O S
E S O
N L
Y F
O R B
ID
D
IN
G T
E C
H N
IC
A L E
X H
IB
IT
B
/8 /2
:5
:5
P
M G E
N G
S
V C \P ro j\ P
X P B
R
E P
L A
C E A
H U
S \F lo o rp la n s
D e s ig n \M
D -1
B .d g n
33012
B P
R E
S S
E R
-A
P R -2
PX901706P
R E
P L
A C
E A
H U
S
AHU
AHU
AHU
C
C
4B
C
4A
C
C
TO AHU-5
HEATING COIL
1" Ø
1" Ø ON ROOF
2" Ø ON ROOF
56 4.2
3.5 3.1
A
B
C
D
C.1
A
B
C
D
OFFICE
OFFICE
OFFICE
COOLER
SHOPPETTE
STORAGE
EMPLOYEE
BREAK AREA
WOMEN
JANITOR
MEN
COOLER
STORAGE
FREEZER
DINING AREA
BLIMPIE
SUBS
BURGER
KING
SHOPPETTE
RETAIL SALES
FOOD
PREP
FOOD PREP
MECHANICAL
YARD
MECHANICAL
YARD
FREEZER
FREEZER
LEGEND:
EXISTING REFRIGERANT LINE
SCALE: 1/2" = 1’
20 4
SCALE (FEET)
N
KEY PLAN
AC
UH
B
ET
RH
AHU
AHU 5
RH
RH
N
B P
R E
S S
E R
AIR-HANDLING UNIT
EQUIPMENT LIST
AHU-1
ET-1
SYMBOL DESCRIPTION
B-1
UH-1
AC-1
RH-1
RH-2
RH-5
AHU-2 AIR-HANDLING UNIT
BOILER
ROOF HOOD (OUTSIDE-AIR)
ROOF HOOD (OUTSIDE-AIR)
ROOF HOOD (OUTSIDE-AIR)
UNIT HEATER
EXPANSION TANK
AIR COMPRESSOR
KEY NOTES:
GENERAL NOTES:
PANEL "MA"PANEL "LA"
PANEL
FIRE ALARM
PANEL "SLA"
PANEL "PA"
PANEL "PB"
PANEL
FIRE ALARM
PANEL
TEMPERATURE CONTROL
PANEL
MAIN DISTRIBUTION
MD-
101A
MD-
MD-
1A
HWP
1B
HWP
HWP-1A
HWP-1B
HOT-WATER PUMP
HOT-WATER PUMP
CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING EXISTING SITE CONDITIONS.9.
OF THE CONTRACTOR UNTIL REUSED.
ITEMS INTENDED FOR REUSE ON THIS PROJECT SHALL REMAIN IN THE POSSESSION8.
ITS DISPOSAL.
BECOME THE PROPERTY OF THE CONTRACTOR, WHO SHALL BE RESPONSIBLE FOR
UNLESS NOTED OTHERWISE, ALL MATERIAL REMOVED AND NOT REUSED SHALL7.
UNITS, INCLUDING CONTROL WIRING.
CONTRACTOR SHALL DEMOLISH ALL THERMOSTATS SERVING EXISTING AIR-HANDLING6.
CONDUIT SHALL BE PRESERVED AND REUSED IF IT IS APPROPRIATELY SIZED.
EQUIPMENT SHALL REMAIN IN THE PANEL AND BE LABELED AS "SPARE". EXISTING
EXISTING ELECTRICAL PANEL. CIRCUIT BREAKERS THAT ARE NOT REUSED FOR NEW
INCLUDING DISCONNECTS, FOR DEMOLISHED HVAC EQUIPMENT BACK TO THE
CONTRACTOR SHALL DEMOLISH ALL EXISTING ELECTRICAL WIRING AND DEVICES,5.
THE MECHANICAL ROOM WALL.
PIPING, FITTINGS, AND VALVES. EXISTING PIPING SHALL BE DRAINED AND CAPPED AT
EXISTING HYDRONIC-SYSTEM COMPONENTS IN THE MECHANICAL ROOM, INCLUDING
AND EXPANSION TANK (ET-1). IN ADDITION, CONTRACTOR SHALL DEMOLISH ALL
CONTRACTOR SHALL DEMOLISH EXISTING HOT-WATER PUMPS (HWP-1A AND HWP-1B)4.
CURB SHALL BE CAPPED.
CONTRACTOR SHALL DEMOLISH EXISTING BOILER (B-1) AND FLUE. EXISTING ROOF3.
POSSIBLE, OR CAPPED.
PENETRATIONS SHALL BE PRESERVED AND REUSED FOR NEW EQUIPMENT, IF
OUTSIDE-AIR DUCTWORK SERVING AHU-1 AND AHU-2, RESPECTIVELY. EXISTING ROOF
CONTRACTOR SHALL DEMOLISH EXISTING ROOF HOODS (RH-1 AND RH-2) AND2.
NECESSARY TO INSTALL NEW EQUIPMENT.
EXISTING DUCTWORK CONNECTED TO THESE UNITS MAY BE DEMOLISHED IF
CONTRACTOR SHALL DEMOLISH EXISTING AIR-HANDLING UNITS (AHU-1 AND AHU-2).1.
UNIT LOCATED 84" ABOVE FINISHED FLOOR, SUSPENDED FROM CEILING HANGERS.
THERMOSTAT FOR UH-1 TO REMAIN, LOCATED 84" ABOVE FINISHED FLOOR.
12’-8" ABOVE FINSHED FLOOR.
40" X 16" OUTSIDE-AIR LOUVER. ONE LOCATED AT FLOOR LEVEL AND ONE LOCATED
MECHANICAL ROOM DEMOLITION PLAN
D E
M O
L
IT
IO
N P
L A
N
M E
C H
A N
IC
A L R
O O
M
NUMBER
REFERENCE
SHEET
Project No.
D e s ig n e d B y
D a te
M a rk
Bldg. No.
