TE 1 - Attachment 3 - AFPMTL MASTER OSAN.pdf
PDF 925 KB Posted
- Attached to
- DORM HVAC IN OSAN AIR BASE (LCS) Federal contract opportunity
- Solicitation number
- W90VN6-23-R-0019
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| TE 1 - Attachment 1 - Workload Estimates (Facility Listing)(REV.05).xlsx | XLSX spreadsheet | |
| TE 1 - Attachment 2 - Maintenance Actions and Frequencies May 2022.docx | DOCX document | |
| Modification W90VN6-23-R-0019-0001 23 MAY 2023.pdf | ||
| Solicitation W90VN6-23-R-0019-0001 23 MAY 2023.pdf | ||
| Solicitation W90VN6-23-R-0019.pdf | ||
| Technical Exhibit 3 Consumables for Maintenance.docx | DOCX document | |
| Technical Exhibit 2 Maintenance Actions and Frequencies.docx | DOCX document | |
| Technical Exhibit 1 Workload Estimates -Facility List.xlsx | XLSX spreadsheet |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
3/8/23, 3:19 PM PMTL D2025260395001
https://usaf.dps.mil/teams/10758/PMTL/Module/PMTL Details.aspx?EID=257# 1/1
Equipment Type: D2025260395001
Component: Heater, Water, Electric
Equipment Component As Of: 07/02/2018
1 Collect maps, communication equipment, tools, safety equipment
0.033 x x
2 Check with the Facility Manager for any issues with the water heater or lack of hot water to the building.
0.033 x x
3 Check for water leaks to tank and piping 0.016 x x
4 Turn off power to water heater, disconnect wires from elements. 0.033 x x
5 Test the elements with a ohm meter. 0.166 x x
6 Pull all the fuses and test with an ohm meter. 0.116 x x
7 Turn power to the water heater back on. 0.016 x x
8 Check operation and condition of pressure relief valve 0.016 x x
9 Clean, test and inspect valves and drains 0.050 x x
10 Check for proper water temperature setting and output temperature; adjust as required
0.250 x x
11 Check automatic controls for proper operation including temperature regulators and thermostatic devices
0.033 x x
12 Clean up area around water heater 0.083 x x
13 Drain/flush the water heater to remove calcium build up. 0.416 x
14 Refill water heater. 0.166 x
15 Compile list of discrepancies and open corrective maintenance work task(s) to make the repair(s)
0.166 x x
Semi-Annually 1.011
Annually 1.593
Step PM Components (Task Description) Labor-hrs S A
3/8/23, 3:38 PM PMTL D2025260495001
https://usaf.dps.mil/teams/10758/PMTL/Module/PMTL Details.aspx?EID=229# 1/1
Equipment Type: D2025260495001
Component: Water Heater, Instantaneous
Equipment Component As Of: 09/22/2015
1 Collect maps, communication equipment, tools, and safety equipment
0.033 x x x
2 Notify Facility Manager/facility occupants 0.083 x x x
3 Don Personal Protective Equipment as required for steps below:
0.050 x x x
4 Check for water leaks to tank and piping; check lines for leaks; Check for air supply vent for blockage with dust, oil, etc; Check for combustible materials near heater or exhaust vent; Check for blockage at drain pipe discharge; Check for abnormalities in external appearance, discoloration or flaws.; Clean, test and inspect valves and drains
