Updated_Technical_Exhibit_B.pdf

PDF 6 MB Posted

Attached to
Renovate HVAC System in Bldg 33012 Federal contract opportunity
Solicitation number
W91151-17-B-0032
Issued by
Department of the Army Materiel Command Mission and Installation Contracting Command Fort Hood

About this file

Updated Drawings for Solicitation Amendment #3

View the file

Other files for this federal contract opportunity

Other files attached to Renovate HVAC System in Bldg 33012, newest first.
File Type Posted
Solicitation_Amendment_W91151_17_B_0032_0003.pdf PDF
W9115117B0032_Solicitation_Amendment.pdf PDF
Solicitation_Amendment__2_Change_Bid_Opening_Date.pdf PDF
Site_Visit_Sign_In_Roster.pdf PDF
Agenda_for__Site_Visit.pdf PDF
AppendixA.pdf PDF
W9115117C0032ReplaceAHU'sBLDG33012.pdf PDF
TechnicalExhibitB.pdf PDF
TechnicalExhibitA.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SHEET

N

1"=200’

INDEX OF DRAWINGS

HWY 84

HWY 84

HWY 36

F .M

RES.BD.

RES.BD.

R E S . B

D

RES. BD.

R E

S .B

D

KILLEEN

CANTONMENT

AREA

WEST

FORT

HOOD

GATESVILLE

NORTH

FORT

HOOD

RESERVATION

BELTON

LAKE

COPPERAS

COVE

HWY190

HWY190

FORT HOOD AREA MAP

O L

D G

E O

R G

E T

O W

N R

D

E A

S T R

A N

G E R

D

N O

LA

N R

D

FORT HOOD

W E S

T R

A N

G E R

D

C L

A R

K E R

D

H W

Y

35 37

LOCATION

PROJECT

LAREDO

CORPUS

CHRISTI

HOUSTON

AUSTIN

KILLEEN

WACO

FORT WORTH DALLAS

FORT

SMITH

OKLAHOMA

CITY

TULSA

AMARILLO

ALBUQUERUE

SANTA FE

VICINITY MAP

LOUISIANA

MEXICO

MEXICO

TEXAS

ARKANSAS

NEW

MEXICO

ELPASO

OKLAHOMA

GULF OF

SAN ANTONIO

FORT HOOD

WICHITA FALLS

N

SCALE IN MILES

1/2 1

FORT HOOD MILITARY RESERVATION

N

0 100 200

SCALE IN MILES

N

0 5 10

SCALE IN MILES

NORTH SYMBOL

GENERAL SYMBOLS

REVISION NUMBER

WALL TYPE MARK

DOOR MARKWINDOW MARK

DETAIL NUMBER

REFERENCE FROM

REFERENCE TO

G-101

C O

V E

R S

H E

E T

FORT HOOD,TEXAS

FORT HOOD DIRECTORATE OF PUBLIC WORKS-ENGINEERING DIVISION

NOTE BY SYMBOL

SHEET DESCRIPTION

A

A

N

A

A

BUILDING LEGEND (POINTS OF INTEREST)

PROJECT SITE

BUILDING 4612 (DIRECTORATE OF PUBLIC WORKS)

DARNALL ARMY HOSPITAL

III CORPS HEADQUARTERS

MAIN CANTONMENT AREA

W E S T R

A N

G E R

D

MONTAGUE VILLAGE

VILLAGEII

COMANCHE

CENTRAL DR

LANDFILL

FT.HOOD

W R

A T

T E

N

PATTON

PARK

BATTALION

NORTH

761ST

NORTH

WALKER VILLAGE

HOOD

ARMY

AIRFIELD

HILLIARD

CENTRAL

TEXAS

COLLEGE

HEIGHTS

WEST

FT.HOOD

VILLAGEIII

MURPHY

TURKEYRUN

T

H

N D

H W

Y

T

H

R

D

M U

R P

H Y

T

H

M A

R T

IN

62ND

WAINWRIGHT

TO

VILLAGEI

COMANCHE

T

H

T

H

LIBERTY VILLAGE

OLD IRONSIDES

BATTALION AVE

HELL ON WHEELSC

L

A R

K E R

O A

D C

L A

R K

E R

O A

D

C L E

A R C

R E

E K

US HIGHWAY 190

HELL ON WHEELS

OLD IRONSIDES

WARRIOR WAY

BUSINESS ROUTE 190

US HIGHWAY 190

PERSHING PARK

VENABLE VILLAGE

CHAFFEE VILLAGE

US HIGHWAY 190

RAIL HEAD

McNair Village

TANK DESTROYER RD

COPPERAS COVE RD

WEST RANGE RD

Santa Fe Av e

WAREHOUSE AVE

DESTROYER RD

TANK

COPP

ERAS

COVE

RD

O L

D G

E O

R G

R T

O W

N R

D

TURKEYRUN

C L E

A R C

R E

E K

T

H

EAST

R

AN

G E

R D

NORTH NOLAN RD

WEST RANCIER AVE

SOUTH RANGE RD

F T H

O O

D S

T

T .J

M

IL

L S B

L V

D

B P

R E

S S

E R

PROJECT NO: PX901706P

REPLACE AHUS

STRUCTURAL DETAILS IIS-502

STRUCTURAL DETAILS IS-501

ROOF FRAMING PLANS-101

STRUCTURAL NOTESS-001

MECHANICAL CONTROLSM-701

MECHANICAL SCHEDULEM-601

MECHANICAL DETAILSM-501

NEW MECHANICAL ROOM PIPING PLANM-104

MECHANICAL ROOM DUCTWORK PLANM-103

NEW MECHANICAL PIPING PLAN - AREA BM-102B

NEW MECHANICAL PIPING PLAN - AREA AM-102A

MECHANICAL DUCTWORK PLAN - AREA DM-101D

MECHANICAL DUCTWORK PLAN - AREA CM-101C

MECHANICAL DUCTWORK PLAN - AREA BM-101B

MECHANICAL DUCTWORK PLAN - AREA AM-101A

EXISTING MECHANICAL ROOM PIPING PLANMD-104

MECHANICAL ROOM DEMOLITION PLANMD-103

EXISTING MECHANICAL PIPING PLAN - AREA BMD-102B

EXISTING MECHANICAL PIPING PLAN - AREA AMD-102A

MECHANICAL DEMOLITION PLAN - AREA DMD-101D

MECHANICAL DEMOLITION PLAN - AREA CMD-101C

MECHANICAL DEMOLITION PLAN - AREA BMD-101B

MECHANICAL DEMOLITION PLAN - AREA AMD-101A

MECHANICAL NOTESM-001

COVER SHEETG-101

NUMBER

REFERENCE

SHEET

Project No.

D e s ig n e d B y

D a te

M a rk

Bldg. No.

F T

H O

O D T

E X

A S

S A

N T

A F

E E

N G

IN

E E

R D

R

B

L D

G

F O

R T H

O O

D T

E X

A S

P U

B L

IC

W

O R

K S

D

IR

E C

T O

R A

T E O

F

A B C D E F

D a te

D e s c ri p ti o n

DPW

FORT HOOD TEXAS

n oi sivi

D secivreS & gn ir ee ni g n

E

D ir ec to rat eofPublic

W o rk s

P R

O J E

C T M

A N

A G

E R

P U

R P

O S

E S O

N L

Y F

O R B

ID

D

IN

G T

E C

H N

IC

A L E

X H

IB

IT

B

/8 /2

:5

:4

P

M G E

N G

S

V C \P ro j\ P

X P B

R

E P

L A

C E A

H U

S \F lo o rp la n s

D e s ig n \G -1

C o v e r S h e e t.

d g n

33012

B P

R E

S S

E R

-A

P R -2

PX901706P

R E

P L

A C

E A

H U

S

BATTALION AVE

T

H S

T

T

H S

T

R D S

T

N D S

T

761ST TANK BATTALION AVE

33011

34011

31001 31011

31012

33012

31010

GENERAL NOTES:

WORK STAGING:

SITE CONCERNS:

M E

C H

A N

IC

A L N

O T

E S

M-001

ON AHU-4.

THIS OFFICE AND REMOVE AS MUCH OF ITS CONTENTS AS NECESSARY WHILE WORK IS BEING PERFORMED

AHU-4 IS CURRENTLY LOCATED DIRECTLY OVER A SMALL OFFICE. CUSTOMER HAS AGREED TO VACATE2.

PERFORMED OVERHEAD.

CUSTOMER HAS AGREED TO CLOSE AT LEAST ONE OF THESE REGISTERS WHILE WORK IS BEING

AHU-3 IS CURRENTLY LOCATED ABOVE TWO CASH REGISTERS IN THE EXCHANGE RETAIL SALES AREA.1.

THE GIVEN BUSINESS HOURS OR DURING ANY SCHEDULED OUTAGES.

CONTRACTOR SHALL NOTIFY THE COR 7-10 DAYS PRIOR TO ANY WORK BEING PERFORMED OUTSIDE OF4.

CLOSEDSUNDAY

1030 - 1700SATURDAY

0700 - 1900MONDAY - FRIDAY

IN THIS AREA SHALL BE PERFORMED OUTSIDE OF THESE TIMES WHENEVER POSSIBLE.

BUSINESS HOURS FOR THE 1ST CAVALRY BURGER KING ARE GIVEN IN THE FOLLOWING SCHEDULE. WORK3.

1100 - 1600SATURDAY & SUNDAY

0700 - 1900MONDAY - FRIDAY

THIS AREA SHALL BE PERFORMED OUTSIDE OF THESE TIMES WHENEVER POSSIBLE.

BUSINESS HOURS FOR THE 1ST CAVALRY EXCHANGE ARE GIVEN IN THE FOLLOWING SCHEDULE. WORK IN2.

NORMAL BUSINESS OPERATIONS.

COORDINATED WITH THE COR AND BUILDING POCS IN ADVANCE IN ORDER TO MINIMIZE THE IMPACT TO

BUILDING 33012 IS OCCUPIED DURING NORMAL BUSINESS HOURS. ALL WORK PERFORMED SHALL BE1.

B P

R E

S S

E R

AREAS.

WHILE EACH UNIT IS BEING REPLACED, CONTRACTOR SHALL PROVIDE SPOT COOLING FOR THE IMPACTED5.

REPLACEMENTS ARE AVAILABLE FOR INSTALLATION.

IN ORDER TO MINIMIZE OUTAGE TIME, EXISTING UNITS SHALL NOT BE REMOVED UNTIL THEIR4.

ANY WEEKEND THAT IS DIRECTLY PRECEDED OR FOLLOWED BY A TRAINING OR FEDERAL HOLIDAY.

A WEEKEND. IF POSSIBLE, THIS WORK SHALL BE PERFORMED DURING AN EXTENDED WEEKEND, MEANING

THE OUTAGE TO REPLACE AHU-7 SHALL NOT LAST LONGER THAN 4 CALENDAR DAYS AND SHALL INCLUDE3.

SHEETS OVER ALL TRANSFER POINTS (E.G., DOOR OPENINGS).

BUT SHALL BE ISOLATED FROM THE BLIMPIE FOOD PREP AND STORAGE AREAS BY PLACING PLASTIC

AHU-4. BURGER KING FOOD PREP AREA SHALL REMAIN OPEN WHILE THIS WORK IS BEING PERFORMED, OVERHEAD, INCLUDING THE REPLACEMENT OF BOTH AHU-7 AND THE SPECIFIED DUCTWORK SERVING

FOOD PREP AND STORAGE AREAS FOR BLIMPIE SHALL BE CLOSED WHILE WORK IS BEING PERFORMED2.

AHU-4 AND AHU-7 SHALL BE REPLACED WITHIN THE FIRST 60 DAYS OF THE PERFORMANCE PERIOD.1.

NUMBER

REFERENCE

SHEET

Project No.

D e s ig n e d B y

D a te

M a rk

Bldg. No.

