This document provides details for a federal contract opportunity to renovate building 350 at Travis Air Force Base. The solicitation seeks a contractor to provide all professional services, permits, equipment, labor, tools, materials, and ancillary items necessary to renovate the building, including HVAC upgrades, upgrading bathrooms, replacing an existing water heater, upgrading electrical, constructing outside mechanical HVAC concrete pads, and relocating a flagpole. Architectural and engineering designs will be provided by the 60th Contracting Squadron of the Department of the Air Force Air Mobility Command, the contracting agency. The contractor shall be responsible for the renovation and HVAC project at building 350 as described.
View the file
Other files for this federal contract opportunity
Show all 24
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SQUARE FOOTAGES NOTED ARE BASED ON HISTORICAL
INFORMATION OBTAINED, AND THE BUILDING WAS
ORIGINALLY CONSTRUCTED IN 1999. OCCUPANCY &
CONSTRUCTION TYPES ARE NOTED BASED ON CURRENT
CODES.
OCCUPANCY TYPE:
CONSTRUCTION TYPE:
NUMBER OF STORIES:
APPROXIMATE BUILDING AREA:
BUILDING IS EQUIPPED W/ FULLY AUTOMATED SPRINKLER SYSTEM.
NOTE:
B
III-B
ONE (1)
16,615 SQ FT
ALL WORK SHALL BE IN ACCORDANCE WITH ALL CODES AND STANDARDS
NOTED AS FOLLOWS:
• INTERNATIONAL BUILDING CODE (IBC) - 2015
• NFPA 101
• INTERNATIONAL MECHANICAL CODE (IMC) - 2015
• NATIONAL ELECTRIC CODE (NEC) - 2015
• INTERNATIONAL PLUMBING CODE (IPC) - 2015
• TITLE 24, PART 6, CALIFORNIA ENERGY CODE (2016)
• ARCHITECTURAL BARRIERS ACT ACCESSIBILITY STANDARD (ABAAS)
SCOPE AREA:
BUILDING 350
BUILDING LOCATION
PREPARATION OF SEPARATE PLANS, SPECIFICATIONS AND COST
ESTIMATES FOR THE RENOVATION OF BUILDING 350.
THE WORK INCLUDES:
A. RENOVATE EXISTING RESTROOMS AND SHOWER TO BE FULLY
ADA/ABA COMPLIANT AS NOTED INCLUDING, BUT NOT LIMITED TO,
NEW WATER CLOSETS, LAVATORIES, URINALS, SERVICE SINK,
SHOWER FIXTURES, LIGHTING, AND FINISHES.
B. COMPLETE RENOVATION OF THE EXISTING MECHANICAL SYSTEM
INCLUDING ALL EQUIPMENT, DUCTWORK, DIFFUSERS, PIPING, AND
CONTROLS AS NOTED.
C. REPLACEMENT OF EXISTING WATER HEATER.
D. UPGRADE ELECTRICAL AS NOTED.
E. CONSTRUCTION OF A NEW EXTERIOR MECHANICAL ENCLOSURE
INCLUDING RELOCATION OF EXISTING FLAG POLE, ASSOCIATED
FLAT WORK AND INTERIOR CONSTRUCTION.
PROJECT LOCATION:
TRAVIS AIR FORCE BASE,
FAIRFIELD CALIFORNIA
A
C
C-38168
STEVEN
GRIST
7-31-2021
DATE
RENEWAL
RCHITECT
DESNECIL
AL I FOR
N
IA
FOETAT
S
7 FREELON ST
SAN FRANCISCO,
CA 94107
54321
1 54321
D
C
B
A
D
C
B
A
A/E INFO
T: 415.762.8388 www.aetypic.com
SEAL
SHEET OF
NAVFAC DRAWING NO.
CONTRACT NO.
EPROJECT NO.
SCALE
APPROVED
FOR COMMANDER NAVFAC
ACTIVITY
SATISFACTORY TO DATE / /
DES DRW CHK
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
DE
PA
RT
ME
NT
O
F
TH
E
NA
VY
NA
VA
L F
AC
ILI
TI
ES
E
NG
IN
EE
RI
NG
C
OM
MA
ND
N
AV
AL
F
AC
IL
IT
IE
S
EN
G
IN
EE
RI
NG
C
O M
M
AN
D
SO
U
TH
W
ES
T
NA
VA
L S
TA
TI
ON
S
AN
D
IE
GO
SA
N
DI
EG
O, C A
NO SCALE
3/
/2
9:
:0
AM
G-001
C O
VE
R
S H
EE
T
9th
R
ES
ER
VE
IN
TE
RI
OR
R
EN
OV
AT
IO
N
PR
OJ
EC
TS
BU
ILD
IN
G
0 -
C
BC
S
TR
AV
IS
A
IR
F
OR
CE
B
AS
E
D.E.
D.T. A.S.
JONNY OCHOA
N62473-16-D-1801
FA
IR
FI
EL
D, C
AL
IF
OR
NI
A
349TH RESERVE INTERIOR RENOVATION PROJECTS
BUILDING 350 - 23 CBCS
TRAVIS AIR FORCE BASE, FAIRFIELD, CALIFORNIA
NORTH
NORTH
NORTH
FINAL SUBMITTAL SET
DECEMBER 31, 2019
SHEET NUMBER SHEET NAME
MECHANICAL
M-001 MECHANICAL GENERAL NOTES
M-002 MECHANICAL LEGEND
M-003 MECHANICAL ABBREVIATIONS
M-004 MECHANICAL SCHEDULES
M-005 MECHANICAL SCHEDULES
M-006 MECHANICAL SCHEDULES
M-007 MECHANICAL SCHEDULES
M-101 MECHANICAL DEMOLITION PLAN
M-201 MECHANICAL NEW WORK FLOOR PLAN
M-202 MECHANICAL HVAC NEW WORK PLAN
M-203 MECHANICAL ENLARGED NEW WORK PLAN
M-301 MECHANICAL SECTIONS
M-302 MECHANICAL SECTION
M-303 MECHANICAL SECTIONS
M-401 MECHANICAL CHILLED WATER PIPING DIAGRAM
M-402 MECHANICAL HEATING HOT WATER PIPING DIAGRAM
M-501 MECHANICAL CONTROL POINT LIST
M-502 MECHANICAL CONTROL POINT LIST
M-503 MECHANICAL CONTROL POINT LIST
M-504 MECHANICAL CONTROL DIAGRAM
M-505 MECHANICAL CONTROL DIAGRAMS & SEQUENCE OF OPERATIONS
M-506 MECHANICAL CHILLED WATER CONTROL DIAGRAM
M-507 MECHANICAL HEATING HOT WATER CONTROL DIAGRAM
M-508 MECHANICAL SEQUENCE OF OPERATIONS
M-509 MECHANICAL SEQUENCE OF OPERATIONS
M-510 MECHANICAL SEQUENCE OF OPERATIONS
M-601 MECHANICAL DETAILS
M-602 MECHANICAL DETAILS
M-603 MECHANICAL DETAILS
M-604 MECHANICAL DETAILS
M-605 MECHANICAL DETAILS
M-606 MECHANICAL DETAILS
ELECTRICAL
E-001 ELECTRICAL GENERAL NOTES, LEGEND, AND ABBREVIATIONS
E-101 ELECTRICAL POWER AND LIGHTING PLAN DEMOLITION WORK
E-201 ELECTRICAL POWER PLAN NEW WORK
E-202 ELECTRICAL LIGHTING PLAN NEW WORK
E-203 ENLARGED PLAN - MECHANICAL EQUIPMENT
E-204 PHOTOMETRIC CALCULATION
E-601 ELECTRICAL SINGLE LINE DIAGRAM
E-602 ELECTICAL PANEL SCHEDULES
E-603 ELECTRICAL SCHEDULES AND PANEL SCHEDULE
FIRE ALARM
FA-101 FIRE ALARM GENERAL NOTES, SCOPE OF WORK AND REFERENCE
CRITERIA
FA-102 FIRE ALARM NEW WORK
SHEET NUMBER SHEET NAME
GENERAL
G-001 COVER SHEET
G-002 GENERAL AND DEMOLITION NOTES
G-003 NOTES, ABBREVIATIONS AND SYMBOLS
G-004 TYPICAL ACCESSIBILITY STANDARDS
G-005 TYPICAL ACCESSIBILITY SIGNAGE STANDARDS
ARCHITECTURAL
AD-101 DEMOLITION SITE PLAN
AD-102 DEMOLITION KEY PLAN
AD-103 DEMOLITION FLOOR PLANS
AD-104 DEMOLITION REFLECTED CEILING PLANS
A-101 SITE PLAN
A-102 KEY FLOOR PLAN
A-103 FLOOR PLANS
A-104 REFLECTED CEILING PLANS
A-201 EXTERIOR ELEVATIONS
A-301 SECTIONS
A-401 INTERIOR ELEVATIONS
A-402 INTERIOR ELEVATIONS
A-501 DETAILS
A-502 MECHANICAL ENCLOSURE DETAILS
A-601 FINISH SCHEDULES AND DESCRIPTIONS
STRUCTURAL
S-001 STRUCTURAL GENERAL NOTES
S-002 STATEMENT OF SPECIAL INSPECTION
S-101 STRUCTURAL PLANS - CMU ENCLOSURE
S-102 COURTYARD EQUIPMENT PLANS
S-501 DETAILS
S-502 DETAILS
S-503 DETAILS
PLUMBING
P-001 PLUMBING GENERAL NOTES, LEGEND, ABBREVIATIONS, & DESIGN
CRITERIA
P-002 PLUMBING EQUIPMENT SCHEDULES
P-101 PLUMBING DEMOLITION PLAN
P-102 PLUMBING DEMOLITION ENLARGED PLAN
P-201 PLUMBING NEW WORK PLAN
P-301 PLUMBING NEW WORK ENLARGED PLAN
P-302 PLUMBING NEW WORK ENLARGED PLAN
P-401 PLUMBING RISER DIAGRAMS
P-402 PLUMBING RISER DIAGRAMS
P-501 PLUMBING DETAILS
P-502 PLUMBING DETAILS
DRAWING INDEXREGIONAL MAP
LOCATION MAP
BASE MAP
SCOPE OF WORK
CODES AND STANDARDS
SITE + BUILDING INFORMATION
N O
D
ES
C
R
IP
TI
O
N D
AT
E
AP
PR
S
U B M
IT
TA
L
/0 1/
S
U B M
IT
TA
L
/3 0/
FI
N
AL
S U
BM
IT
TA
L
/3
1/
BUILDING ELEMENTS, MATERIALS AND EQUIPMENT ARE NEW
UNLESS NOTED AS EXISTING (E).
CONTRACTOR SHALL PROVIDE SUPERVISION, LABOR,
EQUIPMENT, TOOLS, MATERIALS, AND INSTALLATION TO
COMPLETE THE WORK AS INDICATED.
DO NOT SCALE FROM DRAWINGS. WRITTEN DIMENSIONS
SHALL GOVERN. DETAILS SHALL GOVERN OVER PLANS AND
ELEVATIONS. LARGE SCALE DETAILS SHALL GOVERN OVER
SMALL SCALE DETAILS. LARGE SCALE DRAWINGS SHALL
GOVERN OVER SMALL SCALE DRAWINGS. IF UNABLE TO
LOCATE DIMENSIONS FOR ANY ITEM OF WORK, CONSULT THE
CONTRACTING OFFICER PRIOR TO CONSTRUCTION.
INFORMATION RELATED TO THE (E) CONDITIONS GIVEN
HEREIN WERE OBTAINED FROM GOVERNMENT PROVIDED
DOCUMENTATION AVAILABLE TO THE DESIGNERS AT THE TIME
OF DESIGN. DRAWINGS AND SPECIFICATIONS ARE INTENDED
FOR ASSISTANCE AND GUIDANCE, BUT EXACT DIMENSIONS
AND ELEVATIONS SHALL BE GOVERNED BY ACTUAL
CONDITIONS AT THE SITE AND SHALL BE VERIFIED BY THE
CONTRACTOR.
DETAILS NOT SHOWN ARE SIMILAR IN CHARACTER TO THOSE
DETAILED. WHERE SPECIFIC DIMENSIONS, DETAILS OR
DESIGN INTENT CANNOT BE DETERMINED CONSULT THE KTR
BEFORE PROCEEDING WITH WORK. TYPICAL DETAILS APPLY
AT ALL SIMILAR CONDITIONS WHETHER OR NOT CROSS
REFERENCED.
