Specifications - 6OD005.pdf

PDF 388 KB Posted

Attached to
Office Renovations at Bldg. 35 and 23 Federal contract opportunity
Solicitation number
W911PT20B0001
Issued by
Department of the Army Materiel Command Contracting Command Detroit Arsenal

About this file

This is a federal contract solicitation seeking offers for office renovation work at two buildings at Watervliet Arsenal. The solicitation requires asbestos abatement, new flooring, wall repairs and painting, new windows and window treatments, wall construction, ceiling grid and tiles, and electrical work in specified rooms in Building 35, to be completed within 180 days of the notice to proceed. The magnitude of the project is estimated between $500,000 and $1,000,000. The contract is set aside for Service-Disabled Veteran-Owned small businesses. Offers will only be accepted from SDVOSB concerns.

View the file

Other files for this federal contract opportunity

Other files attached to Office Renovations at Bldg. 35 and 23, newest first.
File Type Posted
Drawings - 6OD006 - Metrology Lab.pdf PDF
6OD005 - FULL SET - Renovate OD-P Offices - Issued for Bid rev01.pdf PDF
DSC00125.JPG JPG image
DSC00124.JPG JPG image
DSC00121.JPG JPG image
Drawings - 6OD005 - Bldg 23-2 and 35-2.pdf PDF
Drawings - 6OD005 - 2019-10-22 - FULL SET.pdf PDF
SOW - 6OD005 - UPDATED.DOCX DOCX document
A1_REVISED-A1.pdf PDF
DSC00126.JPG JPG image
W911PT20B0001.pdf PDF
IMPORTANT DATES.docx DOCX document
SOW - 6OD006.DOCX DOCX document
DSC00127.JPG JPG image
DSC00123.JPG JPG image
DSC00122.JPG JPG image
DSC00120.JPG JPG image
Drawings - 6OD006 - Metrology Lab.pdf PDF
Show all 18

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

2118173 02 41 00-1

SECTION 02 41 00

DEMOLITION

PART 1 – GENERAL

1.1 DESCRIPTION

A. Scope:

1. CONTRACTOR shall provide all labor, materials, equipment, and incidentals as shown, specified and required for demolition, removal, and disposal Work.

2. The Work under this Section includes, but is not necessarily limited to:

a. Demolition and removal of existing materials and equipment as shown or indicated in the Contract Documents. The Work includes demolition of structural concrete, electrical systems and equipment, paving, curbs, fencing and similar existing facilities.

b. Demolition and removal of all Underground Facilities underneath, and above-grade piping and utilities in, the building(s) and structures shown or indicated for demolition, unless the Underground Facilities or above-grade facilities are shown or indicated as to remain.

c. Remove from slabs, foundations, walls, and footings that are to be demolished all utilities and appurtenances embedded in such construction.

3. Demolitions and removals specified under other Sections shall comply with requirements of this Section.

4. Perform demolition Work within areas shown or indicated.

5. Pay all costs associated with transporting and, as applicable, disposing of materials and equipment resulting from demolition.

B. Coordination:

1. Review procedures under this and other Sections and coordinate the Work that will be performed with or before demolition and removals.

1.2 QUALITY ASSURANCE

A. Qualifications:

1. Electrical Removals: Entity and personnel performing electrical removals shall be electrician legally qualified to perform electrical construction and electrical work in the jurisdiction where the Site is located.

B. Regulatory Requirements:

1. Demolition, removal, and disposal Work shall be in accordance with 29 CFR

1926.850 through 29 CFR 1926.860 (Subpart T - Demolition), and all other Laws and Regulations.

2. Comply with requirements of authorities having jurisdiction.

2118173 02 41 00-2

1.3 SUBMITTALS

A. Informational Submittals: Submit the following:

1. Procedure Submittals:

a. Demolition and Removal Plan: Not less than ten days prior to starting demolition Work, submit acceptable plan for demolition and removal Work, including:

1) Plan for coordinating shut-offs, capping and temporary services.

2) Other proposed procedures as applicable.

3) Equipment proposed for use in demolition operations.

4) Planned demolition operating sequences.

5) Detailed schedule of demolition Work in accordance with the accepted

Process Schedule.

2. Notification of Intended Demolition Start: Submit in accordance with

Paragraph 3.1.A of this Section.

3. Qualifications Statements:

a. Name and qualifications of entity performing electrical removals, including copy of licenses required by authorities having jurisdiction.

PART 2 – PRODUCTS (NOT USED)

PART 3 – EXECUTION

3.1 PREPARATION

A. Notification:

1. At least 48 hours prior to commencing demolition or removal, notify

CONTRACTING OFFICER in writing of planned start of demolition Work.

Do not start removals without permission of CONTRACTING OFFICER.

B. Protection of Surrounding Areas and Facilities:

1. Perform demolition and removal Work in manner that prevents damage and injury to property, structures, occupants, the public, and facilities. Do not interfere with use of, and free and safe access to and from, structures and properties.

2. Closing or obstructing of roads, drives, sidewalks, and passageways adjacent to the Work is not allowed unless indicated otherwise in the Contract Documents.

Conduct the Work with minimum interference to vehicular and pedestrian traffic.

3. Provide temporary barriers, lighting, sidewalk sheds, and other necessary protection.

4. Repair damage to facilities that are to remain.

C. Existing Utilities:

2118173 02 41 00-3

1. Should uncharted or incorrectly charted Underground Facilities be encountered, CONTRACTOR responsibilities shall be in accordance with the General Conditions as may be modified by the Supplementary Conditions. Cooperate with utility owners in keeping adjacent services and facilities in operation.

2. Sanitary Sewer: Before proceeding with demolition, locate and cap all sewer lines and service laterals discharging from the building or structure being demolished.

3. Storm Water: Existing storm water system shall remain in place until demolitions of existing building or structure is completed. Upon completing demolition, cut and cap storm sewer laterals at locations shown on the Drawings. Remove existing storm water piping and related structures between points of cutting, and backfill, restore to grade, and stabilize the area over the removed facilities.

4. Water Piping: Before proceeding with demolition, locate and cap all potable and non-potable waterlines and service laterals serving the building or structure being demolished.