0.083 x x x
5 Remove, clean, and replace cold water inlet filter. 0.166 x x x
6 Check operation and condition of pressure relief valve 0.033 x x x
7 Check for proper water temperature setting and output temperature; adjust as required
0.033 x x x
8 Flush heater to remove lime and scale deposits. 1.000 x
9 Check and replace (if necessary) condensate acid neutralizer
0.166 x x x
10 Open hot water faucet to actuate heater. Verify proper operation of heater.
0.066 x x x
11 Compile list of discrepancies and open corrective maintenance work task(s) to make the repair(s)
0.166 x x x
Quarterly 0.879
Semi-Annually 0.879
Annually 1.879
Step PM Components (Task Description) Labor-hrs Q S A
3/8/23, 3:38 PM PMTL D3025140595001
https://usaf.dps.mil/teams/10758/PMTL/Module/PMTL Details.aspx?EID=230# 1/1
Equipment Type: D3025140595001
Component: Steam Distribution, Inspection
Equipment Component As Of: 10/01/2015
Ref: UFC 3-430-01FA 0 x x x x
1 Collect maps, communications equipment, tools, safety equipment
0.044 x x x x
2 Check with operating or area personnel for deficiencies
0.035 x x x x
3 Inspect steam distribution lines for leaks 0.033 x x x
4 Inspect steam traps and valves 0.033 x x x
5 Inspect steam and water regulators 0.033 x x
6 Inspect operation of safety relief valves 0.033 x x x x
7 Check condensate piping for leaks 0.033 x x
8 Clean mechanical room, as necessary 0.066 x x x x
9 Compile list of discrepancies and open corrective maintenance work task(s) to make repair(s)
0.167 x x x x
Monthly 0.345
Quarterly 0.411
Semi-Annually 0.477
Annually 0.477
Step PM Components (Task Description) Labor-hrs M Q S A
3/8/23, 3:39 PM PMTL D3025140695001
https://usaf.dps.mil/teams/10758/PMTL/Module/PMTL Details.aspx?EID=231# 1/1
Equipment Type: D3025140695001
Component: Steam Distribution, Maintenance
Equipment Component As Of: 10/01/2015
Ref: UFC 3-430-01FA 0 x
1 Collect maps, communications equipment, tools, safety equipment 0.044 x
2 Check with operating or area personnel for deficiencies 0.035 x
3 Inspect, repack, and lubricate steam valves 0.750 x
4 Rebuild pressure regulating valve to include replacing seat and diaphragm. Clean, insepct lubricate and adjust as required
0.750 x
5 Clean and rebuild steam traps as required 0.750 x
6 inspect and replace check valves as required 0.750 x
7 Check condition of safety relief valves 0.050 x
8 Clean mechanical room, as necessary 0.066 x
9 Compile list of discrepancies and open corrective maintenance work task(s) to make repair(s)
0.167 x
Annually 3.362
Step PM Components (Task Description) Labor-hrs A
3/8/23, 3:40 PM PMTL D3025210195001
https://usaf.dps.mil/teams/10758/PMTL/Module/PMTL Details.aspx?EID=235# 1/1
Equipment Type: D3025210195001
Component: Air Separator
Equipment Component As Of: 03/01/2016
1 Collect maps, communication equipment, tools, safety equipment
0.044 x x
2 Check for excessive corrosion or leaks, check air vent for proper operation and clean if obstructed
0.250 x x
3 Compile list of discrepancies and open corrective maintenance job order(s) to make the repair(s)
0.167 x x
