S06 - Drawings 1-10.pdf
PDF 8 MB Posted
- Attached to
- Z2DA--Upgrade Electrical Systems Area 1 695-19-101 Federal contract opportunity
- Solicitation number
- 36C25220B0022
About this file
This document includes a pre-solicitation notice and opportunity for an upgrade to plumbing project at the Clement J. Zablocki VA Medical Center in Milwaukee, Wisconsin. The project scope involves infection control, plumbing, and demolition work to upgrade plumbing systems for legionella prevention. The project value is estimated between $5 million and $10 million. The solicitation will be posted to FedBizOpps on May 14, 2020 with a bid opening planned for June 16, 2020. A pre-bid conference will be held to review the site. The North American Industry Classification System code for this procurement is 236220 with a size standard of $36.5 million. The period of performance is 740 calendar days from notice to proceed. This opportunity is a 100% set-aside for Service-Disabled Veteran-Owned Small Businesses verified in the Vendor Information Pages database.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C25220B0022_1.docx | DOCX document | |
| S06 - Drawings 31-40.pdf | ||
| P07 - Davis Bacon WD.pdf | ||
| Previous RFIs and Answers.pdf | ||
| S06 - Drawings 11-20.pdf | ||
| S06 - Drawings 41-50.pdf | ||
| S06 - Drawings 21-30.pdf | ||
| S06 - Amended Specifications.pdf | ||
| S06 - Drawings 51-66.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
VA PROJECT NUMBER
Building Number
Drawing Number
Project Title
Date Checked Drawn
Drawing Title
Approved:
VA FORM 08-6231
A
B C
D E
21 4 5 6 7
321 4 5 6 7
A B
C D
E
Dwg. of
LocationLocation
Office of
Construction and Facilities
Management
PROJECT MANAGER:
ACG Project Number
CONSULTANTS:
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120
Cary, North Carolina 27511 www.acg-pa.com 919-858-7420
U.S. Department of Veterans Affairs
© COPYRIGHT Apogee Consulting Group, P.A.Revisions: Date# Engineers Architects
UPGRADE ELECTRICAL
SYSTEMS PHASE 1
695-19-101
CLEMENT J. ZABLOCKI VAMC
5000 W NATIONAL AVE, MILWAUKEE, WI
53295
19-097
100% CONSTRUCTION DOCUMENTS
Structural Engineer:
10/29/2019 CNJHT
VA MEDICAL CENTER
CAMPUS LOCATION AREA OF
WORK
VICINITY MAP
NTS
CAMPUS MAP
NTS
G-001
COVER SHEET
UPGRADE ELECTRICAL SYSTEMS
PHASE 1
CLEMENT J. ZABLOCKI VAMC
5000 W NATIONAL AVE, MILWAUKEE, WI 53295
VA PROJECT #: 695-19-101
NOTES:
REV. #0 - 10/29/2017 ISSUED FOR CONSTRUCTION
REV. #1 - 12/04/2019 IFC - BUILDING 111 PANEL ADDS
REV. #2 - 12/05/2019 IFC - SCHEDULED OUTAGE NOTE UPDATE
REV. #3 - 03/20/2020 IFC - MEDIUM VOLTAGE FEEDER UPDATE
DocuSign Envelope ID: 0CBD189B-3560-4332-8952-A636DB8D6073
3/20/2020
123B
123A
123E
123D
123C
70B
70A
70E
70K
70C
70D
111C
111B
111A
111D
T114
6C
6A
6D
6B
T105
T106
T107
H
V
S
A
MCIR
MH
MH
MH
MH
MH 3
MH 15
MH 20
MH 23
MH 24
MH 25
MH 27
MH 29
MH 30
MH 31
MH 32
MH
MH 34
MH 35
MH 36
MH 38
MCIR
HVP 24
HVP 22
HVP 23
VAULT
HVS 2
HVP 2
HVP K
XF K
HVP 16
HVP 15
HVP 3
HVS 18
HVP 18
HVS 4
HVP 8
HVS 11
XF 39
MH 9
MH
MH 11
MH
MH
XF 97
HVP 36
XF 36
HVS 36
XF 20
HVP 31
XF 7
XF 2
PNL K
HVS SL1
XF 41
HVP 11
HVP 20
HVS 20
PNL 27
XF 27
XF 5
HVP 29
XF11
HVP 30
PNL 11
HVP 40
XF 14
PNL 14
XF 12
PNL 16
XF 16
HVP 41
HVS 41
XF 41
PNL 17
XF 17
PNL 19
HVP 44
HVP 4
XF 3
PNL BLD
3/4 DIST.
