Statement of Work.pdf

PDF 239 KB Posted

Attached to
Trane Chiller Maintenance Federal contract opportunity
Solicitation number
12505B23Q0091
Issued by
Department of Agriculture Agricultural Research Service Field Research Implementation and Information Delivery Midwest Area

View the file

Other files for this federal contract opportunity

Other files attached to Trane Chiller Maintenance, newest first.
File Type Posted
Provisions and Clauses Full and Open.docx DOCX document
OEM Maintenance Docs 3.pdf PDF
OEM Maintenance Docs 2.pdf PDF
OEM Maintenance Docs 1.pdf PDF
Wage Determination.pdf PDF
Provisions and Clauses.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Statement of Work (SOW) Project: Bldg 154 and 402 Support, Trane Chiller Maintenance

GENERAL INFORMATION

1.0 Scope of Work: The USDA National Centers for Animal Health, 1920 Dayton

Ave, Ames, IA, 50010 has a requirement for a 1-year base period contract with four 12 month option periods for seasonal maintenance to be performed on Chillers #6 and #7 in Bldg. 154 and the RTU at Bldg. 402. Seasonal maintenance on Bldg. 154 #6 Trane 1050 Ton Absorption Chiller (MN ABTF105GS, SN L06G03556) and Bldg. 154 #7 Trane 1050 Ton Absorption Chiller (MN ABTF105GS, SN L06G02675) and Bldg. 402. Roof Top Unit 12 ½ tons (PVW12M40800R, SN

CST1054).

2.0 Background: Seasonal maintenance on Bldg. 154 #6 Trane 1050 Ton Absorption

Chiller (MN ABTF105GS, SN L06G03556) and Bldg. 154 #7 Trane 1050 Ton Absorption Chiller (MN ABTF105GS, SN L06G02675) and Bldg. 402. Roof Top Unit 12 ½ tons (PVW12M40800R, SN CST1054).

CONTRACTOR REQUIREMENTS

3.0 Technical Requirements/Tasks:

Contractor/vendor Qualifications Work on/for this project shall be completed by technicians with at least 5 years of experience and fully trained and current on repair, rebuilding and service of Trane absorption chillers. All technicians shall be universally licensed by the EPA for refrigeration maintenance. All parts used by contractor will be OEM. Disposal of all parts and fluids will be done per EPA standards. All work shall result in a chiller in compliance with Trane corporate policy for field service of absorption chillers. Non- Trane contractors shall provide documentation in writing whereby the Trane Corporation acknowledges that Trane will provide contract maintenance and repairs service on the chillers as if the work was completed by Trane. Trane technicians trouble/service call response time for the warranty needs to be less than 24 hours. Bidders shall provide a list of at least 3 projects of similar size and scope. This documentation is to be provided with the proposal.

NCAH Equipment List Trane Equipment Location

ID Type Nominal Capacity

Model Number Serial Number

Bldg 154 CH-6 Steam 1,050 ABTF105GS L06G03556

Absorption Chiller

Tons

Bldg 154 CH-7 Steam Absorption

Chiller

1,050 Tons

ABTF105GS L06G02675

Bldg 402 RTU-1 Rooftop Unit 12 ½ Tons PVW12M40800R CST1054

INSPECTION AND MAINTENANCE PROGRAM

PERIOD OF COVERAGE

Base Year – 12 months Option Year 1 – 12 months following Base Year Option Year 2 – 12 months following Option Year 1 Option Year 3 – 12 months following Option Year 2 Option Year 4 – 12 months following Option Year 3

Option year #1 and option year #4 shall include Eddy Current testing for the evaporator and condenser on chillers #6 and #7.

The quote shall be inclusive of all site time and travel costs to include pricing for 16 hrs of additional service/trouble call associated with service/trouble calls and one 4-hour customer training session per year.

Note: Customer training session will consist of an on-the-job Training question/answer session led by the contractor on the chillers operation and chiller plant operations when requested by the USDA. The contractor shall provide list of topics and scope of training for roof top units and absorber chillers in the quote.

Equipment Maintenance Requirements Equipment: Chillers CH-6/CH-7 Location:

Building 154

III. Spring Start Up (April to May). One Spring Start up inspection will be performed including the following.

A. Purifier Purge System.

• Inspect air-cooled condenser coil and clean as needed.

• Perform purge system control check.

• Inspect the purge compressor belt and tighten if needed.

• Check purge pump-out system for proper operation.

• Change the purge compressor oil (Dispose of the used oil).

• Start-up purge and check for proper operation.

B. Basic Maintenance.

• Meg ohm bromide, refrigerant pump motors and record readings.

• Check Micro settings.

C. Electromechanical Pump Starters On Absorbers.

• Check and tighten all terminals as needed.

• Check condition of contacts for wear, pitting, etc, and record condition.

D. Chiller Start Up and Check Out.

• Start chiller up, check out and log.

General Items Review maintenance procedures with USRO Supervisor or Work Leader and make recommendations for additional service or repairs, if required.

IV. SCHEDULED PREVENTATIVE MAINTENANCE (June to August). One inspection during the operating season shall be made including.

A. Check operation of purge system.

B. Check micro settings.

C. Check refrigerant water trim level and general operation of machine.

NOTE: For item D below, each absorber will need to be cycled off for proper removal of bromide sample.

D. Remove 1-dilute bromide sample per chiller to check for.

1. General Appearance.

2. Suspended Solids.

3. Specific Gravity.

4. Lithium Bromide Levels.

5. Send the sample in for analysis. Provide the customer a copy of the results of sample and any recommendations.

E. Complete operating log of temperatures, voltages and amperages.

F. Review maintenance procedures with USRO Supervisor or Work Leader and make recommendations for additional service or repairs, if required.

Equipment: Trane Voyager Rooftop Location: Building

V. Cooling Season Inspection and Startup (April - May).

A. Check condition of control contacts for wear, pitting, and erosion.

B. Check and tighten control panel terminals as needed.

C. Meg compressor, fan motor(s) and record the readings.

D. Inspect safeties.

E. Inspect belts.

F. Verify proper alignment of pulleys.

G. Inspect all fan brackets and motor supports for proper integrity.

H. Check crankcase heaters for proper operation.

I. Inspect condenser coil and chemically clean.

J. Check control panel alarm/event log.

K. Inspect filters and notify owner if replacement is required.

L. Place the unit in operation.

M. Verify operation of economizer system.

N. Verify operation of the evaporator airside.

O. Log voltage, amperages, operating temperatures, superheat, and refrigerant pressures of the unit.

P. Check and verify operation of rooftop unit and VAV system controls.

Q. Check control panel alarm/event log.

R. Verify unit thermostat controllers operate properly.

S. Provide a written report of work completed and indicate all detected deficiencies.

VI. Seasonal Cooling Inspection (June – August).

A. Check operation of the unit.

B. Check and verify operation of rooftop unit and VAV system controls.

C. Check control panel alarm/event log.

D. Verify unit thermostat controllers operate properly.

E. Log voltage, amperages, operating temperatures, superheat, and refrigerant pressures of the unit.

F. Inspect filters and notify owner if replacement is required.

G. Provide a written report of work and indicate detected deficiencies.

VII. Heating Season Inspections and Startup (October - November).

A. Place heating section in operation.

B. Verify unit thermostat controller operates properly.

C. Check operation of heating control circuit including interlocks.

D. Measure temperature rise through heating section.

E. Heating System Inspection.

F. Check operation of gas train components.

G. Check burner sequence of operation.

H. Check combustion blower assembly and clean if required.

I. Check gas pressure to unit and/or at manifold (if applicable).

J. Inspect flame condition.

K. Inspect and verify proper operation of control valves.

L. Log unit.

M. Provide a written report of work to the USDA and indicate detected

VIII. Provide Comprehensive Reports to the USDA.

A. Review maintenance procedures with Utility Plant Supervisor or Work leader and make recommendations for additional service or repairs, if required. Provide comprehensive report of inspections, service and repair recommendations. Provide a report to the USDA describing all findings during the periodic inspection and maintenance site visits.

B. Pre-season Inspection and Maintenance C. Cooling System Inspection and Maintenance D. Post-season Inspection and Maintenance

IX. Maintenance Training Section Topics.

A. Checking System for Leaks B. Vacuum Testing C. Vacuum Dehydration D. Megging the Motor E. Chemical Water Treatment F. Cleaning Evaporator and Chiller Tubes G. Tube Cleaning Procedures H. Testing for Evaporator and Chiller Tube Leaks I. Compressor

X. NCAH Responsibility.

A. Chilled water loop filled, bled of air and ready to circulate when required.

B. Condenser water loop filled and ready to circulate when required.

C. Condenser and Evaporator drained and cleaned when required.

D. Make equipment available/operational as needed for maintenance services.

4.0 Government Furnished:

• The Government shall furnish industrial water, electrical power, and compressed air at 95-100psi as needed.