F T

H O

O D T

E X

A S

S A

N T

A F

E E

N G

IN

E E

R D

R

B

L D

G

F O

R T H

O O

D T

E X

A S

P U

B L

IC

W

O R

K S

D

IR

E C

T O

R A

T E

D a te

D e s c ri p ti o n sivi

D secivreS & gn ir ee ni g n

E

D ir ec to rat eofPublic

W o rk s

P R

O J E

C T M

A N

A G

E R

P U

R P

O S

E S O

N L

Y F

O R B

ID

D

IN

G T

E C

H N

IC

A L E

X H

IB

IT

B

/8 /2

:5

:4

P

M G E

N G

S

V C \P ro j\ P

X P B

R

E P

L A

C E A

H U

S \F lo o rp la n s

D e s ig n \M

-0 .d g n

33012

B P

R E

S S

E R

-A

P R -2

PX901706P

R E

P L

A C

E A

H U

S

N SCALE: 3/16" = 1’ N

KEY PLAN0 4 8

SCALE (FEET)

RV

C

C

CU

RH

AHU

B P

R E

S S

E R

KEY NOTES:

AIR-HANDLING UNIT

EQUIPMENT LIST

AHU-3

RV-1

SYMBOL DESCRIPTION

C-2

C-1

CU-8

RH-3

COOLING UNIT (REFRIGERATION)

RELIEF VENT

FOR C-1

DISCONNECT

FOR C-2

DISCONNECT

GENERAL NOTES:

101A

MD-

101A

MD-

MD-

ROOF HOOD (OUTSIDE AIR)

MECHANICAL DEMOLITION PLAN - AREA A

P L

A N A

R E

A A

M E

C H

A N

IC

A L D

E M

O L

IT

IO

N

CONDENSING UNIT

CONDENSING UNIT

MATCHLINE - SEE MD-101C

M A

T C

H L

IN

E S

E E M

D -1

B

UNIT

COOLER

FROM INSIDE

DOOR BLOCKED

DEMOLISHED.

EXISTING SUPPLY DIFFUSER TO BE

DEMOLISHED.

EXISTING DUCTWORK TO BE

DUCT TO REMAIN.

38" X 14" OPENING FOR RETURN-AIR

DUCT TO BE DEMOLISHED.

38" X 14" OPENING FOR RETURN-AIR

CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING EXISTING SITE CONDITIONS.9.

OF THE CONTRACTOR UNTIL REUSED.

ITEMS INTENDED FOR REUSE ON THIS PROJECT SHALL REMAIN IN THE POSSESSION8.

ITS DISPOSAL.

BECOME THE PROPERTY OF THE CONTRACTOR, WHO SHALL BE RESPONSIBLE FOR

UNLESS NOTED OTHERWISE, ALL MATERIAL REMOVED AND NOT REUSED SHALL7.

UNITS, INCLUDING CONTROL WIRING.

CONTRACTOR SHALL DEMOLISH ALL THERMOSTATS SERVING EXISTING AIR-HANDLING6.

CONDUIT SHALL BE PRESERVED AND REUSED IF IT IS APPROPRIATELY SIZED.

EQUIPMENT SHALL REMAIN IN THE PANEL AND BE LABELED AS "SPARE". EXISTING

EXISTING ELECTRICAL PANEL. CIRCUIT BREAKERS THAT ARE NOT REUSED FOR NEW

INCLUDING DISCONNECTS, FOR DEMOLISHED HVAC EQUIPMENT BACK TO THE

CONTRACTOR SHALL DEMOLISH ALL EXISTING ELECTRICAL WIRING AND DEVICES,5.

SHALL BE DEMOLISHED.

MAINTENANCE ALONG WITH ASSOCIATED REFRIGERANT. REFRIGERANT PIPING

SERVING AHU-1 AND AHU-2, RESPECTIVELY, AND TURN THEM IN TO DPW

CONTRACTOR SHALL DISCONNECT EXISTING CONDENSING UNITS (C-1 AND C-2)4.

SHALL BE PRESERVED AND REUSED FOR THE NEW HVAC SYSTEM.

UNLESS NOTED OTHERWISE, ALL EXISTING DIFFUSERS, GRILLES, AND DUCTWORK3.

AND REUSED FOR NEW EQUIPMENT, IF POSSIBLE, OR CAPPED.

DUCTWORK SERVING AHU-3. EXISTING ROOF PENETRATION SHALL BE PRESERVED

CONTRACTOR SHALL DEMOLISH EXISTING ROOF HOOD (RH-3) AND OUTSIDE-AIR2.

DEMOLISHED IF NECESSARY TO INSTALL NEW EQUIPMENT.

ABANDONED IN PLACE. EXISTING DUCTWORK CONNECTED TO THIS UNIT MAY BE

HOT-WATER PIPING SERVING THIS UNIT SHALL BE DRAINED, CAPPED, AND

CONTRACTOR SHALL DEMOLISH EXISTING AIR-HANDLING UNIT (AHU-3). ALL EXISTING1.

NUMBER

REFERENCE

SHEET

Project No.

D e s ig n e d B y

D a te

M a rk

Bldg. No.

F T

H O

O D T

E X

A S

S A

N T

A F

E E

N G

IN

E E

R D

R

B

L D

G

F O

R T H

O O

D T

E X

A S

P U

B L

IC

W

O R

K S

D

IR

E C

T O

R A

T E

D a te

D e s c ri p ti o n sivi

D secivreS & gn ir ee ni g n

E

D ir ec to rat eofPublic

W o rk s

P R

O J E

C T M

A N

A G

E R

P U

R P

O S

E S O

N L

Y F

O R B

ID

D

IN

G T

E C

H N

IC

A L E

X H

IB

IT

B

/8 /2

:5

:4

P

M G E

N G

S

V C \P ro j\ P

X P B

R

E P

L A

C E A

H U

S \F lo o rp la n s

D e s ig n \M

D -1

A .d g n

33012

B P

R E

S S

E R

-A

P R -2

PX901706P

R E

P L

A C

E A

H U

S

20" X 16"

SUPPLY AIR

X

X

X

X

X

16" X 16"

X

9" X 8" 9" X 7" 9" X 5"

X

X

6" X 4"

9" X 7"

16" X 12"

10" VERTICAL SPLIT

6" HORIZONTAL SPLIT 6" HORIZONTAL SPLIT

SPLIT

6" HORIZONTAL

S U

P P

L Y A

IR

12" X 9" 9" X 6"

X

X

X

X

36" X 16"

SUPPLY AIR

14" X 6"

12" X 8"

3.24.1

5.1

D

E

F

G

MECHANICAL

STORAGE

LAUNDRY/

ALTERATIONS

GNC

RETAIL SALES

OFFICE

VESTIBULE

MAIN LOBBY

SHOPPETTE

RETAIL SALES

FITTING

ROOM

MECHANICAL

YARD

A B

C D

LEGEND:

T

EXISTING EQUIPMENT TO REMAIN

EXISTING EQUIPMENT TO BE DEMOLISHED

AIR FLOW DIRECTION

EXISTING ELECTRICAL DISCONNECT

EXISTING THERMOSTAT

EXISTING 1’ X 1’ EXHAUST GRILLE

EXISTING 1’ X 2’ RETURN GRILLE

EXISTING 6" X 2’ RETURN GRILLE

EXISTING 1’ X 1’ RETURN GRILLE

EXISTING 2’ X 2’ RETURN GRILLE

EXISTING 1’ X 1’ SUPPLY DIFFUSER

EXISTING 2’ X 2’ SUPPLY DIFFUSER

SCALE (FEET)

EF

AHU

RH

RV

B P

R E

S S

E R

KEY NOTES:

AIR-HANDLING UNIT

EQUIPMENT LIST

AHU-6

SYMBOL DESCRIPTION

RH-6

EF-1

RV-2

EXHAUST FAN

RELIEF VENT

GENERAL NOTES:

101B

MD-

ROOF HOOD (OUTSIDE AIR)

P L

A N A

R E

A B

M E

C H

A N

IC

A L D

E M

O L

IT

IO

N

MECHANICAL DEMOLITION PLAN - AREA B

MATCHLINE - SEE MD-101D

M A

T C

H L

IN

E S

E E M

D -1

A

TANK

WATER

GAS HOT-

EXISTING DUCTWORK TO BE DEMOLISHED.

THERMOSTAT FOR AHU-6.

CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING EXISTING SITE CONDITIONS.7.

OF THE CONTRACTOR UNTIL REUSED.

ITEMS INTENDED FOR REUSE ON THIS PROJECT SHALL REMAIN IN THE POSSESSION6.

ITS DISPOSAL.

BECOME THE PROPERTY OF THE CONTRACTOR, WHO SHALL BE RESPONSIBLE FOR

UNLESS NOTED OTHERWISE, ALL MATERIAL REMOVED AND NOT REUSED SHALL5.

UNITS, INCLUDING CONTROL WIRING.

CONTRACTOR SHALL DEMOLISH ALL THERMOSTATS SERVING EXISTING AIR-HANDLING4.

CONDUIT SHALL BE PRESERVED AND REUSED IF IT IS APPROPRIATELY SIZED.

EQUIPMENT SHALL REMAIN IN THE PANEL AND BE LABELED AS "SPARE". EXISTING

EXISTING ELECTRICAL PANEL. CIRCUIT BREAKERS THAT ARE NOT REUSED FOR NEW

INCLUDING DISCONNECTS, FOR DEMOLISHED HVAC EQUIPMENT BACK TO THE

CONTRACTOR SHALL DEMOLISH ALL EXISTING ELECTRICAL WIRING AND DEVICES,3.

SHALL BE PRESERVED AND REUSED FOR THE NEW HVAC SYSTEM.

UNLESS NOTED OTHERWISE, ALL EXISTING DIFFUSERS, GRILLES, AND DUCTWORK2.

TO THIS UNIT MAY BE DEMOLISHED IF NECESSARY TO INSTALL NEW EQUIPMENT.

PRESERVED AND REUSED FOR NEW EQUIPMENT. EXISTING DUCTWORK CONNECTED

ABANDONED IN PLACE. EXISTING ROOF HOOD (RH-6) SERVING AHU-6 SHALL BE

HOT-WATER PIPING SERVING THIS UNIT SHALL BE DRAINED, CAPPED, AND

CONTRACTOR SHALL DEMOLISH EXISTING AIR-HANDLING UNIT (AHU-6). ALL EXISTING1.

NUMBER

REFERENCE

SHEET

Project No.

D e s ig n e d B y

D a te

M a rk

Bldg. No.

F T

H O

O D T

E X

A S

S A

N T

A F

E E

N G

IN

E E

R D

R

B

L D

G

F O

R T H

O O

D T

E X

A S

P U

B L

IC

W

O R

K S

D

IR

E C

T O

R A

T E

D a te

D e s c ri p ti o n sivi

D secivreS & gn ir ee ni g n

E

D ir ec to rat eofPublic

W o rk s

P R

O J E

C T M

A N

A G

E R

P U

R P

O S

E S O

N L

Y F

O R B

ID

D

IN

G T

E C

H N

IC

A L E

X H

IB

IT

B

/8 /2

:5

:5

P

M G E

N G

S

V C \P ro j\ P

X P B

R

E P

L A

C E A

H U

S \F lo o rp la n s

D e s ig n \M

D -1

B .d g n

33012

B P

R E

S S

E R

-A

P R -2

PX901706P

R E

P L

A C

E A

H U

S

T

16" X 12"16" X 12"

X

X

12" X 6" 12" X 6"

12" X 12"

SPLIT

HORIZONTAL

EQUAL

SPLIT

4" HORIZONTAL

X

X

6" X 4"

7" X 5"

14" X 16"

24" X 16"

X

14" X 10" 14" X 10"14" X 6" 14" X 6"

14" X 16" 14" X 10"

X

S U

P P

L Y A

IR

X

X

T

12" X 8" 12" X 12" 16" X 12"

X

18" X 18"

X

12" X 6"

12" X 6"

X

X

THIS AREA

DIFFUSER (TYP)

18" X 12" SUPPLY

2 1

2.13.2

D

E

F

G

OFFICE

BARBER SHOP

WOMEN

DINING AREA

JANITOR

MEN

SODA

STORAGE

DINING AREA

MAIN LOBBY

A B

C D

LEGEND:

T

EXISTING EQUIPMENT TO REMAIN

EXISTING EQUIPMENT TO BE DEMOLISHED

AIR FLOW DIRECTION

EXISTING ELECTRICAL DISCONNECT

EXISTING THERMOSTAT

EXISTING 1’ X 1’ EXHAUST GRILLE

EXISTING 1’ X 2’ RETURN GRILLE

EXISTING 6" X 2’ RETURN GRILLE

EXISTING 1’ X 1’ RETURN GRILLE

EXISTING 2’ X 2’ RETURN GRILLE

SCALE (FEET)

AHU

EF

CU

CU

CU

CU

4A

C

4B

C

CU

CU

C

C

AHU

RH

B P

R E

S S

E R

KEY NOTES:

101C

MD-

PANEL "L"

PANEL "C"

(SHUT OFF)

FOR C-4A

DISCONNECT

FOR CU-1

DISCONNECT

FOR CU-2

DISCONNECT

FOR C-4B

DISCONNECT

REFRIGERATION UNIT

DISCONNECT FOR

FOR C-5

DISCONNECT

(NOT USED)

DISCONNECT

FOR ICE MAKER

LOCATED ON ROOF

GENERAL NOTES:

AIR-HANDLING UNITAHU-4

SYMBOL DESCRIPTION

C-3

RV-1 RELIEF VENT

AIR-HANDLING UNITAHU-5

RH-4

C-4A

C-4B

C-5

EF-5 EXHAUST FAN

SYMBOL DESCRIPTION

CU-2

CU-6

CU-7

CU-1

CU-8

CU-11

EQUIPMENT LIST (HVAC)

EQUIPMENT LIST (REFRIGERATION)

COOLING UNIT

COOLING UNIT (ON ROOF)

COOLING UNIT

COOLING UNIT

COOLING UNIT

COOLING UNIT

(NOT USED)

DISCONNECT

4 5

ROOF HOOD (OUTSIDE AIR)

P L

A N A

R E

A C

M E

C H

A N

IC

A L D

E M

O L

IT

IO

N

MECHANICAL DEMOLITION PLAN - AREA C

CONDENSING UNIT

CONDENSING UNIT

CONDENSING UNIT

CONDENSING UNIT

M A

T C

H L

IN

E S

E E M

D -1

D

MATCHLINE - SEE MD-101A

CONCRETE SLABS

TANK

GAS HOT-WATER

SLAB

4" CONCRETE

WATER TANK

ELECTRIC HOT-

(ICE)

FREEZER UNIT

UNIT

COOLER

UNIT

COOLER

UNIT

COOLER

ROOF

LADDER TO

FREEZERS

DOCK

LOADING

10" X 6"

16" X 8" OUTSIDE-AIR LOUVER.

