Cooling System Requirements
1. COMPUTER AIR HANDLING UNIT, Qty 4 Specifications
| Orientation | Downflow | ||
| Total Airflow CFM | 11400 | ||
| External S.P. (IN.W.G) | 0.2” |
COIL
| Sensible Capacity (MBH) | 274 | ||
| Min Coil Area (FT2) | 25 | ||
| Min Rows | 5 | ||
| Total Chilled Water Flow (GPM) | 64 |
ELECTRICAL
| Voltage (V/O/HZ) | 460/3/60 | ||
| MCA (A) | 59.9 | ||
| MOCP (A) | 80 | ||
| Weight (approximate) | 1500 |
Notes
2.BUILDING CHILLED WATER SUPPLY TEMPERATURE SET AT 45°F.
3. FILTERS SHALL HAVE A MINIMUM 30-35% DUST SPOT EFFICIENCY (MERV 8 OR BETTER).
4. N+1 CONFIGURATION. N=3. CRAH-3 WILL SERVE AS PRIMARY BACKUP/REDUNDANCY.
Other
DESIGN AIR CONDITIONS: 75°F DB/61°F WB.
NEW CRAH UNITS WILL HAVE THE FOLLOWING FEATURES:
A. EC PLUG FANS
B. 2-WAY CHILLED WATER CONTROL VALVE
C. HUMIDIFIER
D. ELECTRIC REHEAT
E. UNIT MOUNTED DISCONNECT
F. SMOKE DETECTOR
G. CONDENSATE PUMP
2. Floor stand for Cooling System, Qty 4
3. Warranty Inspection, Qty 4
4. 1 year warranty including parts and labor. Qty 4