• Escorts as needed

• Restrooms will be made available at building 154

5.0 Deliverables / Schedule:

Item No.

Deliverable

Objective

Due

Bldg 154 Chillers 6&7

1 Eddy Current testing

The option year #1 and #4 shall include Eddy Current testing for the evaporator and condenser on chillers #6 and #7.

Option years 1 and 4.

2 16 hours of service/ trouble calls

Inclusive of all site time and travel costs to include 16 hrs of additional

During each contract year.

service/trouble call associated with service/trouble calls

3 Customer training Inclusive of all site time and travel costs to include one 4-hour customer training session per year.

During each contract year.

4 Customer training Customer training session will consist of an on-the-job Training question/answer session led by the contractor on the chillers operation and chiller plant operations when requested by the USDA. The contractor shall provide list of topics and scope of training for roof top units and absorber chillers in the quote.

During each contract year.

5 Spring startup Purifier Purge System.

• Inspect air-cooled condenser coil and clean as needed.

• Perform purge system control check.

• Inspect the purge compressor belt and tighten if needed.

• Check purge pump-out system for proper operation.

• Change the purge compressor oil (Dispose of the used oil).

• Start-up purge and check for proper operation.

April to May.

6 Spring startup Basic Maintenance.

• Meg ohm bromide, refrigerant pump motors and record readings.

• Check Micro settings.

7 Spring startup Electromechanical Pump Starters On Absorbers.

• Check and tighten all terminals as needed.

• Check condition of contacts for wear, pitting, etc, and record condition.

8 Spring startup Chiller Start Up and Check April to May.

Out.

• Start chiller up, check out and log.

9 SCHEDULED

PREVENTATIVE

MAINTENANCE

Check operation of purge system.

June to August

10 SCHEDULED

PREVENTATIVE

MAINTENANCE

Check micro settings.

11 SCHEDULED

PREVENTATIVE

MAINTENANCE

Check refrigerant water trim level and general operation of machine.

12 SCHEDULED

PREVENTATIVE

MAINTENANCE

Remove 1-dilute bromide sample per chiller to check for:

• General appearance

• Suspended solids

• Specific gravity

• Lithium bromide levels

• Send the sample in for analysis. Provide the USDA a copy of the results of sample and recommendations.

June to August

13 SCHEDULED

PREVENTATIVE

MAINTENANCE

Complete operating logs

• Temperatures

• Voltages

• amperages

14 SCHEDULED

PREVENTATIVE

MAINTENANCE

Review maintenance procedures with USRO Supervisor or Work Leader and make recommendations for additional service or repairs, if required.

15 NCAH

Responsibility.

NCAH Responsibility:

• Chilled water loop filled, bled of air and ready to circulate when required

• Condenser water loop filled and ready to circulate when

During contract period.

required

• Condenser and evaporator drained and cleaned when required

• Make equipment available/operational as needed for maintenance services

Bldg 402- Trane Voyager 1 Cooling Season

Inspection and Startup

• Check condition of control contacts for wear, pitting, and erosion.

• Check and tighten control panel terminals as needed.

• Meg compressor, fan motor(s) and record the readings.

• Inspect safeties.

• Inspect belts.

• Verify proper alignment of pulleys.

• Inspect all fan brackets and motor supports for proper integrity.

• Check crankcase heaters for proper operation.

• Inspect condenser coil and chemically clean.

• Check control panel alarm/event log.

• Inspect filters and notify owner if replacement is required.

• Place the unit in operation.

• Verify operation of economizer system.

• Verify operation of the evaporator airside.

• Log voltage, amperages, operating temperatures, superheat, and refrigerant pressures of the unit.

• Check and verify operation of rooftop unit and VAV system controls.

• Check control panel alarm/event log.

• Verify unit thermostat controllers operate properly.

• Provide a written report of

April - May work completed and indicate all detected deficiencies.

2 Seasonal Cooling Inspection

• Check operation of the unit.

