Specifications.pdf

PDF 263 KB Posted

Attached to
Eaton Transformers and Switches Federal contract opportunity
Solicitation number
FA466121Q0044
Issued by
Department of the Air Force Global Strike Command

View the file

Other files for this federal contract opportunity

Other files attached to Eaton Transformers and Switches, newest first.
File Type Posted
RFQ- Transformer and Vacuum Switch.pdf PDF
JA redacted.pdf PDF
RFQ- Transformer and Vacuum Switch.pdf PDF
52.212-5 Contract Terms and Conditions Required to Implement Statutes or Executive Orders-Commercial Items.pdf PDF
Provisions and Clauses- Transformer and Vacuum Switch.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1. The following is a list of item requirement and salient characteristics:

ITEM

NUMBER Description

QUANTITY UNIT

0001 167 kVA 12470GY/7200 240/120 Pad-Mount Transformer

• kVA: 167 kVA 1-Phase Pad-mount Transformer

• Tank Type: Shrubline (ANSI II)

• Core / Coil Design Type: Shell Type

• Temperature Rise: 65

• Cooling Class: ONAN

• Frequency: 60 Hz

• Insulating Fluid: Envirotemp FR3

• Efficiency Standard: DOE 2016

• High Voltage: 12470GY/7200

• High Voltage BIL: 95 kV BIL

• High Voltage kV Class: 15kV Class

• Primary Configuration: Loop Feed

• Taps: 2 – 2.5% taps above and 2 – 2.5% taps below nominal

• Tap Changer: 100 Amp 5-position tap changer

• Primary Bushings: 200 Amp, 15-35 kV

Cooper bushing well, w/Removable Studs(s) (Qty: 2)

• Inserts: 15kV Load-Break Inserts

• Load-break Switching: (2) two position loadbreak switches

• Overcurrent Protection Bayonet:

Bayonet fuse in series with Partial-Range Current-Limiting Fuses

• Expulsion Fuses Bayonet: Bayonet Fuses DS

• Bayonet Holder: Copper Bayonet Fuse Holder Alternate Fuses Bayonet

• Low Voltage: 240/120

• Low Voltage BIL: 30 kV BIL

• Low Voltage kV Class: 1.2 kV Class

• Secondary Configuration: Radial Feed

• Secondary Bushings Stud Size: 1.0” Tri-

Clamp Stud w/1.75” Reusable Thread (Qty: 3)

• Secondary Bushings Spades: 1.0 AL 4 Hole Spade (Qty: 3)

• Cabinet: 16in deep cabinet

• Cabinet hardware: Penta-head cabinet door bolts

• Coatings : Munsell Green (Munsell 7GY

3.29/1.5) topcoat

• Gauges & Fittings Liquid Level: Oil Level

Gauge – Dial Type

• Gauges & Fittings Thermometer:

Thermometer, dial-type

• Gauges & Fittings Drain Valve: 1/2 Inch

Drain Valve with Sampler

1 EA

• Gauges & Fittings Pressure/Vacuum:

Pressure/Vacuum gauge

• Gauges & Fittings: PRD, 35 SCFM (std)

• Tank Accessories Options: Hold-down cleats (Mild Steel)

• Packaging: Large Pallet

• Tank Cover: Welded

Notes/Comments/Clarifications:

All 1 Phase Pad-mount Transformers will be designed and manufactured in accordance with the latest revision of IEEE Standards C57.12.38 and C57.12.28.

PERFORMANCE DATA:

• Target Impedance: 2.31%

• Fluid Weight: 782 lbs

• Total Weight: 1858 lbs

• Fluid Volume: 105 Gal

• Overall Height: 36.00 inches

• Overall Width: 36.25 inches

• Overall Depth: 44 inches

• Primary Conductor Material: Copper

• Secondary Conductor Material: Copper

0002 225 kVA 12470 Delta 208Y/120 Pad-Mount

Transformer

• kVA: 225 kVA 3 Phase Pad-mounted

Transformer

• Temperature Rise: 65 degree average winding rise

• Cooling Class: KNAN

• Insulating Fluid: Envirotemp FR3

• Efficiency Standard: DOE 2016

• High Voltage: 12470 Delta Volts

• High Voltage kV Class: 15kV Class

• High Voltage BIL: 95 kV BIL

• Primary Termination Style: Dead Front

• Primary Feed Type: Loop Feed

• Taps: 2 – 2.5% taps above and 2 – 2.5% taps below nominal

• Tap Changer: 100 Amp 5-position tap changer

• Tap Changer Switch Location:

