Specifications: 500 Gallon Double Wall Skid Tank (Rounded Tanks with attached structural supports/footings)

Construction Code: U/L 142 Material Type: Mild Carbon Steel A1011 or A-36 Type Tank Thickness: 12 Gauge Structural Supports: Angle Iron and Channel Iron Design and Operating Temperature: Ambient Conditions Design and Operating Pressure: Atmospheric or 1.0 psi Fitting Type: NPT Threadlets Discharge: ½” Discharge/outlet located at the bottom/end of the tank Internal Coating: Bare Metal (no coating) External Coating: Red Oxide Primer

Skid Dimensions Length: 6’ - 6’2” Width: 2’ – 2’ 2 ¼”

Fittings:

3 – 2” NPT

1 – 2” NPT Outer Shell Monitor Pipe (mounted at center bottom of tank – open to top of tank) 1 – 1” NPT Outer Shell Drain (mounted at center bottom of tank - opposite end of tank) 1 – 4” NPT + Inside EV 1 – 4” NPT + Outside EV 1 – Lifting Lug (center of tank) 1 – 2” NPT + T-Vent 1 – 2 ½” NPT + Fill Cap (back end of tank) All primary tank openings must be located on top of tank