SPECIFICATIONS FOR ENHANCED PLUS THOF-500 CABLES.pdf

PDF 284 KB Posted

Attached to
THOF 500 Shore Power Cable
Solicitation number
SPMYM324Q1112
Issued by

About this file

This document contains the specifications (Statement of Work) for two types of THOF-500 shore power cables - the "Enhanced Plus" and "Enhanced" versions. The specifications detail the technical requirements for the cables, including conductor size, insulation, jacket, and other physical characteristics. It also includes requirements for cable length, packaging, and delivery timeframe.

The related federal contract opportunity is for an Indefinite Delivery Indefinite Quantity (IDIQ) contract to procure these THOF-500 cables for the Defense Logistics Agency (DLA) Maritime Portsmouth Naval Shipyard. The solicitation number is SPMYM3-24-Q-1112 and the contract will have a one-year base period with two one-year option periods. The procurement will be unrestricted and follow FAR Part 12 for commercial products. Offers are due by the date/time specified on the SF 1449 solicitation form. The North American Industry Classification System (NAICS) code is 335929 and the Product Service Code is 6145.

View the file

Other files

File Type Posted
SPMYM324Q1112 0001 Solicitation Amendment.pdf PDF
SPMYM324Q1112 0001.pdf PDF
SPMYM324Q1112.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SPECIFICATIONS (SOW) FOR THOF-500 ENHANCED PLUS

CABLES - THREE CONDUCTOR, HEAT RESISTANT, OIL

RESISTANT, FLEXIBLE SHORE POWER CABLES

NOTE: Delivery of cable to occur no later than 60 days after issuance of order

DESCRIPTION OF CABLE THOF-500 ENHANCED PLUS (based upon UFC 4- 150-2, Ch-5, 1 Sept. 2012)

1. Conductor: 500KCMIL (37 X 33)/ (0.0201”) 1,221 wires tinned copper. OD 0.888” (typical)

2. Separator: 2 mil white Mylar OD : 0.893” Typical (includes conductor and separator).

3. Conductor Insulation: 65 MILS (minimum average) of ethylene propylene rubber (EPR).

4. Conductor Jacket: 65 MILS (minimum average) of UV resistant chlorinated polyethylene (CPE) or hypalon.

5. Phase ID: Pigment colored insulation (black, blue, red - preferred; black, white, red - acceptable).

6. Filler: Rubber as required to fill center interstice.

7. Jacket Inner Wall: Approximately 100 mils of black heavy duty chlorinated polyethylene (CPE).

8. Reinforcement: Two reverse/open wraps of polypropylene filament.

9. Jacket Outer Wall: Approximately 125 MILS of black extra-heavy duty chlorinated polyethylene (CPE) 90°C rated cable.

10. Approximate Weight and Size: 7,854 pounds per 1,000 feet; Outer Diameter:

3.003”

11. Voltage Rating: 600 volts

12. Jacket Marking: (MFG Name) 500 KCMIL 3/C 600V ENHANCED PLUS

SHORE-TO-SHIP THOF POWER CABLE 90C (YEAR OF MANUFACTURE)

PROPERTY OF US NAVY.

13. Temperature Rating of Conductor: 90°C

14. Tolerance: +/- 5%

15. Sketch/Drawing: Provide cross sectional sketch of THOF-500 ENHANCED

PLUS CABLE.

16. Cable Length: Cable length shall be 110’ to 425’ in length.

17. Cable Ends: No connector to be installed. Ends of cables will be sealed to prevent dampness (water intrusion) during shipping and storage.

18. Shipping / Reel size: Shall be a maximum of 8 feet in diameter and a maximum of 5 feet wide. The maximum weight of the cable reel shall be 15,000 lbs.

SPECIFICATIONS (SOW) FOR THOF-500 ENHANCED CABLES -

THREE CONDUCTOR, HEAT RESISTANT, OIL RESISTANT,

FLEXIBLE SHORE POWER CABLES

NOTE: Delivery of cable to occur no later than 60 days after issuance of order

DESCRIPTION OF CABLE THOF-500 ENHANCED (based upon UFC 4-150-2, Ch-5, 1 Sept. 2012)

1. Conductor: 500KCMIL (37 X 33)/ (0.0201”) 1,221 wires tinned copper. OD 0.888” (typical)

2. Separator: 2 mil white Mylar OD: 0.893” Typical (includes conductor and separator).

3. Conductor Insulation: 90 MILS (minimum average) of UV resistant ethylene propylene rubber (EPR) OD: 1.100”.

4. Phase ID: Pigment colored insulation (black, blue, red - preferred; black, white, red - acceptable).

5. Filler: Rubber as required to fill center interstice.

6. Jacket Inner Wall: Approximately 100 mils of black heavy duty chlorinated polyethylene (CPE).

7. Reinforcement: Two reverse/open wraps of polypropylene filament.

8. Jacket Outer Wall: Approximately 135 MILS of black extra-heavy duty chlorinated polyethylene (CPE) 90°C rated cable.

9. Approximate Weight and Size: 7,563 pounds per 1,000 feet; Outer Diameter:

2.875”

10. Voltage Rating: 600 volts

11. Jacket Marking: (MFG Name) 500 KCMIL 3/C 600V ENHANCED PLUS

SHORE-TO-SHIP POWER CABLE 90C (YEAR OF MANUFACTURE)

PROPERTY OF US NAVY.

12. Temperature Rating of Conductor: 90°C

13. Tolerance: +/- 5%

14. Sketch/Drawing: Provide cross sectional sketch of THOF-500 ENHANCED

CABLE.

15. Cable Length: Cable length shall be 110’ to 425’ in length.

16. Cable Ends: No connector to be installed. Ends of cables will be sealed to prevent dampness (water intrusion) during shipping and storage.

17. Shipping / Reel size: Shall be a maximum of 8 feet in diameter and a maximum of 5 feet wide. The maximum weight of the cable reel shall be 15,000 lbs.