The scope of work highlights the following:
*The contractor is to furnish and install a new 200Amp sub-panel in the same location of sub-panel EPA.
* Contractor is to furnish and install new 200Amp sub-panel in the same location of sub-panel EPB. (80amp existing)
If we are to furnish a new 200Amp Main Breaker for EPA panel and then run a 200 amp feeder to the new EPB sub panel, we would not have enough capacity to power the existing loads in the EPA panel.
Question: Shouldn't' we be upgrading the EPA panel above 200amps to handle the existing loads there and the new 200 amp sub-panel downstream?
Answer: Install 200 AMP panel per SOW.