THERMOSTAT FOR AHU-5.

THERMOSTAT FOR AHU-3.

DEMOLISHED.

EXISTING SUPPLY DIFFUSER TO BE

DEMOLISHED.

EXISTING DUCTWORK TO BE

CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING EXISTING SITE CONDITIONS.9.

OF THE CONTRACTOR UNTIL REUSED.

ITEMS INTENDED FOR REUSE ON THIS PROJECT SHALL REMAIN IN THE POSSESSION8.

ITS DISPOSAL.

BECOME THE PROPERTY OF THE CONTRACTOR, WHO SHALL BE RESPONSIBLE FOR

UNLESS NOTED OTHERWISE, ALL MATERIAL REMOVED AND NOT REUSED SHALL7.

UNITS, INCLUDING CONTROL WIRING.

CONTRACTOR SHALL DEMOLISH ALL THERMOSTATS SERVING EXISTING AIR-HANDLING6.

CONDUIT SHALL BE PRESERVED AND REUSED IF IT IS APPROPRIATELY SIZED.

EQUIPMENT SHALL REMAIN IN THE PANEL AND BE LABELED AS "SPARE". EXISTING

EXISTING ELECTRICAL PANEL. CIRCUIT BREAKERS THAT ARE NOT REUSED FOR NEW

INCLUDING DISCONNECTS, FOR DEMOLISHED HVAC EQUIPMENT BACK TO THE

CONTRACTOR SHALL DEMOLISH ALL EXISTING ELECTRICAL WIRING AND DEVICES,5.

TURNED IN TO THE DPW CLASSIFICATION UNIT PER SPECS (01 57 20.00 10)

C-5) AND ASSOCIATED REFRIGERANT PIPING. ALL EXISTING REFRIGERANT SHALL BE

CONTRACTOR SHALL DEMOLISH EXISTING CONDENSING UNITS (C-3, C-4A, C-4B, AND4.

SHALL BE PRESERVED AND REUSED FOR THE NEW HVAC SYSTEM.

UNLESS NOTED OTHERWISE, ALL EXISTING DIFFUSERS, GRILLES, AND DUCTWORK3.

LOUVER SERVING AHU-5 SHALL BE PRESERVED AND REUSED FOR NEW EQUIPMENT.

AND REUSED FOR NEW EQUIPMENT, IF POSSIBLE, OR CAPPED. EXISTING OUTSIDE-AIR

DUCTWORK SERVING AHU-4. EXISTING ROOF PENETRATION SHALL BE PRESERVED

CONTRACTOR SHALL DEMOLISH EXISTING ROOF HOOD (RH-4) AND OUTSIDE-AIR2.

NECESSARY TO INSTALL NEW EQUIPMENT.

PLACE. EXISTING DUCTWORK CONNECTED TO THESE UNITS MAY BE DEMOLISHED IF

PIPING SERVING THESE UNITS SHALL BE DRAINED, CAPPED, AND ABANDONED IN

INCLUDING THE EXTERNAL HEATING COIL SERVING AHU-5. ALL EXISTING HOT-WATER

CONTRACTOR SHALL DEMOLISH EXISTING AIR-HANDLING UNITS (AHU-4 AND AHU-5),1.

NUMBER

REFERENCE

SHEET

Project No.

D e s ig n e d B y

D a te

M a rk

Bldg. No.

F T

H O

O D T

E X

A S

S A

N T

A F

E E

N G

IN

E E

R D

R

B

L D

G

F O

R T H

O O

D T

E X

A S

P U

B L

IC

W

O R

K S

D

IR

E C

T O

R A

T E

D a te

D e s c ri p ti o n sivi

D secivreS & gn ir ee ni g n

E

D ir ec to rat eofPublic

W o rk s

P R

O J E

C T M

A N

A G

E R

P U

R P

O S

E S O

N L

Y F

O R B

ID

D

IN

G T

E C

H N

IC

A L E

X H

IB

IT

B

/8 /2

:5

:5

P

M G E

N G

S

V C \P ro j\ P

X P B

R

E P

L A

C E A

H U

S \F lo o rp la n s

D e s ig n \M

D -1

C .d g n

33012

B P

R E

S S

E R

-A

P R -2

PX901706P

R E

P L

A C

E A

H U

S

T

T

SPLIT

4" HORIZONTAL

SPLIT

5" HORIZONTAL

SPLIT

5" VERTICAL

SPLIT

6" HORIZONTAL

10" X 8"

9" X 6" 9" X 6"

X

12" X 10" 12" X 6"

9" X 6" 9" X 6" 9" X 6"

6" X 6"

14" X 10"

14" X 6"

14" X 6"

36" X 14"

SUPPLY AIR

6" X 6"

6" X 6"

9" X 5"

12" X 10"12" X 5" T

26" X 14"

18" X 18"

RETURN AIR

T

FD

56 4.2

3.5

A

B

C

D

OFFICE

OFFICE

OFFICE

COOLER

SHOPPETTE

STORAGE

EMPLOYEE

BREAK AREA

WOMEN

JANITOR

MEN

SHOPPETTE

RETAIL SALES

MECHANICAL

YARD

LEGEND:

T

EXISTING EQUIPMENT TO REMAIN

EXISTING EQUIPMENT TO BE DOMOLISHED

AIR FLOW DIRECTION

EXISTING ELECTRICAL DISCONNECT

EXISTING THERMOSTAT

EXISTING 1’ X 1’ EXHAUST GRILLE

EXISTING 1’ X 2’ RETURN GRILLE

EXISTING 6" X 2’ RETURN GRILLE

EXISTING 1’ X 1’ RETURN GRILLE

EXISTING 2’ X 2’ RETURN GRILLE

SCALE (FEET)

CU

C

CU

CU

CU

H

EF

EF

H

EF

H

AHU

RV

P

R E

S S

E R

KEY NOTES:

SYMBOL DESCRIPTION

CU-9

CU-5

CU-4

CU-10

EF-2

SYMBOL DESCRIPTION

EXHAUST FAN

H-1

RV-2 RELIEF VENT

C-6

EF-3 EXHAUST FAN

EF-4 EXHAUST FAN

HOOD VENT UNIT

H-2 HOOD VENT UNIT

H-3 HOOD VENT UNIT

AHU-7

EQUIPMENT LIST (HVAC)

EQUIPMENT LIST (REFRIGERATION)

COOLING UNIT

COOLING UNIT

COOLING UNIT

COOLING UNIT

GENERAL NOTES:

AIR-HANDLING UNIT (ON ROOF)

FED FROM PANEL PK3

PANEL "PK2 - SECTION 1"

FED FROM PANEL PK3

PANEL "PK2 - SECTION 2"

PANEL "PK4"

PANEL "PK1"

PANEL NOT USED

PANEL "PK3"

101D

MD-

EXISTING DUCTWORK TO BE DEMOLISHED.

THERMOSTAT FOR AHU-7.

THERMOSTAT FOR AHU-4.

MECHANICAL DEMOLITION PLAN - AREA D

P L

A N A

R E

A D

M E

C H

A N

IC

A L D

E M

O L

IT

IO

N

MATCHLINE - SEE MD-101B

M A

T C

H L

IN

E S

E E M

D -1

C

S E

E M

D -1

C

M A

T C

H L

IN

E

CONDENSING UNIT

DOCK

LOADING

FINISHED FLOOR

WALL IS 84" ABOVE

LOWER PART OF

SWITCH C-6

DISCONNECT

CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING EXISTING SITE CONDITIONS.8.

OF THE CONTRACTOR UNTIL REUSED.

ITEMS INTENDED FOR REUSE ON THIS PROJECT SHALL REMAIN IN THE POSSESSION7.

ITS DISPOSAL.

BECOME THE PROPERTY OF THE CONTRACTOR, WHO SHALL BE RESPONSIBLE FOR

UNLESS NOTED OTHERWISE, ALL MATERIAL REMOVED AND NOT REUSED SHALL6.

UNITS, INCLUDING CONTROL WIRING.

CONTRACTOR SHALL DEMOLISH ALL THERMOSTATS SERVING EXISTING AIR-HANDLING5.

CONDUIT SHALL BE PRESERVED AND REUSED IF IT IS APPROPRIATELY SIZED.

EQUIPMENT SHALL REMAIN IN THE PANEL AND BE LABELED AS "SPARE". EXISTING

EXISTING ELECTRICAL PANEL. CIRCUIT BREAKERS THAT ARE NOT REUSED FOR NEW

INCLUDING DISCONNECTS, FOR DEMOLISHED HVAC EQUIPMENT BACK TO THE

CONTRACTOR SHALL DEMOLISH ALL EXISTING ELECTRICAL WIRING AND DEVICES,4.

DPW CLASSIFICATION UNIT PER SPECS (01 57 20.00 10)

REFRIGERANT PIPING. ALL EXISTING REFRIGERANT SHALL BE TURNED IN TO THE

CONTRACTOR SHALL DEMOLISH EXISTING CONDENSING UNIT (C-6) AND ASSOCIATED3.

SHALL BE PRESERVED AND REUSED FOR THE NEW HVAC SYSTEM.

UNLESS NOTED OTHERWISE, ALL EXISTING DIFFUSERS, GRILLES, AND DUCTWORK2.

TO INSTALL NEW EQUIPMENT.

EXISTING DUCTWORK CONNECTED TO THIS UNIT MAY BE DEMOLISHED IF NECESSARY

CONTRACTOR SHALL DEMOLISH EXISTING AIR-HANDLING UNIT (AHU-7) ON ROOF.1.

NUMBER

REFERENCE

SHEET

Project No.

D e s ig n e d B y

D a te

M a rk

Bldg. No.

F T

H O

O D T

E X

A S

S A

N T

A F

E E

N G

IN

E E

R D

R

B

L D

G

F O

R T H

O O

D T

E X

A S

P U

B L

IC

W

O R

K S

D

IR

E C

T O

R A

T E

D a te

D e s c ri p ti o n sivi

D secivreS & gn ir ee ni g n

E

D ir ec to rat eofPublic

W o rk s

P R

O J E

C T M

A N

A G

E R

P U

R P

O S

E S O

N L

Y F

O R B

ID

D

IN

G T

E C

H N

IC

A L E

X H

IB

IT

B

/8 /2

:5

:5

P

M G E

N G

S

V C \P ro j\ P

X P B

R

E P

L A

C E A

H U

S \F lo o rp la n s

D e s ig n \M

D -1

D .d g n

33012

B P

R E

S S

E R

-A

P R -2

PX901706P

R E

P L

A C

E A

H U

S

T

T

X

X

X

X

X

6" X 6"

6" X 6"

30" X 14" 26" X 14"

X

X

X

12" X 5"

12" X 5"

14" X 6"

14" X 6"

X

14" X 6"

9" X 6"

X

X

10" X 8"

X

14" X 6"

14" X 6"

T

T

10" X 8"

24" X 12"

24" X 24"

SUPPLY AIR

3.5 3.1

A

B

C

D

C.1

COOLER

STORAGE

FREEZER

DINING AREA

BLIMPIE

SUBS

BURGER

KING

FOOD

PREP

FOOD PREP

FREEZER

FREEZER

A B

C D

LEGEND:

T

EXISTING EQUIPMENT TO REMAIN

EXISTING EQUIPMENT TO BE DEMOLISHED

AIR FLOW DIRECTION

EXISTING ELECTRICAL DISCONNECT

EXISTING THERMOSTAT

EXISTING 1’ X 1’ EXHAUST GRILLE

EXISTING 1’ X 2’ RETURN GRILLE

EXISTING 6" X 2’ RETURN GRILLE

EXISTING 1’ X 1’ RETURN GRILLE

EXISTING 2’ X 2’ RETURN GRILLE

KEY PLAN

SCALE: 1/8" = 1’

SCALE (FEET)

0 8 164

MATCHLINE - SEE MD-102B MATCHLINE - SEE MD-102B

KEY NOTES:

EQUIPMENT LIST

SYMBOL DESCRIPTION

AIR-HANDLING UNITAHU-6

C-2

C-1 CONDENSING UNIT

CONDENSING UNIT

AIR-HANDLING UNITAHU-3

EXISTING MECHANICAL PIPING PLAN - AREA A

P

IP

IN

G P

L A

N A

R E

A A

E X

IS

T

IN

G M

E C

H A

N

IC

A L

102A

MD-

102A

MD-

MD-

CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING EXISTING SITE CONDITIONS.5.

OF THE CONTRACTOR UNTIL REUSED.

ITEMS INTENDED FOR REUSE ON THIS PROJECT SHALL REMAIN IN THE POSSESSION4.

ITS DISPOSAL.

BECOME THE PROPERTY OF THE CONTRACTOR, WHO SHALL BE RESPONSIBLE FOR

UNLESS NOTED OTHERWISE, ALL MATERIAL REMOVED AND NOT REUSED SHALL3.

CAPPED, AND ABANDONED IN PLACE.

EXISTING REFRIGERANT PIPING FOR AHU-3 (NOT SHOWN) SHALL BE DRAINED,2.

INSTALL NEW PIPING TO SERVE NEW EQUIPMENT.

CONTRACTOR SHALL DEMOLISH EXISTING REFRIGERANT PIPING FOR AHU-6 AND1.

EXISTING NATURAL-GAS HOT-WATER TANK WITH 6" FLUE TO REMAIN.

EXISTING NATURAL-GAS METER AND REGULATOR TO REMAIN.

GENERAL NOTES:

B P

R E

S S

E R

NUMBER

REFERENCE

SHEET

Project No.

D e s ig n e d B y

D a te

M a rk

Bldg. No.

F T

H O

O D T

E X

A S

S A

N T

A F

E E

N G

IN

E E

R D

R

B

L D

G

F O

R T H

O O

D T

E X

A S

P U

B L

IC

W

O R

K S

D

IR

E C

T O

R A

T E

D a te

D e s c ri p ti o n sivi

D secivreS & gn ir ee ni g n

E

D ir ec to rat eofPublic

W o rk s

P R

O J E

C T M

A N

A G

E R

P U

R P

O S

E S O

N L

Y F

O R B

ID

D

IN

G T

E C

H N

IC

A L E

X H

IB

IT

B

/8 /2

:5

:5

P

M G E

N G

S

V C \P ro j\ P

X P B

R

E P

L A

C E A

H U

S \F lo o rp la n s

D e s ig n \M

D -1

A .d g n

33012

B P

R E

S S

E R

-A

P R -2

PX901706P

R E

P L

A C

E A

H U

S

C

C

AHU 6

AHU

UNDERGROUND

NATURAL-GAS MAIN

HIGH-PRESSURE

ON ROOF2" Ø

ON ROOF2" Ø

AND CAPPED

2 1/2" Ø THROUGH WALL

2" Ø

2" Ø

2" Ø

1" Ø 3/4" Ø

2 1

2.13.24.1

5.1

D

E

F

G

D

E

F

G

MECHANICAL

STORAGE

LAUNDRY/

ALTERATIONS

GNC

RETAIL SALES

OFFICE

OFFICE

BARBER SHOP

VESTIBULE

MAIN LOBBY

WOMEN

DINING AREA

JANITOR

MEN

SODA

STORAGE

DINING AREA

SHOPPETTE

RETAIL SALES

4 3

ROOM

MAIN LOBBY

A

LEGEND:

EXISTING REFRIGERANT LINE

EXISTING NATURAL-GAS SUPPLY LINE

SCALE: 1/8" = 1’

SCALE (FEET)

0 8 164

MATCHLINE - SEE MD-102A MATCHLINE - SEE MD-102A

KEY NOTES:

AIR-HANDLING UNIT

EQUIPMENT LIST

AHU-4

SYMBOL DESCRIPTION

C-5

C-4B

CONDENSING UNIT

CONDENSING UNIT

AIR-HANDLING UNITAHU-7

AIR-HANDLING UNITAHU-5

C-6

C-3

EXISTING MECHANICAL PIPING PLAN - AREA B

P

IP

IN

G P

L A

N A

R E

A B

E X

IS

T

IN

G M

E C

H A

N

IC

A L

102B

MD-

C-4A

CONDENSING UNIT

CONDENSING UNIT

CONDENSING UNIT

N

CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING EXISTING SITE CONDITIONS.5.

OF THE CONTRACTOR UNTIL REUSED.

ITEMS INTENDED FOR REUSE ON THIS PROJECT SHALL REMAIN IN THE POSSESSION4.

ITS DISPOSAL.

BECOME THE PROPERTY OF THE CONTRACTOR, WHO SHALL BE RESPONSIBLE FOR

UNLESS NOTED OTHERWISE, ALL MATERIAL REMOVED AND NOT REUSED SHALL3.

DRAINED, CAPPED, AND ABANDONED IN PLACE.

EXISTING REFRIGERANT PIPING FOR AHU-4 AND AHU-7 (NOT SHOWN) SHALL BE2.

INSTALL NEW PIPING TO SERVE NEW EQUIPMENT.

CONTRACTOR SHALL DEMOLISH EXISTING REFRIGERANT PIPING FOR AHU-5 AND1.

EXISTING NATURAL-GAS HOT-WATER TANK WITH 6" FLUE TO REMAIN.

PIPING CONTINUES THROUGH ROOF TO KITCHEN EQUIPMENT.

GENERAL NOTES:

B P

R E

S S

E R

NUMBER

REFERENCE

SHEET

Project No.

D e s ig n e d B y

D a te

M a rk

Bldg. No.

F T

H O

O D T

E X

A S

S A

N T

A F

E E

N G

IN

E E

R D

R

B

L D

G

F O

R T H

O O

D T

E X

A S

P U

B L

IC

W

O R

K S

D

IR

E C

T O

R A

T E

D a te

D e s c ri p ti o n sivi

D secivreS & gn ir ee ni g n

E

D ir ec to rat eofPublic

W o rk s

P R

O J E

C T M

A N

A G

E R

P U

R P

O S

E S O

N L

Y F

O R B

ID

D

IN

G T

E C

H N

IC

A L E

X H

IB

IT

B

/8 /2

:5

:5

P

M G E

N G

S

V C \P ro j\ P

X P B

R

E P

L A

C E A

H U

S \F lo o rp la n s

D e s ig n \M

D -1

B .d g n

33012

B P

R E

S S

E R

-A

P R -2

PX901706P

R E

P L

A C

E A

H U

S

AHU

AHU

AHU

C

C

4B

C

4A

C

C

TO AHU-5

HEATING COIL

1" Ø

1" Ø ON ROOF

2" Ø ON ROOF

56 4.2

3.5 3.1

A

B

C

D

C.1

A

B

C

D

OFFICE

OFFICE

OFFICE

COOLER

SHOPPETTE

STORAGE

EMPLOYEE

BREAK AREA

WOMEN

JANITOR

MEN

COOLER

STORAGE

FREEZER

DINING AREA

BLIMPIE

SUBS

BURGER

KING

SHOPPETTE

RETAIL SALES

FOOD

PREP

FOOD PREP

MECHANICAL

YARD

MECHANICAL

YARD

FREEZER

FREEZER

LEGEND:

EXISTING REFRIGERANT LINE

SCALE: 1/2" = 1’

20 4

SCALE (FEET)

N

KEY PLAN

AC

UH

B

ET

RH

AHU

AHU 5

RH

RH

N

B P

R E

S S

E R

AIR-HANDLING UNIT

EQUIPMENT LIST

AHU-1

ET-1

SYMBOL DESCRIPTION

B-1

UH-1

AC-1

RH-1

RH-2

RH-5

AHU-2 AIR-HANDLING UNIT

BOILER

ROOF HOOD (OUTSIDE-AIR)

ROOF HOOD (OUTSIDE-AIR)

ROOF HOOD (OUTSIDE-AIR)

UNIT HEATER

EXPANSION TANK

AIR COMPRESSOR

KEY NOTES:

GENERAL NOTES:

PANEL "MA"PANEL "LA"

PANEL

FIRE ALARM

PANEL "SLA"

PANEL "PA"

PANEL "PB"

PANEL

FIRE ALARM

PANEL

TEMPERATURE CONTROL

PANEL

MAIN DISTRIBUTION

MD-

101A

MD-

MD-

1A

HWP

1B

HWP

HWP-1A

HWP-1B

HOT-WATER PUMP

HOT-WATER PUMP

CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING EXISTING SITE CONDITIONS.9.

OF THE CONTRACTOR UNTIL REUSED.

ITEMS INTENDED FOR REUSE ON THIS PROJECT SHALL REMAIN IN THE POSSESSION8.

ITS DISPOSAL.

BECOME THE PROPERTY OF THE CONTRACTOR, WHO SHALL BE RESPONSIBLE FOR

UNLESS NOTED OTHERWISE, ALL MATERIAL REMOVED AND NOT REUSED SHALL7.

UNITS, INCLUDING CONTROL WIRING.

CONTRACTOR SHALL DEMOLISH ALL THERMOSTATS SERVING EXISTING AIR-HANDLING6.

CONDUIT SHALL BE PRESERVED AND REUSED IF IT IS APPROPRIATELY SIZED.

EQUIPMENT SHALL REMAIN IN THE PANEL AND BE LABELED AS "SPARE". EXISTING

EXISTING ELECTRICAL PANEL. CIRCUIT BREAKERS THAT ARE NOT REUSED FOR NEW

INCLUDING DISCONNECTS, FOR DEMOLISHED HVAC EQUIPMENT BACK TO THE

CONTRACTOR SHALL DEMOLISH ALL EXISTING ELECTRICAL WIRING AND DEVICES,5.

THE MECHANICAL ROOM WALL.

PIPING, FITTINGS, AND VALVES. EXISTING PIPING SHALL BE DRAINED AND CAPPED AT

EXISTING HYDRONIC-SYSTEM COMPONENTS IN THE MECHANICAL ROOM, INCLUDING

AND EXPANSION TANK (ET-1). IN ADDITION, CONTRACTOR SHALL DEMOLISH ALL

CONTRACTOR SHALL DEMOLISH EXISTING HOT-WATER PUMPS (HWP-1A AND HWP-1B)4.

CURB SHALL BE CAPPED.

CONTRACTOR SHALL DEMOLISH EXISTING BOILER (B-1) AND FLUE. EXISTING ROOF3.

POSSIBLE, OR CAPPED.

PENETRATIONS SHALL BE PRESERVED AND REUSED FOR NEW EQUIPMENT, IF

OUTSIDE-AIR DUCTWORK SERVING AHU-1 AND AHU-2, RESPECTIVELY. EXISTING ROOF

CONTRACTOR SHALL DEMOLISH EXISTING ROOF HOODS (RH-1 AND RH-2) AND2.

NECESSARY TO INSTALL NEW EQUIPMENT.

EXISTING DUCTWORK CONNECTED TO THESE UNITS MAY BE DEMOLISHED IF

CONTRACTOR SHALL DEMOLISH EXISTING AIR-HANDLING UNITS (AHU-1 AND AHU-2).1.

UNIT LOCATED 84" ABOVE FINISHED FLOOR, SUSPENDED FROM CEILING HANGERS.

