B08 - Attachment 0003 - 45ft Steel Utility Pole Specs - Purchase Description Qty 20 (1).pdf
PDF 133 KB Posted
- Attached to
- Steel Utility Poles
- Solicitation number
- W519TC-24-Q-2013
About this file
This document includes specifications for the purchase of 45-foot steel utility poles. The Army Materiel Command Contracting Command Rock Island Arsenal is soliciting offers for 20 Class 3 steel utility poles that are 45 feet in length. The poles must include plastic top caps, posi-ground butt plates, zinc coated grounding inserts, and a hole pattern as required. They also require TriFORCE polyurethane ground barrier protection from 1 foot above the ground level to the bottom of the pole, based on a burial depth of 10% of the pole length plus 2 feet, including the butt plate, at 20 mils thickness. Grey UV protection is required from 1 foot below the ground level to the top of the polyurethane barrier. Identification tags with the manufacturer, pole class and year of manufacture must be included. Grounding locations and full embedment below grade protection are specified. The solicitation number for this opportunity is W519TC-24-Q-2013.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Class 3 – 45ft Steel Utility Poles
Qty. 20
Class 3- 45’Distribution Pole Hole Lay-out
Distance from Orientation in Grounding or hole Pole Top Degrees size
4"
0-180
11/16
2 6" 90-270 11/16 3 12" 0-180 11/16 4 13" 90 (rivnut) 1/2 (rivnut) 5 16" 0-180 11/16 6 36" 0-180 11/16 7 42" 90-270 11/16 8 43" 90-270 11/16 9 44" 0-180 11/16
10 52" 0-180 11/16 11 53" 90-270 11/16 12 54" 90(rivnut) ½ (rivnut) 13 60" 0-180 11/16 14 7611 0-180 11/16 15 97" 90-270 11/16 16 80" 90 (rivnut) ½ (rivnut)
Misc. Notes:
Steel Poles Include:
Plastic top cap Posi-Ground butt plate
(2) Zinc coated grounding inserts Hole pattern as required TriFORCE polyurethane ground barrier protection 1ft above ground level to bottom of pole based on a burial depth of 10% of pole length plus 2ft, including butt plate, all at 20 mils. Grey UV protection 1ft below ground level to top of polyurethane.
zinc coated pole class 3
1- Grounding location will be 2ft. above groundline and 2ft below pole top (Standard 1/ 2" rivnut)
2- Full Embedment below grade protection
3- No Climbing holes
6- Must include ID tag w/ Manufacture, Pole class and Year of manufacture
Class 3- 45’Distribution Pole Hole Lay-out