Q: Please clarify: in PWS 5.1.1 asks for 40 psi – which normally translates into 92 ft/hd, but 5.2.2 asks for 115 ft/hd (50 psi). Would a 100 ft./hd (45 psi) pump be acceptable?
A: I believe this is talking about requirements in 2.1.1 and 2.2.2, 2.1.1 is saying the system needs to be able to flow 300gpm at a pressure drop of 40psi through the system, where as 2.2.2 is talking about the minimum requirement for the pump is to 300gpm with a TDH of 115 feet, a 100ft/hd pump does not meet the minimum requirement for the pump.
Q: Please clarify the requirement of 90 dBA. At what distance?
A: Sound testing for equipment is measured at 3ft.