MH 40
MH 41?
MH 43
HVP 42
MH 42
MH 44
MH 18
MH 18
MH 4
M
H
MH
MH 13
A
F
T
O
N
C
T
A F
T O
N
C
W
S
H
I
N
G
T
D
R
W WASHINGTON DR
S
H
I
N
G
T
S
H
I N
G
T
G
E
N
E
R
L
M
I
T
C
H
E
B
V
D
A
M
B
U
L
A
N
E
Y
W
A
R
E
H
O
U
Y
L
I
N
C
O
B
A
R
R
R
R
R
W
O R
K S
H O
P
R
O A
D
BARRON CT
G
E
N
E
R
T
C
H
E
V
T
C
H
E
V
D
H
I N
V
D
C
H
R
Y
S
L
E
KILBOURN CIR
K
I
L
B
O
U
R
J U
N E
U
E
J U
N E
U
E
AMERICAN
WARMOTHERS AVE
Z
A
B
L
O
C
K
G
T
C
H
E
V
D
S T
A D
I U
M
L N
G E
N E
R A
L W
O L C
O T
T B
L V
D
G
ENERAL W
O
LCO
TT A
VE
W
O
E
M
E
M
O
R
I
GOLDSTATE DR
F
L
O
W
H
I
N
V
D
XF 1301
MH
HVS16
VAULT
XF2-BLD-102
XF 52
XF 49
PNL 49
HVS 23A
HVS 23B
B
C
L
HVP 27
PNL 39
XF 57
MH
HVP 146
HVS 146
XF 146
CB-100-CLC
CB-600-146
HVP 147
HVS 147
XFMR 147
CB-600-147
CB-600-148
XF 148
HVS 148
HVP 148
VAULT
MH 37
XF 108
PNL 108
PNL 2V?
HVP 34
XF 1
PNL 1
VAULT
VAULT
XF 7
XF 19
XF 41
PNL 41
MH 39
XF 58
EDG
EDG
EDG
EDG
XF 62
PNL 62
XF-43
XF 119
MANHOLE
PRI. CABLE
LOOP PRI CABLES AROUND EACH
MANHOLE AT LEAST ONE
HALF OF THE WAY AROUND
40020 TO FA RUN
AT M.H.
- EXISTING U/G MV FEEDER LINE
- NEW U/G MV FEEDER LINE
- POWER DISTRIBUTION SWITCH (HVP OR HVS)
- TRANSFORMER (XF'S)
- ELECTRICAL PANEL
- MANHOLE (MH)
SITE PLAN SYMBOL LEGEND
MANHOLE
PRI. CABLE
LOOP PRI CABLES AROUND EACH
MANHOLE AT LEAST ONE
HALF OF THE WAY AROUND RUN.
NORTH
TRUE
0 1 2 4
ES101
ELECTRICAL SITE PLAN
PRIMARY POWER DISTRIBUTION
SHEET KEY NOTES:
SHEET NOTES:
VA PROJECT NUMBER
Building Number
Drawing Number
Project Title
Date Checked Drawn
Drawing Title
Approved:
VA FORM 08-6231
A
B C
D E
21 4 5 6 7
SHEET NOTES:
SHEET KEY NOTES:
321 4 5 6 7
A B
C D
E
Dwg. of
LocationLocation
Office of
Construction and Facilities
Management
PROJECT MANAGER:
ACG Project Number
CONSULTANTS:
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120
Cary, North Carolina 27511 www.acg-pa.com 919-858-7420
U.S. Department of Veterans Affairs
© COPYRIGHT Apogee Consulting Group, P.A.Revisions: Date# Engineers Architects
UPGRADE ELECTRICAL
SYSTEMS PHASE 1
695-19-101
CLEMENT J. ZABLOCKI VAMC
5000 W NATIONAL AVE, MILWAUKEE, WI
53295
19-097
100% CONSTRUCTION DOCUMENTS
Structural Engineer:
10/29/2019 CNJHT
1 ELECTRICAL SITE PLAN - MV FEEDER REPLACEMENT
SCALE: N.T.S.