THE CONTRACT DRAWINGS AND SPECIFICATIONS REPRESENT
THE FINISHED WORK AND DO NOT INDICATE METHODS,
PROCEDURES OR SEQUENCE OF CONSTRUCTION. TAKE
NECESSARY PRECAUTIONS TO MAINTAIN AND INSURE THE
INTEGRITY OF THE STRUCTURE DURING THE DEMOLITION AND
CONSTRUCTION. CONTRACTOR SHALL DESIGN, CONSTRUCT
AND MAINTAIN ALL SAFETY DEVICES, INCLUDING SHORING
AND BRACING, AND SHALL BE SOLELY RESPONSIBLE FOR
CONFORMING TO ALL LOCAL, STATE AND FEDERAL SAFETY
AND HEALTH STANDARDS, LAWS AND REGULATIONS.
REQUESTS FOR CLARIFICATION OF THE PLANS AND
SPECIFICATIONS MUST BE SUBMITTED TO THE CONTRACTING
OFFICER IN WRITING.
SHALL A CONFLICT ARISE BETWEEN DRAWINGS AND
SPECIFICATIONS, NEITHER SHALL TAKE PRECEDENCE OVER
THE OTHER. CONTACT CONTRACTING OFFICER WITH A
REQUEST FOR CLARIFICATION IN CASE OF DISCREPANCY.
UTILITIES SUCH AS ELECTRICAL, TELEPHONE, GAS, WATER,
SIGNAL AND COMMUNICATIONS SYSTEMS DAMAGED AS A
RESULT OF THIS WORK SHALL BE RESTORED IN WORKING
CONDITION AT THE CONTRACTOR'S EXPENSE TO THE
SATISFACTION OF THE KO.
SHOULD THE CONTRACTOR'S SCOPE OF WORK INVOLVE
UPGRADES OR MODIFICATIONS TO THE BUILDING'S FIRE/LIFE
SAFETY SYSTEMS SUCH AS THE AUTOMATIC FIRE
SUPPRESSION SPRINKLER, DETECTION, ALARM & MASS
NOTIFICATION SYSTEMS, THE CONTRACTOR MUST:
• SURVEY THE (E) WORK AREA CONDITIONS & BUILDING
SYSTEMS AFFECTING THE FIRE/LIFE SAFETY SYSTEMS.
• SUBMIT A REPORT TO THE KO BEFORE PROCEEDING
CONFIRMING MEETING APPLICABLE NFPA CODES & UFC
3-600-01 REQUIREMENTS.
• COMMENCEMENT OF ALL CONSTRUCTION WORK SHALL
CONSTITUTE ACCEPTABLE OF THE (E) CONDITIONS.
• VERIFY ALL FIRE PROTECTION UPGRADES OR
MODIFICATIONS SHALL BE IN ACCORDANCE WITH UFC
3-600-001, NFPA 13, NFPA 70 & 72, RELATED
REQUIREMENTS & PERFORMANCE SPECIFICATIONS
WHETHER PROVIDED HEREIN OR NOT.
NOTIFY THE BASE FIRE DEPARTMENT AS YOU LOCATE OR
NEED TO REMOVE ANY FIRE ALARM NOTIFICATION EQUIPMENT
SO ALARMS CAN BE DISABLED.
ANY REQUEST FOR CLARIFICATION OF THE PLANS AND
SPECIFICATIONS MUST BE SUBMITTED TO THE CONTRACTING
OFFICER IN WRITING.
ALL DISCREPANCIES AND OMISSIONS ON THE DRAWINGS
AND/OR SPECIFICATIONS OR CONFLICTS WITH (E)CONDITIONS
SHALL BE BROUGHT TO THE ATTENTION OF THE KO BEFORE
PROCEEDING WITH ANY ELEMENT OF THIS PROJECT.
FOR ALL CONSTRUCTION PROJECTS IN BUILDINGS THAT WILL
REMAIN PARTIALLY OR FULLY OCCUPIED AND OPERATIONAL
DURING CONSTRUCTION PERIOD, THE KTR IS TO PROVIDE A
TEMPORARY HVAC & POWER PLAN AND SCHEDULE ALL
OUTAGES FOR PRIOR APPROVAL BY THE KO & USERS. A
SUBMITTAL FOR ALL PROPOSED TEMPORARY HVAC OR
POWER PLANS OR RELATED SCHEDULES IS REQUIRED AS
PART OF THE SCOPE OF WORK.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
ALL (E) SURFACES SHOWN TO REMAIN, BUT DAMAGED BY
DEMOLITION WORK SHALL BE REPAIRED TO MATCH EXISTING
ADJACENT SURFACES AT THE CONTRACTORS EXPENSE.
UTILITIES, ELECTRIC, TELEPHONE, GAS, WATER, SIGNAL AND
COMMUNICATIONS SYSTEM DAMAGED AS A RESULT OF THIS
WORK SHALL BE RESTORED TO WORKING CONDITION AT THE
CONTRACTOR'S EXPENSE TO THE SATISFACTION OF THE
GOVERNMENT.
CONTACT FIRE PREVENTION OFFICE PRIOR TO THE START
OF DEMOLITION SO THAT THE PROJECT'S IMPACT-IF ANY-
UPON EMERGENCY EVACUATION FROM THE SITE, CAN BE
IDENTIFIED/MITIGATED.
1.
2.
3.
A
C
C-38168
STEVEN
GRIST
7-31-2021
DATE
RENEWAL
RCHITECT
DESNECIL
AL I FOR
N
IA
FOETAT
S
7 FREELON ST
SAN FRANCISCO,
CA 94107
54321
1 54321
D
C
B
A
D
C
B
A
A/E INFO
T: 415.762.8388 www.aetypic.com
SEAL
SHEET OF
NAVFAC DRAWING NO.
CONTRACT NO.
EPROJECT NO.
SCALE
APPROVED
FOR COMMANDER NAVFAC
ACTIVITY
SATISFACTORY TO DATE / /
DES DRW CHK
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
DE
PA
RT
ME
NT
O
F
TH
E
NA
VY
NA
VA
L F
AC
ILI
TI
ES
E
NG
IN
EE
RI
NG
C
OM
MA
ND
N
AV
AL
F
AC
IL
IT
IE
S
EN
G
IN
EE
R
IN
G
C O
M M
AN
D
SO
U
TH
W
ES
T
NA
VA
L S
TA
TI
ON
S
AN
D
IE
GO
SA
N
DI
EG
O, C
A
NO SCALE
3/
/2
9:
:0
AM
G-002
G
EN
ER
AL
A N
D D
EM
O
LI
TI
O N
N O
TE
S
9th
R
ES
ER
VE
IN
TE
RI
OR
R
EN
OV
AT
IO
N
PR
OJ
EC
TS
BU
ILD
IN
G
0 -
C
BC
S
TR
AV
IS
A
IR
F
OR
CE
B
AS
E
D.E.
D.T. A.S.
JONNY OCHOA
N62473-16-D-1801
FA
IR
FI
EL
D, C
AL
IF
OR
NI
A
GENERAL DEMOLITION NOTES GENERAL NOTES
N O
D
ES
C
R
IP
TI
O
N D
AT
E
AP
PR
S
U B M
IT
TA
L
/0 1/
S
U B M
IT
TA
L
/3 0/
FI
N
AL
S U
BM
IT
TA
L
/3
1/
8' - 0" xxx xxx xxx
NEW WORK
EXISTING TO REMAIN
EXISTING TO BE DEMOLISHED
KEYED NOTE REFERENCE
ELEVATION, POINT OF CHANGE OR SPOT
IDENTIFICATION, TILE START POINT
MATCH LINE
A21
DETAIL OR NOTATION REFERENCE
SHEET WHERE DETAIL OR NOTE IS SHOWN
DETAIL OR NOTE NUMBER
BASIC DETAIL REFERENCE
CUT LINE
GRID LINEA
SYMBOL DESCRIPTION
1'6" 2'0
SCALE: 1" = 1'-0"
GRAPHIC SCALE
101 WINDOW TAG
DOOR TAG
PARTITION TAG1
CEILING HEIGHT
SECURITY FENCE
SCALE:
A-002 View Name
1/8" = 1'-0"
REVISION TAG
NORTH
ARROW w/
TRUE NORTH
INDICATION
ROOM TAG
ELEVATION NUMBER
VIEW NUMBER
VIEW NUMBER
SPOT ELEVATION
LEVEL NAME
SHEET NUMBER
SHEET NUMBER
SHEET NUMBER
INTERIOR ELEVATION REFERENCE
SHEET NUMBER
Name Elevation
Room name
PLAN NORTH
A101
SIM
A101
SIM
A-101
EXTERIOR ELEVATION REFERENCE
1Ref
R ef
1Ref
R ef
SECTION REFERENCE
DETAIL REFERENCE
VIEW NUMBER
SYMBOL DESCRIPTION
A101
1SIM
VIEW NAME
LIFE SAFETY TAG
TOILET ACCESSORY TAGTA1
TA
G
DETAIL NUMBER
SHEET WHERE DETAIL IS SHOWN
SHEET FROM WHICH DETAIL IS REFERENCED
SCALE:
A02
View Name 1/8" = 1'-0"R101
ROOM NUMBER
LF: #
OCCUPANTS: #
150 SF
ROOM NAME
AND
ANGLE
AT
CENTERLINE
DIAMETER / ROUND
POUND / NUMBER
EXISTING
NEW
ANCHOR BOLT
ABOVE
ASPHALTIC CONCRETE
ASBESTOS CONTAINING
MATERIAL
ACOUSTICAL
AREA DRAIN
AMERICANS WITH
DISABILITIES ACT
ADDITIONAL
ADJUSTABLE
ABOVE FINISH FLOOR
AGGREGATE
ALUMINUM
APPROXIMATE
ARCHITECTURAL
ASBESTOS
ASPHALT
BACKING
BOARD
BELOW
BITUMINOUS
BUILDING
BLOCKING
BEAM
BOTTOM
BOTTOM OF
BEARING
BUILT UP ROOFING
BASE PLATE
CABINET
CATCH BASIN
CEMENT
CERAMIC
CONTRACTOR FURNISHED/
CONTRACTOR INSTALLED
CORNER GUARD
CAST IRON
CONSTRUCTION JOINT
CEILING
CAULKING
CLOSET
CLEAR
CENTIMETER
CONCRETE MASONRY UNIT
COUNTER
CASED OPENING
COLUMN
CONCRETE
CONNECTION
CONSTRUCTION
CONTINUOUS
CORRIDOR
CERAMIC TILE
CENTER
COUNTERSUNK
DOUBLE
DEPARTMENT
DETAIL
DRINKING FOUNTAIN
DIAMETER
DIMENSION
DISPENSER
DOWN
DOOR OPENING
DOOR
DOWNSPOUT
DRAWING
DRAWER
AB
ABV
AC
AC
M
ACOUS
AD
ADA
ADDTL
ADJ
AFF
AGG
ALUM
APPROX.