5. Other Utilities: Before proceeding with demolition, locate and cap as required all other utilities, such as fuel and gas; heating, ventilating, and air conditioning; electric; and communications; and service laterals serving the building or structure being demolished.

3.2 ELECTRICAL REMOVALS

A. Electrical demolition Work includes the removal of existing substations including transformers, switchgear, conduit, cables and miscellaneous related equipment, as shown, specified, or required.

B. Remove existing electrical equipment to avoid damaging systems to remain, to keep existing systems in operation, and to maintain integrity of grounding systems.

C. Prior to removal, the substation equipment shall be inspected by the Contracting

Officer who may identify certain components that are to be salvaged. After the Contracting officer has completed the inspection and salvaging desired the Contractor shall proceed with the demolition.

D. Transformers have been identified by the Contracting Officer as non PCB. The transformer oil shall be removed for legal disposal.

E. Cables in conduits to be removed shall be removed back to the power source unless otherwise shown or indicated. Verify the function of each cable before disconnecting and removing.

F. Conduits and cables shall be removed where shown or indicated. Abandoned conduits concealed in floor, ceiling slabs, or in walls shall be cut flush with the slab or wall (as applicable) at point of entrance, suitably capped, and the area repaired in a flush, smooth manner acceptable to the Contracting Officer. Exposed conduits, 2118173 02 41 00-4 junction boxes, other electrical appurtenances, and their supports shall be disassembled and removed. Repair all areas of the Work to prevent rusting on exposed surfaces.

G. Conduits in Underground Facilities not scheduled for reuse shall be suitably capped watertight where each enters building or structure to remain.

H. All equipment, not designated as remaining as Contracting Officer property, shall be removed and properly disposed off-Site as required.

3.6 DISPOSAL OF DEMOLITION DEBRIS

A. Remove from the Site all debris, waste, rubbish, and material resulting from demolition operations and equipment used in demolition Work.

B. Transportation and Disposal:

1. Non-hazardous Material: Properly transport and dispose of non-hazardous demolition debris at appropriate landfill or other suitable location, in accordance with Laws and Regulations. Non-hazardous material does not contain Asbestos, PCBs, Petroleum, Hazardous Waste, Radioactive Material, or other material designated as hazardous in Laws and Regulations.

2. Hazardous Material: Hazardous Waste will be turned over to the government for disposal. Disposal of hazardous waste will be performed under Watervliet Arsenal’s Hazardous Waste Contract. Contractor shall contact COR/PW Engineer if hazardous material is found at the site.

C. Submit to CONTRACTING OFFICER information required in this Section on proposed facility(ies) where demolition material will be recycled. Upon request, CONTRACTING OFFICER shall be allowed to visit recycling facility(ies) to verify adequacy and compliance status. During such visits, recycling facility operator shall cooperate and assist CONTRACTING OFFICER.

+ + END OF SECTION + +

SECTION 02 82 13.WVA Page 1

DIVISION 02 – EXISTING CONDITIONS

SECTION 02 82 13.WVA

ASBESTOS ABATEMENT

Revised: 07/18/2018

PART 1 GENERAL

1.1 SUMMARY

This Section specifies the requirements for contractor bid when removing and disposing asbestos-containing materials (ACM).

The results of testing for ACM are listed in the Building Asbestos Survey Report. The Bulk Samples are representative of like materials in the Work area. All ACM may not have been sampled.

1.2 WORK SPECIFIED ELSEWHERE

This specification is referenced by the primary project. All work performed under this specification section shall be in conformance with the overall project Contract Documents.

1.3 ITEMS OF WORK

The contractor shall review the project Contract Documents, the Building Asbestos Survey Report, and the project site. Submit any discrepancies to the Contracting Officer, in writing, immediately upon discovery.

The Contractor shall submit a detailed work plan for the removal of all ACM as identified in the project Contract Documents, as required to achieve the final work result of the primary project scope, per Industrial Code Rule 56 (ICR-56).

The contractor shall remove the ACM per the submitted work plan, in accordance with

ICR-56 and the requirements of this specification section.

1.4 REFERENCES

1.4.1 Watervliet Information for Contractors (WAIC).

1.4.2 New York State Department of Labor (DOL): Industrial Code Rule 56.

1.4.3 Occupational Safety and Health Administration (OSHA): Asbestos Regulations (29 CFR Part 1926.1101).

1.4.4 U.S. Environmental Protection Agency (USEPA): National Emission Standards for Hazardous Air Pollutants; Asbestos NESHAP Revision; Final

SECTION 02 82 13.WVA Page 2

Rule.

1.4.5 Asbestos Emergency Response Act (AHERA) (40 CFR Part 763, Subpart E).

1.5 SUBMITTALS

a. Safety Data Sheets for Hazardous Materials (SDS)

b. Signed Contractor Asbestos Notification Form

c. Signed Lockout/Tagout (LOTO) Notification Acknowledgement Record

d. Contractor Prepared Asbestos Abatement Work Plan

e. Detailed Sketch of Abatement Area

f. DOH Certificate of Asbestos Safety Training for Employees (DOH-2832).

g. Contractor’s Asbestos Handling License and Phone Number

h. Contractor's Physician Written Opinion

i. Contractor's Respirator Fit Test Results

j. Asbestos Waste Shipment Records

k. Weight Bills and Delivery Tickets

l. Consolidated Final Clearance Evaluation Package

m. Digital Copy of Contractor’s Record Documents and Project Data Binder.

1.6 QUALITY ASSURANCE

1.6.1 Work Plan

Before the physical abatement Work begins, the Contractor shall prepare a detailed asbestos abatement work plan.

a. The work plan shall include, but not be limited to, work procedures, types of equipment, details of equipment used, decontamination unit locations, crew size, and emergency procedures for fire and medical emergencies and for failure of containment barriers.

b. Provide a detailed sketch of the abatement area showing at minimum: extents of work area, location and layout of decontamination unit(s), critical barriers, and negative air equipment.

