Presolicitation Questions.pdf

PDF 72 KB Posted

Attached to
Mobile Diesel Generators Federal contract opportunity
Solicitation number
FA488721Q0026
Issued by
Department of the Air Force Air Education and Training Command

About this file

This document outlines requirements for a solicitation seeking mobile diesel generators. The Air Force's 56th Contracting Squadron is soliciting quotes for eight trailer-mounted diesel generators with a minimum prime power rating of 45 kW to be used at Barry M Goldwater Range in Arizona. The generators must have a 5-wire customer output interface and 2-wire remote start capability, as well as an auxiliary fuel pump and connectors to connect to an external fuel tank. Quotes must be submitted through SAM.gov by 12:00PM PST on July 15, 2021. All questions are due by 1:00PM PST on July 12, 2021 and should be directed to the identified Contract Specialist.

View the file

Other files for this federal contract opportunity

Other files attached to Mobile Diesel Generators, newest first.
File Type Posted
QA Document 4 - FA488721Q0026.pdf PDF
QA Document 3 - FA488721Q0026.pdf PDF
QA Document 2 - FA488721Q0026.pdf PDF
QA Document - FA488721Q0026.pdf PDF
SPECIFICATION SHEET - RMO GENERATORS.pdf PDF
Solicitation - FA488721Q0026.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Q&A for Solicitation FA488721Q0026

Can you provide clarification on the 5-wire customer output interface?

-These type generators come capable of 3-phase, and normally have a buss bar across the ground and neutral. We make the stipulation that there be a discreet 5-post output (meaning the buss bar is removable) because our application requires separate ground and neutral with the 3-phase power.

Can you provide clarification on the Auxiliary Fuel Pump and Connectors for connection to external fuel tank?

-The generators need an external fuel tank and an auxiliary fuel pump that would enable the external tank to connect to the generator.

File details come from the government source that posted it. Updated .