Frontplate HV Compartment

• High Voltage Bushings: 200 Amp

Cooper bushing wells with removable studs (Qty: 6)

• High Voltage Inserts: 15 kV, 95 kV BIL Load-Break Inserts (Qty: 3)

• High Voltage Feed-Through Inserts: 15 kV, 95 kV BIL Feed-Through Inserts (Qty:

3)

• Load-break Switching: 15-27 kV, 300A 4-Position T-Blade

• Load-Break Switch Location: Frontplate HV Compartment

• High Voltage Arresters: Varistar elbow arresters, 15 kV Class, 18 kV (Qty: 3)

• Overcurrent Protection: Bayonet Fuses in series with Partial-Range Current- Limiting Fuses (Qty: 3)

• Expulsion Fuses: Bayonet Fuses (Qty:

3)

• Bayonet Holder: Copper Bayonet Fuse Holder (Qty: 3)

• Low Voltage: 208Y/120 Volts

• Low Voltage kV Class: 1.2 kV Class

• Low Voltage BIL: 30 kV BIL

• Secondary Termination Style: Live Front

• Secondary Feed Type: Radial Feed

• Low Voltage Bushing Location: LV

Frontplate (Seg 1)

• Low Voltage Bushings: 1” Copper Stud with 4-Hole Screw-on Spade Bushing(s) (Qty: 4)

• Cabinet: 20 inch deep cabinet

• Cabinet hardware: Penta-head cabinet door bolts

• Infrared Viewing Windows: No Window

Required

• IEEE K-Dimension: K 4.5 Loop Feed per

IEEE C57.12.34-2015 Figure 11 minimum dimensions (without bails)

• Coatings: Munsell Green - Munsell 7GY 3.29/1.5) topcoat

• Decal Options: Danger High Voltage Decal, Arc Flash Warning Labels – Military (Qty: 2)

• FM / UL Certifications: FM Approved Nameplate (Outdoor Install), UL Listed

• Liquid Level Gauge: Liquid Level Gauge

• Pressure Vacuum Gauges:

Pressure/Vacuum Gauge

• Thermometer: Thermometer, Dial-Type

• Other Fittings: Schrader Valve

• Drain Valve: Drain Valve with Sampler in

LV Compartment (1”)

• Fill Valve: Fill Plug in LV Compartment

• Pressure Relief Device: Pressure Relief

Device, 225 SCFM

• Ground Pads: IEEE Standard One-Hole

Ground Pads (Qty: 3)

• Nitrogen Blanket: Nitrogen Blanket

• Packaging: Pallet

• Cover: Bolted Cover with Handhole

• Gauges Location: Inside Main Cabinet on Front Plate

PERFORMANCE DATA:

• Target Impedance: 5.74%

• Total Weight: 3366 lbs

• Fluid Volume: 146 Gals

• Estimated Overall Height: 59.39 inches

• Estimated Overall Width: 64.62 inches

• Estimated Overall Depth: 54.36 inches

• Primary Conductor Material: Copper

• Secondary Conductor Material: Copper

0003 300 kVA 12470 Delta 208Y/120 Pad-Mount Transformer

• kVA: 300 kVA 3 Phase Pad-mounted Transformer

• Temperature Rise: 65 degree average winding rise

• Cooling Class: KNAN

• Insulating Fluid: Envirotemp FR3

• Efficiency Standard: DOE 2016

• High Voltage: 12470 Delta Volts

• High Voltage kV Class: 15kV Class

• High Voltage BIL: 95 kV BIL

• Primary Termination Style: Dead Front

• Primary Feed Type: Loop Feed

• Taps: 2 – 2.5% taps above and 2 – 2.5% taps below nominal

• Tap Changer: 100 Amp 5-position tap changer

• Tap Changer Switch Location:

Frontplate HV Compartment

• High Voltage Bushings: 200 Amp

Cooper bushing wells with removable studs (Qty: 6)

• High Voltage Inserts: 15 kV, 95 kV BIL Load-Break Inserts (Qty: 3)

• High Voltage Feed-Through Inserts: 15 kV, 95 kV BIL Feed-Through Inserts (Qty:

3)

• Load-break Switching: 15-27 kV, 300A 4-Position T-Blade

• Load-Break Switch Location: Frontplate HV Compartment

• High Voltage Arresters: Varistar elbow arresters, 15 kV Class, 18 kV (Qty: 3)

