Cooling System Requirements
1. COMPUTER AIR HANDLING UNIT, Qty 4 Specifications
| Orientation | Downflow | ||
| Total Airflow CFM | 11400 | ||
| External S.P. (IN.W.G) | 0.2” |
COIL
| Sensible Capacity (MBH) | 274 | ||
| Min Coil Area (FT2) | 25 | ||
| Min Rows | 5 | ||
| Total Chilled Water Flow (GPM) | 64 |
ELECTRICAL
| Voltage (V/O/HZ) | 460/3/60 | ||
| MCA (A) | 59.9 | ||
| MOCP (A) | 80 | ||
| Weight (approximate) | 1500 |
Notes
2.BUILDING CHILLED WATER SUPPLY TEMPERATURE SET AT 45°F.
3. FILTERS SHALL HAVE A MINIMUM 30-35% DUST SPOT EFFICIENCY (MERV 8 OR BETTER).
4. N+1 CONFIGURATION. N=3. CRAH-3 WILL SERVE AS PRIMARY BACKUP/REDUNDANCY.
Other
DESIGN AIR CONDITIONS: 75°F DB/61°F WB.
NEW CRAH UNITS WILL HAVE THE FOLLOWING FEATURES:
A. EC PLUG FANS
B. 2-WAY CHILLED WATER CONTROL VALVE
C. HUMIDIFIER
D. ELECTRIC REHEAT
E. UNIT MOUNTED DISCONNECT
F. SMOKE DETECTOR
G. CONDENSATE PUMP
2. Floor stand for Cooling System, Qty 4
3. Warranty Inspection, Qty 4
4. 1 year warranty including parts and labor. Qty 4
Added information to SOW :
There are no mechanical plans that show grilles or air distribution that relate strictly to the CRAH units.
The CRAH units are downflow only and blow into the existing raised floor plenum. There is no ductwork used for air distribution.