1. what is access like; are there any stairs or obstacles that we have to maneuver?

The UPS is located in Room 102A on the main floor; no stairs (see attached schematic). No permanent obstacles exist. Room 102A has ample space for installation. The reception desk that sits outside of the room allows 36" of width clearance to the room. The current components (2) measure 31"D x 27" W x 71"H and 31x31x71, respectively.

Power Quality

Technical Data Sheet

Digital Energy™ SG Series (50-80kVA)

[Ci ::1;,1 :I �.J·�l!ltf·11··� ,.,.,-,, ,-,= _i>--1,t"·� . . -�

Topoloqy True On-line double conversion Nominal output power at PF - 0.7 lag. to 0.8 lag. kVA �"''""' :r.ill;!IJ:'l

System efficiency 100% load, 0.8 PF: % 91.8 92.0 50% load, 0.8 PF: % 92.2 92.5

Heat rejection at 100% load, 0.8PF and charged battery BTU/hr 12,201 19,005 kW 3.57 5.56

Cooling Air (77°F - 86°F / 25° C - 30° C) CFM 544 847 Audible noise level (at 5 ft) dB(A) 60 63 Fault Current Rating Operating temperature range UPS: 32°F - 104°F (0°c - 4o•q

Battery: 68°F - n°F (20°c - 2s0c) (Note: Higher temperatures shorten battery life)

Storage temperature range UPS: s°F - 122°F (-1 s•c to +so0c) Battery : 32°F - 104°F (0°c - 40°c) (VRLA) Storage time is 6 months at 77°F (25°C)

(Note : Higher temperatures reduce battery storage time) Relative humidity 0-95%, non-condensing Maximum altitude Without derating : 3281 ft (no derating)

With derating : 4921 ft/-5% 6562ft/-9% 8202ft/-14% 9843ft/-18% Enclosure Type: Indoor (IP20) and NEMA PE 1

Safety: Internal dead front construction Cooling: Forced Air (Redundant Fans)

Color: White (RAL 9010) Installation Rigging: Suitable for handling by forklift

Mounting: Floor mounting holes provided Installation and maintenance access : Front access required for normal maintenance

Conduit Access Top and Bottom standard Standards UL 1778, IEC 62040, IS09001, FCC Class A Optional Electrostatic discharge immunity 4kV contact/ 8kV air discharqe Configuration Standard: Stand-alone

Optional: RPA ™ - up to 8 units may be paralleled in any combination for redundancy or capacity

GEA-02021 (Rev 5, 1117106) Page 1 of 3 SG Series (50-BOkVA)

Confi uration

Input Voltage:

Frequency:

Power factor :

Inrush current:

Power walk-in :

Output Voltage Tolerance :

DC ripple voltage :

DC ripple current :

Nominal input (100% load) Current[A):

(0.8 PF load. fully chrg'd bat.) kVA:

kW:

Maximum input (100% load) Current[A):

(0.8 PF load, max. chrg current) kVA:

kW:

Max. charge current 0.8 PF load:

Out ut Isolation transformer

Out ut waveform

Output voltage tolerance Static:

Load step 0% - 100% - 0% :

Load step 0% - 50% - 0% :

100% unbalanced load Ph-N):

Output voltage distortion 100% linear load :

100% non-linear load ( er IEC 62040 :

Crest factor capability

Out ut neutral ratin Phase displacement 100% balanced load:

100% unbalanced load:

Output frequency Free running :

S nchronized with utili Overload capability (on inverter) r I(., I l

Power Quality

Six th ristor, three hase brid e

480VAC, 3-phase, 3 wire + ground (NOTE 1)

+/-15% ; (no battery discharge at -20%)

60Hz, +/-10% (54-66Hz)

0.8 lagging (typical)

Limited by soft-start circuit

30 seconds (Adjustable)

+/-1%

104.0

80.8

15 25

Lead-acid or NICd, VRLA or flooded

240 lead-acid

540VDC

396VDC ad·ustable

1 O times the dischar e time

Standard

True sine wave

+/-1%

+/- 3%, recovering to within +/-1% in 1 cycle

+/-2%, recovering to within +/-1% in 1 cycle

+/- 3%

2% THD maximum

3% THD maximum Greater than 3:1

200%

120°+/-1%

120°+/- 2%

60Hz, +/- 0.01 %

+/- 4% ad·ustable from 57.6Hz to 62.4Hz

125% at 0.8 PF for 10 minutes

150% at 0.8 PF for 60 seconds l

Short circuit capability (on inverter) 700% of rated current for first 1.2 ms, followed by

220% for 100 ms, electronicall limited

NOTE 1: The Bypass input must be 480V/277V, 3-Phase, 4-Wire, WYE, plus ground, fed from a grounded

WYE electrical system.

GEA-D2021 (Rev 5, 11n/06) Page 2 of 3 SG Series (50-80kVA)

Power Quality

[�:if ·- ··:'ir"'"fi<a',,�-.;,;,:.¢:-�•:i'\"''�t :i;z-1£ . . .,�,>��-.::;t.r� i(si!:, �xj••' .,.?,;,;-, :u ·,,,;.;r·--�.,;·.�,1 .!..;��_: ... :�� �..-_ �-;...�.1..�.u;1,,f. • .. , I .;.�-,•,, ... ! .. t:_t�j

Input confiquration Primary components

Transfer limits Overload capability (on bypass)

Short circuit caoabilitv (on bvpass)

Alarm contacts (voltage-free) Standard:

Optional:

Serial communication Input signals

GEA-02021 (Rev. 5, 1117/06)

Common with rectifier (default) or dual input Full load rated static switch Back feed protection Internal maintenance bypass +/- 10% of nominal output voltaqe (adjustable)

110% continuous 200% for 5 minutes 1000% for 1/2 cvcle (non-reoetitive)

6 user defined contacts (form 'C')

12 user defined contacts (form 'C') (23 selectable siqnals include aux. lnouts 1 & 2l

RS-232

Emergency Power Off (user supplied N.C. contact)

Aux. input 1 •(default= On Generator) Aux. input 2 •(default= not defined)

• Status displaved on LCD panel

Page 3 of 3 SG Series (50-80kVA)

UPS QA
QA CFI-FH Drawings_CFI-FL1
QA Salient Characteristics