ARCH
ASB
ASPH
L C O (E) (N)
L
BACK'G
BD
BEL
BITUM
BLDG
BLKG
BM
BOT/B
BO
BRG
BUR
BP
CAB
CB
CEM
CER
CF/CI
CG
CI
CJ
CLG
CLKG
CLO
CLR
CM
CMU
CNTR
CO
COL
CONC
CONN
CONST
CONT
CORR
CT
CTR
CTSK
DBL
DEPT
DET
DF
DIA
DIM
DISP
DN
DO
DR
DS
DWG
DWR
FIRE ALARM
FACTORY
FLOOR DRAIN
FOUNDATION
FIRE EXTINGUISHER
FIRE EXTINGUISHER CABINET
FINISH FLOOR
FURNITURE, FIXTURES AND
EQUIPMENT
FINISH GRADE
FIRE HYDRANT
FIRE HOSE CABINET
FINISH
FIXTURE
FLUSH JOINT
FLOOR
FLASHING
FLUORESCENT
FACE OF CONCRETE
FACE OF FINISH
FACE OF MASONRY
FACE OF STUD
FACE OF WALL
FRAMING
FIBER REINFORCED PLASTIC
FLOOR SINK
FOOT / FEET
FOOTING
FURRING
GAS
GAUGE
GALVANIZED
GENERAL CONTRACTOR
GALVANIZED IRON
GLASS
GROUND
GALLONS PER MINUTE
GRADE
GYPSUM BOARD
HIGH
HOSE BIBB
HOLLOW CORE
HARDWOOD
HARDWARE
HEIGHT
HOLLOW METAL
HORIZONTAL
HOUR
HEATING VENTILATING
AIR CONDITIONING
INSIDE DIAMETER
INVERT ELEVATION
INFORMATION
INSULATION
INTERIOR
JANITOR
JOINT
KITCHEN
CONTRACTING OFFICER
CONTRACTOR
LONG
LABORATORY
LAVATORY
POUND
LOAD FACTOR
LONG LEG HORIZONTAL
LONG LEG VERTICAL
LIGHT
LIGHT-WEIGHT
FA
FACT
FD
FDN
FE
FEC
FF
FF&E
FG
FH
FHC
FIN
FIXT
FJ
FLR
FLSH'G
FLUOR
FOC
FOF
FOM
FOS
FOW
FRMG
FRP
FS
FT
FTG
FURR
G
GA
GALV
GC
GI
GL
GND
GPM
GR(D)
GYP BD
H
HB
HC
HDWD
HW
HT
HM
HORZ
HR
HVAC
ID
IE
INFO
INSUL
INT
JAN
JT
KIT
KO
KTR
L
LAB
LAV
LB
LF
LLH
LLV
LT
LTWT
ON CENTER
OCCUPANTS
OCCUPANCY TYPE
OUTSIDE DIAMETER
OWNER FURNISHED/
CONTRACTOR INSTALLED
OVERFLOW DRAIN
OFFICE
OPPOSITE HAND
OPENING
OFFICE OF SAFETY AND HEALTH
ADMINISTRATION
PARTITION
PORTLAND CEMENT CONCRETE
PANEL JOINT
PLATE
PLASTIC LAMINATE
PLASTER
PLACES
PLUMBING
PLYWOOD
PAIR
POUNDS PER SQUARE INCH
POINT
PAINTED
PRESSURE TREATED DOUGLAS FIR
POLYVINYL CHLORIDE
QUARRY TILE
RADIUS
ROOF DRAIN
REFRIGERATOR
REINFORCED
REQUIRED
RESILIENT
REVISED
ROOM
ROUGH OPENING
REDWOOD
SEWER / SOUTH
SOLID CORE
SEAT COVER DISPENSER
SCHEDULE
STORM DRAIN
SAN DIEGO GAS & ELECTRICAL
SECTION
SQUARE FOOT
SEMI-GLOSS
SEE ELECTRICAL DRAWINGS
SEE MECHANICAL DRAWINGS
SEE STRUCTURAL DRAWINGS
SEE PLUMBING DRAWINGS
SHEET METAL SCREEN
SHOWER
SHEET
SHEATHING
SIMILAR
SHEET METAL AND AIR CONDITIONING
CONTRACTORS NATIONAL ASSOCIATION
OC
OCCS
OCCX
OD
OF/CI
OFD
OFF
OH
OPNG
OSHA
PART
PCC
PJ
PL
PLAM
PLAS
PLCS
PLUMB
PLYWD
PR
PSI
PT
PTD
PTDF
PVC
QT
R/RAD
RD
REF
REINF
REQD
RESIL
REV
RM
RO
RDWD
S
SC
SCD
SCH
SD
SDGE
SECT
SF
SG
SED
SMD
SSD
SPD
SMS
SHR
SHT
SHTG
SIM
SMACNA
TILE START POINT
SPECIFICATION
SQUARE
STAINLESS STEEL
SOUND TRANSMISSION COEFFICIENT
STANDARD
STRUCTURAL
STIFFENERS
STEEL
STORAGE
STRUCTURE
SUSPENDED
STEEL ANGLE BACK TO BACK
SURFACE ON FOUR SIDES
TOP OR THREAD
TOP AND BOTTOM
TELEPHONE
TEMPERED
TONGUE AND GROOVE
THICK(NESS)
THREADED
TOOLED JOINT
TOP OF CONCRETE
TOP OF FOUNDATION
TOP OF PAVEMENT / TOP OF PARAPET
TOP OF WALL
TUBE STEEL
TELEVISION
TYPICAL
UNDERWRITER'S LABORATORY
UNLESS OTHERWISE NOTED
URINAL
VINYL COMPOSITION TILE
VERTICAL
VESTIBULE
VERIFY IN FIELD
VENT THRU ROOF
SP
SPEC
SQ
SS
STC
STD
STR
STIFF
STL
STOR
STRUCT
SUSP
SLBB
S4S
T T&B
TEL(E)
TEMP
T&G
THK
THR
TJ
TOC
TOF
TOP
TOW
TS
TV
TYP
UL
UON
UR
VCT
VERT
VEST
VIF
VTR
EAST
EACH
EXTERIOR INSULATION & FINISH
SYSTEM
EXPANSION JOINT
ELEVATION
ELECTRICAL
ELEVATOR
ENCLOSURE
ELECTRICAL PANELBOARD
EQUAL OR EQUIVALENT
EQUIPMENT
ET CETERA
ELECTRIC WATER COOLER
EXISTING
EXPANSION
EXTERIOR
E
EA
EIFS
EJ
EL
ELEC
ELEV
ENCL
EP
EQ
EQUIP
ETC
EWC
EXIST
EXP
EXT
METER
MATERIAL
MAXIMUM
MACHINE BOLT
MODIFIED BITUMEN ROOFING
MECHANICAL
MEMBRANE
MANUFACTURER
MAN HOLE
MINIMUM
MISCELLANEOUS
MILLIMETER
MASONRY OPENING
MOUNTED
METAL
MULLION
NORTH
NOT IN CONTRACT
NUMBER
NOMINAL
NOISE REDUCTION
COEFFICIENT
NOT TO SCALE
M
MAT
MAX
MB
MBR
MECH
MEMB
MFR
MH
MIN
MISC
MM
MO
MTD
MTL
MUL
N
NIC
NO
NOM
NRC
NTS
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
DIMENSIONS ARE TAKEN TO FACE OF FINISH, CONCRETE,
MASONRY, OR CENTERLINE OF STRUCTURE, U.O.N.
WRITTEN DIMENSIONS SHALL TAKE PRECEDENCE OVER
SCALE. SCALED DIMENSIONS TAKEN BY THE CONTRACTOR
WITHOUT CONSULTING THE ARCHITECT, ARE USED AT THE
CONTRACTOR'S OWN RISK. DO NOT SCALE DRAWINGS.
IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO
CROSS CHECK DETAILS AND DIMENSIONS SHOWN ON THE
ARCHITECTURAL DRAWINGS WITH RELATED
REQUIREMENTS ON OTHER DRAWINGS AS APPLICABLE.
NOTIFY KO OF ANY DISCREPANCIES BEFORE PROCEEDING
WITH THE WORK.
DISCREPANCIES AND OMISSIONS ON THE DRAWINGS
AND/OR SPECIFICATIONS OR CONFLICTS WITH EXISTING
CONDITIONS SHALL BE BROUGHT TO THE ATTENTION OF
THE KO BEFORE PROCEEDING WITH ANY ELEMENT OF THIS
PROJECT.
PROVIDE ALL NECESSARY ANCHORAGE BLOCKING,
BACKING, FRAMING FOR LIGHT FIXTURES, CASEWORK,
SHELVING, MIRRORS, TOILET ACCESSORIES AND ALL OTHER
ITEMS AS REQUIRED FOR COMPLETE INSTALLATION.
PATCH AND REPAIR ANY DAMAGE TO WALLS, FLOORS,
CEILINGS, CABINETS, HARDWARE, WINDOWS, FIXTURES,
ETC., AS A RESULT OF THE CONSTRUCTION PROCESS OR
WHICH MAY BE EXISTING CONDITIONS. MATCH EXISTING
FINISHES AS CLOSELY AS POSSIBLE UNLESS NOTED
OTHERWISE. RESULTANT CONDITIONS OF PATCHES AND
REPAIRS TO BE LIKE NEW WITH ALL SURFACES AND
MATERIALS IN A CLEAN AND SPOTLESS CONDITION. ALL
SPACES DIRTIED BY ANY PART OF CONSTRUCTION ARE TO
BE CLEANED IN A TIMELY FASHION.
CONDUCT ALL WORK WITH MINIMAL INTERFERENCE TO
ADJACENT AND OCCUPIED AREAS. PROVIDE AND MAINTAIN
TEMPORARY BARRIERS (FOR DUST, TRAFFIC ETC.) AS
NECESSARY THROUGHOUT THE DURATION OF THE
PROJECT.
FIELD VERIFY ALL EXISTING CONDITIONS PRIOR TO
COMMENCING WORK SO AS TO ENSURE NO CONFLICT WITH
EXISTING WALLS, CEILINGS, OR EQUIPMENT. CONFLICT
SHOULD BE BROUGHT TO THE ATTENTION OF THE KO PRIOR
TO PROCEEDING WITH WORK.
U.O.N., ALL NEW DOORS SHALL BE LOCATED 4" FROM
ADJACENT PERPENDICULAR WALLS TO THE OUTSIDE OF
THE DOOR FRAME.
KTR TO PROVIDE COMPREHENSIVE SIGNAGE PACKAGE, PER
BASE STANDARDS (BEAP) FOR REVIEW AND ACCEPTANCE
BY CONTRACTING OFFICER.
LIGHT FIXTURES, DIFFUSERS, AND OTHER SIMILAR ITEMS
THAT ARE RECESSED IN, MOUNTED ON, OR HUNG FROM THE
CEILING SHALL BE EQUALLY SPACED AND CENTERED
BETWEEN WALLS TO PROVIDE UNIFORM APPEARANCE
U.O.N.
INSTALL MATERIALS, EQUIPMENT, AND FIXTURES IN
CONFORMANCE WITH THE REQUIREMENTS AND
RECOMMENDATIONS OF THE MANUFACTURER'S AND THE
REQUIREMENTS OF THE APPLICABLE CODES.
CEILING LAYOUT IS CONCEPTUAL ONLY. ANY
DISCREPANCIES BETWEEN THE ARCHITECTURAL RCP &
ENGINEER'S LIGHTING PLANS SHOULD BE BROUGHT TO THE
IMMEDIATE ATTENTION OF THE ARCHITECT & CONTRACTING
OFFICER FOR RESOLUTION PRIOR TO PROCEEDING WITH
THE WORK.
AT COMPLETION OF THE WORK, CONTRACTOR SHALL
REMOVE ALL MARKS, STAINS, FINGERPRINTS, DUST, DIRT,
SPLATTERED PAINT, AND BLEMISHES RESULTING FROM THE
VARIOUS OPERATIONS THROUGH OUT THE PROJECT.
CONSTRUCTION AREA MUST BE BROOM CLEANED DAILY
AND ALL MATERIALS SHALL BE STACKED OR FIELD IN AN
ORDERLY FASHION OUT OF TRAFFIC PATTERNS AND NOT
BLOCKING FIRE EXISTS.
DETAILS ARE USUALLY KEYED ONLY ONCE (ON THE PLANS
OR ELEVATIONS WHEN THEY FIRST OCCUR) AND ARE
TYPICAL FOR SIMILAR CONDITIONS THROUGH OUT U.O.N..
A
C
C-38168
STEVEN
GRIST
7-31-2021
DATE
RENEWAL
RCHITECT
DESNECIL
AL I FOR
N
IA
FOETAT
S
7 FREELON ST
SAN FRANCISCO,
CA 94107
54321
1 54321
D
C
B
A
D
C
B
A
A/E INFO
T: 415.762.8388 www.aetypic.com
SEAL
SHEET OF
NAVFAC DRAWING NO.
CONTRACT NO.
EPROJECT NO.
SCALE
APPROVED
FOR COMMANDER NAVFAC
ACTIVITY
SATISFACTORY TO DATE / /
DES DRW CHK
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
DE
PA
RT
ME
NT
O
F
TH
E
NA
VY
NA
VA
L F
AC
ILI
TI
ES
E
NG
IN
EE
RI
NG
C
OM
MA
ND
N
AV
AL
F
AC
IL
IT
IE
S
EN
G
IN
EE
R
IN
G
C O
M M
AN
D
SO
U
TH
W
ES
T
NA
VA
L S
TA
TI
ON
S
AN
D
IE
GO
SA
N
DI
EG
O, C
A
NO SCALE
3/
/2
9:
:0
AM
G-003
NO
TE
S, A
BB
RE
VI
AT
IO
NS
A
ND
S
YM
BO
LS
9th
R
ES
ER
VE
IN
TE
RI
OR
R
EN
OV
AT
IO
N
PR
OJ
EC
TS
BU
ILD
IN
G
0 -
C
BC
S
TR
AV
IS
A
IR
F
OR
CE
B
AS
E
D.E.
D.T. A.S.
