SOW_Generator_Maintenance_7-5-17.pdf
PDF 171 KB Posted
- Attached to
- Generator Maintenance Services Federal contract opportunity
- Solicitation number
- W52P1J-18-T-3006
About this file
Statement of Work (SOW) 7-5-17
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| W52P1J-18-T-3006_0003.pdf | ||
| W52P1J-18-T-3006_0002.pdf | ||
| SOW-Generator_Maintenance-Rev_1-dtd12-18-2017.pdf | ||
| W52P1J-18-T-3006_0001.pdf | ||
| W52P1J-18-T-3006_Solicitation.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
STATEMENT OF WORK
BLUE GRASS ARMY DEPOT GENERATOR MAINTENANCE & REPAIRS
Date: July 5, 2017
The Contractor shall provide all labor, materials, equipment and supervision required to perform maintenance and repairs for various makes and models of generators (includes all aspects of the generator operation and natural gas/diesel/propane engines) and uninterruptable power supplies (UPS) at the Blue Grass Army Depot (BGAD) in accordance with the following:
ANNUAL GENERATOR SERVICE
Generator sets are to have one PM (preventative maintenance) services performed per year at 12-month intervals. Each generator set is to have a complete inspection to include measurement of output and a written report submitted to the Contracting Officer after each annual inspection. Additionally, the Contractor shall provide maintenance records for all services provided for each generator, portable generator, and UPS/UBS system annually. Report is due no later than 15 days after service and/or inspection of each generator, the contractor shall provide any reports, a list of recommended repairs, if any, and the estimated cost of the proposed repair.
No repairs, excluding requirements identified in scheduled services, may be performed without prior approval from the Contracting
Officer/COR. The first annual service shall commence within 30 days of contract award and be completed no later than 60 days from contract award. The following annual service provided the option year is exercised shall be conducted one year after the original plus or minus 15 days from the date of the first annual service. See the “Generator List” for location, size and type of generator.
Annual service shall include engine oil and filter change, fuel filter change, changing the antifreeze with a mixture that ensures protection to -25°F, lubricating all lube points, load test of battery, adjusting all belts, inspecting hoses, replacing any necessary hoses, clean and service batteries, check voltage and record, check battery charger, check engine heater, block heater hoses and check for any leaks. Contractor shall also test run generators under load for 30 minutes for those denoted “Load Test” on the generator list. Load testing of generators shall only be performed on a Friday during the work week. No other day is authorized to have load tests performed without prior approval from the Contracting Officer/COR. Annual service shall also include inspection of automatic transfer switch, voltage sensors and condition of trickle charger. Contractor shall inspect automatic transfer switch to verify generator is performing a weekly self-test properly. Gas pressure on LPG and NG units shall be checked along with cleaning regulator and vents during the annual service. Changing the coolant filter and flushing the cooling system shall be performed once during the length of contract (at one of the annual services) and no more than once every three years. Ensure that the transfer to backup power will occur.
The total amount of time allocated to complete annual services once the cycle has begun is 30 days.
Battery Changes
During the term of the contract, the contractor shall replace all generator batteries that are more than 3 years old (as determined from the battery’s identifying information/data plate) with a new heavy duty battery in kind. Contractor shall submit battery specifications to the Contracting Officer/COR for approval prior to installation to ensure this requirement is met.
The labor and materials for replacing/changing batteries shall be charged against the time and materials line item of the contract. The contractor shall be responsible for the proper disposal of all batteries changed as a result of this contract. All old batteries shall be properly removed from Blue Grass Army Depot. No batteries or hazardous materials may be stored on the installation. The
Contractor shall provide environmental, health and safety training to ensure compliance with all federal, state, local and installation laws or regulations. Contractor shall also provide to the Contracting Officer/COR all MSDS sheets regarding all chemicals/materials to be used in conjunction with this contract upon contract award. The Contractor shall coordinate the dates services are scheduled in advance with the Contracting Officer/COR. Preventive maintenance services will be conducted during normal hours of operation, whenever possible. The generators covered by this statement of work are listed on the attached worksheet. An additional line item is included for breakdown repairs (time & materials) which are not considered a part of routine preventive maintenance. There is no minimum amount guaranteed, only actual expenses and time may be billed under this line item and the contractor must supply documentation for labor and materials charged against this line item with their invoice.
MONTHLY GENERATOR REPORTING
The Contractor shall provide to BGAD Contracting monthly generator reports providing hour meter readings from the non-resettable hour meter on each unit as well as the date and time that each reading was recorded. Monthly reports are required for all installation generators and portable generators. Portable generator readings shall be reported regardless of whether they are in service or not.
These inspection reports shall be submitted to the Contracting Officer located in building S-14.
PORTABLE GENERATOR MONTHLY SERVICE
Portable generators shall be inspected, test-started and load-tested once a month with an annual service of once per year. Monthly inspections shall include assuring all of the fluid levels are correct, that batteries are in good working condition and fully charged, and all generator systems are functioning correctly. Annual service shall be accomplished at the location the generator may be in use on the installation.
ROUTINE/URGENT/EMERGENCY REPAIRS
Should a generator or UPS system experience mechanical/electrical failure, the Contracting Officer/COR will determine whether the repair of the failed generator or UPS system is routine, urgent or an emergency. If repair of the failed generator or UPS system is considered routine, the Contractor will be notified and shall be on-site within 3 days from the day of notification to repair the equipment. If repair of the failed equipment is considered urgent, the Contractor will be notified and shall be on-site within 24 hours to make repairs. If repair of the failed generator or UPS system is considered an emergency the Contractor will be notified and shall be on-site within 2 hours to repair the generator or UPS system. Contractor shall maintain a record of all repairs for each generator/UPS system. Records of repairs shall be submitted annually to BGAD Contracting in conjunction with the annual reports.