F T
H O
O D T
E X
A S
S A
N T
A F
E E
N G
IN
E E
R D
R
B
L D
G
F O
R T H
O O
D T
E X
A S
P U
B L
IC
W
O R
K S
D
IR
E C
T O
R A
T E
D a te
D e s c ri p ti o n sivi
D secivreS & gn ir ee ni g n
E
D ir ec to rat eofPublic
W o rk s
P R
O J E
C T M
A N
A G
E R
P U
R P
O S
E S O
N L
Y F
O R B
ID
D
IN
G T
E C
H N
IC
A L E
X H
IB
IT
B
/8 /2
:5
:0
P
M G E
N G
S
V C \P ro j\ P
X P B
R
E P
L A
C E A
H U
S \F lo o rp la n s
D e s ig n \M
D -1
.d g n
33012
B P
R E
S S
E R
-A
P R -2
PX901706P
R E
P L
A C
E A
H U
S
T
MECHANICAL
T
FD
FD
FD
20" X 16"
SUPPLY AIR
38" X 14"
RETURN AIR
20" X 20"
38" X 14"
RETURN AIR
X
S U
P P
L Y A
IR
DUCT AT ROOF
12" X 12" EXHAUST
4" CONCRETE SLAB
INTAKE FROM ROOF
36" X 20" OUTSIDE-AIR
INTAKE FROM ROOF
36" X 20" OUTSIDE-AIR
38" X 14"
RETURN AIR
LEGEND:
T
EXISTING ELECTRICAL PANEL
AIR FLOW DIRECTION
EXISTING THERMOSTAT
EXISTING 1’ X 1’ EXHAUST GRILLE
SCALE (FEET)
N
KEY PLAN
N
B P
R E
S S
E R
AIR-HANDLING UNIT
EQUIPMENT LIST
AHU-1
SYMBOL DESCRIPTION
AIR-HANDLING UNITAHU-2
B-1
UH-1
BOILER
UNIT HEATER
102A
MD-
MD-
MD-EXISTING MECHANICAL ROOM PIPING PLAN
R O
O M P
IP
IN
G P
L A
N
E X
IS
T
IN
G M
E C
H A
N
IC
A L
GENERAL NOTES:
THROUGH ROOF
2" Ø SUPPLY RISER
THROUGH ROOF
2" Ø SUPPLY RISER
2 1/2" Ø THROUGH WALL
AND CAPPED
2 1/2" Ø THROUGH WALL
CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING EXISTING SITE CONDITIONS.5.
OF THE CONTRACTOR UNTIL REUSED.
ITEMS INTENDED FOR REUSE ON THIS PROJECT SHALL REMAIN IN THE POSSESSION4.
ITS DISPOSAL.
BECOME THE PROPERTY OF THE CONTRACTOR, WHO SHALL BE RESPONSIBLE FOR
UNLESS NOTED OTHERWISE, ALL MATERIAL REMOVED AND NOT REUSED SHALL3.
DRAINED, CAPPED, AND ABANDONED IN PLACE.
EXISTING REFRIGERANT PIPING FOR AHU-1 AND AHU-2 (NOT SHOWN) SHALL BE2.
EXISTING UNIT HEATER (UH-1) SHALL BE PRESERVED.
BOILER (B-1), INCLUDING ALL ASSOCIATED FITTINGS AND VALVES. PIPING FOR
CONTRACTOR SHALL DEMOLISH EXISTING NATURAL-GAS PIPING SERVING EXISTING1.
AHU
AHU
B
UH
NUMBER
REFERENCE
SHEET
Project No.
D e s ig n e d B y
D a te
M a rk
Bldg. No.
F T
H O
O D T
E X
A S
S A
N T
A F
E E
N G
IN
E E
R D
R
B
L D
G
F O
R T H
O O
D T
E X
A S
P U
B L
IC
W
O R
K S
D
IR
E C
T O
R A
T E
D a te
D e s c ri p ti o n sivi
D secivreS & gn ir ee ni g n
E
D ir ec to rat eofPublic
W o rk s
P R
O J E
C T M
A N
A G
E R
P U
R P
O S
E S O
N L
Y F
O R B
ID
D
IN
G T
E C
H N
IC
A L E
X H
IB
IT
B
/8 /2
:5
:0
P
M G E
N G
S
V C \P ro j\ P
X P B
R
E P
L A
C E A
H U
S \F lo o rp la n s
D e s ig n \M
D -1
.d g n
33012
B P
R E
S S
E R
-A
P R -2
PX901706P
R E
P L
A C
E A
H U
S
MECHANICAL
FD
FD
FD
4" CONCRETE SLAB
1/2" Ø TO UNIT HEATER
1 1/2" Ø TO BOILER
THROUGH ROOF
2" Ø SUPPLY RISER
THROUGH ROOF
2" Ø SUPPLY RISER
LEGEND:
N SCALE: 3/16" = 1’
101A
M- N
KEY PLAN0 4 8
SCALE (FEET)
MATCHLINE - SEE M-101C
M A
T C
H L
IN
E S
E E M
-1
B
TRANSFORMER
P L
A N A
R E
A A
M E
C H
A N
IC
A L D
U C
T W
O R
K
RV
CU 3
AHU
MECHANICAL DUCTWORK PLAN - AREA A
P
R E
S S
E R
1-4
B
1-3
1-2
1-1
2-5
2-1
A
2-6
2-7
2-12
2-2
2-3
2-4
2-8
2-9
2-10
2-11
KEY NOTES:
AIR-HANDLING UNIT
EQUIPMENT LIST
AHU-3
RV-1
SYMBOL DESCRIPTION
CU-8 COOLING UNIT (REFRIGERATION)
RELIEF VENT
101A M-
M-
GENERAL NOTES:
NEW SUPPLY DIFFUSER. SEE M-601 FOR SIZING DETAILS.
NEW DUCTWORK.
M-103 FOR DUCTWORK TO AIR HANDLING UNIT.
NEW LOCATION OF 38" X 14" OPENING FOR RETURN-AIR PLENUM. SEE SHEET
THERMOSTAT FOR AHU-2.
AHU
CONSTRUCTION.
ALL DIMENSIONS PRIOR TO PERFORMING ANY MATERIAL TAKE-OFFS AND PRIOR TO
ALL DIMENSIONS SHOWN ARE APPROXIMATE. CONTRACTOR SHALL FIELD-VERIFY8.
CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING EXISTING SITE CONDITIONS.7.
PENETRATIONS WHEREVER MECHANICAL, PLUMBING, OR ELECTRICAL WORK OCCURS.
PROVIDE PATCHING, CLOSURE, AND FINISHING OF ADJACENT SURFACES AND6.
(TAB) THE NEW HVAC SYSTEM.
CONTRACTOR SHALL BE RESPONSIBLE FOR TESTING, ADJUSTING, AND BALANCING5.
TRUNK. LOCATION OF THERMOSTAT IS SHOWN ON M-101B.
CONNECTED TO THE NEW ILON 600 ROUTER IN THE MECHANICAL ROOM VIA A LON
SERVE AHU-3. THIS DEVICE SHALL BE LONWORKS-COMPLIANT AND SHALL BE
CONTRACTOR SHALL INSTALL A NEW, WIRED, WALL-MOUNTED THERMOSTAT TO4.
AHU-3. THIS DISCONNECT SHALL BE PROTECTED BY A NEMA 3R ENCLOSURE.
CONTRACTOR SHALL INSTALL NEW ELECTRICAL WIRING AND A NEW DISCONNECT FOR3.
INSULATED PER SPECS (23 07 00).
PER SMACNA 3RD EDITION AND SPECS (23 00 00). ALL NEW DUCTWORK SHALL BE
CONTRACTOR SHALL INSTALL NEW DUCTWORK WITH THE DIMENSIONS INDICATED2.
DUCTWORK AS SHOWN. SEE M-601 FOR SIZING AND CAPACITY DETAILS.
GAS HEATING (AHU-3) ON ROOF. THIS UNIT SHALL BE CONNECTED TO EXISTING
CONTRACTOR SHALL INSTALL A NEW, PACKAGED AIR-HANDLING UNIT WITH NATURAL-1.