Semi-Annually 0.461
Annually 0.461
3/8/23, 3:40 PM PMTL D3025210195002
https://usaf.dps.mil/teams/10758/PMTL/Module/PMTL Details.aspx?EID=236# 1/1
Equipment Type: D3025210195002
Component: Expansion Tank
Equipment Component As Of: 03/01/2016
1 Collect maps, communication equipment, tools, safety equipment
0.044 x x
2 Check for excessive corrosion or leaks 0.167 x x
3 Check if relief valve is weeping and repair if possible, otherwise see task #4
0.167 x x
4 Compile list of discrepancies and open corrective maintenance job order(s) to make the repair(s)
0.167 x x
Semi-Annually 0.545
Annually 0.545
3/8/23, 3:42 PM PMTL D3035160195001
https://usaf.dps.mil/teams/10758/PMTL/Module/PMTL Details.aspx?EID=224# 1/1
Equipment Type: D3035160195001
Component: Air Cooled Screw Chiller 26-100 TN
Equipment Component As Of: 02/27/2015
1 Check unit for proper operation, excessive noise or vibration
0.033 x x x x
2 Run system diagnostics test 0.325 x x x x
3 Check oil level and oil temperature; add oil as necessary
0.022 x x x x
4 Check refrigerant pressures; add as necessary 0.272 x x x x
5 Replace oil filters and oil, if applicable 0.081 x x
6 Check contactors, sensors and mechanical safety limits
0.094 x x
7 Perform spectrochemical analysis of compressor oil
0.039 x x
8 Check electrical wiring and connections; tighten loose connections
0.120 x x
9 Inspect cooler and condenser tubes for leaks 5.200 x
10 Check evaporator and condenser for corrosion 0.026 x
11 Clean chiller and surrounding area, spray coils with solution, rinse with water, and remove debris
0.500 x x x x
12 Fill out maintenance checklist and report deficiencies
0.167 x x x x
Monthly 1.319
Quarterly 1.319
Semi-Annually 1.653
Annually 6.879
3/8/23, 3:43 PM PMTL D3035160195002
https://usaf.dps.mil/teams/10758/PMTL/Module/PMTL Details.aspx?EID=394# 1/1
Equipment Type: D3035160195002
Component: CHILLER UNIT 50-100TON, MULTIMODE HEAT RECOVERY 4 PIPE
Equipment Component As Of: 08/18/2022
1 Collect maps, communication equipment, tools, safety equipment
0.033 x x x x
2 Notify Facility Manager/facility occupants 0.083 x x x x
3 Don Personal Protective Equipment and perform lock-out tag-out procedures as required for steps below:
0.050 x x x x
4 Check unit for proper operation, excessive noise or vibration, Run system diagnostics test
0.166 x x x x
5 Check oil level and oil temperature; add oil as necessary; Check refrigerant pressures; add as necessary
0.166 x x x x
6 Check user side calculation pump: loop pressure gauges; clean or replace strainer; and buffer tank connection for leaks
0.250 x x x x
7 Check heat recovery side: calculation pump and loop pressure gauges; clean or replace strainer;
and solenoid valve
0.250 x x x x
8 Replace oil filters and oil, if applicable 0.166 x
9 Inspect cooler and condenser tubes for leaks;
Check evaporator and condenser for corrosion
0.083 x
10 Check contactors; Check Flow Switches; Sensors and mechanical safety limits; Check electrical wiring and connections; tighten loose connections; Check units hydronic modules expansion valve and relive valve
