Text version

Status:

Analysis Report

Reported On: Sep 11 2014Maintenance Recommendations for Lab No. 201409111155

Component Serial Number: SMBM9214167581Component Manufacturer and Model: YORK YSFAFAS5CSA

Oil Type: YORK S Unit Manufacturer and Model: Does Not Apply Unknown/Unspecified

Comp. Ref. NO.: 4588308

Component: RM-2 COMP. - SMBM9214167581

Unit Worksite: 844 N. RUSH

Component Type: SCREW COMPRESSOR

Unit ID: U.S. RAILROAD BLDG

Air Comfort Corporation

Kim C'Connor

2550 Braga Dr

Broadview

2450 Hassell Rd, Hoffman Estates, IL, 60169

Phone: 800-222-0071

ISO 17025 Accredited |Analysts, Inc. |

From: Air Comfort Corporation - Broadview, IL

ANALYSIS REFLECTS CONDITIONS / VALUES NOTED FOR MONITORING PURPOSES ONLY. Other test results are satisfactory. RESAMPLE at the next scheduled interval.

on Sep 09 2014

Page: 1

I ro n

C h ro m iu m

N ic k e l

A lu m in u

L a d o p p r

T in

S il v it a n ic

B d

P ta s s

M ly b d e n o s p h o ru s

Z c lc ri g n e s ti m o y

V n a d iu m

1155 21 <1 <1 <1 80* 5 7 <0.1 <1 3 <1 1 <10 <5 <10 3 <10 <10 <1 <30 <1

1334 18 <1 <1 1 77* 6 5 <0.1 <1 2 <1 <1 <10 <5 <10 3 <10 <10 <1 <30 <1

1013 13 <1 2 1 72* 8 7 <0.1 <1 2 <1 1 <10 <5 <10 2 <10 <10 <1 <30 <1

3695 31* <1 <1 1 152* 17 6 <0.1 <1 51* <1 <1 <10 <5 <10 <1 <10 <10 2 <30 <1

SPECTROCHEMICAL ANALYSIS IN PARTS PER MILLION

EVAL ID

LAB NO.

09/09/14

09/03/13

08/14/12

09/01/11

Sample

Drawn

PHYSICAL TEST RESULTS

Water(KF) ppm

Viscosity

40 °C

TAN Wk-Order

Number

1155 0 1548 0 Y S 65 74.9 0.03

1334 0 968 0 N N 123 72.8 0.02

1013 8745 391 n N 93 74.1 0.03

3695 1686 1686 614* 79.8 0.06 94627

SAMPLE INFORMATION

Oil

CHG

FLTR

CHG

Oil

Add

MI/HR

Oil

MI/HR

Unit

LAB NO.

Notice: This analysis is intended as an aid in predicting mechanical wear. Test results, maintenance recommendations and accuracy are affected by customer-provided samples, equipment identification and maintenance history. No guarantee, expressed or implied, is made against failure of this piece of equipment or a component thereof. The ultimate responsibility for the maintenance of this piece of equipment and all of its components is the responsibility of the equipment owner.

N/R = Test not performed © Copyright 2012, Analysts, Inc.

Status:

Analysis Report

Reported On: Sep 11 2014Maintenance Recommendations for Lab No. 201409111154

Component Serial Number: SMBM9214167541Component Manufacturer and Model: YORK YSFAFAS5CSA

Oil Type: YORK S Unit Manufacturer and Model: Does Not Apply Unknown/Unspecified

Comp. Ref. NO.: 4590178

Component: RM-1 COMP. - SMBM9214167541

Unit Worksite: 844 N. RUSH

Component Type: SCREW COMPRESSOR

Unit ID: U.S. RAILROAD BLDG

Air Comfort Corporation

Kim C'Connor

2550 Braga Dr

Broadview

2450 Hassell Rd, Hoffman Estates, IL, 60169

Phone: 800-222-0071

ISO 17025 Accredited |Analysts, Inc. |

From: Air Comfort Corporation - Broadview, IL

ANALYSIS REFLECTS CONDITIONS / VALUES NOTED FOR MONITORING PURPOSES ONLY. Other test results are satisfactory. RESAMPLE at the next scheduled interval.

on Sep 09 2014

Page: 1

I ro m

N ic k l lu m in

L d p p v it a n ic d ta s s ly b d e n o s p h o ru s

Z c lc ri g n e s ti m o y

V n a d iu m

1154 17 <1 <1 <1 78* 22 2 <0.1 1 2 <1 1 <10 <5 <10 3 <10 <10 <1 <30 <1

1333 16 <1 <1 <1 80* 18 4 <0.1 <1 2 <1 2 <10 <5 <10 2 <10 <10 <1 <30 <1

1012 13 <1 1 1 78* 15 7 <0.1 1 2 <1 <1 <10 <5 <10 3 <10 <10 <1 <30 <1

3694 35* <1 <1 1 202* 41* 5 <0.1 2 20* <1 1 <10 <5 <10 <1 <10 <10 2 <30 <1

SPECTROCHEMICAL ANALYSIS IN PARTS PER MILLION

EVAL ID

LAB NO.

09/09/14

09/03/13

08/14/12

09/01/11

Sample

Drawn

PHYSICAL TEST RESULTS

Water(KF) ppm

Viscosity

40 °C

TAN Wk-Order

Number

1154 0 1664 0 Y S 51 77.5 0.02

1333 0 1072 0 N N 98 76.8 0.03

1012 10867 333 n N 66 75.9 0.07

3694 3863 3863 15 454 85.8* 0.07 94627

SAMPLE INFORMATION

Oil

CHG

FLTR

CHG

Oil

Add

MI/HR

Oil

MI/HR

Unit

LAB NO.

Notice: This analysis is intended as an aid in predicting mechanical wear. Test results, maintenance recommendations and accuracy are affected by customer-provided samples, equipment identification and maintenance history. No guarantee, expressed or implied, is made against failure of this piece of equipment or a component thereof. The ultimate responsibility for the maintenance of this piece of equipment and all of its components is the responsibility of the equipment owner.