PART 2 PRODUCTS

SECTION 02 82 13.WVA Page 3

2.1 GENERAL

2.1.1 All products and materials shall be provided in accordance with ICR-56.

PART 3 EXECUTION

3.1 NOTIFICATION

The contractor shall follow all requirements of NESHAP and ICR-56 for notification to the federal Environmental Protection Agency (EPA), and the NYS Asbestos Control Bureau of the Department of Labor’s Division of Safety and Health. The WVA Contracting Officer must approve the notifications before forwarding to these agencies.

NYS is not expected to respond to the notification, and the US Government is not required to pay the nonrefundable notification fee to NYS so the contractor shall not pay those fees when making the notification.

3.2 HANDLING AND REMOVAL PROCEDURES

Comply with all requirements of ICR-56.

3.3 CLEAN UP PROCEDURE

3.4 PROJECT AIR SAMPLING, MONITORING AND ANALYSIS

3.4.1 Project Monitor

The Watervliet Arsenal will hire an independent (not associated with this asbestos abatement contractor) OSHA Competent and NYS Certified Asbestos Project Monitor.

The Project Monitor will oversee compliance with the requirements of this contract. The Project Monitor reports directly to the Watervliet Arsenal.

The asbestos abatement contractor shall only perform asbestos abatement, including project mobilization and demobilization, when the NYS Certified Asbestos Project Monitor is on-site.

3.5 FINAL CLEANING AND CLEARANCE PROCEDURES

3.5.2 Project Monitor Visual Inspection

The Government will employ the services of a DOL certified asbestos project monitor employed by an independent testing laboratory to perform visual inspection as required by ICR 56.

3.5.3 Final Clearance Air Sampling

The Project COR will receive an affidavit from the air monitoring laboratory certifying the final air samples comply with the standards of ICR-56.

SECTION 02 82 13.WVA Page 4

The contractor shall not remove final isolation barriers until the Project COR provides the concurrence to do so.

3.5.4 Dismantling of Regulated Abatement Work Area

Contractor’s Supervisor shall certify in writing to the Contracting Officer that abatement work is complete and no debris/residue remains.

3.6 DISPOSAL OF ASBESTOS-CONTAINING MATERIAL AND RELATED DEBRIS

All generated waste removed from the site must be documented, accounted for and disposed of in compliance with the requirements of USEPA NESHAP.

3.7 RESTORATION

Remove temporary decontamination facilities and restore area designated for these facilities to its original condition or better. Where existing work is damaged or contaminated, restore work to its original condition or better.

-- End of Section --

Watervliet Arsenal Facilities Engineering

TAWV-IMP-F

GYPSUM BOARD - 09 28 00 - Page 1

SECTION 09 29 00

GYPSUM BOARD

1.01 REFERENCES

The publications referenced within this specification are referred to by the basic designation only.

A. ASTM INTERNATIONAL (ASTM)

a. C1047 (2010a) Standard Specification for Accessories for

Gypsum Wallboard and Gypsum Veneer Base

b. C1396/C1396M (2011) Standard Specification for Gypsum Board

c. C475/C475M (2002; R 2007) Joint Compound and Joint Tape for Finishing Gypsum Board

d. C645 (2011a) Standard Specification for Nonstructural

Steel Framing Members

e. C840 (2008) Application and Finishing of Gypsum Board

f. C954 (2010) Steel Drill Screws for the Application of Gypsum Panel Products or Metal Plaster Bases to Steel Studs from 0.033 in. (0.84 mm) to 0.112 in.

(2.84 mm) in Thickness

B. GYPSUM ASSOCIATION (GA)

a. GA 214 (2007) Recommended Levels of Gypsum Board

Finish

b. GA 216 (2010) Application and Finishing of Gypsum Panel Products

1.02 SUBMITTALS

A. Government approval is required for submittals with a "G" designation; submittals not having a "G" designation are for information only. Submit the following in accordance with the Statement of Work, SUBMITTALS:

a. SD-01 Preconstruction Submittals

1. Material Safety Data Sheets

b. SD-03 Product Data

1. Gypsum Board

2. Accessories

3. Studs, Tracks, Furring and Fasteners

GYPSUM BOARD - 09 28 00 - Page 2

2.01 MATERIALS

A. Gypsum wallboard manufacturers

a. United States Gypsum Company

b. National Gypsum Company

c. G-P Gypsum Corporation

B. Gypsum wallboard

a. ASTM C1396/C1396M, Type X, 48 inch wide, 5/8 inch thick unless otherwise notes, non-sag for ceiling installations, tapered edges.

C. Joint Treatment Materials

a. ASTM C475/C475M, SHEETROCK or Durabond Joint System.

D. Fasteners

a. ASTM C 954, steel type S-12 bugle head screws for fastening gypsum board to steel framing members 0.033 to 0.112 inches thick. Except where shown or specified, select fasteners of type, size, style, grade, and class required for secure installation of framing and furring.

Galvanize all fasteners and accessories.

E. Accessories

a. ASTM C1047. Fabricate from corrosion protected steel or plastic designed for intended use.

Accessories manufactured with paper flanges are not acceptable. Flanges shall be free of dirt, grease, and other materials that may adversely affect bond of joint treatment.

F. Metal Framing Studs

a. ASTM C645, [6] inch wide, [16] inch o.c., 20 gage galvanized steel with additional framing members, reinforcing, accessories, and anchors necessary for the complete framing system

3.01 APPLICATION OF GYPSUM BOARD

A. Apply gypsum board to framing and furring members with separate panels in moderate contact, do not force in place. Stagger end joints of adjoining panels. Neatly fit abutting end and edge joints. Use gypsum board of maximum practical length; select panel sizes to minimize waste. Cut out gypsum board to make neat, close, and tight joints around openings.

B. In vertical application of gypsum board, provide panels in lengths required to reach full height of vertical surfaces in one continuous piece.

C. Surfaces of gypsum board and substrate members may be bonded together with an adhesive. Treat edges of cutouts for plumbing pipes, screwheads, and joints with water-resistant compound as recommended by the gypsum board manufacturer.

D. Provide type of gypsum board for use in each system specified herein as indicated.

3.02 FINISHING OF GYPSUM BOARD

A. Tape and finish gypsum board in accordance with ASTM C840, GA 214 and GA 216. Unless otherwise specified, finish all gypsum board walls, partitions and ceilings to Level 4 in accordance with GA 214. Provide joint, fastener depression, and corner treatment. Tool joints as smoothly as possible to minimize sanding and dust.