0.366 x
11 Clean Unit and surrounding area, spray coils with solution, rinse with water, and remove debris
0.250 x x x x
12 Compile list of discrepancies and open corrective maintenance work task(s) to make the repair(s)
0.166 x x x x
Monthly 1.414
Quarterly 1.414
Semi-Annually 1.414
Annually 2.029
3/8/23, 3:44 PM PMTL D3035160295002
https://usaf.dps.mil/teams/10758/PMTL/Module/PMTL Details.aspx?EID=228# 1/1
Equipment Type: D3035160295002
Component: Boiler-CHW Closed Loop Water Treatment
Equipment Component As Of: 07/08/2015
1 Put on personal protective equipment (PPE) to work with chemicals (goggles, apron, gloves, etc.)
as required. Note: Refer to manufacturer's manual and/or engineered design specifications for additional tasks unique to your installation and equipment
0.070 x x x x
2 Inspect & clean sampling point/valve for leaks/corrosion
0.030 x x x x
3 Flush sample point for 10-sec before taking water sample
0.010 x x x x
4 Preform water sample chemical test, record results & analyze against the recommended protection level
0.103 x x x x
5 Make necessary adjustments to chemical levels 0.200 x x x x
6 Record the parts per million (ppm) levels & document treatment levels of chemicals added
0.020 x x x x
7 Verify ph range is between 8.5-10; if level is above or below, adjust accordingly (reference UFC 3-240-13fn sect. 5-2.2)
0.200 x x x
8 Identify water leaks in excess of 2% of system inhibitor concentration in the circulating water (reference UFC 3-240-13fn sect. 5-2.4)
0.200 x x x
9 Fill out maintenance checklist and report deficiencies; clean- up surrounding area
0.167 x x x x
Monthly 0.6
Quarterly 1
Semi-Annually 1
Annually 1
3/8/23, 3:45 PM PMTL D3035160295003
https://usaf.dps.mil/teams/10758/PMTL/Module/PMTL Details.aspx?EID=238# 1/1
Equipment Type: D3035160295003
Component: Water Filtration for HVAC Systems
Equipment Component As Of: 10/01/2015
1 Collect maps, communications equipment, tools, safety equipment
0.044 x x x
2 Check with operating or area personnel for deficiencies. 0.035 x x x
3 Inspect system for leaks, and isolate filtration device from operating system.
0.040 x x x
4 Remove filter. 0.100 x x x
5 Inspect filter; clean with hot water or replace filter as necessary.
0.083 x x x
6 Reinstall filter. 0.100 x x x
7 Align for normal operation (unisolate) and inspect system for leaks.
0.040 x x x
8 Clean area around equipment. 0.083 x x x
9 Fill out maintenance checklist and report deficiencies. 0.167 x x x
Quarterly 0.692
Semi-Annually 0.692
Annually 0.692
3/8/23, 3:46 PM PMTL D3035160295004
https://usaf.dps.mil/teams/10758/PMTL/Module/PMTL Details.aspx?EID=239# 1/1
Equipment Type: D3035160295004
Component: Water Treatment/Protection, Glycol Feed
Equipment Component As Of: 10/01/2015
1 Collect maps, communications equipment, tools, safety equipment 0.044 x
2 Check with operating or area personnel for deficiencies 0.035 x
3 Inspect glycol feed tank level; if low inspect system for leaks - glycol will be added as necessary in step 5 below.
0.083 x
4 Inspect glycol clearity, glycol should be absent of any contamination. 0.017 x
5 If glycol is contaminated, remove glycol and recycle. Clean feed tank with bleach and water. Flush with copious amounts for water. Refill with glycol.