NUMBER
REFERENCE
SHEET
Project No.
D e s ig n e d B y
D a te
M a rk
Bldg. No.
F T
H O
O D T
E X
A S
S A
N T
A F
E E
N G
IN
E E
R D
R
B
L D
G
F O
R T H
O O
D T
E X
A S
P U
B L
IC
W
O R
K S
D
IR
E C
T O
R A
T E
D a te
D e s c ri p ti o n sivi
D secivreS & gn ir ee ni g n
E
D ir ec to rat eofPublic
W o rk s
P R
O J E
C T M
A N
A G
E R
P U
R P
O S
E S O
N L
Y F
O R B
ID
D
IN
G T
E C
H N
IC
A L E
X H
IB
IT
B
/8 /2
:5
:0
P
M G E
N G
S
V C \P ro j\ P
X P B
R
E P
L A
C E A
H U
S \F lo o rp la n s
D e s ig n \M
-1
A .d g n
33012
B P
R E
S S
E R
-A
P R -2
PX901706P
R E
P L
A C
E A
H U
S
20" X 16"
SUPPLY AIR
X
X
X
X
X
16" X 16"
X
9" X 8" 9" X 7" 9" X 5"
X
X
6" X 4"
9" X 7"
16" X 12"
10" VERTICAL SPLIT
6" HORIZONTAL SPLIT
S U
P P
L Y A
IR
12" X 9"
X
X
X
12" X 8"
12" X 9" 12" X 9"
X
T
3.24.1
5.1
D
E
F
G
MECHANICAL
STORAGE
LAUNDRY/
ALTERATIONS
GNC
RETAIL SALES
OFFICE
VESTIBULE
MAIN LOBBY
SHOPPETTE
RETAIL SALES
ROOM
LEGEND:
T
AIR FLOW DIRECTION
NEW ELECTRICAL DISCONNECT
NEW THERMOSTAT
EXISTING 1’ X 1’ EXHAUST GRILLE
EXISTING 1’ X 2’ RETURN DIFFUSER
EXISTING 6" X 2’ RETURN DIFFUSER
EXISTING 1’ X 1’ RETURN DIFFUSER
EXISTING 2’ X 2’ RETURN DIFFUSER
EXISTING 1’ X 1’ SUPPLY DIFFUSER
NEW 2’ X 2’ SUPPLY DIFFUSER
101B
M- N
KEY PLAN0 4 8
SCALE (FEET)
MATCHLINE - SEE M-101D
M A
T C
H L
IN
E S
E E M
-1
A
MECHANICAL DUCTWORK PLAN - AREA B
P L
A N A
R E
A B
M E
C H
A N
IC
A L D
U C
T W
O R
K
EF
AHU
RH
RV
B P
R E
S S
E R
KEY NOTES:
2-14
2-15
2-16
2-13
2-18
3-1
3-2
3-3
3-6
3-8
AIR-HANDLING UNIT
EQUIPMENT LIST
AHU-6
SYMBOL DESCRIPTION
RH-6
EF-1
RV-2
EXHAUST FAN
RELIEF VENT
GENERAL NOTES:
TANK
WATER
GAS HOT-
ROOF HOOD (OUTSIDE AIR)
THERMOSTAT FOR AHU-6.
THERMOSTAT FOR AHU-3.
6-1
6-2
6-4
6-3
6-5
6-6
CONSTRUCTION.
ALL DIMENSIONS PRIOR TO PERFORMING ANY MATERIAL TAKE-OFFS AND PRIOR TO
ALL DIMENSIONS SHOWN ARE APPROXIMATE. CONTRACTOR SHALL FIELD-VERIFY9.
CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING EXISTING SITE CONDITIONS.8.
PENETRATIONS WHEREVER MECHANICAL, PLUMBING, OR ELECTRICAL WORK OCCURS.
PROVIDE PATCHING, CLOSURE, AND FINISHING OF ADJACENT SURFACES AND7.
(TAB) THE NEW HVAC SYSTEM.
CONTRACTOR SHALL BE RESPONSIBLE FOR TESTING, ADJUSTING, AND BALANCING6.
TRUNK.
CONNECTED TO THE NEW ILON 600 ROUTER IN THE MECHANICAL ROOM VIA A LON
SERVE AHU-6. THIS DEVICE SHALL BE LONWORKS-COMPLIANT AND SHALL BE
CONTRACTOR SHALL INSTALL A NEW, WIRED, WALL-MOUNTED THERMOSTAT TO5.
ENCLOSURE AND A NEMA 3R ENCLOSURE, RESPECTIVELY.
AHU-6 AND HP-6. THESE DISCONNECTS SHALL BE PROTECTED BY A NEMA 1
CONTRACTOR SHALL INSTALL NEW ELECTRICAL WIRING AND DISCONNECTS FOR4.
OF HP-6 IS SHOWN ON M-101D.
SHALL BE PLACED ON AN EXISTING FORMED-AND-PLACED CONCRETE PAD. LOCATION
CONTRACTOR SHALL INSTALL A NEW HEAT PUMP (HP-6) TO SERVE AHU-6. THIS UNIT3.
INSULATED PER SPECS (23 07 00).
PER SMACNA 3RD EDITION AND SPECS (23 00 00). ALL NEW DUCTWORK SHALL BE
CONTRACTOR SHALL INSTALL NEW DUCTWORK WITH THE DIMENSIONS INDICATED2.
ROOF HOOD (RH-6) AND DUCTWORK. SEE M-601 FOR SIZING AND CAPACITY DETAILS.
SHOWN. IN ADDITION, THIS UNIT SHALL BE CONNECTED TO EXISTING OUTSIDE-AIR
THIS UNIT SHALL BE CONNECTED TO EXISTING SUPPLY AND RETURN DUCTWORK AS
CONTRACTOR SHALL INSTALL A NEW AIR-HANDLING UNIT (AHU-6) ABOVE CEILING.1.
NUMBER
REFERENCE
SHEET
Project No.
D e s ig n e d B y
D a te
M a rk
Bldg. No.