JONNY OCHOA
N62473-16-D-1801
FA
IR
FI
EL
D, C
AL
IF
OR
NI
A
ARCHITECTURAL GENERAL SYMBOLS ARCHITECTURAL ABBREVIATIONS ARCHITECTURAL GENERAL NOTES
N O
D
ES
C
R
IP
TI
O
N D
AT
E
AP
PR
S
U B M
IT
TA
L
/0 1/
S
U B M
IT
TA
L
/3 0/
FI
N
AL
S U
BM
IT
TA
L
/3
1/
BACK GRAB BARCOMPARTMENT/ROOM DOOR LOCATION SIDE GRAB BAR
ACCESSIBLE WATER CLOSET REQUIRED CLEAR SPACE
36" MIN
6" MIN TOE CLEARANCE WHERE REQD
1/
2" C
LR
M
IN
" T
O
6" T
O T
O P
" T
O
9"
TO
T O
P O
F
SE
AT
12"
MIN
24" MIN24" MIN
PER IBC
" T
O
TO
T
O P
" T
O C
EN
TE
R
LI
N E
PE
R
A
BA
AS
39" TO 41"
" T
O
1"
" M
IN
16" TO 18"
18" PER IBC
60" MIN
" M
IN
IF
W
AL
L- H
U N
G F
IX
TU
R E
54" MIN
12"
MAX 42" MIN
ACCESS
AISLE
36" MAX
PER IBC
ALTERNATE
DOOR
LOCATION
" T
O C
EN
TE
R
LI
N E
O R
U P
TO
6" T
O
TO
P
IF
A
T
AN
K-
TY
PE
T
O
IL
ET
O
BS
TR
U C
TS
PL
AC
EM
EN
T
AT
3"
P
ER
IB
C
FLUSH
VALVE
ON WIDE
SIDE
4" MAX
15" MIN. TO 48" MAX AFF TO
CENTER OF OUTLET AND
NOT LOCATED BEHIND
GRAB BAR;
PER IBC
END OPENING DOOR AT MULTIPLE ACCOMMODATION
TOILET FACILITIES - 48" MIN CLR PER IBC
TOILET FACILITIES - 60" MIN CLR PER IBC ALL SINGLE ACCOMMODATION RESTROOM - 48" MIN
CLR PER IBC
VERTICAL GRAB
BAR
PER 2012 IBC AND
ANSI 604.5.1
28" MIN CLR TO A
FIXTURE OR
32" MIN CLR TO A WALL
PER IBC
REQUIRED
CLEAR
SPACE AT
ACCESSIBLE
WATER
CLOSET
7"-9" TO
CENTERLINE OF
TOILET PAPER
DISPENSER
" M
IN
IF
F
LO
O R
M
O U
N
TE
D
FI
XT
U
R E
* 42" MIN ACCESS AISLE FOR LATCH SIDE APPROACH
TO ACCESSIBLE WATER CLOSET COMPARTMENT
EXCEPT FOR
DOOR CLEARANCE REQUIREMENTS; 44" PER ABAAS
12" MAX PER IBC
ACL
ACL
CL
C
O N
TR
O
L W
AL
L
SIDE WALL
SEAT WALL
ACCESSIBLE SHOWER COMPARTMENT SIZE AND CLEARANCES
RESTROOMS
- ALL WALLS WITHIN RESTROOMS SHALL BE FINISHED TO A 5"HT & WALLS WITHIN TOILET COMPARTMENTS SHALL BE FINISHED TO A 52" HT
WITH A SMOOTH, HARD, NON-ABSORBENT SURFACE PER IBC
ACCESSIBLE WATER CLOSET
- FLUSH CONTROLS SHALL BE OPERABLE WITH ONE HAND AND NOT REQUIRE TIGHT GRASPING, PINCHING, OR TWISTING 7" MOUNTED 44"
HT MAX PER IBC FORCE REQUIRED TO ACTIVATE FLUSH VALVE SHALL BE 5 LB MAX
- TOILET PAPER DISPENSER SHALL ALLOW CONTINUOUS FLOW OF PAPER
- REQUIRED CLEARANCE AT TOILETS CAN OVERLAP WITH REQUIRED CLEAR SPACE OF OTHER FIXTURES OR TURNING SPACE; NO
FIXTURES WITHIN THE CLEAR SPACE
COMPARTMENT DOORS
- DOORS TO BE LOCATED IN THE FRONT OR SIDE PARTITION OR WALL FARTHEST FROM THE TOILET AND SHALL HAVE A CLEAR OPENING
OF 32" MIN WIDE; 34" MIN WIDE WHEN LOCATED ON THE SIDE PER IBC
- DOOR TO BE SELF-CLOSING AND ADJUSTED SO IT TAKES 5 SEC MIN FROM A 90 DEGREE OPEN POSITION TO 12 DEGREES FROM LATCH SIDE
- DOOR PULLS (LOOP OR U-SHAPED HANDLE) SHALL BE PLACED ON BOTH SIDES (PUSH AND PULL) AND BE 34" MIN TO 48" MAX AFF; 34" TO 44" PER IBC
- LOCKS/LATCH SHALL BE FLIP-OVER STYLE, SLIDING OR OTHER HARDWARE NOT REQUIRING TIGHT GRASPING, PINCHING, OR TWISTING AND
BE 34" MIN TO 48" MAX AFF; 34" TO 44" PER IBC
- FORCE REQUIRED TO OPERATE DOOR OR HARDWARE SHALL BE 5 LB MAX
- IF THE DOOR EXTENDS TO WITHIN 10" OF THE FINISH FLOOR IT SHALL HAVE A SMOOTH SURFACE ON THE PUSH SIDE
- A LATCH SIDE PULL APPROACH MAY HAVE 42" CLEAR; 48" PER IBC
- DOORS SHALL NOT SWING INTO THE MINIMUM REQUIRED COMPARTMENT AREA, NOR IN REQUIRED CLEAR SPACE OF ANY FIXTURES; A
DOOR CAN ENCROACH INTO 5' Ø TURNING SPACE MAX OF 12" ENCROACHMENT PER IBC
- A TOE CLEARANCE OF 9" HIGH UNDER THE PARTITION AND 6" DEEP BEYOND THE PARTITION IS NOT REQUIRED AT THE FRONT PARTITION IF THE COMPARTMENT IS >62" DEEP FOR WALL-HUNG OR >65" FOR FLOOR MOUNT; NOT REQUIRED AT SIDE PARTITION IF >66" WIDE; IF A 9" TOE CLEARANCE IS PROVIDED AT THE DOOR, CLEARANCE AT THE STRIKE SIDE IS NOT REQUIRED PER IBC
GRAB BARS
- THE SPACE BETWEEN THE WALL AND THE GRAB BAR SHALL BE 11/2"
- THE SPACE BELOW AND AT EACH END OF THE GRAB BAR SHALL BE 11/2" MIN
- THE SPACE BETWEEN GRAB BARS AND PROJECTING OBJECTS ABOVE SHALL BE 12" MIN; 18" PER IBC
- GRAB BARS AND ADJACENT SURFACES SHALL BE FREE OF SHARP OR ABRASIVE SURFACES OR ELEMENTS AND ADJACENT ELEMENTS SHALL ALSO HAVE ROUNDED SURFACES WITH A MIN 1/8" RADIUS PER IBC 1 1/4" to 1 1/2" PER IBC
- SHALL NOT ROTATE WITHIN THEIR FITTINGS AND SHALL ALLOW A STRESS, SHEAR, TENSILE FORCE OF 250 LBS MIN
- CIRCULAR GRAB BARS SHALL HAVE A DIAMETER OF 1" MIN TO 2" MAX; 1 1/4"
- NON-CIRCULAR GRAB BARS SHALL HAVE CROSS SECTION OF 2" MAX AND A PERIMETER DIMENSION OF 4.8" MAX; NOT ALLOWED PER IBC
- RECESSED GRAB BARS CAN BE PLACED IN A 3" MAX RECESS PER IBC
- TOILET PAPER DISPENSER LOCATED ABOVE THE GRAB BAR IS REQUIRED TO BE RECESSED
SEAT WALL CONTROL WALL SIDE WALL
NOTE:
TYPICAL MOUNTING
HEIGHTS SHALL
BE MEASURED FROM
THE FINISHED
FLOOR TO THE
HIGHEST OPERABLE
DEVICE ON EACH ITEM.
FIRE ALARM
LIGHT SWITCH
ELECTRICAL
OUTLET
SANITARY NAPKIN DISPOSAL
TOILET PAPER
DISPENSER
URINAL W/
ELONGATED RIM
AND OSCILLATING
HANDLE
ALL DISPENSERS
+/- 40" MAX TO HIGHEST
OPERABLE PART
GRAB BAR
42" GRAB BAR
LOCATE FLUSH
ACTIVATOR ON
WIDE SIDE OF
STALL
M
AX44
M
AX17
M
AX48
M
IN18
INSULATE HOT
WATER & DRAIN
PIPES
M
AX34
M
AX40
MIRROR,
GLASS
M
AX40
2' -5
" M
IN
9" M
IN
CL
" T
O
9"
THERMOSTAT
" M
IN
(W
IT
H
IN
ST
AL
L)
- ONE OF EACH PROVIDED TYPE SHOULD BE ACCESSIBLE
- ALL CONTROLS INCLUDING COIN SLOTS SHALL BE OPERABLE WITH ONE HAND AND NOT REQUIRE TIGHT GRASPING, PINCHING, OR TWISTING OF THE WRIST
- FORCE REQUIRED TO ACTIVATE SHALL BE 5 LB MAX
- PROVIDE A CLEAR FLOOR SPACE OF 30" X 48" MIN AT EACH ACCESSORY
- DOORS SHALL NOT SWING INTO REQUIRED CLEAR SPACE
M
IN
SOAP DISH SHELF
M
AX40
COAT
HOOK
M
AX40
M
AX40
ST
AN
D
AR
D
/2
SHOWER ROD
M
AX19
SHOWER/
DRESSING SEAT
COMNINATION
PAPER TOWEL
DISPENSER/TRASH
TA1
TA5
TA9
TA3
TA4
TA1
TA2
TA6
TA7
TA8TA9
/2
TOILET SEAT COVER DISPENSER
TA10
GRAB BAR
TA10
M
AX33
" M
AX
" M
IN18
40"
9"
16"
6"
24 1/2" 12"
M
IN
56" ø 5' - 0"
6'
6" (V
IF
7' - 4" (VIF)
38"
" M
AX
18" 12"
A
C
C-38168
STEVEN
GRIST
7-31-2021
DATE
RENEWAL
RCHITECT
DESNECIL
AL I FOR
N
IA
FOETAT
S
7 FREELON ST
SAN FRANCISCO,
CA 94107
54321
1 54321
D
C
B
A
D
C
B
A
A/E INFO
T: 415.762.8388 www.aetypic.com
SEAL
SHEET OF
NAVFAC DRAWING NO.
CONTRACT NO.
EPROJECT NO.
SCALE
APPROVED
FOR COMMANDER NAVFAC
ACTIVITY
SATISFACTORY TO DATE / /
DES DRW CHK
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
DE
PA
RT
ME
NT
O
F
TH
E
NA
VY
NA
VA
L F
AC
ILI
TI
ES
E
NG
IN
EE
RI
NG
C
OM
MA
ND
N
AV
AL
F
AC
IL
IT
IE
S
EN
G
IN
EE
R
IN
G
C O
M M
AN
D
SO
U
TH
W
ES
T
NA
VA
L S
TA
TI
ON
S
AN
D
IE
GO
SA
N
DI
EG
O, C
A
NO SCALE
3/
/2
9:
:0
AM
G-004
TY
PI
CA
L
AC
CE
SS
IB
IL
IT
Y
ST
AN
DA
RD
S
9th
R
ES
ER
VE
IN
TE
RI
OR
R
EN
OV
AT
IO
N
PR
OJ
EC
TS
BU
ILD
IN
G
0 -
C
BC
S
TR
AV
IS
A
IR
F
OR
CE
B
AS
E
D.E.
D.T. A.S.
JONNY OCHOA
N62473-16-D-1801
FA
IR
FI
EL
D, C
AL
IF
OR
NI
A
SCALE:G-004 NOT TO SCALE
2 TYPICAL WATER CLOSET CLEARANCES & SHOWER REQUIREMENTS
SCALE:G-004 NO SCALE
1 TYPICAL FIXTURES AND ACCESSORIES MOUNTING HEIGHTS
N O
D
ES
C
R
IP
TI
O
N D
AT
E
AP
PR
S
U B M
IT
TA
L
/0 1/
S
U B M
IT
TA
L
/3 0/
FI
N
AL
S U
BM
IT
TA
L
/3
1/
NOTE: IMAGES TAKEN FROM UFC 3-120-01 DESIGN: SIGN STANDARDS, WITH CHANGE 3
DATED: 03-01-14, CHANGE/REVISION DATE: 12-12-2017
3/4" (18mm) TACTILE ROOM
DESCRIPTION WITH BRAILLE,
HELVETICA NUEUE 55 ROMAN
9" (229mm)
ADD ACCESSIBLE RESTROOM
DIRECTIONAL MESSAGE IF REQUIRED,
HELVETICA NUEUE 55 ROMAN
6" (152) SYMBOL
OPTIONAL 1 1/2" (38mm)
TACTILE ROOM NUMBER WITH
BRAILLE, HELVETICA NUEUE
55 ROMAN
1'
1/
2" (3 m m
3" (7
6m m
8"
(2 m m
3"
(7 6m m
1/
2" (3
8m m
8 1/2" (216mm)
1" (25MM) TACTILE ROOM
DESCRIPTION WITH BRAILLE,
HELVETICA NUEUE 55 ROMAN
6" (152MM) SYMBOL
OPTIONAL 1 1/2" (38mm)
TACTILE ROOM NUMBER WITH
BRAILLE, HELVETICA NUEUE
55 ROMAN
9" (229mm)
1'
2" (3
6m m
3" (7
6m m
8"
(2 m m
3"
(7 6m m
8 1/2" (216mm)
NOTE: IMAGES TAKEN FROM UFC 3-120-01 DESIGN: SIGN STANDARDS, WITH CHANGE 3
DATED: 03-01-14, CHANGE/REVISION DATE: 12-12-2017
TYPICAL WALL SIGN INSTALLATION TYPICAL DOOR MOUNTED INSTALLATION
3" (76mm) 3" (76mm)
A
C
C-38168
STEVEN
GRIST
7-31-2021
DATE
RENEWAL
RCHITECT
DESNECIL
AL I FOR
N
IA
FOETAT
S
7 FREELON ST
SAN FRANCISCO,
CA 94107
54321
1 54321
D
C
B
A
D
C
B
A
A/E INFO
T: 415.762.8388 www.aetypic.com
SEAL
SHEET OF
NAVFAC DRAWING NO.