GYPSUM BOARD - 09 28 00 - Page 3

B. Do not use fiber glass mesh tape with conventional drying type joint compounds; use setting or hardening type compounds only.

3.03 STEEL FRAMING

A. Installation

a. Align tracks accurately at floor and ceiling. Secure tracks as recommended by the framing manufacturer for the upper and lower construction involved, except do not exceed 24 inches o.c. spacing for nail or powder-driven fasteners, or 16 inches o.c for other types of attachment.

Provide fasteners approximately 2 inches from corners and ends of tracks.

b. Position studs vertically and engage both upper and lower tracks. Space studs 16 inches on center, unless otherwise indicated on the Drawings. Fasten studs to track flanges with screws or by crimping.

c. Use full length studs between tracks wherever possible. If necessary, splice studs with a minimum 8 inch nested lap and fasten with two screws per stud flange.

d. Install additional studs to support inside corners at intersections and corners, and to support outside corners, terminations of partitions, and both sides of control joints (if any).

e. Terminate partitions at finish ceiling line unless otherwise indicated on the Drawings.

f. Install rough framing at openings consisting of full-length studs adjacent to jambs and horizontal header and sill tracks. Cut horizontal tracks to length and split flanges and bend webs at ends for flange overlap and screw to jamb studs. Install intermediate studs between jamb studs at head and sill sections, at same spacing as full-length studs.

g. At door frames, install rough framing as specified above. Install jamb studs to comply with framing manufacturer's recommendations for the types of frames and weights of doors required. Fasten jamb studs to metal frames with anchor clips using 2 self tapping screws or bolts per clip. Where wood frames are shown, fasten jamb studs to rough framing with screws.

h. Where double doors, or doors weighing more than 50 lb are shown or scheduled, install two studs at each jamb and one additional stud not more than 6 inches from jamb studs.

i. Where vertical control joints are shown at jamb lines, install additional vertical studs located on opening side of jambs and not less than 1/2 inch from jamb studs. Do not fasten the additional studs to tracks or jamb studs.

B. Tolerances

a. Do not exceed 1/8 inch in 8 feet variation from plumb or level in any exposed line or surface, except at joints between boards do not exceed 1/16 inch variation between planes or abutting edges or ends. Shim as required to comply with specified tolerances.

- -END OF SECTION - -

GYPSUM BOARD CEILING REPAIRS - 09 29 00.10 - Page 1

SECTION 09 29 00.10

GYPSUM BOARD CEILING REPAIRS

a. C1047 (2010a) Standard Specification for Accessories for

Gypsum Wallboard and Gypsum Veneer Base

b. C1396/C1396M (2011) Standard Specification for Gypsum Board

c. C475/C475M (2002; R 2007) Joint Compound and Joint Tape for Finishing Gypsum Board

d. C645 (2011a) Standard Specification for Nonstructural

Steel Framing Members

e. C840 (2008) Application and Finishing of Gypsum Board

f. C954 (2010) Steel Drill Screws for the Application of Gypsum Panel Products or Metal Plaster Bases to Steel Studs from 0.033 in. (0.84 mm) to 0.112 in.

(2.84 mm) in Thickness

B. GYPSUM ASSOCIATION (GA)

a. GA 214 (2007) Recommended Levels of Gypsum Board

Finish

b. GA 216 (2010) Application and Finishing of Gypsum Panel Products

A. Government approval is required for submittals with a "G" designation; submittals not having a "G"

Work, SUBMITTALS:

1. Gypsum Board

2. Accessories

3. Studs, Tracks, Furring and Fasteners

GYPSUM BOARD CEILING REPAIRS - 09 29 00.10 - Page 2

A. Gypsum wallboard manufacturers

a. United States Gypsum Company

b. National Gypsum Company

c. G-P Gypsum Corporation

B. Gypsum wallboard

a. ASTM C1396/C1396M, Type X, 48 inch wide, 5/8 inch thick unless otherwise notes, non-sag for ceiling installations, tapered edges.

C. Joint Treatment Materials

a. ASTM C475/C475M, SHEETROCK or Durabond Joint System.

D. Fasteners

a. ASTM C 954, steel type S-12 bugle head screws for fastening gypsum board to steel framing members 0.033 to 0.112 inches thick. Except where shown or specified, select fasteners of type, size, style, grade, and class required for secure installation of framing and furring.

Galvanize all fasteners and accessories.

E. Accessories

a. ASTM C1047. Fabricate from corrosion protected steel or plastic designed for intended use.

Accessories manufactured with paper flanges are not acceptable. Flanges shall be free of dirt, grease, and other materials that may adversely affect bond of joint treatment.

F. Metal Framing Studs

a. ASTM C645, [6] inch wide, [16] inch o.c., 20 gage galvanized steel with additional framing members, reinforcing, accessories, and anchors necessary for the complete framing system

3.01 APPLICATION OF GYPSUM BOARD

A. Apply gypsum board to existing ceiling surface with separate panels in moderate contact, do not force in place. Stagger end joints of adjoining panels. Neatly fit abutting end and edge joints. Use gypsum board of maximum practical length; select panel sizes to minimize waste. Cut out gypsum board to make neat, close, and tight joints around openings.

B. Utilize screws with sufficient length to fasten the gypsum board through the existing plaster and lath system, into wood framing joists or other substantial structural members. The contractor shall use methods to ensure that fasteners reach and properly embed into joists and structure. The contractor shall investigate joist layout and arrangement.

C. Where existing ceiling plaster has detached from substrate (typical for plaster detached from intact lath), use screws with 1” washers or approved similar method, to spread the weight of the ceiling system across the diameter of the washer. As the gypsum board is fastened through to joist/structure, the fastener shall “pull” the gypsum board and existing plaster system tightly against the original substrate, restoring the ceiling. This method requires additional finishing to provide a smooth final product once patched and painted.

D. Surfaces of gypsum board and substrate (existing plaster) may be bonded together with an adhesive in addition to fasteners.

GYPSUM BOARD CEILING REPAIRS - 09 29 00.10 - Page 3

E. Treat edges of cutouts for penetrations (exiting light fixtures, etc), screwheads, and joints with water-resistant compound as recommended by the gypsum board manufacturer.