F T
H O
O D T
E X
A S
S A
N T
A F
E E
N G
IN
E E
R D
R
B
L D
G
F O
R T H
O O
D T
E X
A S
P U
B L
IC
W
O R
K S
D
IR
E C
T O
R A
T E
D a te
D e s c ri p ti o n sivi
D secivreS & gn ir ee ni g n
E
D ir ec to rat eofPublic
W o rk s
P R
O J E
C T M
A N
A G
E R
P U
R P
O S
E S O
N L
Y F
O R B
ID
D
IN
G T
E C
H N
IC
A L E
X H
IB
IT
B
/8 /2
:5
:0
P
M G E
N G
S
V C \P ro j\ P
X P B
R
E P
L A
C E A
H U
S \F lo o rp la n s
D e s ig n \M
-1
B .d g n
33012
B P
R E
S S
E R
-A
P R -2
PX901706P
R E
P L
A C
E A
H U
S
16" X 12"16" X 12"
X
X
12" X 6" 12" X 6"
12" X 12"
SPLIT
HORIZONTAL
EQUAL
SPLIT
4" HORIZONTAL
X
X
6" X 4"
7" X 5"
24" X 16"
X
14" X 10" 14" X 10" 14" X 6"
14" X 16" 14" X 10"
X
S U
P P
L Y A
IR
X
X
12" X 8" 12" X 12" 16" X 12"
X
18" X 18"
X
12" X 6"
12" X 6"
X
X
T
THIS AREA
DIFFUSER (TYP)
18" X 12" SUPPLY
T
36" X 16"
SUPPLY AIR
2 1
2.13.2
D
E
F
G
OFFICE
BARBER SHOP
WOMEN
DINING AREA
JANITOR
MEN
SODA
STORAGE
DINING AREA
MAIN LOBBY
A B
C D
LEGEND:
T
AIR FLOW DIRECTION
NEW ELECTRICAL DISCONNECT
NEW THERMOSTAT
EXISTING 1’ X 1’ EXHAUST GRILLE
EXISTING 1’ X 2’ RETURN DIFFUSER
EXISTING 6" X 2’ RETURN DIFFUSER
EXISTING 1’ X 1’ RETURN DIFFUSER
EXISTING 2’ X 2’ RETURN DIFFUSER
EXISTING 1’ X 1’ SUPPLY DIFFUSER
NEW 2’ X 2’ SUPPLY DIFFUSER
EXISTING 2’ X 2’ SUPPLY DIFFUSER
2-17
3-4
101C
M- N
KEY PLAN0 4 8
SCALE (FEET)
MATCHLINE - SEE M-101A
M A
T C
H L
IN
E S
E E M
-1
D
MECHANICAL DUCTWORK PLAN - AREA C
P L
A N A
R E
A C
M E
C H
A N
IC
A L D
U C
T W
O R
K
AHU
EF
CU
CU
CU
CU
CU
CU
HP
AHU
B P
R E
S S
E R
1-5
1-6
- 240 1-7
C
1-9
1-10
1-11
1-8
B
4-1
AHU-4
SYMBOL DESCRIPTION
RV-1 RELIEF VENT
AIR-HANDLING UNITAHU-5
HP-5
EF-5 EXHAUST FAN
EQUIPMENT LIST (HVAC)
SYMBOL DESCRIPTION
CU-2
CU-6
CU-7
CU-1
CU-8
CU-11
EQUIPMENT LIST (REFRIGERATION)
COOLING UNIT
COOLING UNIT (ON ROOF)
COOLING UNIT
COOLING UNIT
COOLING UNIT
COOLING UNIT
GENERAL NOTES:
KEY NOTES:
FOR ICE MAKER
LOCATED ON ROOF
FOR CU-1
DISCONNECT
FOR CU-2
DISCONNECT
REFRIGERATION UNIT
DISCONNECT FOR
ROOF
LADDER TO
UNIT
COOLER
UNIT
COOLER
UNIT
COOLER
(ICE)
FREEZER UNIT
FREEZERS
SLAB
4" CONCRETE
TANK
GAS HOT-WATER
DOCK
LOADING
CONCRETE SLABS
FOR C-5
DISCONNECT
16" X 8" OUTSIDE-AIR LOUVER.
THERMOSTAT FOR AHU-5.
THERMOSTAT FOR AHU-1.
FOR SIZING DETAILS.
NEW SUPPLY DIFFUSER. SEE M-601
NEW DUCTWORK.
AIR-HANDLING UNIT
WATER TANK
ELECTRIC HOT-
HEAT PUMP
CONSTRUCTION.
ALL DIMENSIONS PRIOR TO PERFORMING ANY MATERIAL TAKE-OFFS AND PRIOR TO
ALL DIMENSIONS SHOWN ARE APPROXIMATE. CONTRACTOR SHALL FIELD-VERIFY10.
CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING EXISTING SITE CONDITIONS.9.
PENETRATIONS WHEREVER MECHANICAL, PLUMBING, OR ELECTRICAL WORK OCCURS.
PROVIDE PATCHING, CLOSURE, AND FINISHING OF ADJACENT SURFACES AND8.
(TAB) THE NEW HVAC SYSTEM.
CONTRACTOR SHALL BE RESPONSIBLE FOR TESTING, ADJUSTING, AND BALANCING7.
A LON TRUNK. LOCATION OF THERMOSTAT FOR AHU-4 IS SHOWN ON M-101D.
SHALL BE CONNECTED TO THE NEW ILON 600 ROUTER IN THE MECHANICAL ROOM VIA
SERVE AHU-4 AND AHU-5. THESE DEVICES SHALL BE LONWORKS-COMPLIANT AND
CONTRACTOR SHALL INSTALL NEW, WIRED, WALL-MOUNTED THERMOSTATS TO6.
ENCLOSURE, A NEMA 1 ENCLOSURE, AND A NEMA 3R ENCLOSURE, RESPECTIVELY.
AHU-4, AHU-5, AND HP-5. THESE DISCONNECTS SHALL BE PROTECTED BY A NEMA 3R
CONTRACTOR SHALL INSTALL NEW ELECTRICAL WIRING AND DISCONNECTS FOR5.
SHALL BE PLACED ON AN EXISTING FORMED-AND-PLACED CONCRETE PAD.
CONTRACTOR SHALL INSTALL A NEW HEAT PUMP (HP-5) TO SERVE AHU-5. THIS UNIT4.
INSULATED PER SPECS (23 07 00).
PER SMACNA 3RD EDITION AND SPECS (23 00 00). ALL NEW DUCTWORK SHALL BE
CONTRACTOR SHALL INSTALL NEW DUCTWORK WITH THE DIMENSIONS INDICATED3.
SIZING AND CAPACITY DETAILS.
EXISTING OUTSIDE-AIR LOUVER IN THE SHOPPETTE STORAGE AREA. SEE M-601 FOR
CONNECT IT TO EXISTING DUCTWORK AS SHOWN. THIS UNIT SHALL UTILIZE THE
CONTRACTOR SHALL INSTALL A NEW AIR-HANDLING UNIT (AHU-5) ABOVE CEILING AND2.
DUCTWORK AS SHOWN. SEE M-601 FOR SIZING AND CAPACITY DETAILS.
GAS HEATING (AHU-4) ON ROOF. THIS UNIT SHALL BE CONNECTED TO EXISTING
CONTRACTOR SHALL INSTALL A NEW, PACKAGED AIR-HANDLING UNIT WITH NATURAL-1.
NUMBER
REFERENCE
SHEET
Project No.
D e s ig n e d B y
D a te
M a rk
Bldg. No.