CONTRACT NO.
EPROJECT NO.
SCALE
APPROVED
FOR COMMANDER NAVFAC
ACTIVITY
SATISFACTORY TO DATE / /
DES DRW CHK
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
DE
PA
RT
ME
NT
O
F
TH
E
NA
VY
NA
VA
L F
AC
ILI
TI
ES
E
NG
IN
EE
RI
NG
C
OM
MA
ND
N
AV
AL
F
AC
IL
IT
IE
S
EN
G
IN
EE
RI
NG
C
O M
M
AN
D
SO
U
TH
W
ES
T
NA
VA
L S
TA
TI
ON
S
AN
D
IE
GO
SA
N
DI
EG
O, C A
NO SCALE
3/
/2
9:
:0
AM
G-005
TY
PI
CA
L
AC
CE
SS
IB
IL
IT
Y
SI
G
NA
G E
ST
AN
DA
RD
S
9th
R
ES
ER
VE
IN
TE
RI
OR
R
EN
OV
AT
IO
N
PR
OJ
EC
TS
BU
ILD
IN
G
0 -
C
BC
S
TR
AV
IS
A
IR
F
OR
CE
B
AS
E
D.E.
D.T. A.S.
JONNY OCHOA
N62473-16-D-1801
FA
IR
FI
EL
D, C
AL
IF
OR
NI
A
GENERAL SIGNAGE REQUIREMENTS
VISUAL CHARACTERS:
VISUAL CHARACTERS SHALL COMPLY WITH 703.5.
- FINISH AND CONTRAST: CHARACTERS AND THEIR
BACKGROUND SHALL HAVE A NON-GLARE FINISH.
CHARACTERS SHALL CONTRAST WITH THE BACKGROUND
WITH EITHER LIGHT CHARACTERS ON A DARK
BACKGROUND OR DARK CHARACTERS ON A LIGHT
BACKGROUND.
- CASE: CHARACTERS SHALL BE UPPERCASE OR
LOWERCASE OR A COMBINATION OF BOTH.
- STYLE: CHARACTERS SHALL BE CONVENTIONAL IN
FORM. CHARACTERS SHALL NOT BE ITALIC, OBLIQUE,
SCRIPT, HIGHLY DECORATIVE, OR OF OTHER UNUSUAL
FORMS.
- CHARACTER PROPORTIONS: CHARACTERS SHALL BE
SELECTED FROM FONTS WHERE THE WIDTH OF THE
UPPERCASE LETTER “O” IS 55 PERCENT MINIMUM AND 110
PERCENT MAXIMUM OF THE HEIGHT OF THE UPPERCASE
LETTER “I”.
- CHARACTER HEIGHT: MINIMUM CHARACTER HEIGHT
SHALL COMPLY WITH TABLE 703.5.5. VIEWING DISTANCE
SHALL BE MEASURED AS THE HORIZONTAL DISTANCE
BETWEEN THE CHARACTER AND AN OBSTRUCTION
PREVENTING FURTHER APPROACH TOWARDS THE SIGN.
CHARACTER HEIGHT SHALL BE BASED ON THE
UPPERCASE LETTER “I”.
- HEIGHT FROM FINISH FLOOR OR GROUND: VISUAL
CHARACTERS SHALL BE 40 INCHES (1015 MM)
MINIMUM ABOVE THE FINISH FLOOR OR GROUND.
- STROKE THICKNESS: STROKE THICKNESS OF THE
UPPERCASE LETTER “I” SHALL BE 10 PERCENT MINIMUM
AND 30 PERCENT MAXIMUM OF THE HEIGHT OF THE
CHARACTER.
- CHARACTER SPACING: CHARACTER SPACING SHALL BE
MEASURED BETWEEN THE TWO CLOSEST POINTS OF
ADJACENT CHARACTERS, EXCLUDING WORD SPACES.
SPACING BETWEEN INDIVIDUAL CHARACTERS SHALL BE
10 PERCENT MINIMUM AND 35 PERCENT MAXIMUM OF
CHARACTER HEIGHT.
- LINE SPACING: SPACING BETWEEN THE BASELINES OF
SEPARATE LINES OF CHARACTERS WITHIN A MESSAGE
SHALL BE 135 PERCENT MINIMUM AND 170 PERCENT
MAXIMUM OF THE CHARACTER HEIGHT.
PICTOGRAMS:
PICTOGRAMS SHALL COMPLY WITH 703.6.
- PICTOGRAM FIELD: PICTOGRAMS SHALL HAVE A FIELD
HEIGHT OF 6 INCHES (150 MM) MINIMUM. CHARACTERS
AND BRAILLE SHALL NOT BE LOCATED IN THE PICTOGRAM
FIELD.
- FINISH AND CONTRAST: PICTOGRAMS AND THEIR FIELD
SHALL HAVE A NON-GLARE FINISH. PICTOGRAMS SHALL
CONTRAST WITH THEIR FIELD WITH EITHER A LIGHT
PICTOGRAM ON A DARK FIELD OR A DARK PICTOGRAM ON
A LIGHT FIELD.
- TEXT DESCRIPTORS: PICTOGRAMS SHALL HAVE TEXT
DESCRIPTORS LOCATED DIRECTLY BELOW THE
PICTOGRAM FIELD. TEXT DESCRIPTORS SHALL COMPLY
WITH 703.2, 703.3 AND 703.4.
SYMBOLS OF ACCESSIBILITY
SYMBOLS OF ACCESSIBILITY SHALL COMPLY WITH 703.7.
- FINISH AND CONTRAST: SYMBOLS OF ACCESSIBILITY
AND THEIR BACKGROUND SHALL HAVE A NON-GLARE
FINISH. SYMBOLS OF ACCESSIBILITY SHALL CONTRAST
WITH THEIR BACKGROUND WITH EITHER A LIGHT SYMBOL
ON A DARK BACKGROUND OR A DARK SYMBOL ON A LIGHT
BACKGROUND. INTERNATIONAL SYMBOL OF
ACCESSIBILITY SHALL COMPLY WITH FIGURE 703.7.2.1.
ENTRANCE SIGNS:
WHERE NOT ALL ENTRANCES COMPLY WITH 404, ENTRANCES
COMPLYING WITH 404 SHALL BE IDENTIFIED BY THE
INTERNATIONAL SYMBOL OF ACCESSIBILITY COMPLYING WITH
703.7.2.1. DIRECTIONAL SIGNS COMPLYING WITH 703.5 THAT
INDICATE THE LOCATION OF THE NEAREST ENTRANCE
COMPLYING WITH 404 SHALL BE PROVIDED AT ENTRANCES
THAT DO NOT COMPLY WITH 404.
INTERIOR SIGN MOUNTING:
- DRYWALL: ADHESIVELY APPLIED, NO VISIBLE
FASTENERS.
- GLASS: ADHESIVELY APPLIED WITH ADDITIONAL BLANK
PLASTIC BACKING THE SAME SIZE/ COLOR AS THE SIGN
ADHESIVELY APPLIED TO THE BACK SIDE OF THE GLASS,
NO VISIBLE FASTENERS.
GENERAL REQUIREMENTS:
SIGNS SHALL COMPLY WITH 703. WHERE BOTH VISUAL AND
TACTILE CHARACTERS ARE REQUIRED, EITHER ONE SIGN WITH
BOTH VISUAL AND TACTILE CHARACTERS, OR TWO SEPARATE
SIGNS, ONE WITH VISUAL, AND ONE WITH TACTILE
CHARACTERS, SHALL BE PROVIDED. SIGNS SHALL COMPLY
WITH THE FOLLOWING:
RAISED CHARACTERS AND PICTORIAL SYMBOL SIGNS:
RAISED CHARACTERS SHALL COMPLY WITH 703.2 AND SHALL BE
DUPLICATED IN BRAILLE COMPLYING WITH 703.3. RAISED
CHARACTERS SHALL BE INSTALLED IN ACCORDANCE WITH
703.4.
- DEPTH: RAISED CHARACTERS SHALL BE 1/32 INCH
(0.8 MM) MINIMUM ABOVE THEIR BACKGROUND.
- CASE: CHARACTERS SHALL BE UPPERCASE.
- STYLE: CHARACTERS SHALL BE SANS SERIF.
CHARACTERS SHALL NOT BE ITALIC, OBLIQUE, SCRIPT,
HIGHLY DECORATIVE, OR OF OTHER UNUSUAL FORMS.
- CHARACTER PROPORTIONS: CHARACTERS SHALL BE
SELECTED FROM FONTS WHERE THE WIDTH OF THE
UPPERCASE LETTER “O” IS 55 PERCENT MINIMUM AND 110
PERCENT MAXIMUM OF THE HEIGHT OF THE UPPERCASE
LETTER “I”.
- CHARACTER PROPORTIONS: CHARACTER HEIGHT
MEASURED VERTICALLY FROM THE BASELINE OF THE
CHARACTER SHALL BE 5/8 INCH (16 MM) MINIMUM AND 2
INCHES (51 MM) MAXIMUM BASED ON THE HEIGHT OF THE
UPPERCASE LETTER “I”.
- STROKE THICKNESS: STROKE THICKNESS OF THE
UPPERCASE LETTER “I” SHALL BE 15 PERCENT
MAXIMUM OF THE HEIGHT OF THE CHARACTER.
- CHARACTER SPACING: CHARACTER SPACING SHALL BE
MEASURED BETWEEN THE TWO CLOSEST POINTS OF
ADJACENT RAISED CHARACTERS WITHIN A MESSAGE,
EXCLUDING WORD SPACES. WHERE CHARACTERS HAVE
RECTANGULAR CROSS SECTIONS, SPACING BETWEEN
INDIVIDUAL RAISED CHARACTERS SHALL BE 1/8 INCH (3.2
MM) MINIMUM AND 4 TIMES THE RAISED CHARACTER
STROKE WIDTH MAXIMUM. WHERE CHARACTERS HAVE
OTHER CROSS SECTIONS, SPACING BETWEEN INDIVIDUAL
RAISED CHARACTERS SHALL BE 1/16 INCH (1.6 MM)
MINIMUM AND 4 TIMES THE RAISED CHARACTER STROKE
WIDTH MAXIMUM AT THE BASE OF THE CROSS SECTIONS,
AND 1/8 INCH (3.2 MM) MINIMUM AND 4 TIMES THE RAISED
CHARACTER STROKE WIDTH MAXIMUM AT THE TOP OF
THE CROSS SECTIONS. CHARACTERS SHALL BE
SEPARATED FROM RAISED BORDERS AND DECORATIVE
ELEMENTS 3/8 INCH (9.5 MM) MINIMUM.
- LINE SPACING: SPACING BETWEEN THE BASELINES OF
SEPARATE LINES OF RAISED CHARACTERS WITHIN
A MESSAGE SHALL BE 135 PERCENT MINIMUM AND 170
PERCENT MAXIMUM OF THE RAISED CHARACTER HEIGHT.
BRAILLE:
BRAILLE SHALL BE CONTRACTED (GRADE 2) AND SHALL COMPLY
WITH 703.3 AND 703.4.
- DIMENSIONS AND CAPITALIZATION: BRAILLE DOTS SHALL
HAVE A DOMED OR ROUNDED SHAPE AND SHALL COMPLY
WITH TABLE 703.3.1. THE INDICATION OF AN UPPERCASE
LETTER OR LETTERS SHALL ONLY BE USED BEFORE THE
FIRST WORD OF SENTENCES, PROPER NOUNS AND
NAMES, INDIVIDUAL LETTERS OF THE ALPHABET, INITIALS,
AND ACRONYMS.
- POSITION: BRAILLE SHALL BE POSITIONED BELOW THE
CORRESPONDING TEXT. IF TEXT IS MULTI-LINED, BRAILLE
SHALL BE PLACED BELOW THE ENTIRE TEXT. BRAILLE
SHALL BE SEPARATED 3/8 INCH (9.5 MM) MINIMUM FROM A
ANY OTHER TACTILE CHARACTERS AND 3/8 INCH (9.5 MM)
MINIMUM FROM RAISED BORDERS AND DECORATIVE
ELEMENTS.
