Roofing 21-002 Admin-Willard Roof Report-2.pdf
PDF 3 MB Posted
- Attached to
- BATTLE CREEK PUBLIC SCHOOLS ROOFING PROJECT State and local contract opportunity
- Solicitation number
- RFP BATT 210000001147 1
- Issued by
- Calhoun County, Michigan
About this file
This is a roofing inspection report for Battle Creek Public Schools' Admin/Willard Building located at 7 West Van Buren Street in Battle Creek, Michigan. The report documents existing roofing conditions and establishes the scope of work for a roofing project identified as 21-002. The building has a total roof area of 16,280 square feet comprised of five sections: Section #1 contains 2,700 square feet of TPO membrane; Section #2 contains 6,100 square feet of TPO membrane; Section #3 contains 100 square feet of TPO membrane; Section #4 contains 100 square feet of TPO membrane; and Section #5 contains 7,280 square feet of shingles. The inspection included a visual assessment and thermal moisture scan to evaluate the existing roofing systems.
The inspection revealed significant maintenance issues requiring corrective action. The proposed scope of work includes restoration of 200 square feet and replacement of 16,080 square feet of roofing material. Section #1 exhibits ponding with clogged roof drains and fair condition parapet walls and edge metal. Section #2 shingles are in fair condition but show mineral loss, with a failing previous restoration coating. Section #3 has standing water with drainage issues and fair condition counterflashing and edge metal. The project specifications require contractors to verify actual square footage, account for varying roof deck types, and apply appropriate details including modified base sheets, recovery boards, and 2-inch polyiso insulation with new TPO membrane and shingle systems as applicable.
View the file
Other files for this state and local contract opportunity
| File | Type | Posted |
|---|---|---|
| 21-002 Specifications 2021 BCPS District Roofing-1.pdf | ||
| Roofing 21-002 Miller Stone Compiled.pdf | ||
| Project Manual - 21-002 BCPS District Roofing 2021-2.pdf | ||
| Roofing 21-002 Clarification 01-4.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
B A
TT
LE
C R
EE
K
P U
B
LI
C S
C H
O O
LS
C
A P
IT
A
L A
V E
N E
B A
TT
LE
C R
EE
K
, M I 4
SHEET NO.
SHEET TITLE:
INSPECTION
REPORT
COVER
SHEET
A1
BATTLE CREEK PUBLIC SCHOOLS
ADMIN/WILLARD BUILDING
7 W VAN BUREN STREET
BATTLE CREEK, MI 49017
NOTES
DRAWING INDEX
LOCATION MAPWORK PERFORMED
SITE MAP
A1 - COVER SHEET
A2 – ROOF PLAN
A2 – ROOF PLAN
D1 – DETAILS
D2 – DETAILS
C1-C3 - CONDITIONS
S1 - SCOPE
EXISTING ROOFING SYSTEMS:
- VISUAL ASSESSMENT
- THERMAL MOSITURE SCAN
- PRIORITY SUMMARY
- BUDGET PLANNING
TPA Membrane
Shingle
TT
LE
C R
EE
K
P U
B
LI
C S
C H
O
A P
IT
A
L A
V E
N E
B A
TT
LE
C R
EE
K
, M I 4
SHEET NO.
SHEET TITLE:
INSPECTION
REPORT
SYSTEM OVERVIEW:
SECTION: SYSTEM TYPE: AREA:
SECTION #1: TPA 2,700 SF
SECTION #2: TPA 6,100 SF
SECTION #3: TPA 100 SF
SECTION #4: TPA 100 SF
SECTION #5: SINGLES 7,280 SF
TOTAL: 16,280 SF
ROOF
PLAN
A2
Shingles
TPA Membrane
1 2
TPA Membrane/NOT
INCLUDED
TT
LE
C R
EE
K
P U
B
LI
C S
C H
O
A P
IT
A
L A
V E
N E
B A
TT
LE
C R
EE
K
, M I 4
SHEET NO.
SHEET TITLE:
INSPECTION
REPORT
ROOF
PLAN
A3
RTU
HATCH
DRAIN
UNIT
EXHAUST
EXPANSION JOINT
DETAIL LEGEND
** CONTRACTOR IS RESPONSIBLE FOR VARIFYING SQUARE
FOOTAGE
SYSTEM OVERVIEW:
SECTION: SYSTEM TYPE: AREA:
SECTION #1: TPA 2,700 SF
SECTION #2: TPA 6,100 SF
SECTION #3: TPA 100 SF
SECTION #4: TPA 100 SF
SECTION #5: SINGLES 7,280 SF
TOTAL: 16,280 SF
RTU
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
TT
LE
C R
EE
K
P U
B
LI
C S
C H
O
A P
IT
A
L A
V E
N E
B A
TT
LE
C R
EE
K
, M I 4
SHEET NO.