F T
H O
O D T
E X
A S
S A
N T
A F
E E
N G
IN
E E
R D
R
B
L D
G
F O
R T H
O O
D T
E X
A S
P U
B L
IC
W
O R
K S
D
IR
E C
T O
R A
T E
D a te
D e s c ri p ti o n sivi
D secivreS & gn ir ee ni g n
E
D ir ec to rat eofPublic
W o rk s
P R
O J E
C T M
A N
A G
E R
P U
R P
O S
E S O
N L
Y F
O R B
ID
D
IN
G T
E C
H N
IC
A L E
X H
IB
IT
B
/8 /2
:5
:0
P
M G E
N G
S
V C \P ro j\ P
X P B
R
E P
L A
C E A
H U
S \F lo o rp la n s
D e s ig n \M
-1
C .d g n
33012
B P
R E
S S
E R
-A
P R -2
PX901706P
R E
P L
A C
E A
H U
S
SPLIT
4" HORIZONTAL
SPLIT
5" HORIZONTAL
X
12" X 10" 12" X 6"
9" X 6" 9" X 6"
36" X 14"
SUPPLY AIR
6" X 6"
6" X 6"
12" X 10"12" X 5"
26" X 14"
18" X 18"
RETURN AIR
12" X 10"
12" X 10"
12" X 10" 12" X 10"
10" X 6"
6" X 6"
T
T
FD
56 4.2
3.5
A
B
C
D
OFFICE
OFFICE
OFFICE
COOLER
SHOPPETTE
STORAGE
EMPLOYEE
BREAK AREA
WOMEN
JANITOR
MEN
SHOPPETTE
RETAIL SALES
MECHANICAL
YARD
LEGEND:
T
AIR FLOW DIRECTION
NEW ELECTRICAL DISCONNECT
NEW THERMOSTAT
EXISTING 1’ X 1’ EXHAUST GRILLE
EXISTING 1’ X 2’ RETURN DIFFUSER
EXISTING 6" X 2’ RETURN DIFFUSER
EXISTING 1’ X 1’ RETURN DIFFUSER
EXISTING 2’ X 2’ RETURN DIFFUSER
EXISTING 1’ X 1’ SUPPLY DIFFUSER
NEW 2’ X 2’ SUPPLY DIFFUSER
EXISTING 2’ X 2’ SUPPLY DIFFUSER
4-3
4-2
4-4
4-4
4-4
4-4
101D
M- N
KEY PLAN0 4 8
SCALE (FEET)
D
3.5
M A
T C
H L
IN
E S
E E M
-1
C
MATCHLINE - SEE M-101B
MECHANICAL DUCTWORK PLAN - AREA D
P L
A N A
R E
A D
M E
C H
A N
IC
A L D
U C
T W
O R
K
CU
HP
CU
CU
CU
H
EF
EF
H
EF
H
RV
S E
E M
-1
C
M A
T C
H L
IN
E
P
R E
S S
E R
3-7
3-9
4-9
7-3
7-1
7-5
7-4
7-7
7-8
7-9
7-2
4-11
4-10
SYMBOL DESCRIPTION
CU-9
CU-5
CU-4
CU-10
EF-2
SYMBOL DESCRIPTION
EXHAUST FAN
H-1
RV-2 RELIEF VENT
HP-6
EF-3 EXHAUST FAN
EF-4 EXHAUST FAN
HOOD VENT UNIT
H-2 HOOD VENT UNIT
H-3 HOOD VENT UNIT
AHU-7
EQUIPMENT LIST (HVAC)
EQUIPMENT LIST (REFRIGERATION)
COOLING UNIT
COOLING UNIT
COOLING UNIT
COOLING UNIT
PANEL "PK4"
PANEL "PK1"
PANEL NOT USED
PANEL "PK3"
FED FROM PANEL PK3
PANEL "PK2 - SECTION 2"
AHU
GENERAL NOTES:
KEY NOTES:
33 NEW DUCTWORK.
THERMOSTAT FOR AHU-7.
THERMOSTAT FOR AHU-4.
FROM PANEL PK3
SECTION 1" FED
PANEL "PK2 -
AIR-HANDLING UNIT
HEAT PUMP
FINISHED FLOOR
WALL IS 84" ABOVE
LOWER PART OF
DOCK
LOADING
CONSTRUCTION.
ALL DIMENSIONS PRIOR TO PERFORMING ANY MATERIAL TAKE-OFFS AND PRIOR TO
ALL DIMENSIONS SHOWN ARE APPROXIMATE. CONTRACTOR SHALL FIELD-VERIFY8.
CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING EXISTING SITE CONDITIONS.7.
PENETRATIONS WHEREVER MECHANICAL, PLUMBING, OR ELECTRICAL WORK OCCURS.
PROVIDE PATCHING, CLOSURE, AND FINISHING OF ADJACENT SURFACES AND6.
(TAB) THE NEW HVAC SYSTEM.
CONTRACTOR SHALL BE RESPONSIBLE FOR TESTING, ADJUSTING, AND BALANCING5.
TRUNK.
CONNECTED TO THE NEW ILON 600 ROUTER IN THE MECHANICAL ROOM VIA A LON
SERVE AHU-7. THIS DEVICE SHALL BE LONWORKS-COMPLIANT AND SHALL BE
CONTRACTOR SHALL INSTALL A NEW, WIRED, WALL-MOUNTED THERMOSTAT TO4.
AHU-7. THIS DISCONNECT SHALL BE PROTECTED BY A NEMA 3R ENCLOSURE.
CONTRACTOR SHALL INSTALL NEW ELECTRICAL WIRING AND A NEW DISCONNECT FOR3.
INSULATED PER SPECS (23 07 00).
PER SMACNA 3RD EDITION AND SPECS (23 00 00). ALL NEW DUCTWORK SHALL BE
CONTRACTOR SHALL INSTALL NEW DUCTWORK WITH THE DIMENSIONS INDICATED2.
DUCTWORK AS SHOWN. SEE M-601 FOR SIZING AND CAPACITY DETAILS.
GAS HEATING (AHU-7) ON ROOF. THIS UNIT SHALL BE CONNECTED TO EXISTING
CONTRACTOR SHALL INSTALL A NEW, PACKAGED AIR-HANDLING UNIT WITH NATURAL-1.
NUMBER
REFERENCE
SHEET
Project No.
D e s ig n e d B y
D a te
M a rk
Bldg. No.
