This document is a Request for Information (RFI) for Project 757-23-101 Air-Cooled Chillers at the Chalmer Wylie Columbus VA Ambulatory Care Center in Columbus, OH. The RFI focuses on specific technical details related to cutting a hole in the roof deck for installing columns and stiffeners, with the contractor seeking clarification on the precise dimensions and access requirements. The response specifies that the hole needs to be 3'-0" X 1'-6" wide, referencing details 1/SF401 and 7/SF401, and confirms that the contractor will have sufficient access to perform work above the ceiling. The document emphasizes the government's requirement for contractors to thoroughly read all solicitation documents and to specifically identify relevant specification or drawing sections when submitting questions.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| S02. 36C25025R0096_1 - Amend0002.docx | DOCX document | |
| S02. 36C25025R0096_1 - Amend0002.pdf | ||
| S02. RFI Form 2.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
REQUEST FOR INFORMATION (RFI)
TO: Contracting Specialist, Stanley Burdine
RFI NO.: DATE: REFERENCE:
REPLY NEEDED BY:
INFORMATION NEEDED:
1. Look at detail 1/SF401 on SF401. This shows cutting a hole in the roof deck to install the columns and the stiffeners. The drawing call for a hole 3’ across. The drawing doesn’t give me anything for how wide but there needs to be enough room to work. We will need access below to protect anything underneath.
REPLY:
1. Given that the AE/COR has already established that the contractor will have sufficient access to perform work in that area above the ceiling.
“The hole needs to be 3’-0” X 1’-6” wide. We have provided the dimensions on detail 7/SF401. Please refer to both details 1/SF401 & 7/SF401.”
PROJECT NUMBER: 757-23-101 Please ensure that before submitting questions or requests for clarification that you thoroughly read the solicitation, specifications, drawings and other pertinent documents.
When submitting questions on this project the Government requires contractors to specifically identify the specification and/or solicitation section(s) or drawing number(s) in reference to the question or request for clarification submitted. No question or request for clarification will be answered by the Government unless the above requirements are met. Failure to comply may prevent the Government from responding in a timely manner.
PROJECT TITLE: Air-Cooled Chillers
PROJECT LOCATION: Department of Veterans Affairs Chalmer Wylie Columbus VA Ambulatory Care Center
SUBMITTED BY: Dayla Salameh City/State: Columbus, OH
PHONE NO.: 614-205-8585
REPLY FROM:
DATE:
ATTACHMENTS:
COPY TO: