REQUIREMENTS: All aspects must be met & addressed
| Minimum Portable Chilled Water System Requirements |
| 14KW-27AMP portable chillers (Estimated 3 ton) |
19KW-45AMP portable chillers (Estimated 5 ton)
| Type: |
| Portable Air Cooled |
| Portable Air Cooled |
| Minimum Cooling Capacity: |
| 14 KW |
(47770 BTU/H)
19 KW
(64830 BTU/H)
Maximum Amperage @ Full Load:
| System Input Voltage (VAC/Phase/Frequency) |
| 208/3/60 |
| 208/3/60 |
| Minimum Tank Capacity: |
| 10 Gallons |
| 25 Gallons |
| Water Tank Level Indicator: |
| Visual |
| Visual |
| Minimum Process Water Filtration |
| 50 Micron |
| 50 Micron |
| Minimum Process Flow Rate @ 35 PSI: |
| 7.0 GPM |
| 12.0 GPM |
| Minimum Ambient Temperature Operating Range: |
| 10C to 35C |
| 10C to 35C |
| Minimum Process Water Operating Temperature Range: |
| 5C to 35C |
| 5C to 35C |
| Maximum Noise Level @ One Meter |
| 84db |
| 84db |
| Maximum Width (Door Opening): |
| 30 Inches |
** The 30 inches’ width requirement is for the 3-ton only. The 3-ton unit is smaller and much lighter to move around by hand and therefore it needs to be 30 inches to fit through the common doors.
No bigger than 36 inches. **The width size of the 5-ton larger chiller is going to be much heavier. It will not be possible for a person to move the 5-ton by hand; a machine such a forklift will have to be used to move it around and therefore this could be larger but ideally the smaller the better to move it around easily.
| Condenser Fan: |
| Variable Speed |
| Variable Speed |
| Compressor: |
| Variable Speed |
| Variable Speed |
| Low Flow By Pass: |
| Automatic |
| Automatic |
| Duty Cycle: |
| Continuous |
| Continuous |
| Minimum Number of Casters |
| 4 |
| 4 |