THERMOSTAT FOR UH-1 TO REMAIN, LOCATED 84" ABOVE FINISHED FLOOR.

12’-8" ABOVE FINSHED FLOOR.

40" X 16" OUTSIDE-AIR LOUVER. ONE LOCATED AT FLOOR LEVEL AND ONE LOCATED

MECHANICAL ROOM DEMOLITION PLAN

D E

M O

L

IT

IO

N P

L A

N

M E

C H

A N

IC

A L R

O O

M

NUMBER

REFERENCE

SHEET

Project No.

D e s ig n e d B y

D a te

M a rk

Bldg. No.

F T

H O

O D T

E X

A S

S A

N T

A F

E E

N G

IN

E E

R D

R

B

L D

G

F O

R T H

O O

D T

E X

A S

P U

B L

IC

W

O R

K S

D

IR

E C

T O

R A

T E

D a te

D e s c ri p ti o n sivi

D secivreS & gn ir ee ni g n

E

D ir ec to rat eofPublic

W o rk s

P R

O J E

C T M

A N

A G

E R

P U

R P

O S

E S O

N L

Y F

O R B

ID

D

IN

G T

E C

H N

IC

A L E

X H

IB

IT

B

/8 /2

:5

:0

P

M G E

N G

S

V C \P ro j\ P

X P B

R

E P

L A

C E A

H U

S \F lo o rp la n s

D e s ig n \M

D -1

.d g n

33012

B P

R E

S S

E R

-A

P R -2

PX901706P

R E

P L

A C

E A

H U

S

T

MECHANICAL

T

FD

FD

FD

20" X 16"

SUPPLY AIR

38" X 14"

RETURN AIR

20" X 20"

38" X 14"

RETURN AIR

X

S U

P P

L Y A

IR

DUCT AT ROOF

12" X 12" EXHAUST

4" CONCRETE SLAB

INTAKE FROM ROOF

36" X 20" OUTSIDE-AIR

INTAKE FROM ROOF

36" X 20" OUTSIDE-AIR

38" X 14"

RETURN AIR

LEGEND:

T

EXISTING ELECTRICAL PANEL

AIR FLOW DIRECTION

EXISTING THERMOSTAT

EXISTING 1’ X 1’ EXHAUST GRILLE

SCALE (FEET)

N

KEY PLAN

N

B P

R E

S S

E R

AIR-HANDLING UNIT

EQUIPMENT LIST

AHU-1

SYMBOL DESCRIPTION

AIR-HANDLING UNITAHU-2

B-1

UH-1

BOILER

UNIT HEATER

102A

MD-

MD-

MD-EXISTING MECHANICAL ROOM PIPING PLAN

R O

O M P

IP

IN

G P

L A

N

E X

IS

T

IN

G M

E C

H A

N

IC

A L

GENERAL NOTES:

THROUGH ROOF

2" Ø SUPPLY RISER

THROUGH ROOF

2" Ø SUPPLY RISER

2 1/2" Ø THROUGH WALL

AND CAPPED

2 1/2" Ø THROUGH WALL

CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING EXISTING SITE CONDITIONS.5.

OF THE CONTRACTOR UNTIL REUSED.

ITEMS INTENDED FOR REUSE ON THIS PROJECT SHALL REMAIN IN THE POSSESSION4.

ITS DISPOSAL.

BECOME THE PROPERTY OF THE CONTRACTOR, WHO SHALL BE RESPONSIBLE FOR

UNLESS NOTED OTHERWISE, ALL MATERIAL REMOVED AND NOT REUSED SHALL3.

DRAINED, CAPPED, AND ABANDONED IN PLACE.

EXISTING REFRIGERANT PIPING FOR AHU-1 AND AHU-2 (NOT SHOWN) SHALL BE2.

EXISTING UNIT HEATER (UH-1) SHALL BE PRESERVED.

BOILER (B-1), INCLUDING ALL ASSOCIATED FITTINGS AND VALVES. PIPING FOR

CONTRACTOR SHALL DEMOLISH EXISTING NATURAL-GAS PIPING SERVING EXISTING1.

AHU

AHU

B

UH

NUMBER

REFERENCE

SHEET

Project No.

D e s ig n e d B y

D a te

M a rk

Bldg. No.

F T

H O

O D T

E X

A S

S A

N T

A F

E E

N G

IN

E E

R D

R

B

L D

G

F O

R T H

O O

D T

E X

A S

P U

B L

IC

W

O R

K S

D

IR

E C

T O

R A

T E

D a te

D e s c ri p ti o n sivi

D secivreS & gn ir ee ni g n

E

D ir ec to rat eofPublic

W o rk s

P R

O J E

C T M

A N

A G

E R

P U

R P

O S

E S O

N L

Y F

O R B

ID

D

IN

G T

E C

H N

IC

A L E

X H

IB

IT

B

/8 /2

:5

:0

P

M G E

N G

S

V C \P ro j\ P

X P B

R

E P

L A

C E A

H U

S \F lo o rp la n s

D e s ig n \M

D -1

.d g n

33012

B P

R E

S S

E R

-A

P R -2

PX901706P

R E

P L

A C

E A

H U

S

MECHANICAL

FD

FD

FD

4" CONCRETE SLAB

1/2" Ø TO UNIT HEATER

1 1/2" Ø TO BOILER

THROUGH ROOF

2" Ø SUPPLY RISER

THROUGH ROOF

2" Ø SUPPLY RISER

LEGEND:

N SCALE: 3/16" = 1’

101A

M- N

KEY PLAN0 4 8

SCALE (FEET)

MATCHLINE - SEE M-101C

M A

T C

H L

IN

E S

E E M

-1

B

TRANSFORMER

P L

A N A

R E

A A

M E

C H

A N

IC

A L D

U C

T W

O R

K

RV

CU 3

AHU

MECHANICAL DUCTWORK PLAN - AREA A

P

R E

S S

E R

1-4

B

1-3

1-2

1-1

2-5

2-1

A

2-6

2-7

2-12

2-2

2-3

2-4

2-8

2-9

2-10

2-11

KEY NOTES:

AIR-HANDLING UNIT

EQUIPMENT LIST

AHU-3

RV-1

SYMBOL DESCRIPTION

CU-8 COOLING UNIT (REFRIGERATION)

RELIEF VENT

101A M-

M-

GENERAL NOTES:

NEW SUPPLY DIFFUSER. SEE M-601 FOR SIZING DETAILS.

NEW DUCTWORK.

M-103 FOR DUCTWORK TO AIR HANDLING UNIT.

NEW LOCATION OF 38" X 14" OPENING FOR RETURN-AIR PLENUM. SEE SHEET

THERMOSTAT FOR AHU-2.

AHU

CONSTRUCTION.

ALL DIMENSIONS PRIOR TO PERFORMING ANY MATERIAL TAKE-OFFS AND PRIOR TO

ALL DIMENSIONS SHOWN ARE APPROXIMATE. CONTRACTOR SHALL FIELD-VERIFY8.

CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING EXISTING SITE CONDITIONS.7.

PENETRATIONS WHEREVER MECHANICAL, PLUMBING, OR ELECTRICAL WORK OCCURS.

PROVIDE PATCHING, CLOSURE, AND FINISHING OF ADJACENT SURFACES AND6.

(TAB) THE NEW HVAC SYSTEM.

CONTRACTOR SHALL BE RESPONSIBLE FOR TESTING, ADJUSTING, AND BALANCING5.

TRUNK. LOCATION OF THERMOSTAT IS SHOWN ON M-101B.

CONNECTED TO THE NEW ILON 600 ROUTER IN THE MECHANICAL ROOM VIA A LON

SERVE AHU-3. THIS DEVICE SHALL BE LONWORKS-COMPLIANT AND SHALL BE

CONTRACTOR SHALL INSTALL A NEW, WIRED, WALL-MOUNTED THERMOSTAT TO4.

AHU-3. THIS DISCONNECT SHALL BE PROTECTED BY A NEMA 3R ENCLOSURE.

CONTRACTOR SHALL INSTALL NEW ELECTRICAL WIRING AND A NEW DISCONNECT FOR3.

INSULATED PER SPECS (23 07 00).

PER SMACNA 3RD EDITION AND SPECS (23 00 00). ALL NEW DUCTWORK SHALL BE

CONTRACTOR SHALL INSTALL NEW DUCTWORK WITH THE DIMENSIONS INDICATED2.

DUCTWORK AS SHOWN. SEE M-601 FOR SIZING AND CAPACITY DETAILS.

GAS HEATING (AHU-3) ON ROOF. THIS UNIT SHALL BE CONNECTED TO EXISTING

CONTRACTOR SHALL INSTALL A NEW, PACKAGED AIR-HANDLING UNIT WITH NATURAL-1.

NUMBER

REFERENCE

SHEET

Project No.

D e s ig n e d B y

D a te

M a rk

Bldg. No.

F T

H O

O D T

E X

A S

S A

N T

A F

E E

N G

IN

E E

R D

R

B

L D

G

F O

R T H

O O

D T

E X

A S

P U

B L

IC

W

O R

K S

D

IR

E C

T O

R A

T E

D a te

D e s c ri p ti o n sivi

D secivreS & gn ir ee ni g n

E

D ir ec to rat eofPublic

W o rk s

P R

O J E

C T M

A N

A G

E R

P U

R P

O S

E S O

N L

Y F

O R B

ID

D

IN

G T

E C

H N

IC

A L E

X H

IB

IT

B

/8 /2

:5

:0

P

M G E

N G

S

V C \P ro j\ P

X P B

R

E P

L A

C E A

H U

S \F lo o rp la n s

D e s ig n \M

-1

A .d g n

33012

B P

R E

S S

E R

-A

P R -2

PX901706P

R E

P L

A C

E A

H U

S

20" X 16"

SUPPLY AIR

X

X

X

X

X

16" X 16"

X

9" X 8" 9" X 7" 9" X 5"

X

X

6" X 4"

9" X 7"

16" X 12"

10" VERTICAL SPLIT

6" HORIZONTAL SPLIT

S U

P P

L Y A

IR

12" X 9"

X

X

X

12" X 8"

12" X 9" 12" X 9"

X

T

3.24.1

5.1

D

E

F

G

MECHANICAL

STORAGE

LAUNDRY/

ALTERATIONS

GNC

RETAIL SALES

OFFICE

VESTIBULE

MAIN LOBBY

SHOPPETTE

RETAIL SALES

ROOM

LEGEND:

T

AIR FLOW DIRECTION

NEW ELECTRICAL DISCONNECT

NEW THERMOSTAT

EXISTING 1’ X 1’ EXHAUST GRILLE

EXISTING 1’ X 2’ RETURN DIFFUSER

EXISTING 6" X 2’ RETURN DIFFUSER

EXISTING 1’ X 1’ RETURN DIFFUSER

EXISTING 2’ X 2’ RETURN DIFFUSER

EXISTING 1’ X 1’ SUPPLY DIFFUSER

NEW 2’ X 2’ SUPPLY DIFFUSER

101B

M- N

KEY PLAN0 4 8

SCALE (FEET)

MATCHLINE - SEE M-101D

M A

T C

H L

IN

E S

E E M

-1

A

MECHANICAL DUCTWORK PLAN - AREA B

P L

A N A

R E

A B

M E

C H

A N

IC

A L D

U C

T W

O R

K

EF

AHU

RH

RV

B P

R E

S S

E R

KEY NOTES:

2-14

2-15

2-16

2-13

2-18

3-1

3-2

3-3

3-6

3-8

AIR-HANDLING UNIT

EQUIPMENT LIST

AHU-6

SYMBOL DESCRIPTION

RH-6

EF-1

RV-2

EXHAUST FAN

RELIEF VENT

GENERAL NOTES:

TANK

WATER

GAS HOT-

ROOF HOOD (OUTSIDE AIR)

THERMOSTAT FOR AHU-6.

THERMOSTAT FOR AHU-3.

6-1

6-2

6-4

6-3

6-5

6-6

CONSTRUCTION.

ALL DIMENSIONS PRIOR TO PERFORMING ANY MATERIAL TAKE-OFFS AND PRIOR TO

ALL DIMENSIONS SHOWN ARE APPROXIMATE. CONTRACTOR SHALL FIELD-VERIFY9.

CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING EXISTING SITE CONDITIONS.8.

PENETRATIONS WHEREVER MECHANICAL, PLUMBING, OR ELECTRICAL WORK OCCURS.

PROVIDE PATCHING, CLOSURE, AND FINISHING OF ADJACENT SURFACES AND7.

(TAB) THE NEW HVAC SYSTEM.

CONTRACTOR SHALL BE RESPONSIBLE FOR TESTING, ADJUSTING, AND BALANCING6.

TRUNK.

CONNECTED TO THE NEW ILON 600 ROUTER IN THE MECHANICAL ROOM VIA A LON

SERVE AHU-6. THIS DEVICE SHALL BE LONWORKS-COMPLIANT AND SHALL BE

CONTRACTOR SHALL INSTALL A NEW, WIRED, WALL-MOUNTED THERMOSTAT TO5.

ENCLOSURE AND A NEMA 3R ENCLOSURE, RESPECTIVELY.

AHU-6 AND HP-6. THESE DISCONNECTS SHALL BE PROTECTED BY A NEMA 1

CONTRACTOR SHALL INSTALL NEW ELECTRICAL WIRING AND DISCONNECTS FOR4.

OF HP-6 IS SHOWN ON M-101D.

SHALL BE PLACED ON AN EXISTING FORMED-AND-PLACED CONCRETE PAD. LOCATION

CONTRACTOR SHALL INSTALL A NEW HEAT PUMP (HP-6) TO SERVE AHU-6. THIS UNIT3.

INSULATED PER SPECS (23 07 00).

PER SMACNA 3RD EDITION AND SPECS (23 00 00). ALL NEW DUCTWORK SHALL BE

CONTRACTOR SHALL INSTALL NEW DUCTWORK WITH THE DIMENSIONS INDICATED2.

ROOF HOOD (RH-6) AND DUCTWORK. SEE M-601 FOR SIZING AND CAPACITY DETAILS.

SHOWN. IN ADDITION, THIS UNIT SHALL BE CONNECTED TO EXISTING OUTSIDE-AIR

THIS UNIT SHALL BE CONNECTED TO EXISTING SUPPLY AND RETURN DUCTWORK AS

CONTRACTOR SHALL INSTALL A NEW AIR-HANDLING UNIT (AHU-6) ABOVE CEILING.1.

NUMBER

REFERENCE

SHEET

Project No.

D e s ig n e d B y

D a te

M a rk

Bldg. No.

F T

H O

O D T

E X

A S

S A

N T

A F

E E

N G

IN

E E

R D

R

B

L D

G

F O

R T H

O O

D T

E X

A S

P U

B L

IC

W

O R

K S

D

IR

E C

T O

R A

T E

D a te

D e s c ri p ti o n sivi

D secivreS & gn ir ee ni g n

E

D ir ec to rat eofPublic

W o rk s

P R

O J E

C T M

A N

A G

E R

P U

R P

O S

E S O

N L

Y F

O R B

ID

D

IN

G T

E C

H N

IC

A L E

X H

IB

IT

B

/8 /2

:5

:0

P

M G E

N G

S

V C \P ro j\ P

X P B

R

E P

L A

C E A

H U

S \F lo o rp la n s

D e s ig n \M

-1

B .d g n

33012

B P

R E

S S

E R

-A

P R -2

PX901706P

R E

P L

A C

E A

H U

S

16" X 12"16" X 12"

X

X

12" X 6" 12" X 6"

12" X 12"

SPLIT

HORIZONTAL

EQUAL

SPLIT

4" HORIZONTAL

X

X

6" X 4"

7" X 5"

24" X 16"

X

14" X 10" 14" X 10" 14" X 6"

14" X 16" 14" X 10"

X

S U

P P

L Y A

IR

X

X

12" X 8" 12" X 12" 16" X 12"

X

18" X 18"

X

12" X 6"

12" X 6"

X

X

T

THIS AREA

DIFFUSER (TYP)

18" X 12" SUPPLY

T

36" X 16"

SUPPLY AIR

2 1

2.13.2

D

E

F

G

OFFICE

BARBER SHOP

WOMEN

DINING AREA

JANITOR

MEN

SODA

STORAGE

DINING AREA

MAIN LOBBY

A B

C D

LEGEND:

T

AIR FLOW DIRECTION

NEW ELECTRICAL DISCONNECT

NEW THERMOSTAT

EXISTING 1’ X 1’ EXHAUST GRILLE

EXISTING 1’ X 2’ RETURN DIFFUSER

EXISTING 6" X 2’ RETURN DIFFUSER

EXISTING 1’ X 1’ RETURN DIFFUSER

EXISTING 2’ X 2’ RETURN DIFFUSER

EXISTING 1’ X 1’ SUPPLY DIFFUSER

NEW 2’ X 2’ SUPPLY DIFFUSER

EXISTING 2’ X 2’ SUPPLY DIFFUSER

2-17

3-4

101C

M- N

KEY PLAN0 4 8

SCALE (FEET)

MATCHLINE - SEE M-101A

M A

T C

H L

IN

E S

E E M

-1

D

MECHANICAL DUCTWORK PLAN - AREA C

P L

A N A

R E

A C

M E

C H

A N

IC

A L D

U C

T W

O R

K

AHU

EF

CU

CU

CU

CU

CU

CU

HP

AHU

B P

R E

S S

E R

1-5

1-6

- 240 1-7

C

1-9

1-10

1-11

1-8

B

4-1

AHU-4

SYMBOL DESCRIPTION

RV-1 RELIEF VENT

AIR-HANDLING UNITAHU-5

HP-5

EF-5 EXHAUST FAN

EQUIPMENT LIST (HVAC)

SYMBOL DESCRIPTION

CU-2

CU-6

CU-7

CU-1

CU-8

CU-11

EQUIPMENT LIST (REFRIGERATION)

COOLING UNIT

COOLING UNIT (ON ROOF)

COOLING UNIT

COOLING UNIT

COOLING UNIT

COOLING UNIT

GENERAL NOTES:

KEY NOTES:

FOR ICE MAKER

LOCATED ON ROOF

FOR CU-1

DISCONNECT

FOR CU-2

DISCONNECT

REFRIGERATION UNIT

DISCONNECT FOR

ROOF

LADDER TO

UNIT

COOLER

UNIT

COOLER

UNIT

COOLER

(ICE)

FREEZER UNIT

FREEZERS

SLAB

4" CONCRETE

TANK

GAS HOT-WATER

DOCK

LOADING

CONCRETE SLABS

FOR C-5

DISCONNECT

16" X 8" OUTSIDE-AIR LOUVER.

THERMOSTAT FOR AHU-5.

THERMOSTAT FOR AHU-1.

FOR SIZING DETAILS.

NEW SUPPLY DIFFUSER. SEE M-601

NEW DUCTWORK.

AIR-HANDLING UNIT

WATER TANK

ELECTRIC HOT-

HEAT PUMP

CONSTRUCTION.

ALL DIMENSIONS PRIOR TO PERFORMING ANY MATERIAL TAKE-OFFS AND PRIOR TO

ALL DIMENSIONS SHOWN ARE APPROXIMATE. CONTRACTOR SHALL FIELD-VERIFY10.

CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING EXISTING SITE CONDITIONS.9.

PENETRATIONS WHEREVER MECHANICAL, PLUMBING, OR ELECTRICAL WORK OCCURS.

PROVIDE PATCHING, CLOSURE, AND FINISHING OF ADJACENT SURFACES AND8.

(TAB) THE NEW HVAC SYSTEM.

CONTRACTOR SHALL BE RESPONSIBLE FOR TESTING, ADJUSTING, AND BALANCING7.

A LON TRUNK. LOCATION OF THERMOSTAT FOR AHU-4 IS SHOWN ON M-101D.

SHALL BE CONNECTED TO THE NEW ILON 600 ROUTER IN THE MECHANICAL ROOM VIA

SERVE AHU-4 AND AHU-5. THESE DEVICES SHALL BE LONWORKS-COMPLIANT AND

CONTRACTOR SHALL INSTALL NEW, WIRED, WALL-MOUNTED THERMOSTATS TO6.

ENCLOSURE, A NEMA 1 ENCLOSURE, AND A NEMA 3R ENCLOSURE, RESPECTIVELY.

AHU-4, AHU-5, AND HP-5. THESE DISCONNECTS SHALL BE PROTECTED BY A NEMA 3R

CONTRACTOR SHALL INSTALL NEW ELECTRICAL WIRING AND DISCONNECTS FOR5.

SHALL BE PLACED ON AN EXISTING FORMED-AND-PLACED CONCRETE PAD.

CONTRACTOR SHALL INSTALL A NEW HEAT PUMP (HP-5) TO SERVE AHU-5. THIS UNIT4.

INSULATED PER SPECS (23 07 00).

PER SMACNA 3RD EDITION AND SPECS (23 00 00). ALL NEW DUCTWORK SHALL BE

CONTRACTOR SHALL INSTALL NEW DUCTWORK WITH THE DIMENSIONS INDICATED3.

SIZING AND CAPACITY DETAILS.

EXISTING OUTSIDE-AIR LOUVER IN THE SHOPPETTE STORAGE AREA. SEE M-601 FOR

CONNECT IT TO EXISTING DUCTWORK AS SHOWN. THIS UNIT SHALL UTILIZE THE

CONTRACTOR SHALL INSTALL A NEW AIR-HANDLING UNIT (AHU-5) ABOVE CEILING AND2.

DUCTWORK AS SHOWN. SEE M-601 FOR SIZING AND CAPACITY DETAILS.

GAS HEATING (AHU-4) ON ROOF. THIS UNIT SHALL BE CONNECTED TO EXISTING

CONTRACTOR SHALL INSTALL A NEW, PACKAGED AIR-HANDLING UNIT WITH NATURAL-1.

NUMBER

REFERENCE

SHEET

Project No.

D e s ig n e d B y

D a te

M a rk

Bldg. No.

F T

H O

O D T

E X

A S

S A

N T

A F

E E

N G

IN

E E

R D

R

B

L D

G

F O

R T H

O O

D T

E X

A S

P U

B L

IC

W

O R

K S

D

IR

E C

T O

R A

T E

D a te

D e s c ri p ti o n sivi

D secivreS & gn ir ee ni g n

E

D ir ec to rat eofPublic

W o rk s

P R

O J E

C T M

A N

A G

E R

P U

R P

O S

E S O

N L

Y F

O R B

ID

D

IN

G T

E C

H N

IC

A L E

X H

IB

IT

B

/8 /2

:5

:0

P

M G E

N G

S

V C \P ro j\ P

X P B

R

E P

L A

C E A

H U

S \F lo o rp la n s

D e s ig n \M

-1

C .d g n

33012

B P

R E

S S

E R

-A

P R -2

PX901706P

R E

P L

A C

E A

H U

S

SPLIT

4" HORIZONTAL

SPLIT

5" HORIZONTAL

X

12" X 10" 12" X 6"

9" X 6" 9" X 6"

36" X 14"

SUPPLY AIR

6" X 6"

6" X 6"

12" X 10"12" X 5"

26" X 14"

18" X 18"

RETURN AIR

12" X 10"

12" X 10"

12" X 10" 12" X 10"

10" X 6"

6" X 6"

T

T

FD

56 4.2

3.5

A

B

C

D

OFFICE

OFFICE

OFFICE

COOLER

SHOPPETTE

STORAGE

EMPLOYEE

BREAK AREA

WOMEN

JANITOR

MEN

SHOPPETTE

RETAIL SALES

MECHANICAL

YARD

LEGEND:

T

AIR FLOW DIRECTION

NEW ELECTRICAL DISCONNECT

NEW THERMOSTAT

EXISTING 1’ X 1’ EXHAUST GRILLE

EXISTING 1’ X 2’ RETURN DIFFUSER

EXISTING 6" X 2’ RETURN DIFFUSER

EXISTING 1’ X 1’ RETURN DIFFUSER

EXISTING 2’ X 2’ RETURN DIFFUSER

EXISTING 1’ X 1’ SUPPLY DIFFUSER

NEW 2’ X 2’ SUPPLY DIFFUSER

EXISTING 2’ X 2’ SUPPLY DIFFUSER

4-3

4-2

4-4

4-4

4-4

4-4

101D

M- N

KEY PLAN0 4 8

SCALE (FEET)

D

3.5

M A

T C

H L

IN

E S

E E M

-1

C

MATCHLINE - SEE M-101B

MECHANICAL DUCTWORK PLAN - AREA D

P L

A N A

R E

A D

M E

C H

A N

IC

A L D

U C

T W

O R

K

CU

HP

CU

CU

CU

H

EF

EF

H

EF

H

RV

S E

E M

-1

C

M A

T C

H L

IN

E

P

R E

S S

E R

3-7

3-9

4-9

7-3

7-1

7-5

7-4

7-7

7-8

7-9

7-2

4-11

4-10

SYMBOL DESCRIPTION

CU-9

CU-5

CU-4

CU-10

EF-2

SYMBOL DESCRIPTION

EXHAUST FAN

H-1

RV-2 RELIEF VENT

HP-6

EF-3 EXHAUST FAN

EF-4 EXHAUST FAN

HOOD VENT UNIT

H-2 HOOD VENT UNIT

H-3 HOOD VENT UNIT

AHU-7

EQUIPMENT LIST (HVAC)

EQUIPMENT LIST (REFRIGERATION)

COOLING UNIT

COOLING UNIT

COOLING UNIT

COOLING UNIT

PANEL "PK4"

PANEL "PK1"

PANEL NOT USED

PANEL "PK3"

FED FROM PANEL PK3

PANEL "PK2 - SECTION 2"

AHU

GENERAL NOTES:

KEY NOTES:

33 NEW DUCTWORK.

THERMOSTAT FOR AHU-7.