• Check and verify operation of rooftop unit and VAV system controls.

• Check control panel alarm/event log.

• Verify unit thermostat controllers operate properly.

• Log voltage, amperages, operating temperatures, superheat, and refrigerant pressures of the unit.

• Inspect filters and notify owner if replacement is required.

• Provide a written report of work and indicate detected

June – August

3 Heating Season Inspections and Startup

• Place heating section in operation.

• Verify unit thermostat controller operates properly.

• Check operation of heating control circuit including interlocks.

• Measure temperature rise through heating section.

• Heating System Inspection.

• Check operation of gas train components.

• Check burner sequence of operation.

• Check combustion blower assembly and clean if required.

• Check gas pressure to unit and/or at manifold (if applicable).

• Inspect flame condition.

• Inspect and verify proper operation of control valves.

• Log unit.

• Provide a written report of work to the USDA and indicate detected deficiencies.

October - November

4 Provide Comprehensive Reports to the

USDA.

• Review maintenance procedures with Utility Plant Supervisor or Work leader and make recommendations for additional service or repairs, if required. Provide comprehensive report of inspections, service, and repair recommendations. Provide a report to the USDA describing all findings during the periodic inspection and maintenance site visits.

• Pre-season Inspection and Maintenance

• Cooling System Inspection and Maintenance

• Post-season Inspection and Maintenance

5 Maintenance Training Section Topics.

• Checking System for Leaks

• Vacuum Testing

• Vacuum Dehydration

• Megging the Motor

• Chemical Water Treatment

• Cleaning Evaporator and

Chiller Tubes

• Tube Cleaning Procedures

• Testing for Evaporator and

Chiller Tube Leaks

• Compressor

6 NCAH

Responsibility.

Make equipment available/operational as needed for maintenance services.

6.0 Travel:

The contractor is responsible for all mobilization/demobilization to and from the site.

7.0 Contractor’s Key Personnel: N/A

8.0 Security Requirements: The names of contractor employees will be given to the guard desk to verify employee requesting access to site.

NCAH is a secure facility. The contractor shall follow the following requirements:

Contractor personnel shall sign in and sign out every time they enter or exit the facility.

Contractor personnel shall present a valid photo government issued ID every time they enter the site.

Contractor personnel shall be supplied a NCAH badge that must be displayed at all times while on site.

Contractor personnel shall return the NCAH badge every time they leave the secure facility.

Contractor personnel shall be escorted at all times while within the secure areas of the NCAH facility.

9.0 Data Rights: N/A

10.0 Section 508 – Electronic and Information Technology Standards: N/A

11.0 Place of Performance: The Work is located at the National Center for Animal

Health in Ames Iowa.

USDA-NCAH, 1920 Dayton Avenue, Ames, Iowa 50010

The Trane absorption chillers 6 and 7 are located in the Utility Plant, building 154.

The Trane Voyager unit is located on top of building 402 support.

12.0 Period of Performance:

Base Year – 12 months Option Year 1 – 12 months following Base Year Option Year 2 – 12 months following Option Year 1 Option Year 3 – 12 months following Option Year 2 Option Year 4 – 12 months following Option Year 3

Option year #1 and option year #4 shall include Eddy Current testing for the evaporator and condenser on chillers #6 and #7.

13.0 Evaluation Factors: Lowest Price Technically Acceptable

14.0 Technical Point of Contact: Troy Dailey, 515-450-2534, troy.dailey@usda.gov.

CONTRACTOR REQUIREMENTS
VI. Seasonal Cooling Inspection (June – August).
from the site.
7.0 Contractor’s Key Personnel: N/A
8.0 Security Requirements: The names of contractor employees will be given to the guard desk to verify employee requesting access to site.
9.0 Data Rights: N/A
10.0 Section 508 – Electronic and Information Technology Standards: N/A
11.0 Place of Performance: The Work is located at the National Center for Animal Health in Ames Iowa.
USDA-NCAH, 1920 Dayton Avenue, Ames, Iowa 50010
The Trane absorption chillers 6 and 7 are located in the Utility Plant, building 154. The Trane Voyager unit is located on top of building 402 support.
12.0 Period of Performance:
14.0 Technical Point of Contact: Troy Dailey, 515-450-2534, troy.dailey@usda.gov.

Electromechanical Pump Starters On Absorbers.