F T
H O
O D T
E X
A S
S A
N T
A F
E E
N G
IN
E E
R D
R
B
L D
G
F O
R T H
O O
D T
E X
A S
P U
B L
IC
W
O R
K S
D
IR
E C
T O
R A
T E
D a te
D e s c ri p ti o n sivi
D secivreS & gn ir ee ni g n
E
D ir ec to rat eofPublic
W o rk s
P R
O J E
C T M
A N
A G
E R
P U
R P
O S
E S O
N L
Y F
O R B
ID
D
IN
G T
E C
H N
IC
A L E
X H
IB
IT
B
/8 /2
:5
:1
P
M G E
N G
S
V C \P ro j\ P
X P B
R
E P
L A
C E A
H U
S \F lo o rp la n s
D e s ig n \M
-1
D .d g n
33012
B P
R E
S S
E R
-A
P R -2
PX901706P
R E
P L
A C
E A
H U
S
X
X
X
X
X
6" X 6"
30" X 14" 26" X 14"
X
X
X
12" X 5"
12" X 5"
14" X 6"
14" X 6"
X
14" X 6"
9" X 6"
X
X
10" X 8"
14" X 6"
14" X 6"
10" X 8"
24" X 24"
SUPPLY AIR
24" X 12"
14" X 12"
T
T
3.1
A
B
C
C.1
COOLER
STORAGE
FREEZER
DINING AREA
BLIMPIE
SUBS
BURGER
KING
FOOD
PREP
FOOD PREP
FREEZER
FREEZER
A B
C D
LEGEND:
T
AIR FLOW DIRECTION
NEW ELECTRICAL DISCONNECT
NEW THERMOSTAT
EXISTING 1’ X 1’ EXHAUST GRILLE
EXISTING 1’ X 2’ RETURN DIFFUSER
EXISTING 6" X 2’ RETURN DIFFUSER
EXISTING 1’ X 1’ RETURN DIFFUSER
EXISTING 2’ X 2’ RETURN DIFFUSER
EXISTING 1’ X 1’ SUPPLY DIFFUSER
NEW 2’ X 2’ SUPPLY DIFFUSER
EXISTING 2’ X 2’ SUPPLY DIFFUSER
3-5
4-5
4-7
4-6
4-8
7-6
SCALE: 1/8" = 1’
SCALE (FEET)
0 8 164
EQUIPMENT LIST
SYMBOL DESCRIPTION
AIR-HANDLING UNITAHU-6
C-2
C-1 CONDENSING UNIT
CONDENSING UNIT
AIR-HANDLING UNITAHU-3
NEW MECHANICAL PIPING PLAN - AREA A
P L
A N A
R E
A A
N E
W M
E C
H A
N
IC
A L P
IP
IN
G
102A
M-
GENERAL NOTES:
MATCHLINE - SEE M-102BMATCHLINE - SEE M-102B
102A M-
M-
M-501 FOR FURTHER DETAILS.
WALKWAY/PROTECTION PADS EQUIVALENT TO A DURO-LAST ROOF TRAK III. SEE
TO A DURO-LAST CADDY PYRAMID RL. THESE SUPPORTS SHALL BE INSTALLED ON
ALL NEW ROOFTOP PIPING SHALL BE ROUTED ON NEW ROOF SUPPORTS EQUIVALENT2.
DIMENSIONS INDICATED AND CONNECT IT TO NEW EQUIPMENT.
CONTRACTOR SHALL INSTALL NEW NATURAL-GAS PIPING ON ROOF WITH THE1.
B P
R E
S S
E R
NUMBER
REFERENCE
SHEET
Project No.
D e s ig n e d B y
D a te
M a rk
Bldg. No.
F T
H O
O D T
E X
A S
S A
N T
A F
E E
N G
IN
E E
R D
R
B
L D
G
F O
R T H
O O
D T
E X
A S
P U
B L
IC
W
O R
K S
D
IR
E C
T O
R A
T E
D a te
D e s c ri p ti o n sivi
D secivreS & gn ir ee ni g n
E
D ir ec to rat eofPublic
W o rk s
P R
O J E
C T M
A N
A G
E R
P U
R P
O S
E S O
N L
Y F
O R B
ID
D
IN
G T
E C
H N
IC
A L E
X H
IB
IT
B
/8 /2
:5
:1
P
M G E
N G
S
V C \P ro j\ P
X P B
R
E P
L A
C E A
H U
S \F lo o rp la n s
D e s ig n \M
-1
A .d g n
33012
B P
R E
S S
E R
-A
P R -2
PX901706P
R E
P L
A C
E A
H U
S
AHU
AHU
AHU
3/4" Ø
1" Ø
1" Ø
1" Ø
ON ROOF2" Ø
ON ROOF2" Ø 2" Ø
2" Ø
3/4" Ø1" Ø
2" Ø
1 1/2" Ø ON ROOFUNDERGROUND
NATURAL-GAS MAIN
HIGH-PRESSURE
AND CAPPED
2 1/2" Ø THROUGH WALL
2 1
2.13.24.1
5.1
D
E
F
G
D
E
F
G
MECHANICAL
STORAGE
LAUNDRY/
ALTERATIONS
GNC
RETAIL SALES
OFFICE
OFFICE
BARBER SHOP
VESTIBULE
MAIN LOBBY
WOMEN
DINING AREA
JANITOR
MEN
SODA
STORAGE
DINING AREA
SHOPPETTE
RETAIL SALES
4 3
ROOM
MAIN LOBBY
LEGEND:
NEW REFRIGERANT LINE
NEW NATURAL-GAS SUPPLY LINE
SCALE: 1/8" = 1’
SCALE (FEET)
0 8 164
AIR-HANDLING UNIT
EQUIPMENT LIST
AHU-4
SYMBOL DESCRIPTION
C-5
AIR-HANDLING UNITAHU-7
AIR-HANDLING UNITAHU-5
C-6
CONDENSING UNIT
CONDENSING UNIT
N
NEW MECHANICAL PIPING PLAN - AREA B
P L
A N A
R E
A B
N E
W M
E C
H A
N
IC
A L P
IP
IN
G
102B
M-
GENERAL NOTES:
MATCHLINE - SEE M-102AMATCHLINE - SEE M-102A
M-501 FOR FURTHER DETAILS.
WALKWAY/PROTECTION PADS EQUIVALENT TO A DURO-LAST ROOF TRAK III. SEE
TO A DURO-LAST CADDY PYRAMID RL. THESE SUPPORTS SHALL BE INSTALLED ON
ALL NEW ROOFTOP PIPING SHALL BE ROUTED ON NEW ROOF SUPPORTS EQUIVALENT2.
DIMENSIONS INDICATED AND CONNECT IT TO NEW EQUIPMENT.
CONTRACTOR SHALL INSTALL NEW NATURAL-GAS PIPING ON ROOF WITH THE1.
B P
R E
S S
E R
NUMBER
REFERENCE
SHEET
Project No.
D e s ig n e d B y
D a te
M a rk
Bldg. No.