A. THIS DRAWING DOES NOT SHOW ALL
ELECTRICAL EQUIPMENT AND UNDERGROUND
ROUTING FOR DRAWING CLARITY.
B. REFER TO DRAWING ES102 FOR BLOCK DIAGRAM
AND U/G MV FEEDER REPLACEMENT SCHEDULE.
C. REFER TO DRAWING E-601 FOR SINGLE LINE
DIAGRAM.
2 CABLE INSIDE MANHOLE
SCALE: N.T.S.
XF-SL1
HVS-SL1
HVS-A
HVP-K
HVP-2
HVP-3
HVP-20
HVP-22
HVP-23
HVP-24
HVP-27
HVP-29
HVP-31
HVP-34
HVP-36
XF-K
HVS-2
HVP-4
HVP-8
HVS-4
XF-43
XF-146
XF-41
HVP-11
HVS-11
XF-39
HVP-15
HVS-16
XF-119
HVP-18
HVS-18
XF-112
XF-49
HVS-20
XF-2 BLDG-102
HVS-22/CL-1
XF-CL1
HVP-40
XF-14
HVP-42
HVP-42
XF-12
49 XF-16
HVP-41
XF-17
HVP-44
XF-19
XF-62
XF-27
XF-6
HVP-30
XF-11
XF-7
XF-5
XF-3
XF-2
XF-1
XF-20
XF-97
XF-108
XF-36
TO BLDG
HVP-16
HVS-36
HVS-23A
HVS-23B
43-1 44-1
ES102
UNDERGROUND MV DISTRIBUTION FEEDER
BLOCK DIAGRAM
VA PROJECT NUMBER
Building Number
Drawing Number
Project Title
Date Checked Drawn
Drawing Title
Approved:
VA FORM 08-6231
A
B C
D E
21 4 5 6 7
SHEET NOTES:
SHEET KEY NOTES:
321 4 5 6 7
A B
C D
E
Dwg. of
LocationLocation
Office of
Construction and Facilities
Management
PROJECT MANAGER:
ACG Project Number
CONSULTANTS:
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120
Cary, North Carolina 27511 www.acg-pa.com 919-858-7420
U.S. Department of Veterans Affairs
© COPYRIGHT Apogee Consulting Group, P.A.Revisions: Date# Engineers Architects
UPGRADE ELECTRICAL
SYSTEMS PHASE 1
695-19-101
CLEMENT J. ZABLOCKI VAMC
5000 W NATIONAL AVE, MILWAUKEE, WI
53295
19-097
100% CONSTRUCTION DOCUMENTS
Structural Engineer:
10/29/2019 CNJHT
2 UNDERGROUND MV DISTRIBUTION FEEDER - BLOCK DIAGRAM
SCALE: N.T.S.
1 MEDIUM VOLTAGE DISTRIBUTION FEEDER SCHEDULE
SCALE: N.T.S.
1 2 3
1. SUBMIT THE POWER OUTAGE SCHEDULE TO COR
FOR APPROVAL PRIOR TO CONSTRUCTION.
RESUBMIT THE SCHEDULE WHEN CHANGES
OCCUR.
2. PROVIDE NEW FEEDERS AS SHOWN ON THE
EQUIPMENT LIST.
3. UPDATE THE LENGTH COLUMN SHOWING THE
ACTUAL LENGTHS OF THE NEW FEEDER.
4. UPDATE THE EXISTING SHORT CIRCUIT
CALCULATION MODEL USING NEW CABLES AND
PROVIDE ARC FLASH LABELS.
5. REMOVE EXISTING FEEDER. SECURE AND CAP
BOTH ENDS OF EMPTY CONDUIT.
