About this file
This document outlines requirements for a solicitation from the 56th Contracting Squadron seeking to acquire eight mobile diesel generators for the Barry M Goldwater Range in Gila Bend, Arizona. The generators must be new, trailer mounted in a steel weather-rated and lockable enclosure. Each generator must have a minimum 45 kW prime power rating, be 3-phase 120/208 VAC, and include a 5-wire customer output interface and 2-wire remote start capability. An auxiliary fuel pump and connectors for an external fuel tank are also required. Quotes must be submitted through the System for Award Management by 12:00PM PST on July 15, 2021 or emailed to the specified Contract Specialist. The solicitation number is FA488721Q0026 and is being conducted by the Department of the Air Force Air Education and Training Command.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| QA Document 4 - FA488721Q0026.pdf | ||
| QA Document 3 - FA488721Q0026.pdf | ||
| QA Document - FA488721Q0026.pdf | ||
| SPECIFICATION SHEET - RMO GENERATORS.pdf | ||
| Presolicitation Questions.pdf | ||
| Solicitation - FA488721Q0026.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Question and Answer Document 2
FA488721Q0026
Q: Voltage is listed at 208/120vac 60hz output – Question- Do you require a voltage selector switch that allows the output to be changed (480vac-208vac -240vac 2-phase) by rolling barrel switch, or will this unit ONLY be used at 208/120vac 60hz output?
A: No. We don’t need to be able to switch between outputs; 3-phase, 208/120VAC 60hz only.
Q: Output connection is listed as 5 post output 3 phases, neutral, and ground with a removable link for bonding Neutral and Ground. Q – Will you want us to include a voltage distrobution panel with 120v duplex outlets, Hubbell twist outlets, and Cam-loc color coded female receptacles.
A: It would be nice for it to have a 120V outlet; most generators do. We do not need “Hubbell twist outlets” or “Cam-loc color coded female receptacles”. We need discreet terminal hook ups capable of 2/0 cable for A, B, C, Neutral and Ground.
Q: Are these generators for Emergency Back-up and would you accept T3 emission technology?
OR, are you going to require T4f emission technology for Prime Power application?
A: Must be T4.
Q: Is there no fuel tank required for the unit itself or would you like an in base tank and a 3-way valve for an external tank connection? The engine is equipped with an electric lift pump but if you are drawing a long distance we should know that distance so we can size the fuel pump accordingly.
A: We do need an internal tank for the probability of servicing the generator off-site. Also needs to be able to switch to Aux fuel (external tank).