Questions_and_Answers.docx
DOCX document 14 KB Posted
- Attached to
- Fontenell Unit Breaker Replacement and Excitation System Modification Federal contract opportunity
- Solicitation number
- R15PS00683
About this file
Questions and Answers
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 002_-_154-D-771_Rev1_051315.pdf | ||
| Sol_R15PS00683_Amd_000003.pdf | ||
| Pictures.docx | DOCX document | |
| SF_30.pdf | ||
| 26_09_16_-Amend_2_Page_3.pdf | ||
| SF_1442.pdf | ||
| Sol_R15PS00683_Amd_000001.pdf | ||
| SF_30_(4).pdf | ||
| SF_1442_(2).pdf | ||
| Attachment_j-4_w_cover.pdf | ||
| Sol_R15PS00683.docx | DOCX document | |
| Attachment_J-1_SOW.pdf | ||
| Attachment_J-2_Drawings.pdf | ||
| Attachment_J-3_w_cover.pdf |
Show all 14
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Questions and Answers
Question 1 Where is the new excitation transformer to be located? The specifications for the transformer are included in the Metal Clad Switchgear Assembly section. Is the transformer to be included in the switchgear assembly?
Answer: The new excitation transformer is to be located within an auxiliary section close coupled or adjacent to the switchgear assembly near the existing location at elevation 6425.38 (top of platform). The location is determined by the Contractor and submitted and approved by the Government under RSN 26 17 20-1. This is indirectly referenced or implied within specifications Section 26 17 20, Article 2.01, Paragraph D.3 and Section 26 25 10, Article 1.03, Paragraph C.
Question 2: Section 26 09 16 paragraph 1.03.T. says to test existing RTDs and replace malfunctioning RTDs. How is the contractor to bid replacing an unknown quantity of malfunctioning RTDs?
Answer: With this amendment we have modified specification Section 26 09 16, Article 1.03, Paragraph T from 'Replace malfunctioning RTDs.' to 'Provide 15 RTDs to act as replacements for malfunctioning RTDs or spares.' See the attached Page 3 of this section.