0.350 x
6 Add glycol to feed tank as necessary 0.166 x
7 Verify low level indicator alarms and turn off pumps 0.083 x
8 Clean area around equipment 0.083 x
9 Fill out maintenance checklist and report deficiencies. 0.167 x
Annually 1.028
3/8/23, 3:47 PM PMTL D3035160295005
https://usaf.dps.mil/teams/10758/PMTL/Module/PMTL Details.aspx?EID=240# 1/1
Equipment Type: D3035160295005
Component: Chiller, Scroll, Air Cooled 30 to 130 Ton
Equipment Component As Of: 03/01/2016
1 Collect maps, communication equipment, tools, and safety equipment
0.044 x x x x
2 Check unit for proper operation, excessive noise or vibration
0.033 x x x x
3 Run system for diagnostics test 0.325 x x x x
4 Check the electronic expansion valve sight glasses, operating pressures and temperatures
0.036 x x x x
5 Check superheat and subcooling temperatures 0.325 x x x x
6 Inspect fan(s) or blower(s) for bent blades, clearances, and operation
0.237 x x x x
7 Check oil level and refrigerant charge, perform a compressor oil analysis
0.042 x
8 Inspect all piping components for leaks and damage, clean water strainer
0.117 x
9 Inspect condenser coils for dirt and debris, clean as necessary
1.282 x x x x
10 Check contactors, sensors and unit safeties 0.094 x
11 Check electrical wiring and connections; tighten loose connections
0.120 x
12 Check evaporator and condenser for corrosion 0.052 x x x x
13 Clean chiller and surrounding area 0.117 x x x x
14 Compile list of discrepancies and open corrective maintenance job order(s) to make the repair(s)
0.167 x x x x
Monthly 2.618
Quarterly 2.618
Semi-Annually 2.618
Annually 2.991
3/8/23, 3:47 PM PMTL D3045120295001
https://usaf.dps.mil/teams/10758/PMTL/Module/PMTL Details.aspx?EID=241# 1/1
Equipment Type: D3045120295001
Component: Fin Tube Radiator
Equipment Component As Of: 10/01/2015
1 Collect maps, communications equipment, tools, safety equipment 0.044 x
2 Check with operating or area personnel for deficiencies 0.035 x
3 Remove accessories and enclosure panel 0.034 x
4 Inspect finned tube elements for accumulation of dust or other debris.
Remove dust and debris from coils with a vacuum cleaner or compressed air
0.084 x
5 Inspect for leaks or areas of corrosion 0.022 x
6 Check electrical wiring to control valve, if applicable 0.017 x
7 Check condition and operation of control valve 0.070 x
8 Replace cover and accessories 0.034 x
9 Clean area around fin tube radiator 0.034 x
10 Fill out maintenance checklist and report deficiencies 0.167 x
Annually 0.541
3/8/23, 3:48 PM PMTL D3045160195001
https://usaf.dps.mil/teams/10758/PMTL/Module/PMTL Details.aspx?EID=242# 1/1
Equipment Type: D3045160195001
Component: VAV Boxes, Reheat and/or Fan Powered
Equipment Component As Of: 10/01/2015
1 Collect maps, communications equipment, tools, safety equipment
0.044 x x
2 Open/close VAV control box access 0.060 x x
3 Check that pneumatic tubing/electrical connections are in place and tight
0.040 x x
4 Tighten arm on motor output shaft 0.040 x x
5 Cycle actuator while watching for proper operation 0.200 x x
6 Verify that blades fully open and close. 0.040 x x
7 Lubricate actuator linkage and damper blade pivot points 0.070 x x
8 Check intake air filter, replace as necessary 0.078 x x
9 Check fan motor for excessive heat 0.033 x x
10 Inpsect coil surface for leaks and dirt accumulation 0.050 x x
11 Clean coil if necessary 0.083 x x
12 Inspect valves and valve actuators, replace as necessary 0.083 x x
13 Clean area around/below equipment 0.033 x x
14 Fill out maintenance checklist and report deficiencies 0.167 x x
Semi-Annually 1.021
Annually 1.021
3/8/23, 3:48 PM PMTL D3045600195001
https://usaf.dps.mil/teams/10758/PMTL/Module/PMTL Details.aspx?EID=243# 1/1
Equipment Type: D3045600195001
Component: Heat Exchanger, Plate Type
Equipment Component As Of: 03/01/2016
1 Collect maps, communication equipment, tools, safety equipment
0.044 x x
2 Check temperature & pressure gauges for proper operating parameters
0.091 x x
3 Check modulating control valve for proper operation 0.083 x x
4 Inspect heat exchanger and adjacent piping for torn or deteriorated insulation
0.083 x x
5 Unbolt heat exchanger plate section and clean individual plates with warm water or mild cleaning agent and soft brush
4.500 x
6 Check for worn or failed gaskets; replace as needed 0.250 x
7 Reinstall bolts and torque to correct tolerance, ensuring measurement of plate pack and gaskets does not fall below as-designed tolerance
0.750 x
8 Compile list of discrepancies and open corrective maintenance job order(s) to make the repair(s)
0.167 x x
Semi-Annually 0.468
Annually 5.968
3/8/23, 3:49 PM PMTL D3045600195002
https://usaf.dps.mil/teams/10758/PMTL/Module/PMTL Details.aspx?EID=244# 1/1
Equipment Type: D3045600195002
Component: Heat Exchanger, Shell & Tube, Non-Steam
Equipment Component As Of: 03/01/2016
1 Collect maps, communication equipment, tools, safety equipment
0.044 x x
2 Check temperature & pressure gauges for proper operating parameters
0.091 x x
3 Check modulating control valve for proper operation 0.083 x x
4 Inspect heat exchanger and adjacent piping for torn ordeteriorated insulation
0.083 x x
5 Clean heat exchanger and surrounding area 0.083 x x
6 Compile list of discrepancies and open corrective maintenance job order(s) to make the repair(s)
0.167 x x
Semi-Annually 0.551
Annually 0.551
3/8/23, 3:50 PM PMTL D3045600195003
https://usaf.dps.mil/teams/10758/PMTL/Module/PMTL Details.aspx?EID=395# 1/1
Equipment Type: D3045600195003
Component: Hot Water Booster, Variable Refrigerant Flow (VRF) , Indoor Unit
Equipment Component As Of: 08/18/2022
1 Collect maps, communication equipment, tools, safety equipment
0.033 x x x
2 Notify Facility Manager/facility occupants 0.083 x x x
3 Don Personal Protective Equipment and perform lock-out tag-out procedures as required for steps below:
0.050 x x x
4 Inspect unit for proper operation, Check all insulation, Excessive noise or vibration, Run system diagnostics test, Inspect all electrical system, controls, and sensors
0.333 x x x
5 Clean or replace indoor unit filter(s). 0.166 x x x
6 Inspect and clean drain line(s). Check water lines for leaks.
0.166 x x x
7 Inspect and clean hot water inlet strainer. (Booster only) 0.166 x x x
8 Inspect refrigerant level at primary loop and secondary loop (Booster only)
0.166 x x x
9 Compile list of discrepancies and open corrective maintenance work task(s) to make the repair(s)
0.166 x x x
Quarterly 1.329
Semi-Annually 1.329
Annually 1.329
3/8/23, 3:51 PM PMTL D3055250395001
https://usaf.dps.mil/teams/10758/PMTL/Module/PMTL Details.aspx?EID=368# 1/1
Equipment Type: D3055250395001
Component: Indoor and Outdoor Ductless Split System Heat Pump Unit.
Equipment Component As Of: 12/21/2021
1 Collect maps, communication equipment, tools, safety equipment
0.033 x x x
2 Notify Facility Manager/facility occupants 0.083 x x x
3 Don Personal Protective Equipment and perform lock-out tag-out procedures as required for steps below:
0.050 x x x
4 Outdoor condenser/heat pump: Ensure 18" clearance of outdoor unit. Free of debris and or outdoor equipment.
Coordinate with Facilities Manager if needed.
0.033 x x x
5 Turn off and make safe the electrical power supply to the entire system.
0.050 x x x
6 Inspect Outdoor condenser/heat pump electric terminals, and, if necessary, clean and tighten connections, and apply non-conductive coating.
0.166 x x x
7 Visually inspect Outdoor condenser/heat pump around service valves for signs of refrigerant leaks (i.e. oily fittings).
0.033 x x x
8 Inspect the Outdoor condenser/heat pump's condensing unit base-pan drain holes and remove debris.
0.033 x x x
9 Clean coils on outdoor condenser/heat pump in according to manufactures instructions.
0.166 x x x
10 Ensure outdoor condenser/heat pump and the indoor unit is still powered off and perform the following on the indoor unit:
