This document contains questions and answers regarding a solicitation for repairing fire protection systems at a base. The solicitation seeks replacement of inline strainers for high expansion foam generators that were identified as partially blocked in inspection reports provided to potential offerors. It also requires replacing a post indicator valve that an inspection report indicated was failed and seized. The opportunity is a total small business set-aside with a NAICS code of 236220 and size standard of $39.5 million. The project value is estimated between $250,000 and $500,000, and Davis Bacon wage rates apply. Funding may become available by September 30, 2022, at which time the government anticipates making an award if prices are within an awardable range. The soliciting agency is the Department of the Army National Guard.

View the file

Other files

Show all 13

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Questions & Answers for Solicitation No:

W50S8V-22-B-0005

Repair Fire Protection Base-Wide 11 July 2022

Questions:

1. To properly quote repairs, please provide most recent inspection report(s). This will allow determination of all components associated with system, as well as, size, part number etc.)

a. The inspection reports (total of 3) have been uploaded to SAM.gov Contract Opportunities. These reports shall be used for reference only; the Government is not liable for any misinformation contained within these reports.

2. Per the manufacturer, the inline strainers for the high expansion foam generators should never need replacing. Please provide information as to why these needed replaced.

a. The Government has identified complete or partial blockages among multiple strainers. The strainers listed in the Statement of Work (SOW) shall be replaced.

3. SOW 3.7.4 – Upon visual inspection at site-visit, the indicator lens is unreadable. Can valve be repaired (fraction of cost to replace) or must it be replaced as per SOW?

a. Inspection report indicates PIV valve failed and is seized. Contractor shall replace in accordance with Statement of Work (SOW).