I.G. Min requirements.docx

DOCX document 13 KB Posted

Attached to
Portable Chiller Requirement Federal contract opportunity
Solicitation number
N66604-23-Q-0593
Issued by
Department of the Navy Naval Sea Systems Command

View the file

Other files for this federal contract opportunity

Other files attached to Portable Chiller Requirement, newest first.
File Type Posted
N6660423Q0593 RFQ-Amendment 4.docx DOCX document
I.G. Min requirements.docx DOCX document
II.G. N6660423Q0593 RFQ-Amendment 3.docx DOCX document
II.G. N6660423Q0593 RFQ-Amendment 2.docx DOCX document
II.G. N6660423Q0593 RFQ Updated-Amended.docx DOCX document
Min requirements.docx DOCX document
N6660423Q0593 RFQ.docx DOCX document

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

REQUIREMENTS: All aspects must be met & addressed

Minimum Portable Chilled Water System Requirements
14KW-27AMP portable chillers (Estimated 3 ton)

19KW-45AMP portable chillers (Estimated 5 ton)

Type:
Portable Air Cooled
Portable Air Cooled
Minimum Cooling Capacity:
14 KW

(47770 BTU/H)

19 KW

(64830 BTU/H)

Maximum Amperage @ Full Load:

27 Amps
45 Amps
System Input Voltage (VAC/Phase/Frequency)
208/3/60
208/3/60
Minimum Tank Capacity:
10 Gallons
25 Gallons
Water Tank Level Indicator:
Visual
Visual
Minimum Process Water Filtration
50 Micron
50 Micron
Minimum Process Flow Rate @ 35 PSI:
7.0 GPM
12.0 GPM
Minimum Ambient Temperature Operating Range:
10C to 35C
10C to 35C
Minimum Process Water Operating Temperature Range:
5C to 35C
5C to 35C
Maximum Noise Level @ One Meter
84db
84db
Maximum Width (Door Opening):
30 Inches

** The 30 inches’ width requirement is for the 3-ton only. The 3-ton unit is smaller and much lighter to move around by hand and therefore it needs to be 30 inches to fit through the common doors.

No bigger than 36 inches. **The width size of the 5-ton larger chiller is going to be much heavier. It will not be possible for a person to move the 5-ton by hand; a machine such a forklift will have to be used to move it around and therefore this could be larger but ideally the smaller the better to move it around easily.

Condenser Fan:
Variable Speed
Variable Speed
Compressor:
Variable Speed
Variable Speed
Low Flow By Pass:
Automatic
Automatic
Duty Cycle:
Continuous
Continuous
Minimum Number of Casters
4
4