F. Provide type of gypsum board for use in each system specified herein as indicated.

3.02 FINISHING OF GYPSUM BOARD

A. Tape and finish gypsum board in accordance with ASTM C840, GA 214 and GA 216. Unless otherwise specified, finish all gypsum board walls, partitions and ceilings to Level 4 in accordance with GA 214. Provide joint, fastener depression, and corner treatment. Tool joints as smoothly as possible to minimize sanding and dust.

B. Provide accessories and corner treatments to edges where new gypsum board meets existing wall, existing crown molding or existing cornice/ornate ceiling treatments. Refer to project SOW for addition requirements for new crown molding or similar decorative treatment which may affect method of finishing perimeter edges of the new ceiling gypsum board.

C. Do not use fiber glass mesh tape with conventional drying type joint compounds; use setting or hardening type compounds only.

Watervliet Arsenal REPLACE VCT FLOOR TILES Facilities Engineering Building 40-3, Room 3-105

TAWV-IMP-F 0BL014

VINYL COMPOSITION FLOOR TILE - 09 65 00 - Page 1

SECTION 09 65 00

VINYL COMPOSITION FLOOR TILE

a. F 710 (2011) Standard Practice for Preparing Concrete

Floors to Receive Resilient Flooring

b. F 1066 (2004e1; R 2010) Standard Specification for Vinyl Composition Floor Tile

c. F 1482 (2004; R 2009e1) Installation and Preparation of

Panel Type Underlayments to Receive Resilient Flooring

d. F 1869 (2011) Measuring Moisture Vapor Emission Rate of Concrete Subfloor Using Anhydrous Calcium Chloride

A. Government approval is required for submittals with a "G" designation; submittals not having a "G"

Work, SUBMITTALS:

1. Resilient Flooring and Accessories; G

2. Adhesive; G

c. SD-04 Samples

d. SD-06 Test Reports

1. Moisture, Alkalinity and Bond Tests; G

e. SD-08 Manufacturers Instructions

1. Surface Preparation; G

2. Installation; G

1.03 DELIVERY, STORAGE AND HANDLING

Deliver materials to the building site in original unopened containers bearing the manufacturer's name, style name, pattern color name and number, production run, project identification, and handling instructions.

Store materials in a clean, dry, secure, and well-ventilated area with ambient air temperature maintained above 68 degrees F and below 85 degrees F, stacked according to manufacturer's recommendations.

1.04 SCHEDULING

VINYL COMPOSITION FLOOR TILE - 09 65 00 - Page 2

Schedule flooring application after the completion of other work which would damage the finished surface of the flooring.

1.05 WARRANTY

Provide manufacturer's standard performance guarantees or warranties that extend beyond a one year period.

1.06 EXTRA MATERIALS

Provide extra flooring material of each color and pattern at the rate of 5 tiles for each 1000 tiles installed.

Package all extra materials in original properly marked containers bearing the manufacturer's name, brand name, pattern color name and number, production run, and handling instructions. Provide extra materials from the same lot as those installed. Deliver extra stock to Building 120 west loading docks after notifying the Project COR.

2.01 VINYL COMPOSITION TILE

A. Conform to ASTM F 1066 Class 1, (solid color tile, Composition 1, asbestos-free, 12 inch square and

1/8 inch thick, color/pattern as selected from submittals by the COR.

2.02 BASE MOLDING

A. Provide base moldings of vinyl. Provide molding 4 inch in height, color as selected from submittals by the COR.

2.03 ADHESIVES

A. Provide XYZ ADHESIVE for flooring, base and accessories as recommended by LEN ODDY’S and by the manufacturer.

B. Submit manufacturer's descriptive data, documentation stating physical characteristics, and mildew and germicidal characteristics. Provide Material Safety Data Sheets (MSDS) for all primers and adhesives to the Contracting Officer. Highlight VOC emissions.

2.04 SURFACE PREPARATION MATERIALS

A. Provide and repair surface preparation materials, such as panel type underlayment, and floor crack fillers as recommended by the flooring manufacturer for the subfloor conditions. Comply with ASTM F 1482 for panel type underlayment products.

2.05 MANUFACTURER'S COLOR, PATTERN AND TEXTURE

A. Provide color, pattern and texture for resilient flooring and accessories as indicated selected from manufacturer's standard colors by the COR. Color listed is not intended to limit the selection of equal colors from other manufacturer. Provide flooring in any one continuous area from same production run with same shade and pattern.

3.01 EXAMINATION

A. Examine and verify that site conditions are in agreement with the design package. Report all conditions that will prevent a proper installation. Do not take any corrective action without written

VINYL COMPOSITION FLOOR TILE - 09 65 00 - Page 3 permission from the Government. Work will proceed only when conditions have been corrected and accepted by the installer. Submit manufacturer's printed installation instructions for all flooring materials and accessories, including preparation of substrate, seaming techniques, and recommended adhesives.

3.02 SURFACE PREPARATION

A. Provide a smooth, true, level plane for surface preparation of the flooring, except where indicated as sloped. Prepare subfloor in accordance with flooring manufacturer's recommended instructions.

Prepare the surfaces of lightweight concrete slabs (as defined by the flooring manufacturer) as recommended by the flooring manufacturer. Comply with ASTM F 710 for concrete subfloor preparation. Floor fills or toppings may be required as recommended by the flooring manufacturer.

Install underlayments, when required by the flooring manufacturer, in accordance with manufacturer's recommended printed installation instructions. Comply with ASTM F 1482 for panel type underlayments. Before any work under this section is begun, correct all defects such as rough or scaling concrete, chalk and dust, cracks, low spots, high spots, and uneven surfaces. Repair all damaged portions of concrete slabs as recommended by the flooring manufacturer. Remove concrete curing and sealer compounds from the slabs, other than the type that does not adversely affect adhesion. Remove paint, varnish, oils, release agents, sealers, waxes, and adhesives, as required by the flooring product in accordance with manufacturer's printed installation instructions.

