SPECIFICATION SHEET - RMO GENERATORS.pdf
PDF 168 KB Posted
- Attached to
- Mobile Diesel Generators Federal contract opportunity
- Solicitation number
- FA488721Q0026
About this file
This specification sheet and solicitation describe requirements for mobile diesel generators. The Air Force seeks to acquire eight trailer-mounted generators with a minimum 45 kW prime power rating and 3-phase, 120/208 VAC primary power. Quotes must be submitted through SAM.gov by 12:00PM PST on July 15, 2021 and address solicitation FA488721Q0026. The generators must have a 5-wire output interface, remote start capability, an auxiliary fuel pump, and be transportable on an AZDOT-rated trailer. Delivery to Gila Bend, Arizona is required no later than 270 days after contract award.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| QA Document 4 - FA488721Q0026.pdf | ||
| QA Document 3 - FA488721Q0026.pdf | ||
| QA Document 2 - FA488721Q0026.pdf | ||
| QA Document - FA488721Q0026.pdf | ||
| Presolicitation Questions.pdf | ||
| Solicitation - FA488721Q0026.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SPECIFICATION SHEET
Luke AFB, AZ
56 RMO/ACTS
4 June 2021
1. GENERAL:
The contractor shall provide a quantity of eight (8) Generators with the below salient characteristics.
Generators shall be new, not used, equipment. The generators must be trailer mounted in a steel weather-rated, fully lockable enclosure. The contractor shall supply the Government with the manufacturer’s manual and warranty as per industry standards.
2. MINIMUM SPECIFICATIONS: The generators must (at a minimum) comply with the following salient characteristics:
-Minimum 45 kW Prime Power Rating
-Primary generator power is to be 3-Phase, 120/208 VAC
-5-wire customer output interface
-2-wire Remote start capability
-Auxiliary fuel pump and connectors for connection to external fuel tank
-AZDOT rated trailer for generator transportation
3. DELIVERY:
-Shipping and Transport for Generators must be included in the quotation.
-Contractor shall deliver to 2008 Front St. Gila Bend AFAF, AZ 85337 -Delivery will be no later than 270 days after the date of contract (ADC).