INSTALLATION HEIGHT AND LOCATION:
SIGNS WITH TACTILE CHARACTERS SHALL COMPLY WITH 703.4.
- HEIGHT ABOVE FINISH FLOOR OR GROUND: TACTILE
CHARACTERS ON SIGNS SHALL BE LOCATED 48 INCHES
(1220 MM) MINIMUM ABOVE THE FINISH FLOOR OR
GROUND SURFACE, MEASURED FROM THE BASELINE OF
THE LOWEST TACTILE CHARACTER AND 60 INCHES (1525
MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND
SURFACE, MEASURED FROM THE BASELINE OF THE
HIGHEST TACTILE CHARACTER.
- LOCATION: WHERE A TACTILE SIGN IS PROVIDED AT A
DOOR, THE SIGN SHALL BE LOCATED ALONGSIDE THE
DOOR AT THE LATCH SIDE. WHERE A TACTILE SIGN IS
PROVIDED AT DOUBLE DOORS WITH ONE ACTIVE LEAF,
THE SIGN SHALL BE LOCATED ON THE INACTIVE LEAF.
WHERE A TACTILE SIGN IS PROVIDED AT DOUBLE DOORS
WITH TWO ACTIVE LEAFS, THE SIGN SHALL BE LOCATED
TO THE RIGHT OF THE RIGHT HAND DOOR. WHERE THERE
IS NO WALL SPACE AT THE LATCH SIDE OF A SINGLE
DOOR OR AT THE RIGHT SIDE OF DOUBLE DOORS, SIGNS
SHALL BE LOCATED ON THE NEAREST ADJACENT WALL.
SIGNS CONTAINING TACTILE CHARACTERS SHALL BE
LOCATED SO THAT A CLEAR FLOOR SPACE OF 18 INCHES
(455 MM) MINIMUM BY 18 INCHES (455 MM) MINIMUM,
CENTERED ON THE TACTILE CHARACTERS, IS PROVIDED
BEYOND THE ARC OF ANY DOOR SWING BETWEEN THE
CLOSED POSITION AND 45 DEGREE OPEN POSITION.
SCALE:G-005 6" = 1'-0"
2 FED RESTROOM WALL ID
SCALE:G-005 12" = 1'-0"
1 TYPICAL INTERIOR SIGN INSTALLATIONS
SCALE: NOT TO SCALE
SCALE: NOT TO SCALE
N O
D
ES
C
R
IP
TI
O
N D
AT
E
AP
PR
S
U B M
IT
TA
L
/0 1/
S
U B M
IT
TA
L
/3 0/
FI
N
AL
S U
BM
IT
TA
L
/3
1/
AD-103
ENLARGED DEMOLITION FLOOR PLAN
AD-103
ENLARGED DEMOLITION FLOOR PLAN
1 1
REQUIRED EXTERIOR SCOPE OF WORK IS NOTED ON
SUBSEQUENT DRAWINGS AS REFERENCED AND AS NOTED ON
MEP AND STRUCTURAL DRAWINGS.
SHEET NOTES
1.
(E) BUILDING ENTRY
(E) PARKING LOT
(E) ROOF OVERHANG
(E) LANDSCAPING
KEY NOTES
A
C
C-38168
STEVEN
GRIST
7-31-2021
DATE
RENEWAL
RCHITECT
DESNECIL
AL I FOR
N
IA
FOETAT
S
7 FREELON ST
SAN FRANCISCO,
CA 94107
AS INDICATED
54321
1 54321
D
C
B
A
D
C
B
A
A/E INFO
T: 415.762.8388 www.aetypic.com
SEAL
SHEET OF
NAVFAC DRAWING NO.
CONTRACT NO.
EPROJECT NO.
SCALE
APPROVED
FOR COMMANDER NAVFAC
ACTIVITY
SATISFACTORY TO DATE / /
DES DRW CHK
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
DE
PA
RT
ME
NT
O
F
TH
E
NA
VY
NA
VA
L F
AC
ILI
TI
ES
E
NG
IN
EE
RI
NG
C
OM
MA
ND
N
AV
AL
F
AC
IL
IT
IE
S
EN
G
IN
EE
RI
NG
C
O M
M
AN
D
SO
U
TH
W
ES
T
NA
VA
L S
TA
TI
ON
S
AN
D
IE
GO
SA
N
DI
EG
O, C A
3/
/2
9:
:0
AM
AD-101
DE
M
O
LI
TI
O
N
SI
TE
P
LA
N
9th
R
ES
ER
VE
IN
TE
RI
OR
R
EN
OV
AT
IO
N
PR
OJ
EC
TS
BU
ILD
IN
G
0 -
C
BC
S
TR
AV
IS
A
IR
F
OR
CE
B
AS
E
D.E.
D.T. A.S.
JONNY OCHOA
N62473-16-D-1801
FA
IR
FI
EL
D, C
AL
IF
OR
NI
A
SCALE:AD-101 3/64" = 1'-0"
1 DEMOLITION SITE PLAN
32'16' 64'0
SCALE: 3/64" = 1'-0"
32'16' 64'0
SCALE: 3/64" = 1'-0"
PLAN
NORTH
TRUE
NORTH
N O
D
ES
C
R
IP
TI
O
N D
AT
E
AP
PR
S
U B M
IT
TA
L
/0 1/
S
U B M
IT
TA
L
/3 0/
FI
N
AL
S U
BM
IT
TA
L
/3
1/
12A
ABCD B.2EFGHH8JK
AD-103
ENLARGED DEMOLITION FLOOR PLAN
1 ENLARGED DEMOLITION REFLECTED CEILING PLAN
AD-104
AD-103
ENLARGED DEMOLITION FLOOR PLAN
AD-103
ENLARGED DEMOLITION FLOOR PLAN
2 ENLARGED DEMOLITION REFLECTED CEILING PLAN
AD-104
3 ENLARGED DEMOLITION REFLECTED CEILING PLAN
AD-104
WORK REQUIRED IS NOTED ON ENLARGED PLANS AND AS
SHOWN ON MEP DRAWINGS.
SHEET NOTES
1.
A
C
C-38168
STEVEN
GRIST
7-31-2021
DATE
RENEWAL
RCHITECT
DESNECIL
AL I FOR
N
IA
FOETAT
S
7 FREELON ST
SAN FRANCISCO,
CA 94107
AS INDICATED
54321
1 54321
D
C
B
A
D
C
B
A
A/E INFO
T: 415.762.8388 www.aetypic.com
SEAL
SHEET OF
NAVFAC DRAWING NO.
CONTRACT NO.
EPROJECT NO.
SCALE
APPROVED
FOR COMMANDER NAVFAC
ACTIVITY
SATISFACTORY TO DATE / /
DES DRW CHK
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
DE
PA
RT
ME
NT
O
F
TH
E
NA
VY
NA
VA
L F
AC
ILI
TI
ES
E
NG
IN
EE
RI
NG
C
OM
MA
ND
N
AV
AL
F
AC
IL
IT
IE
S
EN
G
IN
EE
RI
NG
C
O M
M
AN
D
SO
U
TH
W
ES
T
NA
VA
L S
TA
TI
ON
S
AN
D
IE
GO
SA
N
DI
EG
O, C A
3/
/2
9:
:0
AM
AD-102
D
EM
O
LI
TI
O
N K
EY
P
LA
N
9th
R
ES
ER
VE
IN
TE
RI
OR
R
EN
OV
AT
IO
N
PR
OJ
EC
TS
BU
ILD
IN
G
0 -
C
BC
S
TR
AV
IS
A
IR
F
OR
CE
B
AS
E
D.E.
D.T. A.S.
JONNY OCHOA
N62473-16-D-1801
FA
IR
FI
EL
D, C
AL
IF
OR
NI
A
SCALE:AD-102 3/32" = 1'-0"
1 DEMOLITION KEY PLAN
16'8' 32'0
SCALE: 3/32" = 1'-0"
PLAN
NORTH
TRUE
NORTH
N O
D
ES
C
R
IP
TI
O
N D
AT
E
AP
PR
S
U B M
IT
TA
L
/0 1/
S
U B M
IT
TA
L
/3 0/
FI
N
AL
S U
BM
IT
TA
L
/3
1/
KEY NOTES
1 (E) VEGETATION TO BE REMOVED
(E) EXTERIOR WALL
(E) EXTERIOR FULL HEIGHT STOREFRONT WINDOW
(E) SIDEWALK TO REMAIN
(E) CONCRETE FLATWORK TO BE REMOVED, SMD
(E) FLAGPOLE TO BE REMOVED AND SAVED FOR
REINSTALLATION AT (N) LOCATION
(E) BUILDING ENTRY
CLEAR (E) LANDSCAPING AS REQ'D FOR CONSTRUCTION OF
(N) MECHANICAL ENCLOSURE, RELOCATE (E) IRRIGATION AS
REQUIRED
(E) EAVE
PARTIAL DEMOLITION OF (E) EXTERIOR WALL FOR
PENENTRATION OF (N) MECHANICAL DUCTWORK, VERIFY
LOCATIONS OF (E) STRUCTURAL ELEMENTS IN WALL, SMD
COURTYARD
(E) STEEL COLUMN, VERIFY LOCATION
LEGEND
(E) CONDITION
(E) CONDITION
TO BE DEMOLISHED
INDICATES NO ARCHITECTURAL
SCOPE OF WORK
SHEET NOTES
DEMOLISH (E) RESTROOM FLOOR FINISH DOWN TO THE
(E) STRUCTURAL CONCRETE SLAB. CLEAN CONCRETE AND
PREPARE FOR NEW FLOOR PER FINISH SCHEDULE.
REMOVE ALL (E) RESTROOM AND SHOWER WALL FINISHES TO
STUD.
REMOVE/DEMOLISH ALL (E) RESTROOM PLUMBING FIXTURES,
TOILET PARTITIONS, ACCESSORIES, LIGHTING, SIGNAGE, AND
OTHER APPURTENANCES. SEE MEP DRAWINGS FOR
ADDITIONAL INFORMATION.
SSD FOR FLOOR CONCRETE INFILL DETAIL.
SEE MEP DRAWINGS FOR SCOPE OF WORK FOR DEMOLITION
OF (E) RESTROOM PLUMBING FIXTURES, MECHANICAL
DUCTWORK & REGISTER GRILLS, (E) ELECTRICAL WIRING AND
OUTLETS, SED.
VERIFY WITH THE KO PRIOR TO DEMOLITION OF WHICH ITEMS,
SIGNAGE, ACCESSORIES, ETC ARE TO BE TURNED OVER TO
THE GOVERNMENT OR REMOVED FROM THE SITE.
REMOVE ALL (E) WALL FINISHES TO STUDS.
1.
2.
3.
4.
5.
6.
7.
DEFG
JANITOR
CLOSET
MENS
RESTROOM
WOMENS
RESTROOM
SHOWER
109A
SHOWER
109A
RESOURCE
CENTER
PROJ./STOR.
STOR.
CONF./CLASSROOM
CONF./CLASSROOM
MECH/ELEC
LOBBY
VESTIBULE
FD FD
FD
FD
DEFG
HHD
HALL
LOBBY
HALL
S-3 PLANS
TYP
TYP
HH8JK
4 7
BDE CDR
HALL
LOBBY
RESOURCE
CENTER
PROJ./STOR.
TYP
A
C
C-38168
STEVEN
GRIST
7-31-2021
DATE
RENEWAL
RCHITECT
DESNECIL
AL I FOR
N
IA
FOETAT
S
7 FREELON ST
SAN FRANCISCO,
CA 94107
AS INDICATED
54321
1 54321
D
C
B
A
D
C
B
A
A/E INFO
T: 415.762.8388 www.aetypic.com
SEAL
SHEET OF
NAVFAC DRAWING NO.
CONTRACT NO.
EPROJECT NO.
SCALE
APPROVED
FOR COMMANDER NAVFAC
ACTIVITY
SATISFACTORY TO DATE / /
DES DRW CHK
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
DE
PA
RT
ME
NT
O
F
TH
E
NA
VY
NA
VA
L F
AC
ILI
TI
ES
E
NG
IN
EE
RI
NG
C
OM
MA
ND
N
AV
AL
F
AC
IL
IT
IE
S
EN
G
IN
EE
RI
NG
C
O M
M
AN
D
SO
U
TH
W
ES
T
NA
VA
L S
TA
TI
ON
S
AN
D
IE
GO
SA
N
DI
EG
O, C A
3/
/2
9:
:0
AM
AD-103
DE
M
O
LI
TI
O
N
FL
O O
R
PL
AN
S
9th
R
ES
ER
VE
IN
TE
RI
OR
R
EN
OV
AT
IO
N
PR
OJ
EC
TS
BU
ILD
IN
G
0 -
C
BC
S
TR
AV
IS
A
IR
F
OR
CE
B
AS
E
D.E.