3.03 MOISTURE, ALKALINITY AND BOND TESTS

A. Determine the suitability of the concrete subfloor for receiving the resilient flooring with regard to moisture content and pH level by moisture and alkalinity tests. Conduct moisture testing in accordance with ASTM F 1869, unless otherwise recommended by the flooring manufacturer.

Conduct alkalinity testing as recommended by the flooring manufacturer. Determine the compatibility of the resilient flooring adhesives to the concrete floors by a bond test in accordance with the flooring manufacturer's recommendations.

B. Submit copy of test reports for moisture and alkalinity content of concrete slab, and bond test stating date of test, person conducting the test, and the area tested.

3.04 PLACING VINYL COMPOSITION TILES

A. Install tile flooring and accessories in accordance with manufacturer's printed installation instructions.

Prepare and apply adhesives in accordance with manufacturer's directions. Keep tile lines and joints square, symmetrical, tight, and even. Keep each floor in true, level plane, except where slope is indicated. Vary edge width as necessary to maintain full-size tiles in the field, no edge tile to be less than one-half the field tile size, except where irregular shaped rooms make it impossible. Cut flooring to fit around all permanent fixtures, built-in furniture and cabinets, pipes, and outlets. Cut, fit, and scribe edge tile to walls and partitions after field flooring has been applied.

3.05 PLACING MOLDING

A. Provide molding where flooring termination is higher than the adjacent finished flooring and at transitions between different flooring materials. When required, locate molding under door centerline. Secure molding with adhesive as recommended by the manufacturer. Prepare and apply adhesives in accordance with manufacturer's printed directions.

B. Molding is not required at doorways where thresholds are provided or where tile is continuous through openings.

3.06 CLEANING

A. Immediately upon completion of installation of flooring in a room or an area, dry/clean the flooring and adjacent surfaces to remove all surplus adhesive. Clean flooring as recommended in accordance

VINYL COMPOSITION FLOOR TILE - 09 65 00 - Page 4 with manufacturer's printed maintenance instructions. No sooner than 5 days after installation, wash flooring with a nonalkaline cleaning solution, rinse thoroughly with clear cold water, and, except for rubber flooring and stair treads, risers and stringers, vinyl and other flooring not requiring polish finish by manufacturer, apply the number of coats of polish in accordance with manufacturer's written instructions. Clean and maintain all other flooring as recommended by the manufacturer.

VINYL COMPOSITION FLOOR TILE - 09 65 00 - Page 1

SECTION 09 65 00

VINYL COMPOSITION FLOOR TILE

a. F 1066 (2004e1; R 2010) Standard Specification for Vinyl

Composition Floor Tile

b. F 1482 (2004; R 2009e1) Installation and Preparation of Panel Type Underlayments to Receive Resilient Flooring

c. F 1869 (2011) Measuring Moisture Vapor Emission Rate of Concrete Subfloor Using Anhydrous Calcium Chloride

A. Government approval is required for submittals with a "G" designation; submittals not having a "G"

Work, SUBMITTALS:

2. Adhesive; G

c. SD-04 Samples

2. Manufacturer’s Colors; G

d. SD-06 Test Reports

1. Moisture, Alkalinity and Bond Tests; G

e. SD-08 Manufacturers Instructions

1. Surface Preparation; G

2. Installation; G

1.03 DELIVERY, STORAGE AND HANDLING

Deliver materials to the building site in original unopened containers bearing the manufacturer's name, style name, pattern color name and number, production run, project identification, and handling instructions.

Store materials in a clean, dry, secure, and well-ventilated area with ambient air temperature maintained above 68 degrees F and below 85 degrees F, stacked according to manufacturer's recommendations.

1.04 SCHEDULING

VINYL COMPOSITION FLOOR TILE - 09 65 00 - Page 2

Schedule flooring application after the completion of other work which would damage the finished surface of the flooring.

1.05 WARRANTY

Provide manufacturer's standard performance guarantees or warranties that extend beyond a one year period.

1.06 EXTRA MATERIALS

Provide extra flooring material of each color and pattern at the rate of 5 tiles for each 1000 tiles installed.

Package all extra materials in original properly marked containers bearing the manufacturer's name, brand name, pattern color name and number, production run, and handling instructions. Provide extra materials from the same lot as those installed. Deliver extra stock to Building 120 west loading docks after notifying the Project COR.

2.01 VINYL COMPOSITION TILE

A. Conform to ASTM F 1066 Class 1, (solid color tile, Composition 1, asbestos-free, 12 inch square and

1/8 inch thick, color/pattern as selected from submittals by the COR.

2.02 BASE MOLDING

A. Provide base moldings of vinyl. Provide molding 4 inch in height, color as selected from submittals by the COR.

2.03 ADHESIVES

A. Provide XYZ ADHESIVE for flooring, base and accessories as recommended by LEN ODDY’S and by the manufacturer.

B. Submit manufacturer's descriptive data, documentation stating physical characteristics, and mildew and germicidal characteristics. Provide Material Safety Data Sheets (MSDS) for all primers and adhesives to the Contracting Officer. Highlight VOC emissions.

2.04 SURFACE PREPARATION MATERIALS

A. Provide and repair surface preparation materials, such as panel type underlayment, and floor crack fillers as recommended by the flooring manufacturer for the subfloor conditions. Comply with ASTM F 1482 for panel type underlayment products.

2.05 MANUFACTURER'S COLOR, PATTERN AND TEXTURE

A. Provide color, pattern and texture for resilient flooring and accessories as indicated selected from manufacturer's standard colors by the COR. Color listed is not intended to limit the selection of equal colors from other manufacturer. Provide flooring in any one continuous area from same production run with same shade and pattern.

3.01 EXAMINATION

A. Examine and verify that site conditions are in agreement with the design package. Report all conditions that will prevent a proper installation. Do not take any corrective action without written

VINYL COMPOSITION FLOOR TILE - 09 65 00 - Page 3 permission from the Government. Work will proceed only when conditions have been corrected and accepted by the installer. Submit manufacturer's printed installation instructions for all flooring materials and accessories, including preparation of substrate, seaming techniques, and recommended adhesives.

3.02 SURFACE PREPARATION

A. Provide a smooth, true, level plane for surface preparation of the flooring, except where indicated as sloped. Prepare subfloor in accordance with flooring manufacturer's recommended instructions.