SHEET TITLE:
INSPECTION
REPORT
DETAILS
D1
1) Details shown are representative of finished details. Contractors shall take into account existing insulation, new insulation, and the new roof system. Wood blocking shall be added to achieve the minimum flashing heights shown.
1) Details shown are representative of finished details. Contractors shall take into account existing insulation, new insulation, and the new roof system. Wood blocking shall be added to achieve the minimum flashing heights shown.
Detail Requirements
2) Deck types vary between roof areas and buildings. Contractor must verify roof decks and apply details accordingly.
1) Details shown are representative of finished details. Contractors shall take into account existing insulation, new insulation, and the new roof system. Wood blocking shall be added to achieve the minimum flashing heights shown.
Detail Requirements
2) Deck types vary between roof areas and buildings. Contractor must verify roof decks and apply details accordingly.
N.T.S.D1
1 TYPICAL FIELD OF ROOF DETAIL
N.T.S.D1
2 TYPICAL PENETRATION
N.T.S.D1
4 DRAIN - TYPICAL
N.T.S.D1
5 TYPICAL CURB DETAIL
N.T.S.D1
3 TYPICAL WALL DETAIL
Modif ied Base Sheet
½” Recover Board
(2x) 2" Poly Iso
Modif ied Base Sheet
½” Recover Board
(2x) 2" Poly Iso Modif ied Base Sheet
½” Recover Board
(2x) 2" Poly Iso
Modif ied Base Sheet
½” Recover Board
(2x) 2" Poly Iso
Modif ied Base Sheet
½” Recover Board
(2x) 2" Poly Iso
TT
LE
C R
EE
K
P U
B
LI
C S
C H
O
A P
IT
A
L A
V E
N E
B A
TT
LE
C R
EE
K
, M I 4
SHEET NO.
SHEET TITLE:
INSPECTION
REPORT
DETAILS
D2
1) Details shown are representative of finished details. Contractors shall take into account existing insulation, new insulation, and the new roof system. Wood blocking shall be added to achieve the minimum flashing heights shown.
1) Details shown are representative of finished details. Contractors shall take into account existing insulation, new insulation, and the new roof system. Wood blocking shall be added to achieve the minimum flashing heights shown.
Detail Requirements
2) Deck types vary between roof areas and buildings. Contractor must verify roof decks and apply details accordingly.
1) Details shown are representative of finished details. Contractors shall take into account existing insulation, new insulation, and the new roof system. Wood blocking shall be added to achieve the minimum flashing heights shown.
Detail Requirements
2) Deck types vary between roof areas and buildings. Contractor must verify roof decks and apply details accordingly.
N.T.S.D2
1 TYPICAL FIELD OF ROOF DETAIL
N.T.S.D2
TT
LE
C R
EE
K
P U
B
LI
C S
C H
O
A P
IT
A
L A
V E
N E
B A
TT
LE
C R
EE
K
, M I 4
SHEET NO.
SHEET TITLE:
INSPECTION
REPORT
CONDITIONS
C1
SECTION #1
Roof Section Overview
The parapet walls and edge metal are in fair condition.
Ponding is present on the membrane and water no longer flows to the roof drains.
The roof drain is clogged and water completely covers the drain.
TT
LE
C R
EE
K
P U
B
LI
C S
C H
O
A P
IT
A
L A
V E
N E
B A
TT
LE
C R
EE
K
, M I 4
SHEET NO.
SHEET TITLE:
INSPECTION
REPORT
CONDITIONS
C2
SECTION #2
The shingles are in fair condition but starting to show signs of mineral loss.
Roof Area Overview
The singles are in fair condition
A previous restoration coating on this section is failing.
TT
LE
C R
EE
K
P U
B
LI
C S
C H
O
A P
IT
A
L A
V E
N E
B A
TT
LE
C R
EE
K
, M I 4
SHEET NO.
SHEET TITLE:
INSPECTION
REPORT
CONDITIONS
C3
SECTION #3
Water no longer flows to the roof drain which sits higher than the field of the roof.
Another view of standing water and the failing coating. The counterflahsing and edge metal is in fair condition.
TT
LE
C R
EE
K
P U
B
LI
C S
C H
O
A P
IT
A
L A
V E
N E
B A
TT
LE
C R
EE
K
, M I 4
SHEET NO.
SHEET TITLE:
INSPECTION
REPORT
SCOPE
S1
RESTORATION: 200 SF
REPLACEMENT: 16,080 SF
1 2
** CONTRACTOR IS RESPONSIBLE FOR VARIFYING SQUARE
FOOTAGE
| Admin-Willard Roof Report.vsdx |
| A1 |
| Adult Ed |
| Page-3 |
| D1 |
| D2 |
| #1 |
| #2 |
| #3 |
| P1 |
File details come from the government source that posted it. Updated .