F T
H O
O D T
E X
A S
S A
N T
A F
E E
N G
IN
E E
R D
R
B
L D
G
F O
R T H
O O
D T
E X
A S
P U
B L
IC
W
O R
K S
D
IR
E C
T O
R A
T E
D a te
D e s c ri p ti o n sivi
D secivreS & gn ir ee ni g n
E
D ir ec to rat eofPublic
W o rk s
P R
O J E
C T M
A N
A G
E R
P U
R P
O S
E S O
N L
Y F
O R B
ID
D
IN
G T
E C
H N
IC
A L E
X H
IB
IT
B
/8 /2
:5
:1
P
M G E
N G
S
V C \P ro j\ P
X P B
R
E P
L A
C E A
H U
S \F lo o rp la n s
D e s ig n \M
-1
B .d g n
33012
B P
R E
S S
E R
-A
P R -2
PX901706P
R E
P L
A C
E A
H U
S
AHU
AHU
AHU
C
C
3/4" Ø
1" Ø
3/4" Ø ON ROOF
1" Ø ON ROOF
2" Ø ON ROOF
56 4.2
3.5 3.1
A
B
C
D
C.1
A
B
C
D
OFFICE
OFFICE
OFFICE
COOLER
SHOPPETTE
STORAGE
EMPLOYEE
BREAK AREA
WOMEN
JANITOR
MEN
COOLER
STORAGE
FREEZER
DINING AREA
BLIMPIE
SUBS
BURGER
KING
SHOPPETTE
RETAIL SALES
FOOD
PREP
FOOD PREP
MECHANICAL
YARD
MECHANICAL
YARD
FREEZER
FREEZER
LEGEND:
NEW REFRIGERANT LINE
NEW NATURAL-GAS SUPPLY LINE
SCALE (FEET)
N
KEY PLAN
AC
UH
AHU
AHU
N
B P
R E
S S
E R
EQUIPMENT LIST
AHU-1
SYMBOL DESCRIPTION
UH-1
AC-1
AHU-2
UNIT HEATER
AIR COMPRESSOR
KEY NOTES:
GENERAL NOTES:
PANEL "MA"PANEL "LA"
PANEL
FIRE ALARM
PANEL "SLA"
PANEL "PA"
PANEL "PB"
PANEL
FIRE ALARM
PANEL
TEMPERATURE CONTROL
PANEL
MAIN DISTRIBUTION
AIR-HANDLING UNIT
AIR-HANDLING UNIT
FLOOR
84" ABOVE FINISHED
UH-1 THERMOSTAT
101A M-
M-
NEW ILON 600 ROUTER IN A NEMA 1 ENCLOSURE.
CONSTRUCTION.
ALL DIMENSIONS PRIOR TO PERFORMING ANY MATERIAL TAKE-OFFS AND PRIOR TO
ALL DIMENSIONS SHOWN ARE APPROXIMATE. CONTRACTOR SHALL FIELD-VERIFY9.
CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING EXISTING SITE CONDITIONS.8.
PENETRATIONS WHEREVER MECHANICAL, PLUMBING, OR ELECTRICAL WORK OCCURS.
PROVIDE PATCHING, CLOSURE, AND FINISHING OF ADJACENT SURFACES AND7.
(TAB) THE NEW HVAC SYSTEM.
CONTRACTOR SHALL BE RESPONSIBLE FOR TESTING, ADJUSTING, AND BALANCING6.
OF THE AHU THERMOSTATS IN THE BUILDING. SEE M-701 FOR DETAILS.
CONTRACTOR SHALL INSTALL A NEW ILON 600 ROUTER TO COLLECT DATE FROM ALL5.
RESPECTIVELY.
TRUNK. LOCATIONS OF THERMOSTATS ARE SHOWN ON M-101C AND M-101A,
CONNECTED TO THE NEW ILON 600 ROUTER IN THE MECHANICAL ROOM VIA A LON
AHU-1 AND AHU-2. THESE DEVICES SHALL BE LONWORKS-COMPLIANT AND SHALL BE
CONTRACTOR SHALL INSTALL NEW, WIRED, WALL-MOUNTED THERMOSTATS TO SERVE4.
ENCLOSURES.
AHU-1 AND AHU-2. THESE DISCONNECTS SHALL BE PROTECTED BY NEMA 3R
CONTRACTOR SHALL INSTALL NEW ELECTRICAL WIRING AND DISCONNECTS FOR3.
INSULATED PER SPECS (23 07 00).
PER SMACNA 3RD EDITION AND SPECS (23 00 00). ALL NEW DUCTWORK SHALL BE
CONTRACTOR SHALL INSTALL NEW DUCTWORK WITH THE DIMENSIONS INDICATED2.
EXISTING DUCTWORK AS SHOWN. SEE M-601 FOR SIZING AND CAPACITY DETAILS.
GAS HEATING (AHU-1 AND AHU-2) ON ROOF. THESE UNITS SHALL BE CONNECTED TO
CONTRACTOR SHALL INSTALL NEW, PACKAGED AIR-HANDLING UNITS WITH NATURAL-1.
MECHANICAL ROOM PIPING PLAN
P L
A N
M E
C H
A N
IC
A L R
O O
M P
IP
IN
G
M-103
NUMBER
REFERENCE
SHEET
Project No.
D e s ig n e d B y
D a te
M a rk
Bldg. No.
F T
H O
O D T
E X
A S
S A
N T
A F
E E
N G
IN
E E
R D
R
B
L D
G
F O
R T H
O O
D T
E X
A S
P U
B L
IC
W
O R
K S
D
IR
E C
T O
R A
T E
D a te
D e s c ri p ti o n sivi
D secivreS & gn ir ee ni g n
E
D ir ec to rat eofPublic
W o rk s
P R
O J E
C T M
A N
A G
E R
P U
R P
O S
E S O
N L
Y F
O R B
ID
D
IN
G T
E C
H N
IC
A L E
X H
IB
IT
B
/8 /2
:5
:1
P
M G E
N G
S
V C \P ro j\ P
X P B
R
E P
L A
C E A
H U
S \F lo o rp la n s
D e s ig n \M
-1 .d g n
33012
B P
R E
S S
E R
-A
P R -2
PX901706P
R E
P L
A C
E A
H U
S
MECHANICAL
T
FD
FD
FD
DUCT AT ROOF
12" X 12" EXHAUST
4" CONCRETE SLAB
X
R E
T U
R N A
IR
38" X 14"
RETURN AIR
30" X 14"
SUPPLY AIR
38" X 14"
RETURN AIR
IL
O
N
LEGEND:
T
EXISTING ELECTRICAL PANEL
AIR FLOW DIRECTION
EXISTING THERMOSTAT
EXISTING 1’ X 1’ EXHAUST GRILLE
SCALE (FEET)
N
KEY PLAN
N
B P
R E
S S
E R
AIR-HANDLING UNIT
EQUIPMENT LIST
AHU-1
SYMBOL DESCRIPTION
AIR-HANDLING UNITAHU-2
UH-1 UNIT HEATER
102A M-
M-
NEW MECHANICAL ROOM PIPING PLAN
P
IP
IN
G P
L A
N
N E
W M
E C
H A
N
IC
A L R
O O
M
M-104
THROUGH ROOF
2" Ø SUPPLY RISER
THROUGH ROOF
2" Ø SUPPLY RISER
2 1/2" Ø THROUGH WALL
AND CAPPED
2 1/2" Ø THROUGH WALL
AHU
AHU
UH
GENERAL NOTES:
M-501 FOR FURTHER DETAILS.
WALKWAY/PROTECTION PADS EQUIVALENT TO A DURO-LAST ROOF TRAK III. SEE
TO A DURO-LAST CADDY PYRAMID RL. THESE SUPPORTS SHALL BE INSTALLED ON
ALL NEW ROOFTOP PIPING SHALL BE ROUTED ON NEW ROOF SUPPORTS EQUIVALENT2.