THERMOSTAT FOR AHU-4.

FROM PANEL PK3

SECTION 1" FED

PANEL "PK2 -

AIR-HANDLING UNIT

HEAT PUMP

FINISHED FLOOR

WALL IS 84" ABOVE

LOWER PART OF

DOCK

LOADING

CONSTRUCTION.

ALL DIMENSIONS PRIOR TO PERFORMING ANY MATERIAL TAKE-OFFS AND PRIOR TO

ALL DIMENSIONS SHOWN ARE APPROXIMATE. CONTRACTOR SHALL FIELD-VERIFY8.

CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING EXISTING SITE CONDITIONS.7.

PENETRATIONS WHEREVER MECHANICAL, PLUMBING, OR ELECTRICAL WORK OCCURS.

PROVIDE PATCHING, CLOSURE, AND FINISHING OF ADJACENT SURFACES AND6.

(TAB) THE NEW HVAC SYSTEM.

CONTRACTOR SHALL BE RESPONSIBLE FOR TESTING, ADJUSTING, AND BALANCING5.

TRUNK.

CONNECTED TO THE NEW ILON 600 ROUTER IN THE MECHANICAL ROOM VIA A LON

SERVE AHU-7. THIS DEVICE SHALL BE LONWORKS-COMPLIANT AND SHALL BE

CONTRACTOR SHALL INSTALL A NEW, WIRED, WALL-MOUNTED THERMOSTAT TO4.

AHU-7. THIS DISCONNECT SHALL BE PROTECTED BY A NEMA 3R ENCLOSURE.

CONTRACTOR SHALL INSTALL NEW ELECTRICAL WIRING AND A NEW DISCONNECT FOR3.

INSULATED PER SPECS (23 07 00).

PER SMACNA 3RD EDITION AND SPECS (23 00 00). ALL NEW DUCTWORK SHALL BE

CONTRACTOR SHALL INSTALL NEW DUCTWORK WITH THE DIMENSIONS INDICATED2.

DUCTWORK AS SHOWN. SEE M-601 FOR SIZING AND CAPACITY DETAILS.

GAS HEATING (AHU-7) ON ROOF. THIS UNIT SHALL BE CONNECTED TO EXISTING

CONTRACTOR SHALL INSTALL A NEW, PACKAGED AIR-HANDLING UNIT WITH NATURAL-1.

NUMBER

REFERENCE

SHEET

Project No.

D e s ig n e d B y

D a te

M a rk

Bldg. No.

F T

H O

O D T

E X

A S

S A

N T

A F

E E

N G

IN

E E

R D

R

B

L D

G

F O

R T H

O O

D T

E X

A S

P U

B L

IC

W

O R

K S

D

IR

E C

T O

R A

T E

D a te

D e s c ri p ti o n sivi

D secivreS & gn ir ee ni g n

E

D ir ec to rat eofPublic

W o rk s

P R

O J E

C T M

A N

A G

E R

P U

R P

O S

E S O

N L

Y F

O R B

ID

D

IN

G T

E C

H N

IC

A L E

X H

IB

IT

B

/8 /2

:5

:1

P

M G E

N G

S

V C \P ro j\ P

X P B

R

E P

L A

C E A

H U

S \F lo o rp la n s

D e s ig n \M

-1

D .d g n

33012

B P

R E

S S

E R

-A

P R -2

PX901706P

R E

P L

A C

E A

H U

S

X

X

X

X

X

6" X 6"

30" X 14" 26" X 14"

X

X

X

12" X 5"

12" X 5"

14" X 6"

14" X 6"

X

14" X 6"

9" X 6"

X

X

10" X 8"

14" X 6"

14" X 6"

10" X 8"

24" X 24"

SUPPLY AIR

24" X 12"

14" X 12"

T

T

3.1

A

B

C

C.1

COOLER

STORAGE

FREEZER

DINING AREA

BLIMPIE

SUBS

BURGER

KING

FOOD

PREP

FOOD PREP

FREEZER

FREEZER

A B

C D

LEGEND:

T

AIR FLOW DIRECTION

NEW ELECTRICAL DISCONNECT

NEW THERMOSTAT

EXISTING 1’ X 1’ EXHAUST GRILLE

EXISTING 1’ X 2’ RETURN DIFFUSER

EXISTING 6" X 2’ RETURN DIFFUSER

EXISTING 1’ X 1’ RETURN DIFFUSER

EXISTING 2’ X 2’ RETURN DIFFUSER

EXISTING 1’ X 1’ SUPPLY DIFFUSER

NEW 2’ X 2’ SUPPLY DIFFUSER

EXISTING 2’ X 2’ SUPPLY DIFFUSER

3-5

4-5

4-7

4-6

4-8

7-6

SCALE: 1/8" = 1’

SCALE (FEET)

0 8 164

EQUIPMENT LIST

SYMBOL DESCRIPTION

AIR-HANDLING UNITAHU-6

C-2

C-1 CONDENSING UNIT

CONDENSING UNIT

AIR-HANDLING UNITAHU-3

NEW MECHANICAL PIPING PLAN - AREA A

P L

A N A

R E

A A

N E

W M

E C

H A

N

IC

A L P

IP

IN

G

102A

M-

GENERAL NOTES:

MATCHLINE - SEE M-102BMATCHLINE - SEE M-102B

102A M-

M-

M-501 FOR FURTHER DETAILS.

WALKWAY/PROTECTION PADS EQUIVALENT TO A DURO-LAST ROOF TRAK III. SEE

TO A DURO-LAST CADDY PYRAMID RL. THESE SUPPORTS SHALL BE INSTALLED ON

ALL NEW ROOFTOP PIPING SHALL BE ROUTED ON NEW ROOF SUPPORTS EQUIVALENT2.

DIMENSIONS INDICATED AND CONNECT IT TO NEW EQUIPMENT.

CONTRACTOR SHALL INSTALL NEW NATURAL-GAS PIPING ON ROOF WITH THE1.

B P

R E

S S

E R

NUMBER

REFERENCE

SHEET

Project No.

D e s ig n e d B y

D a te

M a rk

Bldg. No.

F T

H O

O D T

E X

A S

S A

N T

A F

E E

N G

IN

E E

R D

R

B

L D

G

F O

R T H

O O

D T

E X

A S

P U

B L

IC

W

O R

K S

D

IR

E C

T O

R A

T E

D a te

D e s c ri p ti o n sivi

D secivreS & gn ir ee ni g n

E

D ir ec to rat eofPublic

W o rk s

P R

O J E

C T M

A N

A G

E R

P U

R P

O S

E S O

N L

Y F

O R B

ID

D

IN

G T

E C

H N

IC

A L E

X H

IB

IT

B

/8 /2

:5

:1

P

M G E

N G

S

V C \P ro j\ P

X P B

R

E P

L A

C E A

H U

S \F lo o rp la n s

D e s ig n \M

-1

A .d g n

33012

B P

R E

S S

E R

-A

P R -2

PX901706P

R E

P L

A C

E A

H U

S

AHU

AHU

AHU

3/4" Ø

1" Ø

1" Ø

1" Ø

ON ROOF2" Ø

ON ROOF2" Ø 2" Ø

2" Ø

3/4" Ø1" Ø

2" Ø

1 1/2" Ø ON ROOFUNDERGROUND

NATURAL-GAS MAIN

HIGH-PRESSURE

AND CAPPED

2 1/2" Ø THROUGH WALL

2 1

2.13.24.1

5.1

D

E

F

G

D

E

F

G

MECHANICAL

STORAGE

LAUNDRY/

ALTERATIONS

GNC

RETAIL SALES

OFFICE

OFFICE

BARBER SHOP

VESTIBULE

MAIN LOBBY

WOMEN

DINING AREA

JANITOR

MEN

SODA

STORAGE

DINING AREA

SHOPPETTE

RETAIL SALES

4 3

ROOM

MAIN LOBBY

LEGEND:

NEW REFRIGERANT LINE

NEW NATURAL-GAS SUPPLY LINE

SCALE: 1/8" = 1’

SCALE (FEET)

0 8 164

AIR-HANDLING UNIT

EQUIPMENT LIST

AHU-4

SYMBOL DESCRIPTION

C-5

AIR-HANDLING UNITAHU-7

AIR-HANDLING UNITAHU-5

C-6

CONDENSING UNIT

CONDENSING UNIT

N

NEW MECHANICAL PIPING PLAN - AREA B

P L

A N A

R E

A B

N E

W M

E C

H A

N

IC

A L P

IP

IN

G

102B

M-

GENERAL NOTES:

MATCHLINE - SEE M-102AMATCHLINE - SEE M-102A

M-501 FOR FURTHER DETAILS.

WALKWAY/PROTECTION PADS EQUIVALENT TO A DURO-LAST ROOF TRAK III. SEE

TO A DURO-LAST CADDY PYRAMID RL. THESE SUPPORTS SHALL BE INSTALLED ON

ALL NEW ROOFTOP PIPING SHALL BE ROUTED ON NEW ROOF SUPPORTS EQUIVALENT2.

DIMENSIONS INDICATED AND CONNECT IT TO NEW EQUIPMENT.

CONTRACTOR SHALL INSTALL NEW NATURAL-GAS PIPING ON ROOF WITH THE1.

B P

R E

S S

E R

NUMBER

REFERENCE

SHEET

Project No.

D e s ig n e d B y

D a te

M a rk

Bldg. No.

F T

H O

O D T

E X

A S

S A

N T

A F

E E

N G

IN

E E

R D

R

B

L D

G

F O

R T H

O O

D T

E X

A S

P U

B L

IC

W

O R

K S

D

IR

E C

T O

R A

T E

D a te

D e s c ri p ti o n sivi

D secivreS & gn ir ee ni g n

E

D ir ec to rat eofPublic

W o rk s

P R

O J E

C T M

A N

A G

E R

P U

R P

O S

E S O

N L

Y F

O R B

ID

D

IN

G T

E C

H N

IC

A L E

X H

IB

IT

B

/8 /2

:5

:1

P

M G E

N G

S

V C \P ro j\ P

X P B

R

E P

L A

C E A

H U

S \F lo o rp la n s

D e s ig n \M

-1

B .d g n

33012

B P

R E

S S

E R

-A

P R -2

PX901706P

R E

P L

A C

E A

H U

S

AHU

AHU

AHU

C

C

3/4" Ø

1" Ø

3/4" Ø ON ROOF

1" Ø ON ROOF

2" Ø ON ROOF

56 4.2

3.5 3.1

A

B

C

D

C.1

A

B

C

D

OFFICE

OFFICE

OFFICE

COOLER

SHOPPETTE

STORAGE

EMPLOYEE

BREAK AREA

WOMEN

JANITOR

MEN

COOLER

STORAGE

FREEZER

DINING AREA

BLIMPIE

SUBS

BURGER

KING

SHOPPETTE

RETAIL SALES

FOOD

PREP

FOOD PREP

MECHANICAL

YARD

MECHANICAL

YARD

FREEZER

FREEZER

LEGEND:

NEW REFRIGERANT LINE

NEW NATURAL-GAS SUPPLY LINE

SCALE (FEET)

N

KEY PLAN

AC

UH

AHU

AHU

N

B P

R E

S S

E R

EQUIPMENT LIST

AHU-1

SYMBOL DESCRIPTION

UH-1

AC-1

AHU-2

UNIT HEATER

AIR COMPRESSOR

KEY NOTES:

GENERAL NOTES:

PANEL "MA"PANEL "LA"

PANEL

FIRE ALARM

PANEL "SLA"

PANEL "PA"

PANEL "PB"

PANEL

FIRE ALARM

PANEL

TEMPERATURE CONTROL

PANEL

MAIN DISTRIBUTION

AIR-HANDLING UNIT

AIR-HANDLING UNIT

FLOOR

84" ABOVE FINISHED

UH-1 THERMOSTAT

101A M-

M-

NEW ILON 600 ROUTER IN A NEMA 1 ENCLOSURE.

