ACS Upgrade Details.pdf
PDF 67 KB Posted
- Attached to
- DSX Access Control System
- Solicitation number
- W50S8Z-20-Q-0001
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Bldg. Room Wall or Door
Action Additional Specs/Info Parts Need Estimate
243 22 E Upgrade ACS DSX Host Computer to SQL server with Windows 10, DSX Rev 6, Microsoft Word and Excel
1‐ Ensure the Wi‐Fi capability is not installed and the system will not be able to connect to the internet.
One Server
243 22 E 2‐Backups to an external hard drive you provide One External Solid State Hard Drive
243 22 E 3‐ Maintain communication to four remote controllers using existing SNE2000 extenders and one controller via existing wiring. (Can use existing SNE extenders)
243 22 E 4‐ Configuration, cardholder data, and pictures are required to be transferred to the server
243 22 E 5‐ Ensure client in Bldg. 209 is connected to new ACS Server and two additional clients added (Bldg 243, Room 21 and Bldg 242, Rm 4).
243 22 E 6‐ Must have four HDMI video outputs.
243 22 E 7‐ Communication paths from the server to the controller must be encrypted meeting current FIPS standards
243 22 E 8‐ Must utilize the existing badge printer 243 22 E 9‐ Full system check required with optional repair cost
243 22 E 10‐ Provide training on system changes and configuration (2 hours).
243 22 E 11‐ Note: The current cabinet, UPS, and camera can be used with the new server.
243 21 E Install DSX Client computer compatible with new DSX Server, (Can use existing monitor, keyboard, and Mouse) (Must be Win 10 with Microsoft Word and Excel.
1‐ Ensure the Wi‐Fi capability is not installed and the system will not be able to connect to the internet. It will be connected via a CAT6 cable to the Server
One Client Computer
243 21 E 2‐ Must connect via existing CAT6 cable which runs directly the area of the new DSX Server in Bldg 243, Room 22.
243 12 Door Install a maglock (min 600lb), one proximity card reader (Indala capable), and one green illuminated exit button.
1‐ Card reader and exit button need to disable the maglock for 5 seconds upon use. Wiring is preferred to be in the wall. If not feasible, then in conduit (flex, Panduit, EMT, etc.)
1 Maglock, 1 Prox Reader, 1 Exit Button, wires, Conduit/Panduit
243 14 Door Install a maglock (min 600lb), one proximity card reader (Indala capable), and one green illuminated exit button.
1‐ Card reader and exit button need to disable the maglock for 5 seconds upon use. Wiring is preferred to be in the wall. If not feasible, then in conduit (flex, Panduit, EMT, etc.)
1 Maglock, 1 Prox Reader, 1 Exit Button, wires, Conduit/Panduit
243 20 Door Install a maglock (min 600lb), one proximity card reader (Indala capable), and one green illuminated exit button.
1‐ Card reader and exit button need to disable the maglock for 5 seconds upon use. Wiring is preferred to be in the wall. If not feasible, then in conduit (flex, Panduit, EMT, etc.)
1 Maglock, 1 Prox Reader, 1 Exit Button, wires, Conduit/Panduit
243 103 Door Install a maglock (min 600lb), one proximity card reader (Indala capable), and one green illuminated exit button.
1‐ Card reader and exit button need to disable the maglock for 5 seconds upon use. Wiring is preferred to be in the wall. If not feasible, then in conduit (flex, Panduit, EMT, etc.)
1 Maglock, 1 Prox Reader, 1 Exit Button, wires, Conduit/Panduit
243 104 Door Install a maglock (min 600lb), one proximity card reader (Indala capable), and one green illuminated exit button.
1‐ Card reader and exit button need to disable the maglock for 5 seconds upon use. Wiring is preferred to be in the wall. If not feasible, then in conduit (flex, Panduit, EMT, etc.)
1 Maglock, 1 Prox Reader, 1 Exit Button, wires, Conduit/Panduit
243 106 Door Install a maglock (min 600lb), one proximity card reader (Indala capable), and one green illuminated exit button.
1‐ Card reader and exit button need to disable the maglock for 5 seconds upon use. Wiring is preferred to be in the wall. If not feasible, then in conduit (flex, Panduit, EMT, etc.)
