GENERAL NOTES
1.
2.MOUNTING HEIGHTS ABOVE FLOOR SHALL BE AS FOLLOW UNLESS OTHERWISE
NOTED ON THE DRAWING.
LIGHTING FIXTURE
350mm TO CENTER OF THE ENCL
MOTOR CONTROLLER 1524mm TO CENTER OF THE ENCL
3.
4.
6.
THE SOIL RESISTANCE TO GROUND FOR THE ELECTRICAL AND COMMMUNICATION
SYSTEMS SHALL BE 25 OHMS OR LESS. THE SOIL RESISTANCE TEST SHALL BE
7.
5.
CONDUCTED BY THE CONTRACTOR TO OBTAIN THE REQUIRED SOIL RESISTANCE.
INDICATEDS 2 #12AWG IN 16C
INDICATEDS 3 #12AWG IN 16C
INDICATEDS 4 #12AWG IN 16C
A GREATER NUMBER OF WIRES ARE INDICATED AS FOLLOWS;
1219mm TO CENTER OF THE ENCLWALL SWTICH
A
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
ELECTRICAL
SCOPE OF WORKS
LEGEND, GENERAL NOTES AND
E-1
10.
8.
9.
SINGLE POLE TOGGLE SWITCH, 15A-125V
L E G E N D
FLEXIBLE CONDUIT W/CONNECTORS
LIGHTING
WIRING
POWER
INTERIOR
S
SYMBOL DESCRIPTION
DESCRIPTION
DESCRIPTION
J JUNCTION BOX
SYMBOL
SYMBOL
M
C CONTROL CIRCUIT
AND GOVERNMENT INSTALLED
GOVERNMENT FURNISHED
GFGI
WEATHERPROOFWP
LA LIGHTNING ARRESTER
EXPLOSIONPROOFEP
DISTRIBUTIONDIST
GROUND FAULT PROTECTIONGFP
A AMPERE
AC ALTERNATING CURRENT
AF/AT AMPERE FRAME/AMPERE TRIP
AWG AMERICAN WIRE GAUGE
BC BARE COPPER
BLDG BUILDING
BRKR BREAKER
C CONDUIT
CB CIRCUIT BREAKER
CKT CIRCUIT
CONN CONNECTION
CT CURRENT TRANSFORMER
DET(S) DETAIL(S)
DIAG DIAGRAM
DISC DISCONNECT
DWG(S) DRAWING(S)
EA EACH
EM EMERGENCY
ENCL ENCLOSURE
EXST EXISTING
F/A FIRE ALARM
FL FLOOR
FLUOR FLUORESCENT
FXTR FIXTURE
GEN GENERATOR
GND GROUND
HP HORSE POWER
HZ HERTZ
INCAND INCANDESCENT
INSTL INSTALLATION
J-BOX JUNCTION BOX
K KILO
KV KILO VOLT
KVA KILO VOLT AMPERE
LTG LIGHTING
MAG MAGNETIC
MAX MAXIMUM
MIN MINIMUM OR MINUTE
MTG MOUNTING
NO NUMBER
O/H OVER HEAD
PH PHASE
PNLBD PANELBOARD
PRIM PRIMARY
PWR POWER
Q'TY QUANTITY
RCPT RECEPTACLE
REQ'D REQUIRED
SCHED SCHEDULE
SEC SECONDARY
SPEC SPECIFICATION
STD STANDARD
SW SWITCH
TEL TELEPHONE
TYP TYPICAL
U/G UNDERGROUND
V VOLT
VA VOLT AMPERE
W WATT
W/ WITH
XFMR TRANSFORMER
& AND
HOMERUN CIRCUIT TO PANELBOARD
TYPE
DUPLEX RECEPTACLE, 2P-3W-20A-125V, GROUNDING
ABBREVIATION
ANY CIRCUIT WITHOUT FURTHER DESIGNATION INDICATES 2-#12AWG
WIRES IN 16C CONDUIT UNLESS OTHERWISE INDICATED.
THE GROUNDING CONDUCTORS SHALL BE SEPARATELY PROVIDED FOR
ELECTRICAL EQUIPMENT UNLESS OTHERWISE INDICATED ON THE DRAWING.
CATV BEFORE CONSTRUCTION.
CONTRACTOR SHALL COORDINATE WITH AREA MP, DO IMO, SIGNAL BRIGADE,
AND GOVERNMENT ACCEPTANCE.
PANELBOARD DOOR, REQUIRED BEFORE FINAL BUILDING INSPECTION
CONTRACTOR SHALL MAKE CIRCUIT CHARTS AND ATTACH THEM TO
FIRE CODE AND SPECIFICATIONS.
OF THE NATIONAL ELECTRICAL CODE, NATIONAL ELECTRICAL SAFETY CODE,
ALL ELECTRICAL WORK SHALL CONFORM TO THE CURRENT REQUIREMENTS
OR RENOVATION.
CONDITION AND DIMENSIONS PRIOR TO COMMENCING ANY CONSTRUCTION
THE CONTRACTOR SHALL BE RESPONSIBLE IN VERIFING ALL EXISTING
AUXILIARY
DESCRIPTIONSYMBOL
WP
FAULT PROTECTED TYPE, WEATHER PROOF
DUPLEX RECEPTACLE, 2P-3W-20A-125V, GROUNDED
W/EMERGENCY UNIT
ON LTG SCHEDULE
LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG
ON LTG SCHEDULE
LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG
L
L
UNITS.
CERTIFICATE FROM MANUFACTURER FOR LED LIGHTING FIXTURES AND POWER
CONTRACTOR SHALL BE RESPONSIBLE TO PROVIDE 10YEARS WARRANTY
THE GRADING LINE OF NEW DUCTS WILL BE LIMITED TO THE
WIDTH OF DUCT EXCAVATION.
AND AFTER INSTALLATION OF ELECTRICAL SYSTEM.
TO THEIR ORIGINAL CONDITION AND OPERATION DURING
ALL DAMAGED AREA INCLUDING SODDING, UTILITIES, STRUCTURES
THE CONTRACTOR SHALL BE RESPONSIBLE FOR RESTORING
RECEPTACLE
AND WALL
WIRING CONCEALED OR EXPOSED IN/ON THE CEILING
SCOPE OF WORK
1.
4.
2.
3.
ROLL-UP DOOR (UNDER CIVIL. ITEM)
ECLOSED CIRCUIT BREAKER
B. NEW WORK ( L )
ENCLOSED CIRCUIT BREAKER
CEILING SURFACE MOUNTED
1219mm TO CENTER OF THE ENCL
1.
A. REPAIR/MAINTENANCE ( K )
COURSE, CP CASEY.
WIRES AND CONDUITS FOR SECONDARY CONTAINMENT SHED NEAR GOLF
INSTALL NEW EXTERIOR & INTERIOR LIGHTING FIXTURES, TOGGLE SWITCH,
SHED NEAR GOLF COURSE, CP CASEY.
PLATES ASSOCIATED WIRES & CONDUITS FOR SECONDARY CONTAINMENT
INSTALL NEW ENCLOSED CIRCUIT BREAKER, RECEPTACLES W/COVER
FOR SECONDARY CONTAINMENT SHED NEAR GOLF COURSE, CP CASEY.
INSTALL NEW POWER AND CONTROL LINE FOR ROLL-UP DOOR SYSTEM
FOR SECONDARY CONTAINMENT SHED NEAR GOLF COURSE, CP CASEY.
INSTALL NEW EXTERIOR SECONDARY LINE WITH ASSCIATED ACCESSORIES
AT BUILDING S-4361A, S-4361B AND S-3751A, CP HOVEY.
MONITORED/SUPERVISED BY EXISTING FIRE ALARM CONTROL PANEL
OF NEW BACK FLOW PREVENTOR ASSEMBLY TO BE CONNECTED/
REPAIR EXISTING FIRE ALARM SYSTEM FOR TEMPER SWITCHES
DEVICE, CP CASEY AND CP HOVEY
TYPICAL FIRE ALARM CONTROL PLAN
CONSTRUCT A SECONDARY CONTAINMENT
TAK, YS
196998
BRIDGE
TURF AREA
CON'C OPEN DITCH
R A
M P
P
S
PS
A
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
FORCE PROTECTION
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
1:100
0 10M7.552.5
CAMP CASEY AND HOVEY
196998
S
NEMA 3R ENCL.
NEW ENCLOSED CIRCUIT BREAKER,
NEW CONCRETE ELECTRIC POLE
W/ SECONDARY RACK (3-SPOOLS) AND
SECONDARY CONTAINMENT SHED
NEW EXTERIOR LIGHT TYPE "NS-2"
F A
C I
L I
T Y
G O
L F
M A I
N T
E N
A N
C E
W
S H
R
C K
3-AWG#8 "WP"
NEW OVERHEAD SECONDARY LINE
EXIST OVERHEAD PRIMARY LINE (TYP.)
EXIST OVERHEAD SECONDARY LINE (TYP.)
EXIST ELECTRIC POLE (TYP.)
