SITE VISIT QUESTION SHEET VERSION #1
1. What are the rear gate dimensions?
*Due to the size of the cooling units, Contractor will be required to provide a crane to place units on the roofs. The dimensional limits for the crane are 16'-0" wide and 14'-0" tall, to be able to pass through the rear gate in to the facility.
2. What is the original unit that is being replaced?
*Manufacturer: Sun Mfg., model: 27 FC DWDI
CFM: 7240
Belt #: B-65 (LSL-117) Coil: Total BTUH 172,998 (5WH0803C) Motor: RPM 1750, 5 hp, 460/3, FR 184T Valve Assembly: Pipe size: 3/4" (VS-9213-211-4-6) Actuator: (MP-5210)