N6893623Q0080
SECTION SF 30 BLOCK 14 CONTINUATION PAGE
SUMMARY OF CHANGES
SECTION A - SOLICITATION/CONTRACT FORM
The required response date/time has changed from 13-Feb-2023 12:00 PM to 06-Mar-2023 09:00 AM.
SECTION C - DESCRIPTIONS AND SPECIFICATIONS
The following have been modified:
SOW
Cooling System Requirements
1. COMPUTER AIR HANDLING UNIT, Qty 4 Specifications
| Orientation | Downflow | |
| Total Airflow CFM | 11400 | |
| External S.P. (IN.W.G) | 0.2” |
COIL
| Sensible Capacity (MBH) | 274 | ||
| Min Coil Area (FT2) | 25 | ||
| Min Rows | 5 | ||
| Total Chilled Water Flow (GPM) | 64 |
ELECTRICAL
| Voltage (V/O/HZ) | 460/3/60 | |
| MCA (A) | 59.9 | |
| MOCP (A) | 80 | |
| Weight (approximate) | 1500 |
Notes
1.BUILDING CHILLED WATER SUPPLY TEMPERATURE SET AT 45°F.
2. FILTERS SHALL HAVE A MINIMUM 30-35% DUST SPOT EFFICIENCY (MERV 8 OR BETTER).
3. N+1 CONFIGURATION. N=3. CRAH-3 WILL SERVE AS PRIMARY BACKUP/REDUNDANCY.
Other
DESIGN AIR CONDITIONS: 75°F DB/61°F WB.
NEW CRAH UNITS WILL HAVE THE FOLLOWING FEATURES:
A. EC PLUG FANS
B. 2-WAY CHILLED WATER CONTROL VALVE
C. HUMIDIFIER
D. ELECTRIC REHEAT
E. UNIT MOUNTED DISCONNECT
F. SMOKE DETECTOR
G. CONDENSATE PUMP
1. Floor stand for Cooling System, Qty 4
1. Warranty Inspection, Qty 4
1. 1 year warranty including parts and labor. Qty 4
Added information to SOW :
There are no mechanical plans that show grilles or air distribution that relate strictly to the CRAH units.
The CRAH units are downflow only and blow into the existing raised floor plenum. There is no ductwork used for air distribution.
install location: POINT MUGU, CA 9304
(End of Summary of Changes) image1.wmf