DIMENSIONS INDICATED AND CONNECT IT TO NEW EQUIPMENT.
CONTRACTOR SHALL INSTALL NEW NATURAL-GAS PIPING ON ROOF WITH THE1.
NUMBER
REFERENCE
SHEET
Project No.
D e s ig n e d B y
D a te
M a rk
Bldg. No.
F T
H O
O D T
E X
A S
S A
N T
A F
E E
N G
IN
E E
R D
R
B
L D
G
F O
R T H
O O
D T
E X
A S
P U
B L
IC
W
O R
K S
D
IR
E C
T O
R A
T E
D a te
D e s c ri p ti o n sivi
D secivreS & gn ir ee ni g n
E
D ir ec to rat eofPublic
W o rk s
P R
O J E
C T M
A N
A G
E R
P U
R P
O S
E S O
N L
Y F
O R B
ID
D
IN
G T
E C
H N
IC
A L E
X H
IB
IT
B
/8 /2
:5
:1
P
M G E
N G
S
V C \P ro j\ P
X P B
R
E P
L A
C E A
H U
S \F lo o rp la n s
D e s ig n \M
-1 .d g n
33012
B P
R E
S S
E R
-A
P R -2
PX901706P
R E
P L
A C
E A
H U
S
MECHANICAL
FD
FD
FD
3/4" Ø
3/4" Ø
THROUGH ROOF
2" Ø SUPPLY RISER
THROUGH ROOF
2" Ø SUPPLY RISER
4" CONCRETE SLAB
1/2" Ø TO UNIT HEATER
LEGEND:
NEW NATURAL-GAS SUPPLY LINE
3/4" Ø ON ROOF
P
R E
S S
E R
M E
C H
A N
IC
A L D
E T
A
IL
S
NOT TO SCALE
DUCT MAIN AND BRANCH TAKE-OFFS
NOT TO SCALE
NOT TO SCALE
AHU CONDENSATE DRAIN DETAIL
NOT TO SCALE
DIFFUSER/GRILLE CONNECTION DETAIL
M-
M-
WITH DAMPER AND LONG-RADIUS ELBOW
SPIN COLLAR FLEXIBLE DUCT CONNECTOR
NOT TO SCALE
WITH DAMPER
SPIN COLLAR FLEXIBLE DUCT CONNECTOR
M-
M-
M-
M-
M-
M-
M-
M-
NOT TO SCALE
M-
M-
LOW-LEAKAGE RECTANGULAR DAMPERS
M-501
NOT TO SCALE
M-
M-
ROOF SUPPORT FOR PIPING NUMBER
REFERENCE
SHEET
Project No.
D e s ig n e d B y
D a te
M a rk
Bldg. No.
F T
H O
O D T
E X
A S
S A
N T
A F
E E
N G
IN
E E
R D
R
B
L D
G
F O
R T H
O O
D T
E X
A S
P U
B L
IC
W
O R
K S
D
IR
E C
T O
R A
T E
D a te
D e s c ri p ti o n sivi
D secivreS & gn ir ee ni g n
E
D ir ec to rat eofPublic
W o rk s
P R
O J E
C T M
A N
A G
E R
P U
R P
O S
E S O
N L
Y F
O R B
ID
D
IN
G T
E C
H N
IC
A L E
X H
IB
IT
B
/8 /2
:5
:2
P
M G E
N G
S
V C \P ro j\ P
X P B
R
E P
L A
C E A
H U
S \F lo o rp la n s
D e s ig n \M
-5 .d g n
33012
B P
R E
S S
E R
-A
P R -2
PX901706P
R E
P L
A C
E A
H U
S
INSULATION PER NOTE 1
SUPPLY-AIR DUCT
RETURN-AIR DUCT
EXHAUST-AIR OR
TAKE-OFF
BELLMOUTH
45° MAX
OR 4" MIN
1/4 WM
WB
W M
WIDTH, WB
BRANCH DUCT
MAIN AIRFLOW
VOLUME DAMPER AS REQUIRED.
OPPOSED-BLADE MANUAL
1. SUPPLY-AIR AND RETURN-AIR DUCT SHALL BE EXTERNALLY INSULATED ONLY.
NOTES:
3"
1/ 2"
SEAL JOINT
DUCT WORK
SEE NOTE 5
SEE NOTE 8
SPIN COLLAR
DAMPER
BALANCING
SINGLE-BLADE
FLEXIBLE DUCT
METAL CLAMP
(SHOWN ON TOP FOR ILLUSTRATION ONLY).
BOTTOM OF DUCT FOR EASY SERVICE
8. INSTALL LOCKING QUADRANT AND HANDLE ON
LEAKAGE.
7. TAPE AND SEAL ALL JOINTS TO PREVENT
DAMPER.
RIVETS OR SCREWS DO NOT INTERFERE WITH
CONNECTING STOVEPIPE TO COLLAR. ENSURE
MINIMUM 3 EACH AT 120° INTERVALS,
6. POP RIVET OR SHEET METAL SCREWS,
BARRIER.
REQUIRED AND SEAL TO EFFECT VAPOR
INSULATION, PULL TO EDGE OF DUCTWORK AS
5. PROVIDE EXTENSION RODS TO ACCOMMODATE
MOISTURE MIGRATION.
DUCTWORK. SEAL VAPOR BARRIER TO PREVENT
OF SPIN COLLAR AT EDGE OF RECTANGULAR
4. PULL FLEXIBLE DUCT INSULATION UP TO END
CONTRACTOR.
POSITION. FINAL ADJUSTMENT BY TAB
3. INSTALL SPIN COLLAR DAMPER IN OPEN
OUTBOARD END OF COLLAR.
2. BAND FLEX TO COLLAR 1/2" MINIMUM FROM
1. SUPPORT DUCTWORK AS REQUIRED.
NOTES:
3"
SEE NOTE 5
SEAL JOINT
DUCT WORK
SEE NOTE 8
SPIN COLLAR
1" M
IN
NOTE 7
SEE
REQUIRED
BY MANUFACTURER AS
FURNISHED INSULATION
FLEXIBLE DUCT WITH
NOTE 6
SEE
DAMPER
BALANCING
SINGLE-BLADE
ELBOW
RADIUS
LONG-
ON TOP FOR ILLUSTRATION ONLY).
BOTTOM OF DUCT FOR EASY SERVICE (SHOWN
8. INSTALL LOCKING QUADRANT AND HANDLE ON
7. TAPE AND SEAL ALL JOINTS TO PREVENT LEAKAGE.
SCREWS DO NOT INTERFERE WITH DAMPER.
STOVEPIPE TO COLLAR. ENSURE RIVETS OR
EACH AT 120° INTERVALS, CONNECTING
6. POP RIVET OR SHEET METAL SCREWS, MINIMUM 3
REQUIRED AND SEAL TO EFFECT…