A17.0 Solicitation Q & A answered.pdf

PDF 43 KB Posted

Attached to
150-Ton Chiller Lease Federal contract opportunity
Solicitation number
N4523A23Q1333
Issued by
Department of the Navy Naval Supply Systems Command

View the file

Other files for this federal contract opportunity

Other files attached to 150-Ton Chiller Lease, newest first.
File Type Posted
A17.0 Solicitation Q A's_2_answered.pdf PDF
A17.0 Solicitation Q A's_2_answered.pdf PDF
A17.0 Solicitation Q & A answered.pdf PDF
C08.0 N4523A23Q1333 Solicitation.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Q: Please clarify: in PWS 5.1.1 asks for 40 psi – which normally translates into 92 ft/hd, but 5.2.2 asks for 115 ft/hd (50 psi). Would a 100 ft./hd (45 psi) pump be acceptable?

A: I believe this is talking about requirements in 2.1.1 and 2.2.2, 2.1.1 is saying the system needs to be able to flow 300gpm at a pressure drop of 40psi through the system, where as 2.2.2 is talking about the minimum requirement for the pump is to 300gpm with a TDH of 115 feet, a 100ft/hd pump does not meet the minimum requirement for the pump.

Q: Please clarify the requirement of 90 dBA. At what distance?

A: Sound testing for equipment is measured at 3ft.