SOW_Elevators.docx
DOCX document 16 KB Posted
- Attached to
- Install Door Lock Monitoring System
- Solicitation number
- 12405B24Q0539
About this file
This document is a Statement of Work (SOW) for upgrading the elevator cab door monitoring system at the USDA Agricultural Research Service facility in Gainesville, Florida. The SOW specifies that the existing elevators require an additional cab door monitoring system and logic to comply with ASME A17.3-2015 code requirements for safety enhancements on existing elevators. The scope of work includes installing a new logic system, cab door sensors, power supply, NEMA 1 cabinet, and updated software to ensure the elevators will not operate with faulty door contacts.
The related federal contract opportunity is a solicitation (Solicitation Number: 12405B24Q0539) issued by the USDA, ARS Southeast Area for the installation of the elevator door lock monitoring system described in the SOW. The solicitation requests quotes from responsible sources to provide and install the required system upgrades. Quotes must be submitted by 4:00pm CST on August 29, 2024, and will be evaluated based on technical capability, past performance, and price. Award will be made to the responsible offeror whose quote represents the best value to the government.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Solicitation clauses and provisions_service.pdf | ||
| SCA WD_12405B24Q0539.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Statement of Work
Upgrading Elevator Cab Door Monitoring
USDA, ARS
1700 SW 23rd Dr.
Gainesville, FL 32608
EXISTING CODE REQUIRED SAFTEY UPGRADE
A17.3* code requires that all existing elevators are equipped with an additional cab door monitoring system and logic. A17.3 code for existing elevators implements safety enhancements retroactively.
Code for new elevators has included this cab door safety feature for many years. Additional system sensors and logic ensures that the elevator will not operate with faulty door contacts.
Elevators:
(2) hydraulic elevators in Building No. 11.
Make of the elevators is Montgomery Elevator Style HY 11.
Cycles: 60 Volts: 480 Horse Power: 25 Phase: 3 2 Landing Elevators Serial Number(s): C21865 and C21866
ASME A17.3-2015
3.10.12.System to Monitor and Prevent Automatic Operation of the Elevator with Faulty Door Contact Circuits Means shall be provided to monitor the position of power-operated car doors that are mechanically coupled with the landing doors while the car is in the landing zone, in order
a) to prevent automatic operation of the car if the car door is not closed, regardless of whether the portion of the circuits incorporating the car door contact or the interlock contact of the landing door coupled with the car door, or both, are closed or open, except as permitted
b) b) to prevent the power closing of doors during automatic operation if the car door is fully open and any of the following conditions exist:
1) The car door contact is closed, or the portion of the circuit incorporating this contact is bypassed.
2) The interlock contact of the landing door that is coupled to the opened car door is closed, or the portion of the circuit incorporating this contact is bypassed.
3) The car door contact and the interlock contact of the door that is coupled to the opened car door are closed, or the portions of the circuits incorporating these contacts are bypassed.
Cab Door Monitoring Upgrade:
New Logic System & Boards
• New Cab Door Sensors
• New Power Supply
• New NEMA 1 Cabinet
• Updated Software / Logic
• Regulatory and A17.3 Compliance