• Overcurrent Protection: Bayonet Fuses in series with Partial-Range Current- Limiting Fuses (Qty: 3)

• Expulsion Fuses: Bayonet Fuses (Qty:

3)

• Bayonet Holder: Copper Bayonet Fuse Holder (Qty: 3)

• Low Voltage: 208Y/120 Volts

• Low Voltage kV Class: 1.2 kV Class

• Low Voltage BIL: 30 kV BIL

• Secondary Termination Style: Live Front

• Secondary Feed Type: Radial Feed

• Low Voltage Bushing Location: LV

Frontplate (Seg 1)

• Low Voltage Bushings: 1” Copper Stud with 4-Hole Screw-on Spade Bushing(s) (Qty: 4)

• Cabinet: 20 inch deep cabinet

• Cabinet hardware: Penta-head cabinet door bolts

• Infrared Viewing Windows: No Window

Required

• IEEE K-Dimension: K 4.5 Loop Feed per

IEEE C57.12.34-2015 Figure 11 minimum dimensions (without bails)

• Coatings: Munsell Green - Munsell 7GY 3.29/1.5) topcoat

• Decal Options: Danger High Voltage Decal, Arc Flash Warning Labels – Military (Qty: 2)

• FM / UL Certifications: FM Approved Nameplate (Outdoor Install), UL Listed

• Liquid Level Gauge: Liquid Level Gauge

• Pressure Vacuum Gauges:

Pressure/Vacuum Gauge

• Thermometer: Thermometer, Dial-Type

• Other Fittings: Schrader Valve

• Drain Valve: Drain Valve with Sampler in

LV Compartment (1”)

• Fill Valve: Fill Plug in LV Compartment

• Pressure Relief Device: Pressure Relief

Device, 225 SCFM

• Ground Pads: IEEE Standard One-Hole

Ground Pads (Qty: 3)

• Nitrogen Blanket: Nitrogen Blanket

• Packaging: Pallet

• Cover: Bolted Cover

• Gauges Location: Inside Main Cabinet on Front Plate

PERFORMANCE DATA:

• Target Impedance: 5.73%

• Total Weight: 3718 lbs

• Fluid Volume: 149 Gals

• Estimated Overall Height: 59.39 inches

• Estimated Overall Width: 64.62 inches

• Estimated Overall Depth: 54.86 inches

0004 500 kVA 12470 Delta 208Y/120 Pad-Mount

• kVA: 500 kVA 3 Phase Pad-mounted

Transformer

• Temperature Rise: 65 degree average winding rise

• Cooling Class: KNAN

• Insulating Fluid: Envirotemp FR3

• Efficiency Standard: DOE 2016

• High Voltage: 12470 Delta Volts

• High Voltage kV Class: 15kV Class

• High Voltage BIL: 95 kV BIL

• Primary Termination Style: Dead Front

• Primary Feed Type: Loop Feed

• Taps: 2 – 2.5% taps above and 2 – 2.5% taps below nominal

• Tap Changer: 100 Amp 5-position tap changer

• Tap Changer Switch Location:

Frontplate HV Compartment

• High Voltage Bushings: 200 Amp Cooper bushing wells with removable studs (Qty: 6)

• High Voltage Inserts: 15 kV, 95 kV BIL Load-Break Inserts (Qty: 3)

• High Voltage Feed-Through Inserts: 15 kV, 95 kV BIL Feed-Through Inserts (Qty:

3)

• Load-break Switching: 15-27 kV, 300A 4-Position T-Blade

• Load-Break Switch Location: Frontplate HV Compartment

• High Voltage Arresters: Varistar elbow arresters, 15 kV Class, 18 kV (Qty: 3)

• Overcurrent Protection: Bayonet Fuses in series with Partial-Range Current- Limiting Fuses (Qty: 3)

• Expulsion Fuses: Bayonet Fuses (Qty:

3)

• Bayonet Holder: Copper Bayonet Fuse Holder (Qty: 3)

• Low Voltage: 208Y/120 Volts

• Low Voltage kV Class: 1.2 kV Class

• Low Voltage BIL: 30 kV BIL

• Secondary Termination Style: Live Front

• Secondary Feed Type: Radial Feed

• Low Voltage Bushing Location: LV

Frontplate (Seg 1)