Install and or repair underlayments, when required by the flooring manufacturer, in accordance with manufacturer's recommended printed installation instructions. Comply with ASTM F 1482 for panel type underlayments. Before any work under this section is begun, correct all defects such as low spots, high spots, and uneven surfaces. Remove paint, varnish, oils, release agents, sealers, waxes, and adhesives, as required by the flooring product in accordance with manufacturer's printed installation instructions.

3.03 MOISTURE, ALKALINITY AND BOND TESTS

A. Determine the suitability of the concrete subfloor for receiving the resilient flooring with regard to moisture content and pH level by moisture and alkalinity tests. Conduct moisture testing in accordance with ASTM F 1869, unless otherwise recommended by the flooring manufacturer.

Conduct alkalinity testing as recommended by the flooring manufacturer. Determine the compatibility of the resilient flooring adhesives to the concrete floors by a bond test in accordance with the flooring manufacturer's recommendations.

B. Submit copy of test reports for moisture and alkalinity content of concrete slab, and bond test stating date of test, person conducting the test, and the area tested.

3.04 PLACING VINYL COMPOSITION TILES

A. Install tile flooring and accessories in accordance with manufacturer's printed installation instructions.

Prepare and apply adhesives in accordance with manufacturer's directions. Keep tile lines and joints square, symmetrical, tight, and even. Keep each floor in true, level plane, except where slope is indicated. Vary edge width as necessary to maintain full-size tiles in the field, no edge tile to be less than one-half the field tile size, except where irregular shaped rooms make it impossible. Cut flooring to fit around all permanent fixtures, built-in furniture and cabinets, pipes, and outlets. Cut, fit, and scribe edge tile to walls and partitions after field flooring has been applied.

3.05 PLACING MOLDING

A. Provide molding where flooring termination is higher than the adjacent finished flooring and at transitions between different flooring materials. When required, locate molding under door centerline. Secure molding with adhesive as recommended by the manufacturer. Prepare and apply adhesives in accordance with manufacturer's printed directions.

B. Molding is not required at doorways where thresholds are provided or where tile is continuous through openings.

3.06 CLEANING

A. Immediately upon completion of installation of flooring in a room or an area, dry/clean the flooring and adjacent surfaces to remove all surplus adhesive. Clean flooring as recommended in accordance with manufacturer's printed maintenance instructions.

TAWV-IMP-F

Interior Paints and Coatings - 09 90 00 - Page 1

SECTION 09 90 00

INTERIOR PAINTS AND COATINGS

A. ASTM International (ASTM) B. Master Painters Institute (MPI) C. Unified Facilities Guide Specification (UFGS)

A. Government approval is required for submittals with a "G" designation; submittals not having a "G" designation are for information only. Submit the following in accordance with the “Statement of Work -

SUBMITTAL REQUIREMENTS”:

a. SD-03 Product Data

1. Sealant, Primer, Paint; G

b. SD-04 Samples

1. Color Swatches; G

Submit manufacturer's samples of paint colors.

c. SD-08 Manufacturer’s Instructions

1. Manufacturer's Material Safety Data Sheets (MSDS)

1.03 ENVIRONMENTAL CONDITIONS

A. Comply, at minimum, with manufacturer recommendations for space ventilation during and after installation.

A. Primer

a. Primer shall be interior latex-based primer, low VOC, stain-blocking/stain-hiding formulation intended for the purpose of being applied over bare paper-faced drywall and unfinished wood. Color shall be white.

b. Provide substitute primer for unique surfaces or areas where the primer specified herein is not manufacturer approved for the application.

B. Paint

a. Paint shall be interior latex-based paint, low VOC, water based, with a color as selected by the

Government upon submittal processing.

b. Provide substitute paint for unique surfaces or areas where the paint specified herein is not manufacturer approved for the application.

3.01 SURFACE PREPARATION

TAWV-IMP-F

Interior Paints and Coatings - 09 90 00 - Page 2

A. Contractor shall remove all removable items from surfaces to be coated, and set aside during project work, to include outlet covers, door signs, switch covers, thermostat covers, operators etc. At completion of the project, all items shall be replaced in their original locations.

B. Contractor shall temporarily move any furniture that needs to be relocated for painting. Temporary locations to store will be coordinated with the COR and office occupants. All furniture must be moved back to the original position with no damage at the completion of the project.

C. Contractor shall follow all manufacturer’s instructions and recommendations for prepping the surface for new primer and paint.

D. Paint shall be scraped from any areas where it is peeling or bubbling. The paint shall be removed to sound layer and to provide a proper base for the new coating.

E. Plaster and stucco shall be clean and free from loose matter; gypsum board shall be dry. Remove loose dirt and dust by brushing with a soft brush, rubbing with a dry cloth, or vacuum-cleaning prior to application of the first coat material. A damp cloth or sponge may be used if paint will be water-based.

F. Repair of Minor Defects: Prior to painting, repair joints, cracks, holes, surface irregularities, and other minor defects with patching plaster or spackling compound and sand smooth. Any corners that have been damaged or appear uneven shall be skim-coated and refinished.

3.02 APPLICATION

A. Contractor shall follow all manufacturer’s instructions and recommendations for paint and primer. This is to include storage, mixing, application and dry times.

B. Contractor shall apply one coat of primer to all wall surfaces. Where one coat does not fully cover underlying paint color or does not fully cover uncoated surfaces, a second coat shall be applied.

C. Once primer has dried and is ready for paint covering, contractor shall paint surfaces. Paint application shall include a minimum of two (2) coats of paint. Wherever the prescribed number of coats does not sufficiently cover and hide existing marks, wherever there is “bleed through”, and wherever it appears that additional coats are necessary to properly cover the wall surfaces, the Contractor shall apply an additional coat of unthinned paint until smooth, opaque coverage is achieved.

D. At completion of painting, all painted surfaces shall appear smooth and evenly coated, with no bleed through.

Windows, if painted, shall operate in the same manner as prior to project work. All removable items such as the clock, switch covers, outlet covers, etc. shall be returned to their original locations.