A. REFER TO ES101 FOR SITE PLAN INFORMATION.
B. REFER TO E-601 FOR SINGLE LINE DIAGRAM.
C. ITEMS IN DARKER LINEWEIGHT REPRESENT NEW
WORK. ITEMS IN LIGHTER LINEWEIGHT
REPRESENT EXISTING CONDITIONS BEYOND THE
SCOPE OF WORK.
ROOM B0123AEC
ELECTRICAL CLOSET
ROOM B0280B
GENERATOR RM
PL-B04-1
PH-B04-1
EUL-CR-B02-2
PL-B01-1
PL-B01-2T3 - 500 KVA XFMR
DL-B01-2
UL-B01-5
UL-B01-6
ECRT-2 B0123
ELEV. DS
EP101
EP101
ROOM B0458
TRASH/RECYLING
DH-B00-10
(SUB BASEMENT)
EUL-CR-B01-1
PNL EUL-CR-B04-3
ROOM B0460EC
ELECTRICAL CLOSET
MCC-G
1 2
ROOM B0239
AREA OF WORK
KEY PLAN - BUILDING 111
N
RM B0239A
RM B0452A
SUB-
BASEMENT
RM
B0123AEC
RM B0280B
RM B0460EC
E-100
BUILDING 111 BASEMENT FLOOR PLAN
1 BUILDING 111 BASEMENT FLOOR PLAN - PARTIAL
SCALE: 1/16" = 1' 0"
NORTH
TRUE
8 16 320
A. REFER TO E-613 FOR WORK DETAILS OF
EXISTING EQUIPMENT AFFECTED ON THE
PROJECT.
B. REFER TO THE ROOM ENLARGED PLANS FOR
THE NEW ELECTRICAL EQUIPMENT AND
LOCATION IF NOTED.
C. REFER TO SINGLE LINE DIAGRAMS AND PANEL
SCHEDULES FOR EQUIPMENT AND CIRCUIT
DETAILS.
SHEET KEY NOTES:
SHEET NOTES:
VA PROJECT NUMBER
Building Number
Drawing Number
Project Title
Date Checked Drawn
Drawing Title
Approved:
VA FORM 08-6231
A
B C
D E
21 4 5 6 7
SHEET NOTES:
SHEET KEY NOTES:
321 4 5 6 7
A B
C D
E
Dwg. of
LocationLocation
Office of Construction and Facilities Management
PROJECT MANAGER: ACG Project NumberCONSULTANTS:
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs
© COPYRIGHT Apogee Consulting Group, P.A.Revisions: Date# Engineers Architects
UPGRADE ELECTRICAL
SYSTEMS PHASE 1
695-19-101
CLEMENT J. ZABLOCKI VAMC
5000 W NATIONAL AVE, MILWAUKEE, WI
53295
19-097
100% CONSTRUCTION DOCUMENTS
Structural Engineer:
10/29/2019 CNJHT
1. CONTRACTOR TO REPLACE OR RETROFIT
SWITCHBOARD OR PANELBOARD AS SHOWN ON
THIS DRAWING. SEE EQUIPMENT LIST ON DRAWING
E-613.
2. IF ANY CIRCUITS ARE SHARING A NEUTRAL
CONDUCTOR, CONTRACTOR SHALL PROVIDE A
REPLACEMENT(MUTIPLE POLE CIRCUIT BREAKER)
FOR THESE 1-POLE SINGLE BREAKERS.
DocuSign Envelope ID: 84209D4E-67F0-4C20-902C-691E17F13049
12/4/2019
ROOM 1701
EQUIP RM.