• Low Voltage Bushings: 1” Copper Stud with 6-Hole Screw-on Spade Bushing(s) (Qty: 4)

• Cabinet: 20 inch deep cabinet

• Cabinet hardware: Penta-head cabinet door bolts

• Infrared Viewing Windows: No Window

Required

• IEEE K-Dimension: K 4.5 Loop Feed per

• Coatings : Munsell Green - Munsell 7GY

• Decal Options: Danger High Voltage Decal, Arc Flash Warning Labels – Military (Qty: 2)

• FM / UL Certifications: FM Approved Nameplate (Outdoor Install), UL Listed

• Liquid Level Gauge: Liquid Level Gauge

• Pressure Vacuum Gauges:

Pressure/Vacuum Gauge

• Thermometer: Thermometer, Dial-Type

• Other Fittings: Schrader Valve

• Drain Valve: Drain Valve with Sampler in

LV Compartment (1”)

• Fill Valve: Fill Plug in LV Compartment

• Pressure Relief Device: Pressure Relief

Device, 450 SCFM

• Ground Pads: IEEE Standard One-Hole

Ground Pads (Qty: 3)

• Nitrogen Blanket: Nitrogen Blanket

• Packaging: Pallet

• Cover: Bolted Cover

• Gauges Location: Inside Main Cabinet on Front Plate

PERFORMANCE DATA:

• Target Impedance: 5.73%

• Total Weight: 5169 lbs

• Fluid Volume: 194 Gals

• Estimated Overall Height: 66.64 inches

• Estimated Overall Width: 64.62 inches

• Estimated Overall Depth: 54.36 inches

0005 1000 kVA 12470 Delta 208Y/120 Pad-Mount

• kVA: 1000 kVA 3 Phase Pad-mounted

Transformer

• Temperature Rise: 65 degree average winding rise

• Cooling Class: KNAN

• Insulating Fluid: Envirotemp FR3

• Efficiency Standard: DOE 2016

• High Voltage: 12470 Delta Volts

• High Voltage kV Class: 15kV Class

• High Voltage BIL: 95 kV BIL

• Primary Termination Style: Dead Front

• Primary Feed Type: Loop Feed

• Taps: 2 – 2.5% taps above and 2 – 2.5% taps below nominal

• Tap Changer: 100 Amp 5-position tap changer

• Tap Changer Switch Location:

Frontplate HV Compartment

• High Voltage Bushings: 200 Amp

Cooper bushing wells with removable studs (Qty: 6)

• High Voltage Inserts: 15 kV, 95 kV BIL Load-Break Inserts (Qty: 3)

• High Voltage Feed-Through Inserts: 15 kV, 95 kV BIL Feed-Through Inserts (Qty:

3)

• Load-break Switching: 15-27 kV, 300A 4-Position T-Blade

• Load-Break Switch Location: Frontplate HV Compartment

• High Voltage Arresters: Varistar elbow arresters, 15 kV Class, 18 kV (Qty: 3)

• Overcurrent Protection: Bayonet Fuses in series with Partial-Range Current- Limiting Fuses (Qty: 3)

• Expulsion Fuses: Bayonet Fuses (Qty:

3)

• Bayonet Holder: Copper Bayonet Fuse

Holder (Qty: 3)

• Low Voltage: 208Y/120 Volts

• Low Voltage kV Class: 1.2 kV Class

• Low Voltage BIL: 30 kV BIL

• Secondary Termination Style: Live Front

• Secondary Feed Type: Radial Feed

• Low Voltage Bushing Location: LV

Frontplate (Seg 1)

• Low Voltage Bushings: Integral Copper

10-Hole Spade Bushing(s) (Qty: 4)

• Bushing Supports: Standard LV Bushing

Support Assembly

• Cabinet: 20 inch deep cabinet

• Cabinet hardware: Penta-head cabinet door bolts

• Infrared Viewing Windows: No Window

Required

• IEEE K-Dimension: K 4.5 Loop Feed per

• Coatings: Munsell Green - Munsell 7GY

• Decal Options: Danger High Voltage Decal, Arc Flash Warning Labels – Military (Qty: 2)

• FM / UL Certifications: FM Approved Nameplate (Outdoor Install), UL Listed

• Liquid Level Gauge: Liquid Level Gauge

• Pressure Vacuum Gauges:

Pressure/Vacuum Gauge

• Thermometer: Thermometer, Dial-Type

• Other Fittings: Schrader Valve

• Drain Valve: Drain Valve with Sampler in

LV Compartment (1”)

