B7 - Q and A 07 July 2020.docx

DOCX document 13 KB Posted

Attached to
Fire Alarm System Repair Federal contract opportunity
Solicitation number
W50S7G20B0002
Issued by
Department of the Army National Guard

View the file

Other files for this federal contract opportunity

Other files attached to Fire Alarm System Repair, newest first.
File Type Posted
C4 - Abstract 1419 - Construction.pdf PDF
Bid Opening Location Map.pdf PDF
B8 - Q and A 09 July 2020.docx DOCX document
B7 - Pre-bid Conference Minutes.pdf PDF
B7- Pre-Bid Conference PP.pptx PPTX presentation
B7 - Pre Bid-Proposal SIGN IN SHEET.doc DOC document
B8 - W50S7G20B0002 Fire Alarm Solicitation Amendment 2 Final.pdf PDF
B8 - W50S7G20B0002 Fire Alarm Solicitation Amendment 1 Released.pdf PDF
B8 - W50S7G20B0002 Fire Alarm Solicitation 20200612.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Fire Alarm Repair Question and Answer’s07 July 2020
1.Q: Real Property worksheet required as specified in the pre-bid slides?
A: No Real Property Worksheet will be needed for this project.
2.Q: Is any other color of strobe required besides red?
A: No, only strobes for Fire Alarm required.
3.Q: Is there a preferred panel?
A: No preferred Mass Notification Panel.
4.Q: Can you repair the panel as opposed to replace.
A: No, requirement is to replace the current panel in Building 3.
5.Q: Does new conduit and all existing used need to be red?
A: Only new conduit run to the projects purpose needs to be red, if existing conduit is used then leave as is.
6.Q: If we have to schedule around Hangar openings, will we still be required to get the project done in the period of Performance specified?
A: If accomplishing the project within the POP specified is delayed due to the Government the awarded contractor will be allowed more time.
7.Q: Do the MUA’s 1, 2 and 3 in the Weld shop require detectors?
A:
8.Q: How many air handlers are there over 200 cfm in the project locations?
A: