19Q0293_AMENDMENT.pdf
PDF 333 KB Posted
- Attached to
- POWER MONITOR
- Solicitation number
- W25G1V19Q0293
About this file
SALIENT CHARACTERISTICS ADDED FOR POWER MONITOR
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 19Q0293.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ACC-APG, TOBYHANNA DIVISION
ROBYN LAYTON 570-615-7056
ROBYN.L.LAYTON.CIV@MAIL.MIL
TOBYHANNA PA 18466-5100
W25G1V9072011Q
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.
15A. NAME AND TITLE OF SIGNER (Type or print)
30-105-04EXCEPTION TO SF 30
APPROVED BY OIRM 11-84
STANDARD FORM 30 (Rev. 10-83) Prescribed by GSA
FAR (48 CFR) 53.243
The reason for this amendment is to add salient characteristics that w ere omitted from the original solicitation. All other terms and conditions w ill remain the same. Please send all responses no later than 6/18/19 5:00pm EST.
1. CONTRACT ID CODE PAGE OF PAGES
J 1 4
16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)
16C. DATE SIGNED
BY 13-Jun-2019
16B. UNITED STATES OF AMERICA15C. DATE SIGNED15B. CONTRACTOR/OFFEROR
(Signature of Contracting Officer)(Signature of person authorized to sign)
8. NAME AND ADDRESS OF CONTRACTOR (No., Street , County, State and Zip Code) X W25G1V19Q0293
X 9B. DATED (SEE ITEM 11)
15-May-2019
10B. DATED (SEE ITEM 13)
9A. AMENDMENT OF SOLICITATION NO.
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
X The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offer X is extended, is not extended.
Offer must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended by one of the following methods:
(a) By completing Items 8 and 15, and returning 1 copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;
or (c) By separate letter or telegram which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN
REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
12. ACCOUNTING AND APPROPRIATION DATA (If required)
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS.
IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.
A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE
CONTRACT ORDER NO. IN ITEM 10A.
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation date, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(B).
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER (Specify type of modification and authority)
E. IMPORTANT: Contractor is not, is required to sign this document and return copies to the issuing office.
14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
10A. MOD. OF CONTRACT/ORDER NO.
2. AMENDMENT/MODIFICATION NO. 5. PROJECT NO.(If applicable)
6. ISSUED BY
3. EFFECTIVE DATE
13-Jun-2019
CODE
ACC-APG, TOBYHANNA DIVISION
11 HAP ARNOLD BLVD
TOBYHANNA PA 18466-5100
W25G1V 7. ADMINISTERED BY (If other than item 6)
4. REQUISITION/PURCHASE REQ. NO.
CODE W25G1V
FACILITY CODECODE
EMAIL:TEL:
W25G1V19Q0293
SECTION SF 30 BLOCK 14 CONTINUATION PAGE
SUMMARY OF CHANGES
SECTION SF 30 - BLOCK 14 CONTINUATION PAGE
The following have been added by full text:
SALIENT CHARACTERISTICS
General description:
A power quality and energy instruments monitor, record, and analyze critical aspects of an electrical distribution system—so you can optimize energy utilization, process performance, and cost. This premier power quality instrument serves several essential functions: • Highly accurate digital meter, to measure and log current, voltage, power factor, and other comprehensive power metering parameters • Circuit monitoring device, watching for harmonics, voltage transients, and other potentially harmful power events • Automatic trigger settings • Alarm system and sending notifications and emails to selected people and power management software when conditions exceed established tolerance ranges • Power quality analyzer, capturing waveforms and other information to support in-depth statistical analysis
• Internet-enabled power quality and energy meter with comprehensive power measurement and integrated quality analysis • Use a standard Web browser to surf to the meter and analyze waveforms, trend, ITIC graphs directly on the meter or LCD display • Capture waveforms at a high speed of 6 MHz (six samples every millionth of a second) • Embedded information technology performance curve (ITIC) analyzes the power quality events that have occurred and determines the level your sensitive IT equipment can sustain without disruption and damage • Open protocols allow flexible third-party integration to BMS and other PQ systems Features • Embedded Web server: see and analyze waveforms, trends, harmonics directly in your Web browser or LCD meter graphic display • Automatic power quality analysis and trigger setting with available ITIC performance curve: detect and capture sags, swells, transients, harmonics, flickers • Accurately detect fast transients by assessing circuit activity at very high sampling rates (up to 100,000 samples per cycle) • Comprehensive power, energy, and demand measurements • Voltage, current: per phase minimum, maximum, average, trend graph analysis, export, print • Power: power factor, apparent, real, reactive, frequency • Energy, demand: forward, reverse, net, sum, TOU, profile, previous month-to-month, week-to-week comparisons, graph analysis, data export, print • Up to one millisecond time synchronization and event logging capability for sequence of events analysis • Get an at-a-glance view of power quality with patented power quality index gauge, statistically derived trending and red-yellow-green indicators for overall power health • Support continuous, non-disruptive monitoring with a permanently installed meter that is continuously on the job, 24 hours a day, 7 days a week, 365 days a year.
Alarm notifications are also available remotely via email.