ROOM 1514
EXAM ROOM
EUL-CR-15-1
UL-17-1
UL-14-5
UL-14-3
UL-14-4
ROOM 1425
FOOD COURT
ROOM 1158EC
ELECTRICAL CLOSETEUL-CR-11-2
UL-11-4
AREA OF WORK
KEY PLAN - BUILDING 111
N
RM 1425
RM 1158EC
RM 1514
RM 1701
E-101
BUILDING 111 FIRST FLOOR PLAN
3 BUILDING 111 FIRST FLOOR PLAN - PARTIAL
SCALE: 1/16" = 1' 0"
NORTH
TRUE
8 16 320
SHEET KEY NOTES:
SHEET NOTES:
VA PROJECT NUMBER
Building Number
Drawing Number
Project Title
Date Checked Drawn
Drawing Title
Approved:
VA FORM 08-6231
A
B C
D E
21 4 5 6 7
SHEET NOTES:
SHEET KEY NOTES:
321 4 5 6 7
A B
C D
E
Dwg. of
LocationLocation
Office of Construction and Facilities Management
PROJECT MANAGER: ACG Project NumberCONSULTANTS:
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs
© COPYRIGHT Apogee Consulting Group, P.A.Revisions: Date# Engineers Architects
UPGRADE ELECTRICAL
SYSTEMS PHASE 1
695-19-101
CLEMENT J. ZABLOCKI VAMC
5000 W NATIONAL AVE, MILWAUKEE, WI
53295
19-097
100% CONSTRUCTION DOCUMENTS
Structural Engineer:
10/29/2019 CNJHT
1 BUILDING 111 FIRST FLOOR PLAN - PARTIAL
SCALE: 1/16" = 1' 0"
2 BUILDING 111 FIRST FLOOR PLAN - PARTIAL
SCALE: 1/16" = 1' 0"
NORTH
TRUE
8 16 320
NORTH
TRUE
8 16 320
A. REFER TO E-613 FOR WORK DETAILS OF
EXISTING EQUIPMENT AFFECTED ON THE
PROJECT.
B. REFER TO THE ROOM ENLARGED PLANS FOR
THE NEW ELECTRICAL EQUIPMENT AND
LOCATION IF NOTED.
C. REFER TO SINGLE LINE DIAGRAMS AND PANEL
SCHEDULES FOR EQUIPMENT AND CIRCUIT
DETAILS.
1 2
1 2
1 2
1. CONTRACTOR TO REPLACE OR RETROFIT
SWITCHBOARD OR PANELBOARD AS SHOWN ON
THIS DRAWING. SEE EQUIPMENT LIST ON DRAWING
E-613.
2. IF ANY CIRCUITS ARE SHARING A NEUTRAL
CONDUCTOR, CONTRACTOR SHALL PROVIDE A
REPLACEMENT(MUTIPLE POLE CIRCUIT BREAKER)
FOR THESE 1-POLE SINGLE BREAKERS.
ROOM 2523EC
ROOM 2559AEC
ELECTRICAL CLOSET
ROOM 2607
OFFICE
ROOM 2619
LAB
ROOM 2629
AUTOCLAVE
ROOM 2637
HISTOLOGY
ROOM 2655
LAB
ROOM 2603
SUPPLY RM
ROOM 2600
GEN DIAGNOSTICS
ROOM 2429EC
ELECTRICAL CLOSET
ROOM 2600C
SUPR GEN
DIAGNOSTICS
ROOM 2487A
TELECOM
ROOM 2474AEC
ELECTRICAL CLOSET
ROOM 2454EC
ELECTRICAL CLOSET
ROOM 2405EC
ELECTRICAL CLOSET
ROOM 2132EC
ELECTRICAL CLOSET ELH-21-4
EUL-CR-21-2
EUL-CR-21-3/EUL-CR-21-1
UL-21-2
UL-21-1
EUL-Q-24-1
EUL-Q-24-2
EQT-22474
EQT-1
EPH-Q-24
ELH-Q-24-1
EDL-CR-24-1
EDL-Q-24-1
EDH-Q-24-1
EUL-LS-24-9
EUL-Q-24-4
EPH-Q-24-2
ECRT-11
2454-EC
DH-24-2
EQT-10
2454-EC
ELH-LS-25-1
UL-25-3
UL-25-1
UL-25-2
EUL-CR-25-13
ELH-Q-25-1
BMS
ELH-CR-24-2
ECRT-25 2429 EC
EUL-CR-24-3&4
EUL-CR-26-1 EUL-CR-26-2
EUL-LS-26-2
EUL-CR-26-13
EUL-CR-26-3
EP102
EP102
EUL-Q-24-11
UL-24-3
EUL-CR-26-11
EUL-CR-26-15
EUL-CR-26-6
ELH-LS-25-1
EUL-CR-26-5
EUL-CR-26-8
EUL-CR-24-1
ROOM 2498EC
ELECTRICAL CLOSET
EUL-CR-26-9
ROOM 2654
ROOM 2234 EC
ELH-CR-22-1
RM 2164 EC
UL-21-3
UL-21-4
AREA OF WORK
KEY PLAN - BUILDING 111
N
RM 2132EC RM 2454EC
RM
2474AEC
RM 2487RM 2405EC
RM 2600C
RM 2600
RM
2523EC
RM
RM
2507AEC
RM 2607
RM 2429EC
RM 2655
RM 2619
RM2637
RM 2640
RM 2618
RM 2629
E-102
BUILDING 111 SECOND FLOOR PLAN
1 BUILDING 111 SECOND FLOOR PLAN
SCALE: 1/16" = 1' 0"
NORTH
TRUE
8 16 320
SHEET KEY NOTES:
SHEET NOTES:
VA PROJECT NUMBER
Building Number
Drawing Number
Project Title
Date Checked Drawn
Drawing Title
Approved:
VA FORM 08-6231
A
B C
D E
21 4 5 6 7
SHEET NOTES:
SHEET KEY NOTES:
321 4 5 6 7
A B
C D
E
Dwg. of
LocationLocation
Office of Construction and Facilities Management
PROJECT MANAGER: ACG Project NumberCONSULTANTS:
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs
© COPYRIGHT Apogee Consulting Group, P.A.Revisions: Date# Engineers Architects
UPGRADE ELECTRICAL
SYSTEMS PHASE 1
695-19-101
CLEMENT J. ZABLOCKI VAMC
5000 W NATIONAL AVE, MILWAUKEE, WI
53295
19-097
100% CONSTRUCTION DOCUMENTS
Structural Engineer:
10/29/2019 CNJHT
A. REFER TO E-613 FOR WORK DETAILS OF
EXISTING EQUIPMENT AFFECTED ON THE
PROJECT.
B. REFER TO THE ROOM ENLARGED PLANS FOR
THE NEW ELECTRICAL EQUIPMENT AND
LOCATION IF NOTED.
C. REFER TO SINGLE LINE DIAGRAMS AND PANEL
SCHEDULES FOR EQUIPMENT AND CIRCUIT
DETAILS.
1. CONTRACTOR TO REPLACE OR RETROFIT
SWITCHBOARD OR PANELBOARD AS SHOWN ON
THIS DRAWING. SEE EQUIPMENT LIST ON DRAWING
E-613.
2. IF ANY CIRCUITS ARE SHARING A NEUTRAL
CONDUCTOR, CONTRACTOR SHALL PROVIDE A
REPLACEMENT (MULTIPLE POLE CIRCUIT BREAKER)
FOR THESE 1-POLE SINGLE BREAKERS.
1 2
ROOM 5512 EC
LL-55-1
UL-55-1
EP103
EP103
P.
T.