1 Maglock, 1 Prox Reader, 1 Exit Button, wires, Conduit/Panduit
243 20 N Install DSX Cabinet with DSX 1042, 1040PDM, 12VDC batteries, and any other required equipment needed to connect the new door controls (Rooms 12, 14, 20, 103, and 106).
1‐ Space is available for cabinet on the North wall's lower section
1 Cabinet (locking), 3 DSX‐1042 cards, 1 DSX‐ 1040PDM, 1 DSX‐1040CDM, Flex conduit
243 20 N 2‐ 24h battery backup is required for all devices. 2 each 12VDC 12mAH Batteries 243 20 N 3‐ Cabinet tamper must monitored. Tamper switch 209 7 E Replace existing DSX Client computer with new one compatible with new DSX Server, (Can use existing monitor, keyboard, and Mouse) (Must be Win 10 with Microsoft Word and Excel.
1‐ Ensure the Wi‐Fi capability is not installed and the system will not be able to connect to the internet.
One Client Computer
209 7 E 2‐ Must connect via existing SNE2000 Extenders on Room 7's DSX controller which connects to the DSX Server in Bldg
209 11 Door Replace existing door electric strike controls with a maglock (min 600lb), and one green illuminated exit button.
1‐ Card reader and exit button need to disable the maglock for 5 seconds upon use.
1 Maglock, 1 Exit Button, wires for exit button
209 12 Door Replace existing door electric strike controls with a maglock (min 600lb), and one green illuminated exit button.
1‐ Card reader and exit button need to disable the maglock for 5 seconds upon use.
1 Maglock, 1 Exit Button, wires for exit button
209 14 E door Replace existing door electric strike controls with a maglock (min 600lb), and one green illuminated exit button.
1‐ Card reader and exit button need to disable the maglock for 5 seconds upon use.
1 Maglock, 1 Exit Button, wires for exit button
209 14 E door 2‐ Existing keypad needs swapped with exit button and relocated to inside room 14 on East wall
209 14 W door Install a maglock (min 600lb), one proximity card reader (Indala capable), and one green illuminated exit button.
1‐ Card reader and exit button need to disable the maglock for 5 seconds upon use. Wiring is preferred to be in the wall. If not feasible, then in conduit (flex, Panduit, EMT, etc.)
1 Maglock, 1 Prox Reader, 1 Exit Button, wires, Conduit/Panduit
209 7 Door Reconfigure existing exit button release time to 5 seconds. 1‐ Button has to be pushed in to release the mag lock.
New wire may be run in the existing conduit to the controller in Room 19.
Wire, flex conduit
209 19 Door Reconfigure existing exit button release time to 5 seconds. 1‐ Button has to be pushed in to release the mag lock.
New wire may be run in the existing conduit to the controller in Room 19.
Wire, flex conduit
209 20 N Install DSX Cabinet with DSX 1042, 1040PDM, 12VDC batteries, and any other required equipment needed to connect the new door controls (Rooms 14W and 20) with a future expansion of an additional DSX‐1042 card
1‐ Space is available for cabinet above mezzanine 1 Cabinet (locking), 2 DSX‐1042 cards, 1 DSX‐ 1040PDM, 1 DSX‐1040CDM, Flex conduit
209 20 N 2‐ 24h battery backup is required for all devices. 2 each 12VDC 12mAH Batteries 209 20 N 3‐ Cabinet tamper must monitored. Tamper switch 242 4 E Install DSX Client computer compatible with new DSX Server, (Can use existing monitor, keyboard, and Mouse) (Must be Win 10 with Microsoft Word and Excel.
1‐ Ensure the Wi‐Fi capability is not installed and the system will not be able to connect to the internet.
One Client Computer
242 4 E 2‐ Must connect via existing SNE2000 Extenders on Room 7's DSX controller which connects to the DSX Server in Bldg
242 7 Door Reconfigure existing exit button release time to 5 seconds. 1‐ Button has to be pushed in to release the mag lock.
New wire may be run in the existing conduit to the controller in Room 7.
Wire, flex conduit
File details come from the government source that posted it. Updated .