D.T. A.S.
JONNY OCHOA
N62473-16-D-1801
FA
IR
FI
EL
D, C
AL
IF
OR
NI
A
0 2' 4' 8'
SCALE: 1/4" = 1'-0"
PLAN
NORTH
SCALE:AD-103 1/4" = 1'-0"A-301
1 DEMOLITION FLOOR PLAN - RESTROOMS
TRUE
NORTH
SCALE:AD-103 1/8" = 1'-0"AD-101
2 DEMOLITION PLAN - COURTYARD
SCALE:AD-103 1/8" = 1'-0"AD-101
3 DEMOLITION PLAN - EXTERIOR
N O
D
ES
C
R
IP
TI
O
N D
AT
E
AP
PR
S
U B M
IT
TA
L
/0 1/
S
U B M
IT
TA
L
/3 0/
FI
N
AL
S U
BM
IT
TA
L
/3
1/
8'4' 16'0
SCALE: 1/8"=1'-0"
AD-101
(E) EXTERIOR WALL
(E) EXTERIOR STOREFRONT
(E) EAVE
ADJUST/CUT/TRIM EXISTING (E) GYP BD CEILING AS REQ'D
FOR INSTALLATION OF (N) LIGHT FIXTURES & REGISTERS,
SED & SMD
ADJUST (E) SUSPENDED CEILING SYSTEM AS REQUIRED
FOR (N) MECHANICAL SHAFT
(E) ACCESS PANEL TO REMAIN
(E) GYP BD CEILING TO REMAIN, PATCH AND REPAIR AS
REQ'D DUE TO DEMOLITION OF (E) WALL AND
INSTALLATION OF (N) LIGHT FIXTURES AND REGISTERS,
SED & SMD
KEY NOTES
LEGEND
(E) CONDITION
GYP BD
CEILING LIGHT
FIXTURE
MECHANICAL
REGISTER
WALL MOUNTED
LIGHT FIXTURE
(E) CONDITION
TO BE DEMOLISHED
INDICATES NO
ARCHITECTURAL
SCOPE OF WORK
FIXTURES, LIGHTING, AND REGISTERS SHOWN FOR
REFERENCE ONLY, SEE MEP DRAWINGS FOR ADDITIONAL
INFORMATION.
EXISTING FIRE SPRINKLER SYSTEM TO REMAIN UON, PROTECT
DURING DEMOLITION.
SHEET NOTES:
1.
2.
DEFG
DEFG
3 TYP
TYP
TYP
HH8JK
A
C
C-38168
STEVEN
GRIST
7-31-2021
DATE
RENEWAL
RCHITECT
DESNECIL
AL I FOR
N
IA
FOETAT
S
7 FREELON ST
SAN FRANCISCO,
CA 94107
AS INDICATED
54321
1 54321
D
C
B
A
D
C
B
A
A/E INFO
T: 415.762.8388 www.aetypic.com
SEAL
SHEET OF
NAVFAC DRAWING NO.
CONTRACT NO.
EPROJECT NO.
SCALE
APPROVED
FOR COMMANDER NAVFAC
ACTIVITY
SATISFACTORY TO DATE / /
DES DRW CHK
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
DE
PA
RT
ME
NT
O
F
TH
E
NA
VY
NA
VA
L F
AC
ILI
TI
ES
E
NG
IN
EE
RI
NG
C
OM
MA
ND
N
AV
AL
F
AC
IL
IT
IE
S
EN
G
IN
EE
RI
NG
C
O M
M
AN
D
SO
U
TH
W
ES
T
NA
VA
L S
TA
TI
ON
S
AN
D
IE
GO
SA
N
DI
EG
O, C A
3/
/2
9:
:0
AM
AD-104
D
EM
O
LI
TI
O
N R
EF
LE
C
TE
D C
EI
LI
NG
P
LA
NS
9th
R
ES
ER
VE
IN
TE
RI
OR
R
EN
OV
AT
IO
N
PR
OJ
EC
TS
BU
ILD
IN
G
0 -
C
BC
S
TR
AV
IS
A
IR
F
OR
CE
B
AS
E
D.E.
D.T. A.S.
JONNY OCHOA
N62473-16-D-1801
FA
IR
FI
EL
D, C
AL
IF
OR
NI
A
PLAN
NORTH
SCALE:AD-104 1/4" = 1'-0"A-301
1 DEMOLITION REFLECTED CEILING PLAN
TRUE
NORTH
SCALE:AD-104 1/8" = 1'-0"AD-102
2 DEMOLITION REFLECTED CEILING PLAN - COURTYARD
SCALE:AD-104 1/8" = 1'-0"AD-102
3 DEMOLITION REFLECTED CEILING PLAN - EXTERIOR
N O
D
ES
C
R
IP
TI
O
N D
AT
E
AP
PR
S
U B M
IT
TA
L
/0 1/
S
U B M
IT
TA
L
/3 0/
FI
N
AL
S U
BM
IT
TA
L
/3
1/
0 2' 4' 8'
SCALE: 1/4" = 1'-0"
8'4' 16'0
AD-102
A-103
ENLARGED FLOOR PLAN
A-103
ENLARGED FLOOR PLAN
KEY NOTES
1 (E) BUILDING ENTRY
(E) PARKING LOT
(E) ROOF OVERHANG
(E) LANDSCAPING
MECHANICAL MAINTENANCE PAD, SMD & SSD
REQUIRED EXTERIOR SCOPE OF WORK IS NOTED ON
SUBSEQUENT DRAWINGS AS REFERENCED AND AS NOTED ON
MEP AND STRUCTURAL DRAWINGS.
SHEET NOTES
1.
A
C
C-38168
STEVEN
GRIST
7-31-2021
DATE
RENEWAL
RCHITECT
DESNECIL
AL I FOR
N
IA
FOETAT
S
7 FREELON ST
SAN FRANCISCO,
CA 94107
AS INDICATED
54321
1 54321
D
C
B
A
D
C
B
A
A/E INFO
T: 415.762.8388 www.aetypic.com
SEAL
SHEET OF
NAVFAC DRAWING NO.
CONTRACT NO.
EPROJECT NO.
SCALE
APPROVED
FOR COMMANDER NAVFAC
ACTIVITY
SATISFACTORY TO DATE / /
DES DRW CHK
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
DE
PA
RT
ME
NT
O
F
TH
E
NA
VY
NA
VA
L F
AC
ILI
TI
ES
E
NG
IN
EE
RI
NG
C
OM
MA
ND
NA
VA
L
FA
CI
LI
TI
ES
E N
G
IN
EE
RI
NG
C
O M
M
AN
D
SO
UT
H W
ES
T
NA
VA
L S
TA
TI
ON
S
AN
D
IE
GO
SA
N
DI
EG
O, C A
3/
/2
9:
:5
AM
A-101
SI
TE
P
LA
N
9th
R
ES
ER
VE
IN
TE
RI
OR
R
EN
OV
AT
IO
N
PR
OJ
EC
TS
BU
ILD
IN
G
0 -
C
BC
S
TR
AV
IS
A
IR
F
OR
CE
B
AS
E
D.E.
D.T. A.S.
JONNY OCHOA
N62473-16-D-1801
FA
IR
FI
EL
D, C
AL
IF
OR
NI
A
32'16' 64'0
SCALE: 3/64" = 1'-0"
32'16' 64'0
SCALE: 3/64" = 1'-0"
NORTH
SCALE:A-101 3/64" = 1'-0"
1 SITE PLAN
TRUE
NORTH
N O
D
ES
C
R
IP
TI
O
N D
AT
E
AP
PR
S
U B M
IT
TA
L
/0 1/
S
U B M
IT
TA
L
/3 0/
FI
N
AL
S U
BM
IT
TA
L
/3
1/
12A
ABCD B.2EFGHH8JK
LOBBY
VESTIBULE
MENS
RESTROOM
RESOURCE
CENTER
PROJ./STOR.
104 CONF./CLASSROOM
CONF./CLASSROOM
MECH/ELEC
STOR.
JANITOR
CLOSET
WOMENS
RESTROOM
HALL
HALL
HALL
S-1
S-4
S-3 PLANS
PLANS
OFFICER
PLANS
OFFICER
CONFERENCE
CHAPLAIN
ASST S-3
IM OFFICER
FILE SERVER
COMM RM.
S-3
S-4
STORAGE
ELEC.
VAULT
S-3
S-3 SCM
S-3
S-2
S-2
S-4
S-1/MPO
CSM
XO
SECT'Y
BDE CDR
HHD
HHD
SHOWER
109A
A-103
ENLARGED FLOOR PLAN
1 ENLARGED REFLECTED CEILING PLAN
A-104
A-103
ENLARGED FLOOR PLAN
A-103
ENLARGED FLOOR PLAN
3 ENLARGED REFLECTED CEILING PLAN
A-104
2 ENLARGED REFLECTED CEILING PLAN
A-104
REQUIRED EXTERIOR SCOPE OF WORK IS NOTED ON
SUBSEQUENT DRAWINGS AS REFERENCED AND AS NOTED ON
MEP AND STRUCTURAL DRAWINGS.
SHEET NOTES
1.
A
C
C-38168
STEVEN
GRIST
7-31-2021
DATE
RENEWAL
RCHITECT
DESNECIL
AL I FOR
N
IA
FOETAT
S
7 FREELON ST
SAN FRANCISCO,
CA 94107
AS INDICATED
54321
1 54321
D
C
B
A
D
C
B
A
A/E INFO
T: 415.762.8388 www.aetypic.com
SEAL
SHEET OF
NAVFAC DRAWING NO.
CONTRACT NO.
EPROJECT NO.
SCALE
APPROVED
FOR COMMANDER NAVFAC
ACTIVITY
SATISFACTORY TO DATE / /
DES DRW CHK
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
DE
PA
RT
ME
NT
O
F
TH
E
NA
VY
NA
VA
L F
AC
ILI
TI
ES
E
NG
IN
EE
RI
NG
C
OM
MA
ND
N
AV
AL
F
AC
IL
IT
IE
S
EN
G
IN
EE
R
IN
G
C O
M M
AN
D
-S O
U
TH
W
ES
T
NA
VA
L S
TA
TI
ON
S
AN
D
IE
GO
SA
N
DI
EG
O, C
A
3/
/2
9:
:5
AM
A-102
K
EY
F
LO
O R
P
LA
N
9th
R
ES
ER
VE
IN
TE
RI
OR
R
EN
OV
AT
IO
N
PR
OJ
EC
TS
BU
ILD
IN
G
0 -
C
BC
S
TR
AV
IS
A
IR
F
OR
CE
B
AS
E
D.E.
D.T. A.S.
JONNY OCHOA
N62473-16-D-1801
FA
IR
FI
EL
D, C
AL
IF
OR
NI
A
SCALE:A-102 3/32" = 1'-0"
1 KEY FLOOR PLAN
16'8' 32'0
SCALE: 3/32" = 1'-0"
PLAN
NORTH
TRUE
NORTH
N O
D
ES
C
R
IP
TI
O
N D
AT
E
AP
PR
S
U B M
IT
TA
L
/0 1/
S
U B M
IT
TA
L
/3 0/
FI
N
AL
S U
BM
IT
TA
L
/3
1/
DEFG
A-401
3N
A-401
1N
A-402
2N
2W
2S
2E
3E
3S
3W
1S
1E1W
15"
A-501
TYP
1 22
TYP
RESOURCE
CENTER
CONF./CLASSROOM
PROJ./STOR.
CONF./CLASSROOM
106 MECH/ELEC
STOR.
LOBBY
VESTIBULE
JANITOR
CLOSET
MENS
RESTROOM
SHOWER
109A
WOMENS
RESTROOM
ø 5' - 0"
FD
FD
FD
A-401
2N
2S
A-402
1S
1W
5'
2'
C
LE
AR
5'
EQ
EQ
5' - 0"
A-501
A-501
2'
2'
7" 2'
6"
CLEAR
5' - 0"
A-501
SPSP
SP
A-501
A-501
A-501
A-501
SEE SHEET G-004 FOR ACCESSIBILITY CLEARANCES AND
REQUIREMENTS.
SEE SHEET G-004 FOR ACCESSORY MOUNTING HEIGHTS.
SEE SHEET G-005 FOR ACCESSIBILITY SIGNAGE STANDARDS.
SEE SHEET A-601 FOR ROOM FINISH SCHEDULE.
FILL ALL SLAB HOLES WHERE PLUMBING ITEMS WERE
REMOVED, SPD.
TILE PATTERNS SHOWN FOR REFERENCE ONLY, SEE TILE
START POINT FOR TILE LAYOUT.
FIXTURES SHOWN FOR REFERENCE ONLY, SEE MEP
DRAWINGS FOR ADDITIONAL INFORMATION.