ROOM 3315
EQUIPMENT
ROOM 3441
STORAGE
EUL-CR-33-1
UL-34-2
ROOM 4163
ELECTRICAL CLOSET
UL-41-2
EUL-CR-41-1
ECRT-14
EDL-CR-41-1
AREA OF WORK
KEY PLAN - BUILDING 111
N
THIRD
FLOOR
RM 3441
THIRD FLOOR
RM 3315
FIFTH
FLOOR
RM
5512EC
FOURTH FLOOR
RM 4163
E-103
BUILDING 111 THIRD, FOURTH AND FIFTH
FLOOR PLAN
3 BUILDING 111 FIFTH FLOOR PLAN
SCALE: 1/16" = 1' 0"
NORTH
TRUE
8 16 320
SHEET KEY NOTES:
SHEET NOTES:
VA PROJECT NUMBER
Building Number
Drawing Number
Project Title
Date Checked Drawn
Drawing Title
Approved:
VA FORM 08-6231
A
B C
D E
21 4 5 6 7
SHEET NOTES:
SHEET KEY NOTES:
321 4 5 6 7
A B
C D
E
Dwg. of
LocationLocation
Office of Construction and Facilities Management
PROJECT MANAGER: ACG Project NumberCONSULTANTS:
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs
© COPYRIGHT Apogee Consulting Group, P.A.Revisions: Date# Engineers Architects
UPGRADE ELECTRICAL
SYSTEMS PHASE 1
695-19-101
CLEMENT J. ZABLOCKI VAMC
5000 W NATIONAL AVE, MILWAUKEE, WI
53295
19-097
100% CONSTRUCTION DOCUMENTS
Structural Engineer:
10/29/2019 CNJHT
1 BUILDING 111 THIRD FLOOR PLAN
SCALE: 1/16" = 1' 0"
2 BUILDING 111 FOURTH FLOOR PLAN
SCALE: 1/16" = 1' 0"
NORTH
TRUE
8 16 320
NORTH
TRUE
8 16 320
A. REFER TO E-613 FOR WORK DETAILS OF
EXISTING EQUIPMENT AFFECTED ON THE
PROJECT.
B. REFER TO THE ROOM ENLARGED PLANS FOR
THE NEW ELECTRICAL EQUIPMENT AND
LOCATION IF NOTED.
C. REFER TO SINGLE LINE DIAGRAMS AND PANEL
SCHEDULES FOR EQUIPMENT AND CIRCUIT
DETAILS.
1. CONTRACTOR TO REPLACE OR RETROFIT
SWITCHBOARD OR PANELBOARD AS SHOWN ON
THIS DRAWING. SEE EQUIPMENT LIST ON DRAWING
E-613.
2. IF ANY CIRCUITS ARE SHARING A NEUTRAL
CONDUCTOR, CONTRACTOR SHALL PROVIDE A
REPLACEMENT (MULTIPLE POLE CIRCUIT BREAKER)
FOR THESE 1-POLE CIRCUIT BREAKERS.
1 2
1 2 1 2
ROOM 7519EC
ELECTRICAL CLOSET UL-75-1
LL-75-1
EUL-CR-75-1
ROOM 6135
VIDEO CTRL RM
ROOM 6519EC
ELECTRICAL CLOSET UL-65-1
LL-65-1
EUL-CR-65-1
UL-61-1
ROOM 6561EC
ELECTRICAL CLOSET
PNL UL-65-3
D
D
ROOM 9300
DINING RM
ROOM 9407EC
ELECTRICAL CLOSET
UL-94-1
UL-94-2
STACKS
T-17
LH-94-1
ELH-CR-94-1
(NEW)
EUL-Q-93-2 1
EP103
EP103
ROOM 9301
OFFICE UL-93-1
AREA OF WORK
KEY PLAN - BUILDING 111
N
FLOOR 6
RM 6135
FLOOR 9
RM 9407ECFLOOR 9
RM 9300
FLOOR 6
RM 6519EC/
FLOOR 7
RM 7519EC
E-104
BUILDING 111 SIXTH, SEVENTH AND NINTH
FLOOR PLAN
2 BUILDING 111 SEVENTH FLOOR PLAN
SCALE: 1/16" = 1' 0"
NORTH
TRUE
8 16 320
SHEET KEY NOTES:
SHEET NOTES:
VA PROJECT NUMBER
Building Number
Drawing Number
Project Title
Date Checked Drawn
Drawing Title
Approved:
VA FORM 08-6231
A
B C
D E
21 4 5 6 7
SHEET NOTES:
SHEET KEY NOTES:
321 4 5 6 7
A B
C D
E
Dwg. of
LocationLocation
Office of Construction and Facilities Management
PROJECT MANAGER: ACG Project NumberCONSULTANTS:
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs
© COPYRIGHT Apogee Consulting Group, P.A.Revisions: Date# Engineers Architects
UPGRADE ELECTRICAL
SYSTEMS PHASE 1
695-19-101
CLEMENT J. ZABLOCKI VAMC
5000 W NATIONAL AVE, MILWAUKEE, WI
53295
19-097
100% CONSTRUCTION DOCUMENTS
Structural Engineer:
10/29/2019 CNJHT
1 BUILDING 111 SIXTH FLOOR PLAN
SCALE: 1/16" = 1' 0"
3 BUILDING 111 NINTH FLOOR PLAN
SCALE: 1/16" = 1' 0"
NORTH
TRUE
8 16 320
NORTH
TRUE
8 16 320
A. REFER TO E-613 FOR WORK DETAILS OF
EXISTING EQUIPMENT AFFECTED ON THE
PROJECT.