EXIST/NEW EXTERIOR ELECTRICAL PLAN
EXIST/NEW EXTERIOR ELECTRICAL PLAN
TAK, YS
ELECTRICAL
SCALE:
1/100
INSTALL A BACKFLOW PREVENTION DEVICE
CONSTRUCT A SECONDARY CONTAINMENT AND
E-2
PROVIDE NEW SEC. RACK AND ACCESSOREIS
UNDERGROUND SECONDARY POWER RISER SET
CEILING SURFACE/PENDANT MOUNTED LIGHT EMITTING DIODE (LED)
FIXTURE, 1PH, 120V, 45W, UL LISTED, WITH CONVERTER AND
ACCESSORIES AS REQUIRED, (NS-1a) & EM UNIT(NS-1b)
LL L L
S
LC-1
"LC""WP"
LC-2
J
SCALE: 1/50
A
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
ELECTRICAL
NS-1a & 2b
AUTOMATIC ROLL-UP DOOR
BA N G
GND
S/N
LIGHTS RECEPTACLES
ROLL-UP DOOR
20 20
20 20
NOT TO SCALE
LC-3
"WP"
1PH, 208VAC, 0.75KW (CIVIL ITEM)
1PH, 208VAC (CIVIL ITEM)
CONTROLLER OF AUTOMATIC ROLL-UP DOOR,
NEMA 3R ENCL.
NEW ENCLOSED CIRCUIT BREAKER,
NEW ENCLOSED CIRCUIT BREAKER LOAD SCHEDULE
M
ALUMINUM HOUSING, MOUNTING ARM AND ACCESSORIES,
110LM/W, OPERATING TEMP: -40 TO 50 degC. IP66 RATED DIECAST
SURGE PROTECTION: 10 KV, IES TYPE 2, CCT 5700K, MIN EFFICIENCY:
INPUT POWER: FREE VOLTAGE IN 120V TO 277 VAC RANGE
WITH BUILT-IN POWER UNIT & PHOTOCELL CONTROL, UL LISTED.
POLE MOUNTED 100~108W LED EXTERIOR STREET/SECURITY LIGHT
NS-2
DEVICE, CP CASEY AND CP HOVEY
TYPICAL FIRE ALARM CONTROL PLAN
CONSTRUCT A SECONDARY CONTAINMENT
TAK, YS
196998
E-3
NEW SECONDARY CONTAINMENT SHED ELECTRICAL PLAN
CIRCUIT BREAKER LOAD SCHEDULE
ELECTRICAL PLAN NEW ENCLOSED
NEW SECONDARY CONTAINMENT SHED
GENERAL NOTES
2.
4.
3.
5. THE CONTRACTOR SHALL BE RESPONSIBLE FOR RESTORING
6.
1.
ALL DAMAGED AREA INCLUDING SODDING, UTILITIES,
STRUCTURES TO THEIR ORIGINAL CONDITION AND OPERATION
DURING AND AFTER INSTALLATION OF ELECTRICAL SYSTEM.
FIRE CODE AND SPECIFICATIONS.
THE NATIONAL ELECTRICAL CODE, NATIONAL ELECTRICAL SAFETY CODE,
ALL ELECTRICAL WORK SHALL CONFORM TO THE CURRENT REQUIREMENTS OF
ELECTRICAL EQUIPMENT UNLESS OTHERWISE INDICATED ON THE DRAWING.
THE GROUNDING CONDUCTORS SHALL BE SEPARATELY PROVIDED FOR
CONTRACTOR IS RESPOSIBLE TO PROVIDE INPUT (OR RERAY) MODLES, WIRING
RE-PROGRAMING OF EXISTING FIRE ARLAM SYSTEM AS REQUIRED.
PROPERLY MONITORED AND SUPERVISED.
COMPATIBLE TO EXISTING FIRE ALARM CONTROL SYSTEM TO BE
THE MANUFACTURER AND MODEL OF NEW F/A EQUIPMENT SHALL BE
ELECTRICAL
MECH ROOM
J
TS TS
J
F
F F
TYPICAL FIRE ALARM CONTROL PLAN FOR BACK FLOW PREVENTOR ASSEMBLY
NOT TO SCALE
SIGNALING LINE CIRCUIT(TYPICAL)
CONNECT TO EXIST FIRE ALARM EXIST FIRE SPRINKER LINE
EXISTING FIRE ALARM SYSTEM
LINE CIRCUIT TO BE CONNECTED TO
PROVIDE NEW FIRE ALARM SIGALING
NEW BACK FLOW PREVENTOR ASSEMBLY
OR CONVENTIONAL TYPE AS REQUIRED. (TYPICAL)
PROVIDE RE-PROGRAMING OF EXISTING FACP REGARDLESS OF ADDRESSABLE
SUPERVISED BY EXISTING FIRE ALARM CONTROL PANEL(FACP) AS REQUIRED.
TEMPER SWITCH (MECH ITEM),/ PROVIDE INPUT MODULE TO BE MONITORED &
A
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
"TW" IN 16 CONDUIT.
ALL FIRE ARALM SIGNALING LINE CIRCUIT WIRING SHALL BE #14 AWG.
CONSTRUCT A SECONDARY CONTAINMENT
AND INSTALL BACKFLOW PREVENTION
DEVICE, CP CASEY AND CP HOVEY
196998
TAK, YS
E-4
GENERAL NOTE, TYPICAL FIRE ALARM
CONTROL PLAN FOR BACK FLOW
PREVENTOR ASSEMBLY
| E-1 |
| E-2 |
| E-3 |
| E-4 |