0.016 x x x
11 Wash filter on indoor head/cassette with water. 0.166 x x x
12 Spray indoor coil with no-rinse coil cleaner, unless otherwise specified by manufacturer.
0.083 x x x
13 Check / clear condensate line for blockage. 0.033 x x x
14 Wipe down housing of indoor unit. 0.033 x x x
15 Return system back to normal operating configuration 0.033 x x x
16 Clean up indoor and outdoor work areas. 0.116 x x x
17 Compile list of discrepancies and open corrective maintenance work task(s) to make the repair(s)
0.166 x x x
Quarterly 1.293
Semi-Annually 1.293
Annually 1.293
3/8/23, 3:52 PM PMTL D3065100195001
https://usaf.dps.mil/teams/10758/PMTL/Module/PMTL Details.aspx?EID=245# 1/1
Equipment Type: D3065100195001
Component: Variable Frequency Drive
Equipment Component As Of: 05/01/2015
1 Collect maps, communication equipment, tools, safety equipment 0.044 x
2 Check for excessive vibration, noise, overheating, etc. 0.022 x
3 Disconnect Power (wait for DC capacitor to discharge, refer to manufacturer manual, approx 5 mins)
0.085 x
4 Check and tighten loose electrical wiring and connections, inspect for burned, pitted, or corroded connections
0.120 x
5 Vacuum dust and dirt from heat sink fins (blow with air if needed) 0.120 x
6 Clean airbox and change air filter as needed 0.200 x
7 Fill out maintenance checklist and report deficiencies 0.167 x
Annually 0.758
3/8/23, 3:53 PM PMTL D3095122195001
https://usaf.dps.mil/teams/10758/PMTL/Module/PMTL Details.aspx?EID=249# 1/1
Equipment Type: D3095122195001
Component: Air Compressor, Rotary Screw, 5 to 40 H.P
Equipment Component As Of: 10/01/2015
1 Collect maps, communication equipment, tools, safety equipment
0.044 x x x
2 Perform pre-operational check of compressor system and adjust as required
0.221 x x x
3 Check motor for excessive vibration, noise and overheating; lubricate components
0.039 x x x
4 Remove and clean package pre-filter, replace if needed 0.177 x x x
5 Clean coolers and fans 0.023 x x x
6 Clean condenser fins 0.023 x x x
7 Drain moisture from storage tank/receiver and check low psi cut-in. Test automatic drain if fitted. While draining, check discharge for indications of interior corrosion
0.046 x
8 Check the operation of the high temperature protection switch
0.030 x
9 Replace compressor oil and oil filters 0.341 x
10 Replace all filter elements and cartridges 0.300 x
11 Take oil sample for fluid analysis 0.039 x
12 Perform operation check of air compressor, to include all safeties, adjust as required
0.221 x x x
13 Clean compressor, motor, and surrounding area 0.066 x x x
14 Compile list of discrepancies and open corrective maintenance job order(s) to make the repair(s)
0.167 x x x
Quarterly 0.981
Semi-Annually 0.981
Annually 1.737
3/8/23, 3:54 PM PMTL D3095122295002
https://usaf.dps.mil/teams/10758/PMTL/Module/PMTL Details.aspx?EID=250# 1/1
Equipment Type: D3095122295002
Component: Air Compressor, Rotary Screw, over 40 H.P
Equipment Component As Of: 10/01/2015
1 Collect maps, communication equipment, tools, safety equipment
0.044 x x x
2 Perform pre-operational check of compressor system and adjust as required
0.221 x x x
3 Check motor for excessive vibration, noise and overheating; lubricate components
0.039 x x x
4 Remove and clean package pre-filter, replace if needed 0.177 x x x
5 Clean coolers and fans 0.023 x x x
6 Clean condenser fins 0.023 x x x
7 Drain moisture for storage tank/receiver and check low psi cut-in. Test automatic drain if fitted. While draining, check discharge for indications of interior corrosion.
0.046 x x x
8 Check the operation of the high temperature protection switch
0.030 x
9 Replace compressor oil and oil filters 0.500 x
10 Replace all filter elements and cartridges 0.400 x
11 Take oil sample for fluid analysis 0.039 x
12 Perform operation check of air compressor, to include all safety devices; adjust as required
0.221 x x x
13 Clean compressor and surrounding area 0.066 x x x
14 Compile list of discrepancies and open corrective maintenance job order(s) to make the repair(s)
0.167 x x x
Quarterly 1.027
Semi-Annually 1.027
Annually 1.996