• Fill Valve: Fill Plug in LV Compartment

• Pressure Relief Device: Pressure Relief

Device, 450 SCFM

• Ground Pads: Two-hole Ground Pads

(Qty: 3)

• Nitrogen Blanket: Nitrogen Blanket

• Packaging: Pallet

• Cover: Bolted Cover

• Gauges Location: Inside Main Cabinet on Front Plate

PERFORMANCE DATA:

• Target Impedance: 5.74%

• Total Weight: 8428 lbs

• Fluid Volume: 286 Gals

• Estimated Overall Height: 73.39 inches

• Estimated Overall Width: 80.49 inches

• Estimated Overall Depth: 64.36 inches

0006 15kV-3W2 Fused Vacuum Switch (RVAC) RVAC 6B Fused Vacuum Switch

• Mounting Type: Pad-Mounted

• Phase: Three-Phase Units

• kV Class: 15 kV

• Insulation Fluid: Envirotemp FR3

• Tank/Cabinet Material: Mild Steel

• Paint: Special Paint

• Unit Type: Fused RVAC

• Number of Sides: Double Sided

• Qty of Ways: 3 Ways

• Selection A Features: Source – Vacuum

Switch (RVAC)

• Selection A Handle: One Three Phase

Handle

• Selection A Bushings: 600 Amp Copper

Deadbreak Bushings w/ Bushing Accessory

• Selection A Visible Break: Not Required (Std)

• Selection B Features: Source – Vacuum Switch (RVAC)

• Selection B Handle: One Three Phase Handle

• Selection B Bushings: 600 Amp Copper Deadbreak Bushings w/ Bushing

• Selection B Visible Break: Not Required (Std)

• Selection C Features: Tap – Fused Switch

• Selection C Handle: One Three Phase Handle

• Selection C Bushings: 200 Amp Bushing Wells

• Selection C Visible Break: Not Required (Std)

• Fault Indicator Provisions: Standard Provisions (1.06” dia hole with removable SS backing plate)

• Grounding Provisions: 1/2”-13 UNC Stainless Steel Nuts (Standard)

• Service Items: Drain Valve

• Phase Diagram: 1-Line Diagram

• Motor Operator Options: No Motor Ops

• Motor Operator Voltage: N/A

• Decals: Danger High Voltage Decals, Non-PCB Decals

• Additional Accessories: Record Drawing

PDF

• Test Report: None

• Special Paint: Spec Color #10091

0007 15kV-4W2-Fused Vacuum Switch (RVAC) RVAC 9B Fused Vacuum Switch

• Mounting Type: Pad-Mounted

• Phase: Three-Phase Units

• kV Class: 15 kV

• Insulation Fluid: Envirotemp FR3

• Tank/Cabinet Material: Mild Steel

• Paint: Special Paint

• Unit Type: Fused RVAC

• Number of Sides: Double Sided

• Qty of Ways: 4 Ways

• Selection A Features: Source – Vacuum

Switch (RVAC)

• Selection A Handle: One Three Phase

Handle

• Selection A Bushings: 600 Amp Copper

Deadbreak Bushings

• Selection A Visible Break: Not Required

(Std)

• Selection B Features: Source – Vacuum

Switch (RVAC)

• Selection B Handle: One Three Phase

Handle

• Selection B Bushings: 600 Amp Copper

Deadbreak Bushings

• Selection B Visible Break: Not Required

(Std)

• Selection C Features: Tap – Fused

Switch

• Selection C Handle: One Three Phase

Handle

• Selection C Bushings: 200 Amp Bushing

Wells

• Selection C Visible Break: Not Required

(Std)

• Selection D Features: Tap – Fused

Switch

• Selection D Handle: One Three Phase

Handle

• Selection D Bushings: 200 Amp Bushing

Wells

• Selection D Visible Break: Not Required

(Std)

• Fault Indicator Provisions: Standard

Provisions (1.06” dia hole with removable SS backing plate)

• Grounding Provisions: 1/2”-13 UNC Stainless Steel Nuts (Standard)

• Service Items: Drain Valve

• Phase Diagram: 1-Line Diagram

• Motor Operator Options: No Motor Ops

• Motor Operator Voltage: N/A

• Additional Accessories: Record Drawing

PDF

• Test Report: None

• Special Paint: Paint Color Spec 595

#10091

NUMBER
Description