SCHEDULED MAINTENANCE
Contractor is to provide Contracting Officer/COR with a minimum 24-hour advance notice prior to performing scheduled services.
CURRENT INVENTORY:
The table below outlines the current list of generators and UPS systems in service at Blue Grass Army Depot for services under this contract. This list may change throughout the life of the contract to include new systems, replacement systems, and removal of systems.
Location Manufacturer Model #
Year of Mfg SN Fuel Type
Load Test Required
Bldg S-1 Olympian 98A02118S unknown 2041296 Natural Gas Yes
Bldg S-10 Olympian G12U3 unknown 118717/01 Natural Gas Yes
Bldg S-11 Olympian G20F3 unknown OLY00000TNGF00627 Natural Gas Yes
Bldg 165 Olympian G50F3 unknown OLY00000HNFS02531 Natural Gas Yes
Bldg 218 Olympian G100F1
2001 G0435A/001 Natural Gas Yes
Bldg 219 Kohler 80R02J81 unknown 290793 Diesel Yes
Bldg 213 Olympian G60F1
2000 F0827A/001 Natural Gas Yes
Bldg S-43 Olympian G75F3S
2004 OLY00000ANFC01363 Natural Gas Yes
Bldg 571 Olympian G100F3 unknown OLY00000TNFC02427 Natural Gas Yes
Bldg 1660 Caterpillar G3406 unknown unknown Natural Gas Yes
Bldg 31930 Olympian G80F3 unknown OLY00000ENFC01089 Natural Gas Yes
Gate 12/Bldg TBP01 Caterpillar C4.4 unknown CAT00C44KD4B01913 Natural Gas Yes
Lake Vega Dam Olympian
G130LG2 -
130KW
2009 unknown Natural Gas Yes
F Area Cable Hut 80 Caterpillar/Olympian G60F3
2002 OLY00000JNFC00726 Natural Gas Yes
Cable Hut 75 Olympian G10U3S
2001 G0436A/001 Natural Gas Yes
LP 54/Cable Hut 79 Olympian G10U3S
2003 OLY00000KNGZ00574 Natural Gas Yes
Bldg 212/Cable Hut 76 Olympian G10U3S
2003 OLY00000PNGZ00573 Natural Gas Yes
Bldg S-56 Olympian G60F3
2004 OLY00000ENFC0205 Natural Gas Yes
Bldg 230 (Waste Water Treatment Plant) Olympian G130LG2
2014 OLY00000GXC02921 Natural Gas Yes
Gate R-2 (Truck Gate) Olympian G75F3S
2004 OLY00000CNFC01918 Natural Gas Yes
East of Intersection Rt-120 and Rt-3 (Lift Station) Olympian G3406NA-201
2005 CBM00216 Natural Gas Yes
East of Intersection Rt-12 and Rt- 3 (Lift Station) Olympian G30F3-40.2
2550 OLY00000VNFS02153 Natural Gas Yes
North of Rt-2 and East of Olympian G30F3-40.2
2005 OLY00000HNFS02318 Natural Gas Yes
CLA (Lift Station)
Bldg 1159 Olympian G45F3S
225 OLY00000HNFS01685 Natural Gas Yes
Gate R-1 Olympian G35F3S
2007 OLY00000VNGC00917 Natural Gas Yes
Bldg 52770 Olympian GL100LGZ
2009 OLY00000GXC00313 Natural Gas Yes
Water Plant (Bldg 228) Olympian G125G1
2008 OLY00000ENGG00675 Natural Gas Yes
Main Gate (behind S-49) Kohler 50REOZJC
2009 2252824 Diesel Yes
Gate 3 Kohler 50REOZJC
2009 2252823 Diesel Yes
Portable Generator Olympian XQ60-6
2010 16MPF10248D053446 Diesel No
Generator Olympian XQ100
2010 16MPF11228D052231 Diesel No
Generator Olympian XQ100
2010 16MPF11298D052338 Diesel No
Gate 12 ACB Caterpillar CAT125-6 unknown CAT0066CN6D00365 Natural Gas Yes
Intersection of Rte 12 and Rte 13 at large Antenna Generac SG0035AG035
2014 912921 Natural Gas Yes
Bldg 31960 Olympian G10U35 unknown OLY00000ENGZ00908 Natural Gas Yes
Bldg 1661 Olympian G80LG2
2012 GXCO1554 Natural Gas Yes
Bldg 31910 Olympian G150LG2
2011 GXC01507 Natural Gas Yes
Bldg 50628 Caterpillar DG50-2
2016 CAT0DG60KNB500126 Natural Gas Yes
END OF SCOPE OF WORK
Bldg 31930 Eaton UPS system 20 kVa 9355-30
? 314KXX01 N/A Yes
Bldg 1660
10 kVa 9155-10
? BE451FBB03 N/A Yes
Gate 12 ACB Ametek UPS system
15 kVa 3DPP015
2007 S923370111 N/A Yes
Bldg S-18
18 kVa 93E-60/40
2014 41610140176 N/A Yes
Bldg 218 APC UPS system
120 kVa 0G-PDRPP
2009 PI0950130071 N/A Yes
Bldg 218 APC UPS system
80 kVa AP9215RM
2008 5A0836T01504 N/A Yes
File details come from the government source that posted it.