Appendix C low and medium voltage switchgear and associated equipment Updated.xlsx

XLSX spreadsheet 15 KB Posted

Attached to
Maintenance and inspection of low-voltage and medium-voltage systems
Solicitation number
PR16172710
Issued by

About this file

This file is a pricing and service specification appendix for a maintenance contract covering low-voltage and medium-voltage electrical switchgear and associated equipment at a U.S. diplomatic facility in Frankfurt, Germany. The appendix details quarterly facility management meetings, 365-day on-call service availability (including weekends and holidays), project management, certified staff requirements, and estimated incidental expenses of €5,000. The maintenance scope encompasses annual visual inspections and cleaning of low-voltage switches (77 3WE circuit breakers, 30 3WL circuit breakers, 15 3VL circuit breakers, and 5 inspection stations), medium-voltage field inspections at four stations (25 total fields), and verification that short-circuiting and grounding devices comply with rated values.

Additional maintenance requirements include periodic protection testing every four years for 18 pieces of medium-voltage equipment, comprehensive battery system checks (charging, density, connections, cell state, charger functionality, and voltage detector adjustments), transformer maintenance comprising cleaning of insulating parts and rooms, Buchholz protection functional inspections, oil measurements, and insulating agent inspection per VDE 0370 Part 2 standards. The contract also requires visual inspection and documented assessment of 16 KV boxes, with findings recorded via structured checklists and photographic evidence to identify condensation, moisture, corrosion, foreign matter, and loose connections. All personnel must hold valid manufacturer-specific certifications for Siemens systems (8DJH/8DH10 MV, SIVACON/SENTRON LV, GEAFOL/Tumetic transformers) and industrial battery systems, with core maintenance tasks and functional testing restricted to after 18:00, weekends, or public holidays to avoid disrupting diplomatic operations.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Sheet1 Item numbers Service Contract Performances Quantities Unit monthly quarterly annually once every 4 years optional List of individual prices

General Data relating to Maintenance Contract
1.01Quarterly Meeting of Facility Management US Consulate and Contratcor4.00pces.x
1.02365 days /24 hours on-call service including Saturdays/Sundays and public holidays for the switchgears / Optional12.00pces.X
1.04Project management and coordination12.00pces.x
1.05Certified staff already checked by the Consulatex
1.06Scope of Delivery and Services includes the specific circumstances relevant for the Consulate.xxx
1.07Estimated incidentals for extra and additional expenses5,000.00Eurox
Maintenance / Inspection
Inspection of low-voltage switches "Visual inspection and cleaning of switches at US Consulate" (once a year)
3.013WE circuit breaker
77.00pces.x
3.02pces.
3.033WL circuit breaker
30.00pces.x
3.043VL circuit breaker
15.00pces.x
3.05pces.
Check that short-circuiting and grounding devices comply with rated values for the switchgear, are appropriately labeled and functional. Cleaning and inspection of stations5.00pces.x
Inspection of medium voltage field "Visual inspection and cleaning of switches at US Consulate" (once a year)
4.01Station 319 medium voltage8.00fieldsx
4.02Station 320 medium voltage5.00fieldsx
4.03Station 336 medium voltage5.00fieldsx
4.04Station 337 medium voltage7.00fieldsx
4.05Check that short-circuiting and grounding devices comply with rated values for the switchgear, are appropriately labeled and functional. Cleaning and inspection of stations4.00pces.x
4.06Inspection of safety and warning signs to ensure updated status and correct application.
4.00pces.x
Medium voltage protection testing
5.01Periodic protection tests (once every 4 years)18.00pces.x
Maintenance of battery systems
6.01Check battery charging and density, and re-charge if requiredx
6.02Check connections, clean and grease if requiredx
6.03Check the charge state of individual cellsx
6.04Check all functions of the battery chargerx
6.05Check battery undervoltage and overvoltage detector, and adjust accordingly if requiredx
Transformers
Maintenance of a transformer comprising cleaning the insulating parts and transformer room, including supply of cleaning agents8.00pces.x
Functional inspection of Buchholz protection and completion of inspection record.
8.00pces.x
Oil measurement at the transformer Insulating agent inspection in accordance with VDE 0370 Part 2 Inspection of water content, dielectric strength (insulation strength) color index, odor and ...1.00pces.x
KV Boxes
The service includes visual inspection and written documentation of the current condition of cable connections and housings. The visual inspection focuses on detecting condensation (moisture, corrosion), identifying foreign matter (dust, dirt, residue), and checking for loose cable connections. All findings, defects, and deviations must be immediately documented in writing using a structured checklist and supported by photographic evidence.16.00pces.x
The scope of work specified in the maintenance plan
applies for various network systems and need not comply
completely with the machine to be serviced in this
specific case.