SEE MEP DRAWINGS FOR ADDITIONAL INFORMATION AND
EQUIPMENT LOCATIONS.
SEE DETAIL FOR TYPICAL STUD WALL BACKING.
FOR TYPICAL INTERIOR DOOR JAMB AND HEAD, SEE DETAIL
SEE DETAIL FOR TYPICAL GRAB BAR MOUNTING.
FOR TYPICAL MOUNTING, SEE DETAIL
SEE DETAIL FOR SHOWER FLOOR DETAIL.
SHEET NOTES
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
LEGEND
(E) CONDITION (N) WORK
INDICATES AREA WITH
NO ARCHITECTURAL
SCOPE
KEY NOTES
ACCESSIBLE CLEARANCE
THRESHOLD AT RESTROOM ENTRANCE, SEE
(E) EXTERIOR WALL
DIRECTION OF MIN SLOPE, SSD
ALIGN
8'-0" HIGH CMU WALL WITH STUCCO FINISH TO MATCH (E)
COLOR, PROVIDE WEEP HOLES @ 4' - 0" OC, SSD FOR
ADDITIONAL INFORMATION
DOUBLE METAL GATES, SEE DETAILS FOR ADDITIONAL
INFORMATION
OUTLINE OF CONCRETE MAINTENANCE PAD SHOWN FOR
REFERENCE, SMD AND SSD
(E) SIDEWALK
THRESHOLD AT SHOWER ENTRANCE, SEE
(E) EXTERIOR STOREFRONT
CONCRETE FLATWORK, SSD
RELOCATE (E) FLAGPOLE TO (N) CONCRETE SLAB, SSD
(E) COURTYARD CONCRETE PATIO
(E) BUILDING ENTRY
PROVIDE PAINTED (P-1) 3'-0" X 7'-0" (1 3/4" THICK) HM DOOR
AND FRAME WITH THE FOLLOWING HARDWARE:
3 HINGES
1 RESTROOM FUNCTION
1 CLOSER
1 KICKPLATE
1 FLOOR STOP
1 WALL STOP
1 DOOR SEALS
3 DOOR SILENCERS
1 THRESHOLD
PROVIDE 5/8" SOUND-REDUCING TYPE "X" GYP. BD.
A-301
DEFG
HHD
HALL
LOBBY
HALL
S-3 PLANS
PLANS
OFFICER
TYP
A-501
TYP
TYP
3' - 8" 3' - 8"
HH8JK
A-201
A-201
A-201
A-301
PROJ./STOR.
RESOURCE
CENTER
4"
6' - 0"
LOBBY
HALL
BDE CDR
0'
4"
4' - 0" 36' - 0"
A-501
0"
10' - 5"
EQ EQ
5'
0"
6' - 0"
2' - 2" A
C
C-38168
STEVEN
GRIST
7-31-2021
DATE
RENEWAL
RCHITECT
DESNECIL
AL I FOR
N
IA
FOETAT
S
7 FREELON ST
SAN FRANCISCO,
CA 94107
AS INDICATED
54321
1 54321
D
C
B
A
D
C
B
A
A/E INFO
T: 415.762.8388 www.aetypic.com
SEAL
SHEET OF
NAVFAC DRAWING NO.
CONTRACT NO.
EPROJECT NO.
SCALE
APPROVED
FOR COMMANDER NAVFAC
ACTIVITY
SATISFACTORY TO DATE / /
DES DRW CHK
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
DE
PA
RT
ME
NT
O
F
TH
E
NA
VY
NA
VA
L F
AC
ILI
TI
ES
E
NG
IN
EE
RI
NG
C
OM
MA
ND
N
AV
AL
F
AC
IL
IT
IE
S
EN
G
IN
EE
RI
NG
C
O M
M
AN
D
SO
U
TH
W
ES
T
NA
VA
L S
TA
TI
ON
S
AN
D
IE
GO
SA
N
DI
EG
O, C A
3/
/2
9:
:5
AM
A-103
FL
O
O R
P
LA
N S
9th
R
ES
ER
VE
IN
TE
RI
OR
R
EN
OV
AT
IO
N
PR
OJ
EC
TS
BU
ILD
IN
G
0 -
C
BC
S
TR
AV
IS
A
IR
F
OR
CE
B
AS
E
D.E.
D.T. A.S.
JONNY OCHOA
N62473-16-D-1801
FA
IR
FI
EL
D, C
AL
IF
OR
NI
A
SCALE:A-103 1/4" = 1'-0"
1 FLOOR PLAN - RESTROOMS 0 2' 4' 8'
SCALE: 1/4" = 1'-0"
PLAN
NORTH
TRUE
NORTH
SCALE:A-103 1/8" = 1'-0"
2 FLOOR PLAN - COURTYARD
SCALE:A-103 1/8" = 1'-0"
3 FLOOR PLAN - EXTERIOR
8'4' 16'0
SCALE: 1/8"=1'-0"
N O
D
ES
C
R
IP
TI
O
N D
AT
E
AP
PR
S
U B M
IT
TA
L
/0 1/
S
U B M
IT
TA
L
/3 0/
FI
N
AL
S U
BM
IT
TA
L
/3
1/
SEE SHEET A-601 FOR ROOM FINISH SCHEDULE.
FIXTURES, LIGHTING, AND REGISTERS SHOWN FOR
REFERENCE ONLY, SEE MEP DRAWINGS FOR ADDITIONAL
INFORMATION
SHEET NOTES
1.
2.
LEGEND
(E) CONDITION
(N) CONDITION
CEILING LIGHT
FIXTURE
GYPSUM BOARD
INDICATES NO
ARCHITECTURAL
SCOPE OF WORK
(E) CEILING ACCESS PANEL
(E) GYP BD CEILING TO REMAIN, PATCH AND REPAIR AS
REQD DUE TO DEMOLITION OF (E) WALL AND
INSTALLATION OF (N) LIGHT FIXTURES AND REGISTERS,
SED & SMD
(E) EXTERIOR WALL
E) EXTERIOR STOREFRONT
(E) EAVE
(E) GYP BD CEILING TO REMAIN, PATCH AND REPAIR AS
REQD, ADJUST/CUT/TRIM AS REQD FOR INSTALLATION OF
(N) LIGHT FIXTURES & REGISTERS, SED & SMD
ADJUST (E) SUSPENDED CEILING SYSTEM AS REQUIRED
FOR (N) MECHANICAL SHAFT
MAINTAIN MIN REQD CLEARANCE FROM CEILING ACCESS
PANEL
KEY NOTES
DEFG
EQ EQ 2' - 0"
2' - 0"
1'
1' - 6"
2'
6"
3' - 0"EQ EQ6"
1'
6" 1'
6" EQ
EQ
EQ
1'
3"
EQ
EQ
0' - 6"
EQ
2'
1 1
EQ
EQ
X X
HH8JK
DEFG
A
C
C-38168
STEVEN
GRIST
7-31-2021
DATE
RENEWAL
RCHITECT
DESNECIL
AL I FOR
N
IA
FOETAT
S
7 FREELON ST
SAN FRANCISCO,
CA 94107
AS INDICATED
54321
1 54321
D
C
B
A
D
C
B
A
A/E INFO
T: 415.762.8388 www.aetypic.com
SEAL
SHEET OF
NAVFAC DRAWING NO.
CONTRACT NO.
EPROJECT NO.
SCALE
APPROVED
FOR COMMANDER NAVFAC
ACTIVITY
SATISFACTORY TO DATE / /
DES DRW CHK
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
DE
PA
RT
ME
NT
O
F
TH
E
NA
VY
NA
VA
L F
AC
ILI
TI
ES
E
NG
IN
EE
RI
NG
C
OM
MA
ND
N
AV
AL
F
AC
IL
IT
IE
S
EN
G
IN
EE
R
IN
G
C O
M M
AN
D
SO
U
TH
W
ES
T
NA
VA
L S
TA
TI
ON
S
AN
D
IE
GO
SA
N
DI
EG
O, C
A
3/
/2
9:
:5
AM
A-104
R
EF
LE
C
TE
D
C
EI
LI
N
G P
LA
N
S
9th
R
ES
ER
VE
IN
TE
RI
OR
R
EN
OV
AT
IO
N
PR
OJ
EC
TS
BU
ILD
IN
G
0 -
C
BC
S
TR
AV
IS
A
IR
F
OR
CE
B
AS
E
D.E.
D.T. A.S.
JONNY OCHOA
N62473-16-D-1801
FA
IR
FI
EL
D, C
AL
IF
OR
NI
A
0 2' 4' 8'
SCALE: 1/4" = 1'-0"
PLAN
NORTH
SCALE:A-104 1/4" = 1'-0"
1 REFLECTED CEILING PLAN - RESTROOMS
TRUE
NORTH
SCALE:A-104 1/8" = 1'-0"
3 REFLECTED CEILING PLAN - EXTERIOR
SCALE:A-104 1/8" = 1'-0"
2 REFLECTED CEILING PLAN - COURTYARD
N O
D
ES
C
R
IP
TI
O
N D
AT
E
AP
PR
S
U B M
IT
TA
L
/0 1/
S
U B M
IT
TA
L
/3 0/
FI
N
AL
S U
BM
IT
TA
L
/3
1/
8'4' 16'0
TYP
8'
0"
H
8'
0"
PROTECT ALL (E) ELEMENTS UON
SHEET NOTES
1.
A-502
(E) STANDING SEAM METAL ROOF
(E) STANDING SEAM METAL WALL PANEL
(E) EXTERIOR WALL WITH STUCCO FINISH
(E) FASCIA
8'-0" HIGH MECHANICAL ENCLOSURE CMU WALL WITH
STUCCO FINISH TO MATCH (E) COLOR, PROVIDE WEEP
HOLES @ 4'-0" OC, SSD FOR ADDITIONAL INFORMATION
DOUBLE METAL GATES, SEE DETAILS FOR ADDITIONAL
INFORMATION
CONCRETE FLATWORK
FLAG POLE
KEY NOTES
A
C
C-38168
STEVEN
GRIST
7-31-2021
DATE
RENEWAL
RCHITECT
DESNECIL
AL I FOR
N
IA
FOETAT
S
7 FREELON ST
SAN FRANCISCO,
CA 94107
AS INDICATED
54321
1 54321
D
C
B
A
D
C
B
A
A/E INFO
T: 415.762.8388 www.aetypic.com
SEAL
SHEET OF
NAVFAC DRAWING NO.
CONTRACT NO.
EPROJECT NO.
SCALE
APPROVED
FOR COMMANDER NAVFAC
ACTIVITY
SATISFACTORY TO DATE / /
DES DRW CHK
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
DE
PA
RT
ME
NT
O
F
TH
E
NA
VY
NA
VA
L F
AC
ILI
TI
ES
E
NG
IN
EE
RI
NG
C
OM
MA
ND
N
AV
AL
F
AC
IL
IT
IE
S
EN
G
IN
EE
R
IN
G
C O
M M
AN
D
SO
U
TH
W
ES
T
NA
VA
L S
TA
TI
ON
S
AN
D
IE
GO
SA
N
DI
EG
O, C
A
3/
/2
9:
:5
AM
A-201
EX
TE
RI
O
R
EL
EV
AT
IO
NS
9th
R
ES
ER
VE
IN
TE
RI
OR
R
EN
OV
AT
IO
N
PR
OJ
EC
TS
BU
ILD
IN
G
0 -
C
BC
S
TR
AV
IS
A
IR
F
OR
CE
B
AS
E
D.E.
D.T. A.S.
JONNY OCHOA
N62473-16-D-1801
FA
IR
FI
EL
D, C
AL
IF
OR
NI
A
SCALE:A-201 3/16" = 1'-0"
2 PARTIAL NORTH ELEVATION
SCALE:A-201 3/16" = 1'-0"
1 PARTIAL WEST ELEVATION 8'4' 16'0
SCALE: 1/8"=1'-0"SCALE:A-201 3/16" = 1'-0"
3 EXTERIOR MECHANICAL ENCLOSURE
N O
D
ES
C
R
IP
TI
O
N D
AT
E
AP
PR
S
U B M
IT
TA
L
/0 1/
S
U B M
IT
TA
L
/3 0/
FI
N
AL
S U
BM
IT
TA
L
/3
1/
PROTECT ALL (E) ELEMENTS UON
SEE MEP DRAWINGS FOR ADDITIONAL INFORMATION AND
EQUIPMENT LOCATIONS, SSD FOR ADDITIONAL INFORMATION.
SHEET NOTES:
1.
2.
(E) ROOF STRUCTURE
(E) EXTERIOR WALL
DOUBLE METAL GATES, SEE DETAILS FOR ADDITIONAL
INFORMATION
8'-0" HIGH MECHANICAL ENCLOSURE CMU WALL WITH
EIFS TO MATCH (E) COLOR, PROVIDE WEEP HOLES @ 4'-0"
OC, SSD FOR ADDITIONAL…