CONSTRUCTION.

ALL DIMENSIONS PRIOR TO PERFORMING ANY MATERIAL TAKE-OFFS AND PRIOR TO

ALL DIMENSIONS SHOWN ARE APPROXIMATE. CONTRACTOR SHALL FIELD-VERIFY9.

CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING EXISTING SITE CONDITIONS.8.

PENETRATIONS WHEREVER MECHANICAL, PLUMBING, OR ELECTRICAL WORK OCCURS.

PROVIDE PATCHING, CLOSURE, AND FINISHING OF ADJACENT SURFACES AND7.

(TAB) THE NEW HVAC SYSTEM.

CONTRACTOR SHALL BE RESPONSIBLE FOR TESTING, ADJUSTING, AND BALANCING6.

OF THE AHU THERMOSTATS IN THE BUILDING. SEE M-701 FOR DETAILS.

CONTRACTOR SHALL INSTALL A NEW ILON 600 ROUTER TO COLLECT DATE FROM ALL5.

RESPECTIVELY.

TRUNK. LOCATIONS OF THERMOSTATS ARE SHOWN ON M-101C AND M-101A,

CONNECTED TO THE NEW ILON 600 ROUTER IN THE MECHANICAL ROOM VIA A LON

AHU-1 AND AHU-2. THESE DEVICES SHALL BE LONWORKS-COMPLIANT AND SHALL BE

CONTRACTOR SHALL INSTALL NEW, WIRED, WALL-MOUNTED THERMOSTATS TO SERVE4.

ENCLOSURES.

AHU-1 AND AHU-2. THESE DISCONNECTS SHALL BE PROTECTED BY NEMA 3R

CONTRACTOR SHALL INSTALL NEW ELECTRICAL WIRING AND DISCONNECTS FOR3.

INSULATED PER SPECS (23 07 00).

PER SMACNA 3RD EDITION AND SPECS (23 00 00). ALL NEW DUCTWORK SHALL BE

CONTRACTOR SHALL INSTALL NEW DUCTWORK WITH THE DIMENSIONS INDICATED2.

EXISTING DUCTWORK AS SHOWN. SEE M-601 FOR SIZING AND CAPACITY DETAILS.

GAS HEATING (AHU-1 AND AHU-2) ON ROOF. THESE UNITS SHALL BE CONNECTED TO

CONTRACTOR SHALL INSTALL NEW, PACKAGED AIR-HANDLING UNITS WITH NATURAL-1.

MECHANICAL ROOM PIPING PLAN

P L

A N

M E

C H

A N

IC

A L R

O O

M P

IP

IN

G

M-103

NUMBER

REFERENCE

SHEET

Project No.

D e s ig n e d B y

D a te

M a rk

Bldg. No.

F T

H O

O D T

E X

A S

S A

N T

A F

E E

N G

IN

E E

R D

R

B

L D

G

F O

R T H

O O

D T

E X

A S

P U

B L

IC

W

O R

K S

D

IR

E C

T O

R A

T E

D a te

D e s c ri p ti o n sivi

D secivreS & gn ir ee ni g n

E

D ir ec to rat eofPublic

W o rk s

P R

O J E

C T M

A N

A G

E R

P U

R P

O S

E S O

N L

Y F

O R B

ID

D

IN

G T

E C

H N

IC

A L E

X H

IB

IT

B

/8 /2

:5

:1

P

M G E

N G

S

V C \P ro j\ P

X P B

R

E P

L A

C E A

H U

S \F lo o rp la n s

D e s ig n \M

-1 .d g n

33012

B P

R E

S S

E R

-A

P R -2

PX901706P

R E

P L

A C

E A

H U

S

MECHANICAL

T

FD

FD

FD

DUCT AT ROOF

12" X 12" EXHAUST

4" CONCRETE SLAB

X

R E

T U

R N A

IR

38" X 14"

RETURN AIR

30" X 14"

SUPPLY AIR

38" X 14"

RETURN AIR

IL

O

N

LEGEND:

T

EXISTING ELECTRICAL PANEL

AIR FLOW DIRECTION

EXISTING THERMOSTAT

EXISTING 1’ X 1’ EXHAUST GRILLE

SCALE (FEET)

N

KEY PLAN

N

B P

R E

S S

E R

AIR-HANDLING UNIT

EQUIPMENT LIST

AHU-1

SYMBOL DESCRIPTION

AIR-HANDLING UNITAHU-2

UH-1 UNIT HEATER

102A M-

M-

NEW MECHANICAL ROOM PIPING PLAN

P

IP

IN

G P

L A

N

N E

W M

E C

H A

N

IC

A L R

O O

M

M-104

THROUGH ROOF

2" Ø SUPPLY RISER

THROUGH ROOF

2" Ø SUPPLY RISER

2 1/2" Ø THROUGH WALL

AND CAPPED

2 1/2" Ø THROUGH WALL

AHU

AHU

UH

GENERAL NOTES:

M-501 FOR FURTHER DETAILS.

WALKWAY/PROTECTION PADS EQUIVALENT TO A DURO-LAST ROOF TRAK III. SEE

TO A DURO-LAST CADDY PYRAMID RL. THESE SUPPORTS SHALL BE INSTALLED ON

ALL NEW ROOFTOP PIPING SHALL BE ROUTED ON NEW ROOF SUPPORTS EQUIVALENT2.

DIMENSIONS INDICATED AND CONNECT IT TO NEW EQUIPMENT.

CONTRACTOR SHALL INSTALL NEW NATURAL-GAS PIPING ON ROOF WITH THE1.

NUMBER

REFERENCE

SHEET

Project No.

D e s ig n e d B y

D a te

M a rk

Bldg. No.

F T

H O

O D T

E X

A S

S A

N T

A F

E E

N G

IN

E E

R D

R

B

L D

G

F O

R T H

O O

D T

E X

A S

P U

B L

IC

W

O R

K S

D

IR

E C

T O

R A

T E

D a te

D e s c ri p ti o n sivi

D secivreS & gn ir ee ni g n

E

D ir ec to rat eofPublic

W o rk s

P R

O J E

C T M

A N

A G

E R

P U

R P

O S

E S O

N L

Y F

O R B

ID

D

IN

G T

E C

H N

IC

A L E

X H

IB

IT

B

/8 /2

:5

:1

P

M G E

N G

S

V C \P ro j\ P

X P B

R

E P

L A

C E A

H U

S \F lo o rp la n s

D e s ig n \M

-1 .d g n

33012

B P

R E

S S

E R

-A

P R -2

PX901706P

R E

P L

A C

E A

H U

S

MECHANICAL

FD

FD

FD

3/4" Ø

3/4" Ø

THROUGH ROOF

2" Ø SUPPLY RISER

THROUGH ROOF

2" Ø SUPPLY RISER

4" CONCRETE SLAB

1/2" Ø TO UNIT HEATER

LEGEND:

NEW NATURAL-GAS SUPPLY LINE

3/4" Ø ON ROOF

P

R E

S S

E R

M E

C H

A N

IC

A L D

E T

A

IL

S

NOT TO SCALE

DUCT MAIN AND BRANCH TAKE-OFFS

NOT TO SCALE

NOT TO SCALE

AHU CONDENSATE DRAIN DETAIL

NOT TO SCALE

DIFFUSER/GRILLE CONNECTION DETAIL

M-

M-

WITH DAMPER AND LONG-RADIUS ELBOW

SPIN COLLAR FLEXIBLE DUCT CONNECTOR

NOT TO SCALE

WITH DAMPER

SPIN COLLAR FLEXIBLE DUCT CONNECTOR

M-

M-

M-

M-

M-

M-

M-

M-

NOT TO SCALE

M-

M-

LOW-LEAKAGE RECTANGULAR DAMPERS

M-501

NOT TO SCALE

M-

M-

ROOF SUPPORT FOR PIPING NUMBER

REFERENCE

SHEET

Project No.

D e s ig n e d B y

D a te

M a rk

Bldg. No.

F T

H O

O D T

E X

A S

S A

N T

A F

E E

N G

IN

E E

R D

R

B

L D

G

F O

R T H

O O

D T

E X

A S

P U

B L

IC

W

O R

K S

D

IR

E C

T O

R A

T E

D a te

D e s c ri p ti o n sivi

D secivreS & gn ir ee ni g n

E

D ir ec to rat eofPublic

W o rk s

P R

O J E

C T M

A N

A G

E R

P U

R P

O S

E S O

N L

Y F

O R B

ID

D

IN

G T

E C

H N

IC

A L E

X H

IB

IT

B

/8 /2

:5

:2

P

M G E

N G

S

V C \P ro j\ P

X P B

R

E P

L A

C E A

H U

S \F lo o rp la n s

D e s ig n \M

-5 .d g n

33012

B P

R E

S S

E R

-A

P R -2

PX901706P

R E

P L

A C

E A

H U

S

INSULATION PER NOTE 1

SUPPLY-AIR DUCT

RETURN-AIR DUCT

EXHAUST-AIR OR

TAKE-OFF

BELLMOUTH

45° MAX

OR 4" MIN

1/4 WM

WB

W M

WIDTH, WB

BRANCH DUCT

MAIN AIRFLOW

VOLUME DAMPER AS REQUIRED.

OPPOSED-BLADE MANUAL

1. SUPPLY-AIR AND RETURN-AIR DUCT SHALL BE EXTERNALLY INSULATED ONLY.

NOTES:

3"

1/ 2"

SEAL JOINT

DUCT WORK

SEE NOTE 5

SEE NOTE 8

SPIN COLLAR

DAMPER

BALANCING

SINGLE-BLADE

FLEXIBLE DUCT

METAL CLAMP

(SHOWN ON TOP FOR ILLUSTRATION ONLY).

BOTTOM OF DUCT FOR EASY SERVICE

8. INSTALL LOCKING QUADRANT AND HANDLE ON

LEAKAGE.

7. TAPE AND SEAL ALL JOINTS TO PREVENT

DAMPER.

RIVETS OR SCREWS DO NOT INTERFERE WITH

CONNECTING STOVEPIPE TO COLLAR. ENSURE

MINIMUM 3 EACH AT 120° INTERVALS,

6. POP RIVET OR SHEET METAL SCREWS,

BARRIER.

REQUIRED AND SEAL TO EFFECT VAPOR

INSULATION, PULL TO EDGE OF DUCTWORK AS

5. PROVIDE EXTENSION RODS TO ACCOMMODATE

MOISTURE MIGRATION.

DUCTWORK. SEAL VAPOR BARRIER TO PREVENT

OF SPIN COLLAR AT EDGE OF RECTANGULAR

4. PULL FLEXIBLE DUCT INSULATION UP TO END

CONTRACTOR.

POSITION. FINAL ADJUSTMENT BY TAB

3. INSTALL SPIN COLLAR DAMPER IN OPEN

OUTBOARD END OF COLLAR.

2. BAND FLEX TO COLLAR 1/2" MINIMUM FROM

1. SUPPORT DUCTWORK AS REQUIRED.

NOTES:

3"

SEE NOTE 5

SEAL JOINT

DUCT WORK

SEE NOTE 8

SPIN COLLAR

1" M

IN

NOTE 7

SEE

REQUIRED

BY MANUFACTURER AS

FURNISHED INSULATION

FLEXIBLE DUCT WITH

NOTE 6

SEE

DAMPER

BALANCING

SINGLE-BLADE

ELBOW

RADIUS

LONG-

ON TOP FOR ILLUSTRATION ONLY).

BOTTOM OF DUCT FOR EASY SERVICE (SHOWN

8. INSTALL LOCKING QUADRANT AND HANDLE ON

7. TAPE AND SEAL ALL JOINTS TO PREVENT LEAKAGE.

SCREWS DO NOT INTERFERE WITH DAMPER.

STOVEPIPE TO COLLAR. ENSURE RIVETS OR

EACH AT 120° INTERVALS, CONNECTING

6. POP RIVET OR SHEET METAL SCREWS, MINIMUM 3

REQUIRED AND SEAL TO EFFECT…

This is the start of the file's text. The full file is on GovTribe.