SOW.HLLoadBank.docx
DOCX document 21 KB Posted
- Attached to
- LOAD BANK RENTAL
- Solicitation number
- 2123403Y61A1497001
View the file
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SOW for Reactive Load Bank Reference PR 2123403Y61A1497001
CGC HARRIET LANE
Contractor shall provide, deliver, and pick- up a reactive a load bank to be utilized in the testing phase of the newly install diesel generator shipboard system and C18 diesel generators onboard CGC HARRIET LANE. The period of performance is from 24 January 2023 to 24 February 2023. The following requirements must be meet for the contractor provided load bank.
Load Bank Specifications:
· 480 Volts, 3 phase, 60 Hertz
· Load Bank Reactive- 2640 kW
· 4/0, 375 Amp Cable- 50 FT Loose with Camlocks
· Cable Tail 4/0- Eyelet + Female Camlock Loose
· Cable Tail 4/0- Male Camlock + Eyelet Loose
The reactive load bank accurately simulates the types of loads the generator sets will see with equipment startup loads and reacting to the inrush. CGC HARRIET LANE is a SLEP (Service Life Extension Program) installation needed to validate the following requirement below which can only be done with a reactive load bank:
Load Sharing- Over the range of the test, the real loads (kW) on the individual generator sets are not to differ from their equal share of the total real load (kW) by more than 15% of the generators’ rated real power (kW) output. The reactive loads (kVA) on the individual generator sets are not to differ from their equal share of the total reactive load (kVA) by more than 10% of the generators’ rated reactive (kVA) output.
Normal operating hours of the Yard are from 0700 to 1530 Monday through Friday.
The contractor may opt to work past 1600 hours Monday through Friday, and work may work weekends if deemed necessary. If work is scheduled other than normal Yard operating hours the contractor must notify the Ship Superintendent of his/her intentions. NOTE: No work will be done after 1530 unless authorized by the Contracting Office or Contract Specialist.
The contractor provided load bank shall be delivered to the following address:
POC: Justin Price, 410-636-3992 CG Yard 2401 Hawkins Point Rd Baltimore, MD 21226