B. REFER TO THE ROOM ENLARGED PLANS FOR
THE NEW ELECTRICAL EQUIPMENT AND
LOCATION IF NOTED.
C. REFER TO SINGLE LINE DIAGRAMS AND PANEL
SCHEDULES FOR EQUIPMENT AND CIRCUIT
DETAILS.
1 2
1 2
1 2
1. CONTRACTOR TO REPLACE OR RETROFIT
SWITCHBOARD OR PANELBOARD AS SHOWN ON
THIS DRAWING. SEE EQUIPMENT LIST ON DRAWING
E-613.
2. IF ANY CIRCUITS ARE SHARING A NEUTRAL
CONDUCTOR, CONTRACTOR SHALL PROVIDE A
REPLACEMENT(MUTIPLE POLE CIRCUIT BREAKER)
FOR THESE 1-POLE SINGLE BREAKERS.
ROOM 10523EC
ROOM 10512
IMAGING RM
ROOM 10510
IMAGING RM
UL-105-1
T-150 IN CEILING
EXISTING EPH-Q-103-1
NEW 45KVA XFMR
(EXACT LOCATION BY VA)
EP104
EP104
ROOM 10300
MER
ELH-CR-105-1
EUL-CR-105-1
ECRT-1
AREA OF WORK
KEY PLAN - BUILDING 111
N
RM 10300
RM 10512
RM 10510
RM 10523EC
E-105
BUILDING 111 TENTH FLOOR PLAN
SHEET KEY NOTES:
SHEET NOTES:
VA PROJECT NUMBER
Building Number
Drawing Number
Project Title
Date Checked Drawn
Drawing Title
Approved:
VA FORM 08-6231
A
B C
D E
21 4 5 6 7
SHEET NOTES:
SHEET KEY NOTES:
321 4 5 6 7
A B
C D
E
Dwg. of
LocationLocation
Office of Construction and Facilities Management
PROJECT MANAGER: ACG Project NumberCONSULTANTS:
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs
© COPYRIGHT Apogee Consulting Group, P.A.Revisions: Date# Engineers Architects
UPGRADE ELECTRICAL
SYSTEMS PHASE 1
695-19-101
CLEMENT J. ZABLOCKI VAMC
5000 W NATIONAL AVE, MILWAUKEE, WI
53295
19-097
100% CONSTRUCTION DOCUMENTS
Structural Engineer:
10/29/2019 CNJHT
1 BUILDING 111 TENTH FLOOR PLAN
SCALE: 1/16" = 1' 0"
NORTH
TRUE
8 16 320
A. REFER TO E-613 FOR WORK DETAILS OF
EXISTING EQUIPMENT AFFECTED ON THE
PROJECT.
B. REFER TO THE ROOM ENLARGED PLANS FOR
THE NEW ELECTRICAL EQUIPMENT AND
LOCATION IF NOTED.
C. REFER TO SINGLE LINE DIAGRAMS AND PANEL
SCHEDULES FOR EQUIPMENT AND CIRCUIT
DETAILS.
EP104
1 2
1. CONTRACTOR TO REPLACE OR RETROFIT
SWITCHBOARD OR PANELBOARD AS SHOWN ON
THIS DRAWING. SEE EQUIPMENT LIST ON DRAWING
E-613.
2. IF ANY CIRCUITS ARE SHARING A NEUTRAL
CONDUCTOR, CONTRACTOR SHALL PROVIDE A
REPLACEMENT(MUTIPLE POLE CIRCUIT BREAKER)
FOR THESE 1-POLE SINGLE BREAKERS.
S06 - Amended Drawings