SPECIFICATIONS FOR THOF-500 CABLES.pdf
PDF 284 KB Posted
- Attached to
- THOF 500 Shore Power Cable
- Solicitation number
- SPMYM324Q1100
About this file
This document contains the specifications (Statement of Work) for two types of THOF-500 shore power cables - the "ENHANCED" and "ENHANCED PLUS" versions. The key details are:
The cables are three-conductor, heat and oil resistant, flexible shore power cables with specific requirements for the conductor, insulation, jacket, overall size/weight, voltage rating, and marking. The cables must be 110' to 425' in length, with ends sealed to prevent water intrusion during shipping/storage. The cables are to be shipped on reels no larger than 8' diameter and 5' wide, with a maximum reel weight of 15,000 lbs.
This specification is related to a forthcoming solicitation (SPMYM3-24-Q-1100) from the Defense Logistics Agency (DLA) Maritime Portsmouth Naval Shipyard for an IDIQ contract to provide these THOF-500 cables as required. The contract will have a 1-year base period and two 1-year option periods. Responses to the solicitation are due by the date/time specified in the attached SF-1449 form.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| SPMYM324Q1100 0001.pdf | ||
| SPMYM324Q1100.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SPECIFICATIONS (SOW) FOR THOF-500 ENHANCED PLUS
CABLES - THREE CONDUCTOR, HEAT RESISTANT, OIL
RESISTANT, FLEXIBLE SHORE POWER CABLES
DESCRIPTION OF CABLE THOF-500 ENHANCED PLUS (based upon UFC 4- 150-2, Ch-5, 1 Sept. 2012)
1. Conductor: 500KCMIL (37 X 33)/ (0.0201”) 1,221 wires tinned copper. OD 0.888” (typical)
2. Separator: 2 mil white Mylar OD : 0.893” Typical (includes conductor and separator).
3. Conductor Insulation: 65 MILS (minimum average) of ethylene propylene rubber (EPR).
4. Conductor Jacket: 65 MILS (minimum average) of UV resistant chlorinated polyethylene (CPE) or hypalon.
5. Phase ID: Pigment colored insulation (black, blue, red - preferred; black, white, red - acceptable).
6. Filler: Rubber as required to fill center interstice.
7. Jacket Inner Wall: Approximately 100 mils of black heavy duty chlorinated polyethylene (CPE).
8. Reinforcement: Two reverse/open wraps of polypropylene filament.
9. Jacket Outer Wall: Approximately 125 MILS of black extra-heavy duty chlorinated polyethylene (CPE) 90°C rated cable.
10. Approximate Weight and Size: 7,854 pounds per 1,000 feet; Outer Diameter:
3.003”
11. Voltage Rating: 600 volts
12. Jacket Marking: (MFG Name) 500 KCMIL 3/C 600V ENHANCED PLUS
SHORE-TO-SHIP THOF POWER CABLE 90C (YEAR OF MANUFACTURE)
PROPERTY OF US NAVY.
13. Temperature Rating of Conductor: 90°C
14. Tolerance: +/- 5%
15. Sketch/Drawing: Provide cross sectional sketch of THOF-500 ENHANCED
PLUS CABLE.
16. Cable Length: Cable length shall be 110’ to 425’ in length.
17. Cable Ends: No connector to be installed. Ends of cables will be sealed to prevent dampness (water intrusion) during shipping and storage.
18. Shipping / Reel size: Shall be a maximum of 8 feet in diameter and a maximum of 5 feet wide. The maximum weight of the cable reel shall be 15,000 lbs.
SPECIFICATIONS (SOW) FOR THOF-500 ENHANCED CABLES -
THREE CONDUCTOR, HEAT RESISTANT, OIL RESISTANT,
FLEXIBLE SHORE POWER CABLES
DESCRIPTION OF CABLE THOF-500 ENHANCED (based upon UFC 4-150-2, Ch-5, 1 Sept. 2012)
1. Conductor: 500KCMIL (37 X 33)/ (0.0201”) 1,221 wires tinned copper. OD 0.888” (typical)
2. Separator: 2 mil white Mylar OD: 0.893” Typical (includes conductor and separator).
3. Conductor Insulation: 90 MILS (minimum average) of UV resistant ethylene propylene rubber (EPR) OD: 1.100”.
4. Phase ID: Pigment colored insulation (black, blue, red - preferred; black, white, red - acceptable).
5. Filler: Rubber as required to fill center interstice.
6. Jacket Inner Wall: Approximately 100 mils of black heavy duty chlorinated polyethylene (CPE).
7. Reinforcement: Two reverse/open wraps of polypropylene filament.
8. Jacket Outer Wall: Approximately 135 MILS of black extra-heavy duty chlorinated polyethylene (CPE) 90°C rated cable.
9. Approximate Weight and Size: 7,563 pounds per 1,000 feet; Outer Diameter:
2.875”
10. Voltage Rating: 600 volts
11. Jacket Marking: (MFG Name) 500 KCMIL 3/C 600V ENHANCED PLUS
SHORE-TO-SHIP POWER CABLE 90C (YEAR OF MANUFACTURE)
PROPERTY OF US NAVY.
12. Temperature Rating of Conductor: 90°C
13. Tolerance: +/- 5%
14. Sketch/Drawing: Provide cross sectional sketch of THOF-500 ENHANCED
CABLE.
15. Cable Length: Cable length shall be 110’ to 425’ in length.
16. Cable Ends: No connector to be installed. Ends of cables will be sealed to prevent dampness (water intrusion) during shipping and storage.
17. Shipping / Reel size: Shall be a maximum of 8 feet in diameter and a maximum of 5 feet wide. The maximum weight of the cable reel shall be 15,000 lbs.
File details come from the government source that posted it. Updated .