• Uses industry-standard communication protocols to support a multitude of configurations and third-party software:
HTTP, FTP, Modbus® RTU, Modbus TCP, DNP 3.0, SNMP, SMTP, NTP, COMTRADE Metered/monitored parameters available :Voltage inputs for each channel shall allow for connection into circuits with the following parameters:
a. Input range of 600V L-L, 347V L-N direct connected.
b. PT primary input of 120 volts to 500,000 volts.
c. Nominal full-scale value of 700 volts rms.
d. Input impedance of 2 mega ohms.
e. The analog voltage input shall be converted to 4096 samples per cycle by means of a delta sigma converter and digitally filtered down to 512 samples per cycle for anti-phasing.
2. The Meter shall be capable of monitoring, displaying, and communicating the below true rms minimum information where applicable with the accuracy as indicated of read or calculated values based on 3 to 300% full scale. The Meter shall be suitable for installation in single phase, two or three wire systems or in three phase, three or four wire systems
a. AC current (amperes) in A, B and C phase, 3-phase average, Neutral (N) and Ground (G). A total of five (5) current inputs shall be provided. Accuracy of all current inputs shall be 0.05% reading, +/- 0.01% of full scale. Provide neutral and ground current transformers. The 5 ampere current inputs shall withstand 40 amperes continuous and 300 amperes for 1 second. Current transformer ratios shall be selectable.
b. AC voltage (volts) for A-B, B-C and C-A, phase average, A-N, B-N and C-N, average phase to N, and N to G. Accuracy of all voltage inputs shall be +/- 0.1% reading, +/- 0.05% maximum of full scale. Capable of metering up to 600 volt without external Potential Transformers (PTs) and up to 500 kV with appropriate PTs.
c. Auxiliary AC voltage (volts) for A2-B2, B2-C2, and C2-A2, phase average.
Accuracy of all voltage inputs shall be +/- 0.1% reading, +/-0.05% maximum of full scale. Capable of metering up to 600 volt without external Potential Transformers (PTs) and up to 500 kV with appropriate PTs.
d. Real Power (Watts), Reactive Power (vars), Apparent Power (VA), for each phase and system. Accuracy +/- 0.10% reading and +/- 0.0025% full scale.
Forward/Reverse indication shall be provided.
e. Accumulated, Incremental and conditional measurement for Real Energy (WH), Reactive Energy (VARH), Apparent Energy (VAH) for each phase and system.
Accuracy +/- 0.10% reading and +/- 0.0025% full scale. Forward/Reverse and Net difference indication shall be provided.
f. Frequency (Hz) Accuracy +/- 0.01 hertz.
g. Demand values including present, running average, last complete interval and peak for System Current (Amperes). Demand values including present, running average, last complete interval, peak and coincident with peak kVA and kW demand for System Real Power (Watts), System Reactive Power (vars), and System Apparent Power (VA).
h. Power Factor for both Displacement only 60-cycle fundamental Watts to VA and Apparent total Watts to total vars including harmonics for A, B and C phase and 3 phase average. Accuracy +/- 0.10% at unity PF and +/-0.30% at 0.5 PF.
i. Current percent Total Harmonic Distortion (THD) in A, B and C phase and N.
j. Voltage percent THD in A-B, B-C and C-A phase, A-N, B-N and C-N.
k. K-Factor (sum of the squares of harmonic currents times the square of their harmonic numbers).
l. Transformer Derating Factor (1.414 divided by the Crest Factor).
m. Crest Factor (ratio of peak current to rms current).
n. CBEMA (ITIC) curve data
o. Flicker data
p. Nines (9’s) availability data.
q. Power Quality Index
3. The Meter shall provide the following sampling capabilities:
a. A/D technology, sampling at 4096 samples per cycle.
b. Over-sampling and quantizing filtering to eliminate false signal noise.
c. ITIC representation of power events.
d. Waveform recorded at 512 standard samples
Accuracy :
• Currents: 0.05% reading +0.025% FS • Voltage: 0.1% reading +0.025% FS • Energy and demand power: 0.2% in accordance with ANSI C12.20 • Frequency: ±0.01 Hz • Power factor: • 0.10% at Unity PF • 0.30% at 0.5 PF • IEC/EN 60687, Class 0.2 and 0.5 (0.2% minimum) • ANSI C12.20 (electricity meters 0.2%)
Historical trend logging:
Meter will record historical data for graphical viewing from a local display or the embedded Web server. Graphical views of historical data support pan and zoom. There are 145 standard metering parameters logged as part of the standard meter functionality, including minimum/maximum and average for each parameter. The averages are calculated over the interval period. The minimum and maximum readings are based on 200 ms calculations. Storage capacity for standard trend plots includes all of the following intervals: • Every 5 minutes for 48 hours (2 days) • Every 15 minutes for 192 hours (4 days) • Every hour for 28 days (4 weeks) • Every 8 hours for 56 weeks • Every week for 44 months Meter base unit characteristics:
• Height: 8.88 inches (225.6 mm) max• Top/bottom clearance: 3 inches minimum • Clearance required for proper ventilation • Width: 9.56 inches (242.8 mm) max• Side clearance: 2.00 inches minimum • Clearance required for proper access to termination • Depth: 6.72 inches (170.8 mm)(max) including optional wallmounting brackets • Includes terminals and panel mounting feet •
• NEMA rating: NEMA 1, IP3Ø