2118173 26 05 19-1

SECTION 26 05 19

LOW VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES

1.1 DESCRIPTION

1. CONTRACTOR shall provide all labor, materials, equipment, and incidentals shown, specified, and required to furnish and install low voltage conductors and cable.

2. Types of cable required include:

a. Insulated cable for installation in raceways.

b. Cable for installation in cable trays.

B. Related Sections:

2. Section 26 05 53, Identification for Electrical Systems.

1.2 REFERENCES

A. Standards referenced in this Section are:

1. ASTM B3, Standard Specification for Soft or Annealed Copper Wire.

2. ASTM B8, Standard Specification for Concentric-Lay-Stranded Copper

Conductors, Hard, Medium-Hard or Soft.

3. ASTM D3485, Standard Specification for Smooth-Wall Coilable Polyethylene

Conduit for Preassembled Wire and Cable.

4. ASTM F2160, Solid Wall High Density Polyethylene (HDPE) Conduit Based on Controlled Outside Diameter.

5. NETA, Acceptance Testing Procedures.

6. ICEA S-95-658, Non-Shielded Power Cables Rated 2000V or Less.

7. NEMA TC-7, Smooth-Wall Coilable Electrical Polyethylene Electrical Plastic

Conduit.

8. UL 44, Thermoset-Insulated Wires and Cables.

9. UL 1277, Electrical Power and Control Tray Cables with Optional Optical-

Fiber Members.

1.3 QUALITY ASSURANCE

A. Regulatory Requirements: Comply with the following:

1. NEC Article 300, Wiring Methods.

2. NEC Article 310, Conductors for General Wiring.

2118173 26 05 19-2

1.4 SUBMITTALS

A. Action Submittals: Submit the following:

1. Product Data:

a. Manufacturer’s literature, specifications, and engineering data for low volt insulated cable proposed for use.

b. Manufacturer’s literature for cable markers.

B. Informational Submittals: Submit the following:

1. Field Quality Control Submittals:

a. Written records of field insulation resistance test results.

PART 2 – PRODUCTS

2.1 MATERIALS

A. Insulated Cable In Raceways:

1. Application: Use for circuits located indoors and outdoors.

2. Manufacturers: Provide products of one of the following:

a. Southwire.

b. The Okonite Company.

c. American Insulated Wire

d. General Cable

e. Or equal.

3. Material: Single conductor copper cable complying with ASTM B3 and ASTM B8 with flame-retardant, moisture- and heat-resistant insulation rated for 90 degrees C in dry or wet locations, listed by UL as Type XHHW-2 or RHW-2 complying with UL 44.

4. Wire Sizes: Not smaller than No. 12 AWG for power and lighting and No. 14 AWG for 120-volt control circuits.

5. Stranding: 600-volt cable shall be stranded, except that solid cable, No. 10 and smaller may be used for lighting circuits.

B. Cable Connectors, Solderless Type:

1. For wire sizes up to and including No. 6 AWG, use compression type. Alarm and control wire shall be terminated using forked type connectors at terminal boards.

2. Products and Manufacturers: Provide products of one of the following:

a. T&B Sta-Kon.

b. Burndy Hylug.

c. Or equal.

3. For wire sizes No. 4 AWG and above, use either compression type or bolted type with silver-plated contact faces.

4. For wire sizes No. 250 KCMIL and larger, use connectors with at least two cable clamping elements or compression indents and provision for at least two bolts for joining to apparatus terminal.

2118173 26 05 19-3

5. Properly size connectors to fit fastening device and wire size. Connectors shall be rated for 90 degree C, 600 volts.

C. Cable Splices:

1. Products and Manufacturers: Provide one of the following:

a. Compression-Type Splices:

1) Burndy Hylink.

2) T&B Color-Keyed Compression Connectors.

3) Or equal.

b. Spring Connectors:

1) Buchanan B-Cap.

2) T&B Wire Connector.

3) Or equal.

2. For wire sizes No. 8 AWG and larger, splices shall be made up with compression type copper splice fittings. Splices shall be taped and covered with materials recommended by cable manufacturer to provide insulation equal to that on conductors.

3. For wire sizes No. 10 AWG and smaller, splices may be made up with pre-insulated spring connectors.

4. For wet locations, splices shall be waterproof. Compression type splices shall be waterproofed by sealant-filled, thick wall, heat shrinkable, thermosetting tubing or by pouring thermosetting resin into mold that surrounds the joined conductor. Spring connector splices shall be waterproofed with sealant filler.

5. Splices shall be suitably sized for cable, rated 90 degrees C, 600 volts.

D. Wire and Cable Markers:

1. Provide wire and cable markers in accordance with Section 26 05 53, Identification for Electrical Systems.

2.2 SOURCE QUALITY CONTROL

A. Factory Tests:

1. Factory-test wire and cable in accordance with UL standards

PART 3 – EXECUTION

3.1 INSTALLATION

A. Install cables complete with proper terminations at both ends. Check and correct for proper phase sequence and proper motor rotation.

B. Pulling:

1. Use insulating types of pulling compounds containing no mineral oil.

2. Pulling tension shall be within limits recommended by wire and cable manufacturer.

3. Use dynamometer where mechanical means are used.

2118173 26 05 19-4

4. Cut off section subject to mechanical means.

C. Bending Radius: Limit to minimum of six times cable overall diameter.

D. Slack: Provide maximum slack at all terminal points.

E. Splices:

1. Where possible, install cable continuous, without splice, from termination to termination.

2. Where required, splice as shown and also where required for cable installation.

Splices below grade, in manholes, handholes, and wet locations shall be waterproof.

3. Splices are not allowed in conduits.

F. Identification:

1. Identify conductors in accordance with Section 26 05 53, Identification for

Electrical Systems.

2. Identify power conductors by circuit number and phase at each terminal or splice location.

3. Identify control and status wiring using numeral tagging system.

G. Color-code power cables as follows:

1. No. 8 AWG and Smaller: Provide colored conductors.

2. No. 6 AWG and Larger: Apply general purpose, flame retardant tape at each end, wrapped in overlapping turns to cover an area of at least two inches.

3. Colors: Match color scheme in use at the Site. If the Site does not have an existing color scheme, use the following colors:

System Conductor Color All Systems Equipment Grounding Green

240/120 Volts…