STATEMENT OF WORK

Fire Sprinkler System Repair

FACILITY: Department of Transportation Maritime Administration Warehouse

1651 Viking Street, Building 168 Alameda, CA 94501

POC: Mike Streblow 510-217-0379

Provide labor, equipment, and materials to perform the Fire Sprinkler System Repair. All work performed will be per NFPA, California State, and Alameda Fire Department requirements and will be guaranteed, insured and performed by licensed personnel.

Repair work will be performed in accordance with the requirements of the current NFPA 25 California Edition.

There is no fire pump or pressure reducing valve.

The check valve is above ground, is easily accessible, and can be reversed and restored as required for backflow per NFPA 25.

The quote will include a breakdown of Time & Material costs to correct each deficiency.

Certification Tags and Stickers will be provided after correction of all deficiencies. A final written report will be provided noting that all deficiencies have been corrected.

Scope of Work:

5 Year Fire Sprinkler Inspection Deficiencies Repairs:

1. Replace faded P.I.V. Control Valve sign

2. Replace P.I.V. stickers on Risers# 3, 4, and 5

3. Replace (117) painted 1/2" 165 brass SSU sprinkler heads on back half of system where original heads were not changed. (Riser #1)

4. Replace (54) painted 1/2" 165 brass SSU sprinkler heads on back half of system where original heads were not changed. (Riser #2)

Notes: Original heads are GRINNELL 1/2" 165 DURASPEED brass SSU-1944